Introduction
L1
Significant change has occurred in electricity networks
L2 M
in the last few years: electronic converters are used
widely in industrial networks due to the increased flex- L3
ibility, efficiency and level of control, and are now ap-
plied at all levels of the electricity network, from do-
mestic applications such as air conditioning and grid-
connected solar photo-voltaic systems, to commercial
Figure 1: Six-pulse thyristor bridge
buildings, large scale renewable energy sources and
distribution and transmission utilities.
The harmful effects of harmonics in power systems
are clear and range from excessive heating, reduced If the converter has a twelve-pulse configuration, har-
equipment life expectancy, to loss of supply and de- monics of the fifth and seventh order do not appear
structive failures. Appropriate care and mitigation be- in general. Twelve-pulse (and higher pulse numbers)
gins with an understanding of the sources of harmon- are more expensive to manufacture than six-pulse
ics. The most common sources of harmonics are devices and are generally used only for high power
described below. An example of how harmonics prop- applications.
agate through an electrical network is presented, then In general we can say that the higher the pulse num-
attention turns to what can be done to mitigate ex- ber, the lower the magnitude of harmonic distortion fed
cessive harmonics in networks. Practical guidance is into the supply. Lack of symmetry (as a result of supply
given on the measurement of harmonic distortion, and system phase unbalance or component mismatches),
real examples of measurements taken in networks and specific faults in the converter can cause unchar-
are presented. Finally operating principles and types acteristic harmonic orders such as the second, third
of harmonic filters are described together with guide- and fourth to appear in the supply current.
lines on the selection of appropriate filters for various
applications. In the ideal case the magnitude of the harmonic cur-
rents produced by the converter is dependent only
on the magnitude of the fundamental current and the
1 Sources of harmonics order of the harmonic concerned according to the
following equation:
Most, but not all network harmonics are caused by
electronic loads that are now commonly used in light- I1
In = (2)
ing and heating, large industrial applications and trans- n
mission networks. We describe some interesting as-
pects of a number of such loads here, from the thyris- where
tor converter to arc furnaces. I1 = fundamental frequency current
n = order of harmonic
In = nth harmonic current
1.1 Thyristor converters
Equation 2 assumes that the converter is fed from
The current drawn from the supply network by a thyris- a strictly symmetrical, stiff three phase network and
tor converter is not sinusoidal. Thyristor converters that the direct current output contains no ripple. In
are treated as harmonic current sources because of practice the magnitude of the harmonic currents pro-
this non-sinusoidal characteristic. The order of the duced is, in addition to order of the harmonic and the
harmonic fed into the supply depends on the construc- magnitude of the fundamental frequency current, also
tion of the convertor. A characteristic feature of the affected by the short-circuit power at the connection
converter is its pulse number. The order of harmonics point of the converter and the ripple on the direct cur-
produced by a converter can be approximated by the rent. Decrease of the short circuit power (increased
equation: network impedance) lengthens the commutation time,
in other words the commutation angle increases and
n = kp 1 (1) the supply side current distortion is reduced.
The circuit inductance is not able to smooth the direct
where current completely, therefore ripple remains in the DC
n = order of harmonic current. This has the effect of increasing some of the
p = pulse number harmonics and decreasing others. Table 1 provides
k = 1, 2, 3, . . . some insight to the difference between the idealised
harmonic current magnitudes predicted by equation 2
Six-pulse converters are in common use and feed har-
and typical levels encountered in practice. The differ-
monics in the order 5, 7, 11, 13 etc. into the supply
ences are mainly caused by the effects of overlap and
system as predicted by the above equation. An exam-
DC ripple.
ple of a simple six-pulse converter topology feeding a
DC load is presented in figure 1.
