Professional Documents
Culture Documents
Development of High Temperature Superconducting Transformers PDF
Development of High Temperature Superconducting Transformers PDF
Transformers
Chandra T. Reis, IGC-SuperPower,Schenectady,New York
Sam P. Mehta, WaukeshaElectricSystems,Waukesh~Wisconsin
Benjamin W. McConnell, Oak RidgeNationalLaboratory,Oak Ridge,Tennessee
Robert H. Jones, RochesterGas and ElectricCorp.,Rochester,New York
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 432
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 433
must run continuously, and are sized for peak
load. For a 30/60 MVA HTS transformer, for B. Siting Benefits
example, this results in no-load losses on the Most of the siting benefits arise from the
order of tens of kilowatts, which is still less than fact that HTS transformers are oil-free. The
the one to two hundred kilowatts of load loss in a region occupied by oil has been replaced by
comparable conventional transformer. Further either vacuum or liquid nitrogen, making the
considerations about losses are discussed below. HTS transformer both non-flammable and much
lighter than conventional oil filled transformers
4) Fault Current Limiting: The current- of the same size. In addition, the large oil filled
voltage characteristics of a superconductor, heat exchangers are replaced with much smaller
discussed in the section on high temperature cryocoolers, which substantially decreases the
superconductivity, lend themselves to the weight and footprint, as shown in Fig. 3. This
possibility of designing the windings to also could allow a utility to locate a transformer
operate as an intrinsic fault current limiter [1-3]. indoors, limited mainly by the weight of tank
The feasibility of fault current limiting in the and core.
transformer depends on instantly achieving a As can be seen in both Fig. I and Fig. 3, the
uniform transition of the entire length of external package of an HTS transformer is very
superconductor to the resistive state, which is a similar to that of a conventional transformer,
difficult technical task for low level faults. The where the large cooling fms have been replaced
benefits to the power system from a transformer with a compact enclosure for support equipment,
that would limit current under severe transient including cryocooler compressors.
fault conditions include: Various of these benefits can be emphasized
Reduction of current interruption and they can be realized to various degrees by
ratings for circuit breakers and HTS transformer design, depending upon the use
reclosers. intended. And each of these benefits will carry a
Elimination of the need for other different measure of importance depending on
current limiting devices[2,3]. the utility and the application within the utility
grid.
5) Lower Leakage Reactance: AC fields are
minimized in the HTS transformer windings to
reduce ac losses and refrigeration costs. This,
coupled with the compactness of the windings
allowed by high current density, make it natural
to design HTS transformers with low leakage
reactance. If HTS transformers take advantage
of these low impedance designs, it may be
necessary to incorporate fault current limiting
capability, so that these units will not cause an
increase in system short circuit currents. The
specific benefits to power systems operation that
result fi-om lower transformer impedance
coupled with fault current limiting are[2,4]:
Improved voltage regulation 30 MVA Tnwwfwm$mi -
Reduced impact of faults elsewhere in Fig. 3: Comparison of weight andfootprint for conventional
the system and HTS transformers.
Reduction in required static and
dynamic VAR capability III. DESIGN APPROACHES
Increased reactive power availability There are two basic design approaches being
from generators explored for HTS transformers. All present
Increased availability of real power design approaches assume a one for one
from existing generators substitution of HTS transformers for existing
conventional transformers.
Transformer designs that separate
The first design approach is a liquid nitrogen
transformer impedance requirements
(LNJ bath cooled transformer. Lnthis design the
from specific system short circuit
coils sit in a bath of liquid nitrogen, and the LN2
current requirements.
provides both thermal and electrical insulation.
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 434
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 435
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 436
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 437