Practive Advisory 6 3187 All
Practive Advisory 6 3187 All
This Practice Advisory highlights concerns about general design and construction practices, as well as
recommended actions you can take to maintain professional standards.
The advisory should be read in conjunction with the cover note for the Practice Advisories 1 to 6 Maintain
professional standards.
This information was confirmed as current in December 2016.
This Practice Advisory is issued as guidance information in accordance with section 175 of the Building Act 2004
and, if used, does not relieve any person of the obligation to consider any matter to which the information relates
according to the circumstances of the particular case. This document is not a compliance document in terms of
the Act and not a substitute for professional advice.
We have produced this guidance to highlight concerns and implications about general design and construction
practices, as well as recommended actions you can take to maintain professional standards.
https://www.building.govt.nz/building-code-compliance/b-stability/b1-structure/practive-advisory-6/ Page 1 of 5
27/03/2017 Practice Advisory 6: Achieve best practice every step of the way
6.1 Diaphragm load paths Damage to floor Be clear on the viability and robustness of load
Inadequate or impractical load diaphragms in a major paths from concept to final design.
paths are provided through earthquake may be Review NZS 3101: 2006 Section 13 Design
diaphragms and transfer significant and may result of Diaphragms.
diaphragms. in failure of the floor to
transfer earthquake and Refer general structural concept texts such
gravity loads. as: White R et al, Structural Engineering,
SESOC Journal, Puzzle Series 2003.
6.2 Diaphragm detailing Significant localised Ensure all links are robust and capable of
Inadequate consideration of damage to the diaphragm performing when deformed by earthquake
detailing requirements of local in a major earthquake and actions. Beware of lightly reinforced toppings
effects due to steps in possible loss of integrity and penetrations for stairs/lifts etc. Confirm
diaphragms, penetrations, or re- of the structure. that a clear structural load path is provided for
entrant corners in diaphragms. all transfer diaphragms. Give consideration to
Inadequate consideration to the effects of variations in relative stiffness of
confirm primary structural load the diaphragm and primary load resisting
paths for transfer diaphragms. elements.
Review NZS 3101 Section 13, note Clause
13.3.3.
6.3 New methods and forms of The use of unusual forms Ensure all new products and systems have been
construction of construction and appropriately tested and formally approved by
New methods and unusual forms products not proven as a recognised authority before using them in
of construction can introduce being fit for purpose can building construction.
significant uncertainties to result in a serious A risk-based approach, taking into consideration
structural performance. reduction in structural the likelihood and consequences of an incorrect
performance and safety. design, could be used to set the level of specialist
expertise, scale modelling, peer review, proof
testing and other steps needed to ensure the
completed structure will satisfy the design
intention.
6.4 Detailing requirements for Significant damage in a Detail reinforcement rigorously with
reinforcement major earthquake but appropriate input from a CPEng structural
Inadequate consideration of the unlikely to lead directly to engineer.
detailing requirements for collapse of the structure. Review NZS 3101 Concrete Structures Standard
curtailment of reinforcement in Section 8, Clause 8.6.12.4.
tension zones and bond stress in
areas of high shear. Refer Park R, Paulay T, Reinforced Concrete
Structures, Chapter 13 The Art of Detailing.
6.5 Anchoring of spiral Serious implications for Anchor both ends of every section of spiral
reinforcement in columns performance in major reinforcement with a 135 degree hook. If welded
Spiral and hoop reinforcing in seismic events. The splices are necessary they should be carried out
columns and piles is not being columns and piles can fail in accordance with AS/NZS 1554. Welding must
correctly anchored into core in a brittle manner if the not affect the main reinforcing bars.
concrete in some circumstances. confining effect of spirals Refer NZS 3101 Section 8.
and hoops is lost.
https://www.building.govt.nz/building-code-compliance/b-stability/b1-structure/practive-advisory-6/ Page 2 of 5
27/03/2017 Practice Advisory 6: Achieve best practice every step of the way
6.7 Reinforcing for lateral Can lead to damage and Place special reinforcement to provide restraint
bursting some loss of strength. against the lateral bursting forces.