Optimised Network Equipment Pty Ltd 1A/70 Prospect Terrace Kelvin Grove QLD 4059
ABN 56 151 739 374 PO Box 1951 Toowong QLD 4066
www.onegrid.com.au info@onegrid.com.au
Table 1: Converter line side harmonics bridge and consequently the harmonic currents sup-
plied by the thyristor currents are greater than those
Harmonic In /I1 , % from a diode bridge.
order, n Typical Idealised
5 40 20
1.3 Distributed renewable energy sources
7 21 14
11 8 9 Whereas domestic and commercial air conditioning
13 6 7
loads are significant users of the frequency converters
17 5 6
above, the large scale application of distributed renew-
19 3 5
able energy sources requires controlled bi-directional
23 3 4
25 2 4
power flow. Modern inverters allow for four-quadrant
operation, with independent direction of flow of ac-
tive and reactive power. Furthermore, sophisticated
switching control and inverter topologies have enabled
development of devices with low harmonic emission
1.2 Frequency converters and flexible fundamental frequency power control.
The relationship between fundamental frequency and The examples in figure 3 demonstrate that indepen-
harmonics fed into the supply network by a frequency dent of the source of energy, a utility interface that
converter does not differ materially from what has transfers power to the network is necessary. Such
been stated regarding the thyristor converter. The or- interfaces are almost always electronic and inject har-
der of the harmonics is also in accordance with equa- monic current into the network. Strict standards apply
tion 1. There are considerable differences, however, to the amount of harmonic distortion that can be in-
in the harmonic currents fed into the supply system jected by such devices.
by different types of frequency converters, due to the
fact that the fundamental frequency currents taken at L1 AC DC
the same torque and frequency are of different magni- L2
L3 DC DC
tudes for different frequency converters.
Two different front end topologies are shown in fig-
ure 2. L1 AC DC
L2
L3 DC AC
L1 P1 1
Output voltage (pu)
L2 DC/AC P2
L3 P3 0 Inverter output
Line side voltage
0 0.01 0.02
Figure 2: Controlled and fixed converter front ends
Time (s)
2
voltage harmonic spectrum at the network connection
a=0.50
point is shown in figure 5. Regardless of topology,
harmonic contributions are generally characterised by
a=0.33
high frequency components, and side-bands around
multiples of the switching frequency.
a=0.25
1
Vn/V1 (pu)
0.1
0.01 a=0.5
0.4 a=0.33
a=0.25
In/I1
0.2
11 21 42
Harmonic order, n
0
0 1 2 3 4
Harmonic order, n
Figure 5: PWM spectrum and limits
Predicting the harmonic contribution of this class of Figure 6: Burst control waveforms and harmonics
load is made complicated by the fact that changes
to the harmonic spectrum can be brought about by
changes in the inverter control system, an approach I
0.1
3
1.6 Arc furnaces
1.0
R Since the current drawn by arc furnaces is, partic-
ularly in the initial melting phases, appreciably non-
P,Q (pu)
2 Distribution of harmonics
M f2 < f1
The harmonic producing part of the total load has
increased continuously over recent years. Power elec-
tronics is being used more extensively in industry for
Figure 9: Cyclo-converter schematic the control of various processes. A consequence of
this has been an increase in the harmonic voltages
and currents in the supply networks of industrial es-
The order of the harmonics in the input current of
tablishments and electricity undertakings. Harmonics
the cyclo-converter depends on the pulse number
cause additional losses in network components and
(equation 1). In addition to these so-called typical
may disrupt communication and control equipment,
harmonics a three-phase cyclo-converter produces
causing loss of time, product and equipment.
harmonics the order of which depends on the cyclo-
converter output frequency as follows: Capacitance whether in the form of power factor
correction equipment or stray capacitance from ca-
f2 ble networks in networks subject to harmonics may
n = (kp 1) 6m (3) cause harmonic currents and voltages to be amplified.
f1
In order to avoid the harmful effects of harmonics it
where is necessary to be informed of the possibility of their
appearance whilst still in the planning phase and if
n = order of harmonic
necessary to carry out a network harmonic study. In
p = pulse number
a network already in use a harmonic analysis will
k = 1, 2, 3, . . .
become necessary if, for example, converter power
m = 0, 1, 2, . . .
increases considerably. An increase in compensation
f1 = supply network frequency
power also generally makes a harmonic analysis nec-
f2 = cyclo-converter output frequency
essary. The better the electrical values of the different
If the output frequency of the cyclo-converter is 3 Hz, network components and their frequency dependent
for example, there appear components on each side impedance are known the more exact will be the pic-
of the fifth harmonic. Additional harmonics will also ture of harmonic distribution given by the harmonic
appear as a function of the output and line frequency. study.
The cyclo-converter harmonic amplitudes depend on For the analysis of harmonics there are now available
the load, load power factor, degree of firing angle various software programs that also take into account
and control mode. In some cases the non-harmonic the frequency dependence of different components,
components may be of greater magnitude than the and that can calculate the distribution of harmonics,
harmonic components. Harmonic is taken to mean find possible resonance situations and are of assis-
integer multiples of the fundamental frequency. Distor- tance in the electrical design of harmonic filters..
tion at frequencies such as 268 Hz is non-harmonic Sources of harmonics are generally represented as
per definition. constant current sources injecting harmonic current
4
110 kV 1500 MVA
to the same busbar as the non-linear load. It is clear
that in this case substantial amplification of harmonic
31.5 MVA
Uk = 10%
current is taking place: for example, for every 1 A of
seventh harmonic generated by the non-linear load,
3.6A will flow into the capacitor bank and 2.6 A will
64%
6 kV ~350 MVA flow into the supply transformer feeding that busbar.
This is a clear example of harmonic resonance.
15% 21%
In examining what factors affect the network reso-
2 MVA 2 MVA nance frequency and the distribution of harmonics it
G
Uk = 6% Uk = 6% is noticed that increase of short circuit power (network
10 MVA inductance decrease) raised the network resonance
Xd = 0.12
frequency and a still greater part of the generated
0.4 kV ~30 MVA harmonics flow into the network. Squirrel cage mo-
5 : 100% tors loading the network also increases the resonance
7 : 100%
11:100% frequency, but at the same time damp the resonance.
13:100%
M
1.5 MVA
Ik/In = 5 P = 1.2 MW
Harmonic amplication
Q = 1.2 Mvar
20
R M
31.5 MVA
Uk = 10%
3 Measurement of harmonics
5
2. Know what network configuration exists. Any 3.2 Recording existing harmonic levels
number of possible scenarios (fault level, bus
configurations, transformer connections and tap It is very important that existing background harmonic
position, etc.) may occur and filter designs will distortion be recorded, whether in greenfield or brown-
be based on the network conditions prevailing field applications. Most filter design will (or at least
when measurements were done. should) require post-installation measurements to ver-
ify the performance of the equipment. Such measure-
3. Be aware of the nature of the loads in the network. ments are almost meaningless unless the pre-existing
With modern IGBT inverters the interesting, high harmonic distortion was measured and taken into ac-
frequency and non-integer harmonics may occur count when the filters were designed.
outside the range of the measurement device.
These measurements should cover a time span of at
4. Plan the analysis process before planning the least a few weeks in order to obtain statistical figures,
measurement regime. One normally only gets keeping in mind the requirements of the measurement
one go at performing site measurements due standards.
to the cost of equipment, travel and access ar-
rangements, so make sure everything you need
to measure to construct the model is covered, 3.3 Measurements during commissioning
and that the locations where the measurements
are made are consistent with the requirements Apart from the normal tests of voltage rise, reactive
of the model. power output and verification of the tuned frequency,
it is highly recommended to install a transient recorder
5. Harmonic measurements create a surprisingly
during energisation of a harmonic filter to capture
large amount of data. Make sure you have a
transient conditions inside the bank and imposed on
plan for the storage, manipulation, verification
the network and switching equipment.
and traceability management of the data. For
example, measurements over a two week period Verification of the harmonic performance of the filter
using 3 second data on three phase of voltage is naturally an important test, keeping in mind that
and current on two feeders results in 240 million the measurement conditions will probably never corre-
discrete measurements if all harmonics to the spond to the worst case conditions for which the filter
fiftieth are recorded. design has been made.
6
If2
Table 3: Harmonics with independent converters
If1 If1+If2
Harmonic order IV //A IV //%
1 817 100
Fifth harmonic
5 28 3.4 current vectors
7 29 3.5
11 57 7
13 32 3.9 Figure 15: Harmonic summation with converters al-
17 11 1.3 most aligned
19 18 2.2
23 18 2.2
If1+If2
Fifth harmonic of the same order of magnitude as predicted by equa-
current vectors tion 2. The table includes the effect of switching two
steps of power factor correction in to compensate for
reactive power. These non-tuned capacitors clearly
Figure 14: Harmonic summation: independent con-
cause parallel resonance as can be seen from the
verters
increase in current distortion through the supply trans-
former and increase in harmonic current distortion.