Poor consideration of the lateral
bursting forces associated with
cranked reinforcing bars.
6.8 Grade 8.8 bolts Depending on the No welding of high strength bolts should be
Welding of high strength (Grade importance of the carried out. This includes tack welding.
8.8 and above) bolts will member to which the
seriously affect their ductility. bolts are fastened, Bolts can be fixed in position through the use of
welding can cause serious temporary frames or adhesive. See details in
failure as the bolts can HERA Report R4-58.
fail in a brittle manner.
6.9 Shear design of beams Likely to be of concern, Always adopt a conservative approach in
Shear design of: especially where the assessing shear capability to avoid brittle
structure is subjected to failures.
beams supporting precast major earthquake actions. Review NZS 3101 Part 1 Section 18, Clause
flooring Localised serious damage 18.5.6.
in a major earthquake
shell beams could result, such as Note that the width to be used in determining
brittle failure of beams shear capacity will vary as a function of the
may be carried out using and floor supports. location along the beam (plastic hinge zone vs.
unconservative values for the
non-hinge zone).
contributory width.
Refer Bull DK,1984. Park R Behaviour of
structural concrete frames with precast
concrete shell beams subjected to seismic
loading.
6.10 Uneven loading When not considered in Consider non-uniform loading, or effect of
Insufficient consideration of design the situation could displacement when determining critical member
uneven loading arrangements or lead to unsatisfactory actions.
imposed lateral displacements, performance, possibly Refer NZS 3101 Commentary Clauses
especially when checking partial collapse of a floor C12.7.1 and C12.7.7.7.3.
punching shear on cast in-situ and even the overall
slabs/column heads. collapse of the structure.
https://www.building.govt.nz/building-code-compliance/b-stability/b1-structure/practive-advisory-6/ Page 3 of 5
27/03/2017 Practice Advisory 6: Achieve best practice every step of the way
6.11 Precast concrete Specific implications are Refer NZS 3101, Chapter 18.
Precast concrete is not covered dealt with in other items Refer CAE Guidelines for the Use of
adequately in NZS 3101. A view in this table. Structural Concrete in Buildings, University of
that precast concrete hollow-core The performance of
Canterbury, Christchurch, New Zealand. 2nd
floors performed poorly in recent precast concrete hollow-
earthquakes in California. core floors in California is Edition December 1999.
not directly comparable to
New Zealand situations
due to different methods of
design and construction.
Contractors:
Structural Steel:
https://www.building.govt.nz/building-code-compliance/b-stability/b1-structure/practive-advisory-6/ Page 4 of 5
27/03/2017 Practice Advisory 6: Achieve best practice every step of the way
6.14 Composite steel beams Could lead to under- Note reduction in shear stud capacities.
Over-estimation of theoretical design of composite Refer HERA Report R4-113. Notes from a
shear stud capacity in precast members and significant seminar on composite construction,
floor systems on composite steel damage under service or
especially sessions 2.2 and 4.2. Consider the
beams. ultimate loads.
effects of accumulated creep and shrinkage
and moment continuity effects on stud
capacity.
6.15 Serviceability The floor system may These are well covered in design guidance.
Performance of composite floor undergo excessive Refer HERA Report R4-107.
systems. Serviceability deflections, especially in
considerations (deflection, local areas, or undergo
vibration) may control the size excessive vibration under
and spacing of support members in-service conditions.
and slab thicknesses in
composite floor systems (insitu-
slab on steel deck supported on
composite steel beams).
This information is published by the Ministry of Business, Innovation and Employments Chief Executive. It is a general guide only and, if used, does not
relieve any person of the obligation to consider any matter to which the information relates according to the circumstances of the particular case. Expert
advice may be required in specific circumstances. Where this information relates to assisting people:
with compliance with the Building Act, it is published under section 175 of the Building Act
with a Weathertight Services claim, it is published under section 12 of the Weathertight Homes Resolution Services Act 2006.