Regulating the thyristor bridge control angles so that
they were almost identical as illustrated in figure 15 Table 5: Harmonics with uncontrolled rectifiers
resulted in measurement of harmonic currents as re-
ported in table 4. This is much closer to what is ex- Harmonic IV /%
pected from equation 2. order 0 kvar 150 kvar 300 kvar
1 100.0 100.0 100.0
Table 4: Harmonics with converters aligned 5 20.9 26.5 26.9
7 6.9 10.1 23.7
Harmonic order IV /A IV /% 11 5.5 16.8 20.7
13 3.3 15.2 10.5
1 800 100
17 2.6 4.5 2.5
5 158 19.9
19 1.9 2.9 2.3
7 71 8.9
11 51 6.4 VT HD /% 4.2 8.3 8.3
13 35 4.4
17 23 2.9
19 16 2.0
23 9 1.1 Non-linear loads affect the power system, specifically
in terms of voltage distortion due to harmonic current
generated by the load and passed into the network.
Power systems also affect non-linear loads. Voltage
The harmonic sources of the network in figure 16 are distortion on the busbar feeding the converter will re-
frequency convertors equipped with fixed intermedi- sult in a different harmonic spectrum drawn by the load
ate circuit voltage (input circuit consisting of uncon- than if there was no distortion of the busbar voltage.
trolled diode bridges) with a total power rating of about In figure 17 a simple network is shown that contains
1 MVA. an uncontrolled rectifier converter and a fifth harmonic
For frequency convertors with diode bridge input cir- filter.
cuits the harmonics sum arithmetically since there is The results of measurements of the converter current
no differences between the control angles. are shown in table 6. It is clear that the presence of
Table 5 presents measurements of harmonics on the the shunt connected filter has a very significant impact
low voltage side of the supply transformer. Values are
7
30
L
20
|Zf| ( )
IV
10 C
If 2 Mvar
6 Mvar
0
Fifth harmonic filter,
640 kvar 660 V 0 250 500 750 1000
Frequency (Hz)
8
5. Required fault withstand capability fr = resonant frequency in Hz
f1 = fundamental frequency in Hz, for
6. Frequency dependent network impedance for all example 50 Hz
possible operating conditions for which the filter SK = short circuit power at the capacitor
is expected to provide the desired mitigation, or if bank connection, in MVA
not available then the actual short circuit current QC = capacitor bank compensating power, in
at the filter connection point and possible range Mvar
of variation
If the natural frequency calculated from equation 4
7. Information of loads generating harmonics is near to some harmonic appearing in the network,
then that harmonic will be amplified considerably. The
8. Permissible harmonic content biggest amplification factor may be in the order of 20.
9. Details of the installation environment (in-
door/outdoor, pollution, temperature range, wind 4.6 Choice of filter
and seismic requirements, etc)
In designing a filter the aim is the simplest and least
cost construction that will satisfy the requirements for
4.5 The need for harmonic filters
reactive power compensation and filtering. In practise
All networks have limits for the extent of harmonic that may mean that the fifth and seventh harmonics
distortion that can be present in the network. In almost may be filtered by single tuned filters, and the upper
all networks there are statutory limitations, for example harmonics by a single wide-band filter.
legislation relating to the conduct of energy users that Filter compensation power affects filter characteristics:
refer to technical standards to determine exactly what the greater the compensation power the better the har-
those limits should be. monic suppression. The different branches of a har-
Two broad categories of standards are used: those monic filter may be connected each to its own circuit
that aim to limit voltage distortion in the network by ap- breaker and use, for example, a reactive power regu-
plying limits to the amount of harmonic current distor- lator to control them according to the reactive power
tion caused by individual customers or loads (the IEEE requirement, or can use a common circuit breaker.
Std 519 approach) and those that allocate permissible When each branch has its own breaker, connection
contribution to voltage distortion at specific nodes in of the different branches to the network should take
the network based on network and load characteris- place in the order of the harmonics, beginning with
tics (the IEC 61000 approach). Neither approach is the lowest, and disconnection should take place in the
perfect or uniformly fair, and both rely on either making reverse order. Switching order is important in order to
simplifying assumptions about the nature of the sup- avoid harmonic resonance.
ply network (for example the IEEE approach does not In choosing and designing a filter a central factor is
expect any reactive power compensating capacitors the distribution of compensating power between the
to be in the supply network) or require detailed knowl- different branches of the filter. This should be carried
edge of the network ( for example the IEC approach out so that:
assumes that the frequency dependent nature of the
supply network is known).
1. The same capacitor units may be used in differ-
As networks become more exposed to harmonic pro- ent branches
ducing loads and simultaneously are expected to last
longer and transfer more power than before, there is 2. Capacitor banks are used at rated voltage (no
widespread implementation of reactive power com- excess voltages)
pensation in networks. These can be implemented as 3. Parallel resonant frequencies occurring at fre-
simple capacitor banks, possibly fitted with inrush cur- quencies between those of the absorption cir-
rent damping reactors, or as detuned or filter capacitor cuits do not coincide with harmonics that may
banks. appear in the network, for example even harmon-
Any addition of capacitor banks to an existing, purely ics
inductive and resistive network will result in a signifi- 4. Branch powers are suitable for (existing)
cant change in the network impedance. If a parallel switchgear
capacitor alone is used in a network containing har-
monics, then the capacitance together with the induc- 5. Filter inductors are reasonable to assemble
tance of the feeding network forms a resonant circuit,
with: 6. Filtering results are adequate.
r
SK 4.7 Effects of filters
fr = f1 (4)
QC
Filters are able to reduce from 60% 90% of harmon-
where ics. Filtering results depend on the relation between
the impedance of the supply network and the filter.
9
The solution is always a compromise since the filter re- where
moves those harmonic for which it has been designed IH = harmonic current produced by the load
but increases harmonics at intermediate frequencies. In = current flowing into the network
An example of a filter application is shown in figure 20, If = current flowing into the filter
where the harmonics produced by a nonlinear load Zn = network impedance
are mitigated by a harmonic filter with three branches: Zf = filter impedance
single tuned filters for the fifth and seventh harmonics, When reviewing the impedance of the network with the
and a wideband filter tuned to the eleventh harmonic. filters connected, illustrated in figure 22, three clear
In what follows, Zn is the frequency dependent resonance points can be observed. The lowest fre-
impedance of the network (dominated by the sup- quency resonance point is produced by the interaction
ply transformer, but with the additional impedance of of the total capacitance of the filter and the inductance
the network in series with the supply transformer), of the network, and this frequency is always lower
and Zf is the equivalent impedance of the three filter than the lowest tuned frequency of the filter. Two other
branches connected in parallel. resonance resonance points represent resonances
between the separate branches of the filter.
110 kV, SK = 1500 MVA
15
Sn = 31.5 MVA Zn || Zf
ZK=10% Zn
11 kV, SK = 250 MVA 10
|Z| () 5
0
0 250 500 750 1000
6 pulse Frequency (Hz)
S=12.7 MVA
I1 = 666 A
I5 = 200 A 5th filter, 7th filter, Wideband filter,
4 Mvar 3 Mvar 3.7 Mvar
Figure 22: Network impedance with filters connected
I7 = 80 A
I11 = 47 A
I13 = 40A
IH If IH If Where the common impedance of the filter and net-
In I5 I7 Iwb In If
work is less than the network impedance, harmonics
are filtered according to the expressions in equation 5,
Zn Z5 Z7 Zwb = Zn Zf
and where the common impedance is greater than the
network impedance, harmonics are amplified.
It is important to note that in most cases, Zn will not
Figure 20: Example of a harmonic filter in industry be a simple inductance the presence of one or
more capacitor banks in the external network and
The frequency dependent impedance of the network changes in supply network topology may result in
and the filter alone are presented in figure 21. wide variations in impedances at fundamental and
higher frequencies. One of the major challenges in
15 filter design is to gain an accurate understanding of the
Zf
Zn
nature of the network impedance. As this is largely out
10 of the control of the filter designer, and may change
|Z| ()
at any time and over time, any filter design must take
5 such variations into account and be robust enough to
be effective under a variety of network conditions.
0
The art of harmonic filter design is to select the shape
0 250 500 750 1000
Frequency (Hz) of the impedance Zf to modify the network impedance
Zn in such a manner that the necessary reduction in
harmonic current is achieved without causing ampli-
Figure 21: Filter and network impedance fication of other harmonics, taking into account the
possible variations in network impedance, and to pro-
duce this solution at the lowest possible cost.
The extent to which harmonics are absorbed by the
filter or injected into the network is determined by the
current divider expressions: Acknowledgements
10