Perimeter Joints Fire Protection:

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 1


Key Learning Points:

1. Risks of Fire & Smoke spreading (statistics)


2. How to Protect the Perimeter joint
3. How to select the correct system according to testing
4. Correct Vs. Incorrect installation
5. UAE Fire Code requirements for Perimeter Joints Fire Protection

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 2


Fire Statistics
Why must we contain Smoke, Toxic Gases and Fire?

3/4 of all fire deaths are caused by


smoke inhalation.
Source: Hall, Jr. John R. NFPA Fire Analysis & Research, Quincy, MA. Burns, Toxic Gases, and other Hazards.

Visibility: 47%of survivors caught in a fire


could not see more than 12 feet (3.6 m).
Source: NFPA Fire Protection Handbook, 18th Ed. Table 1-1P. Pg.1-15.

Approximately 57% of people killed in


fires are not in the room of the fires origin.
Source: NFPA Fire Protection Handbook, 18th Ed. Table 8-1P. Pg. 8-17.

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 3


What is the leading killer in fires?

Smoke & Toxic Gases

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 4


How Fast Does Smoke Travel?
Consider this:

A square room 20 ft x 20 ft x 20 ft has a pencil hole between


compartments.

How long will it take for the smoke to fill the room to a thickness such
that you cannot see your hands 18 inches in front of you?

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 5


20 ft x 20 ft x 20 ft room

Pencil Hole

3 minutes
40 seconds

Smoke travels 120-420 feet per minute (36 128 m/min), under fire conditions
Source: Estimate based upon ceiling jet velocity calculations for typical ceiling heights and heat release rates.

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 6


We cant rely on any single action or safeguard
to keep people safe

The Balanced Approach to Fire Protection


www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 7
Main Risks in Perimeter Joints:

2nd Floor
Chimney Effect
Internal Spread

Floor Slab

1st Floor
Curtain
Wall

Ground
Floor

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 8


Main Risks in Perimeter Joints:
External Spread Leap Frog
Vision glass
3rd Floor

Spandrel panel
(glass, stone, metal...)

Mullions
2nd Floor

Transoms

1st Floor

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 9


Main Risk in Perimeter Joints:
External Spread Leap Frog

Al Tayer Tower Sharjah 2012 Al Nasser Tower Doha 2006

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 10


Testing Of Curtain Wall Systems:

3 Main Testing Standards:


1. ASTM E2307: Standard Test Method for Determining Fire Resistance
of Perimeter Fire Barriers Using Intermediate-Scale, Multi-Story Test
Apparatus
2. EN 1364 Part 3: Fire resistance of curtain walling systems full
Configuration Fire Resistant Glazing
3. EN 1364 Part 4: Fire resistance of parts of curtain walling Non-
Fire Resistant Glazing

NFPA 285: Standard Fire Test Method for Evaluation of Fire


Propagation Characteristics of Exterior Non-Load-Bearing Wall
Assemblies Containing Combustible Components

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 11


ASTM E2307

Standard Test Method for


Determining Fire Resistance
of Perimeter Fire Barriers
Using Intermediate-Scale,
Multi-Story Test Apparatus

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 12


ASTM E2307 Test Assembly

face back

View from front face Cross-section view


www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 13
ASTM E2307 Test Assembly

Vision Glass

Transom above floor


Curtain Wall Test
Assembly Mineral wool insulation at
spandrel area

Pre-Burn Mechanical attachments


supporting insulation

Transom below floor

Mullions

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 14


ASTM E2307 Test Assembly

Assembly
Interior View

Pre-Burn

Thermocouples
measuring temperature
rise

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 15


ASTM E2307 Test Assembly

Video

LSSCWBURN.wmv

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 16


ASTM E2307 Test Assembly
Interior Burner Lit - Time: 0:00

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 17


ASTM E2307 Test Assembly
Exterior Burner Lit - Time: 0:05

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 18


ASTM E2307 Test Assembly

Flames Climbing
Exterior

Time: 0:15

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 19


ASTM E2307 Test Assembly

Melting of Mullions
&
Transoms

Time: 0:45

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 20


ASTM E2307 Test Assembly

Vision Glass
Breaks

Time: 2:00

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 21


Burner Off at 2 hours

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 22


ASTM E2307 Test Assembly

Post Test:

Close up Detail of Mullion


and Transom Damage

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 23


ASTM E2307 Test Assembly
Post Test Interior View

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 24


ASTM E2307 Testing Labs

Only two labs presently perform testing in accordance with


newly developed ASTM test methods:

Northbrook, IL Elmendorf, Texas

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 25


Test result: Laboratory listing with very precise
construction details

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 26


NFPA 285 Testing Method

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 27


NFPA 285 Testing Method

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 28


Perimeter Fire Containment - Basic Design Criteria
1. Provide Backing/Reinforcement Member at
Safing Line

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 29


Reinforcement
Member
1

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 30


Perimeter Fire Containment - Basic Design Criteria
1. Provide Backing/Reinforcement Member at
Safing Line

2. Mechanically Attached Curtain Wall Insulation

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 31


Mechanically
2 Attached
Reinforcement Insulation
Member
(hangers, clips, impaling
1 pins, weld pins,)

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 32


Perimeter Fire Containment - Basic Design Criteria
1. Provide Backing/Reinforcement Member at
Safing Line

2. Mechanically Attached Curtain Wall Insulation

3. Protect Aluminum Mullions

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 33


Mechanically
2 Attached Insulation

Reinforcement
Member
1

3
Protect
Mullions

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 34


Melting Point of
Aluminum - 1220 F1
(660 C) (9 minutes)

Sources:
1. NFPA Fire Protection Handbook, 18th Ed.
Table 4-16A. Pg 4-183.
2. SFPE Handbook of Fire Protection
Engineering, 1st Ed. Table 1-12.1. Pg. 1-166.
3. Owens Corning SSL I or II Fiberglas Insulation
specification sheet.

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 35


Perimeter Fire Containment - Basic Design Criteria
1. Provide Backing/Reinforcement Member at
Safing Line

2. Mechanically Attached Curtain Wall Insulation

3. Protect Aluminum Mullions

4. Compression-fit Safing Insulation


Install Safing Impaling Clips if required per tested assembly

Vertical fiber
orientation

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 36


Mechanically
2 Attached Insulation
Reinforcement
Member
1

Compression Fit
Safing & Safing
3 4 Clips (if required per
Protect tested assembly)
Mullions

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 37


Perimeter Fire Containment - Basic Design Criteria

1. Provide Backing/Reinforcement Member at


Safing Line

2. Mechanically Attached Curtain Wall Insulation

3. Compression-fit Safing Insulation - as required per tested assembly

Install Safing Impaling Clips - as required per tested assembly

4. Protect Aluminum Mullions

5. For Smoke Containment - Add Firestop Coating

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 38


Mechanically
2 Attached Insulation
Reinforcement
Member
1 5 Firestop
Coating
Compression Fit Safing
& Safing Clips (if required
per tested assembly)
3 4
Protect
Mullions

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 39


Firestop
Coating 5

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 40


4

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 41


33%

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 42


www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 43
13mm
3.2mm

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 44


Incorrect Installations:

Traditional Method 6mm sheet metal top and bottom, filled with mineral wool:

General Value Proposition

Can be valid when

All voids closed with Fire and


Acoustic sealant
Key Weaknesses

No movement capabilities
High Load
Slow to install
Not tested
www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 45
Incorrect Installations:

. Incorrect installation of foil boards leaves space for smoke and flames to pass
through and may fall out
. Foil may be damaged very easily
www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 46
Incorrect Installations: Fire Stop

Floor
slab

Fire Stop
Drops

Coated boards are ridged and do not


allow movement
www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 47
Overlapping:
Mastic spray

Curtain Wall
Floor Slab

13mm

Firestop expands

13mm

Wall bulges out


Heat and Flames

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 48


Incorrect Installations:

Faade
www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 49
UAE Fire & Life Safety Code of
Practice

2012 Edition

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 50


UAE Fire Code requirements:

3.2.4. Perimeter fire barriers


Exterior Curtain-wall System

3.2.4.5. Perimeter Fire Barrier System


Ratings shall be established in
accordance with ASTM E 2307 or EN
1364 Part 3 and 4 or NFPA 285 or other
equivalent tests using the Intermediate-
Scale, Multi Story Test Apparatus
(ISMA) as the test method

3.2.4.6. The system refers to all the


necessary components and conditions
in the approved firestop design, which
can include but is not limited to the gap
size, sealant or backing material depth,
and other parameters in the listing.
www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 51
UAE Fire Code requirmeent:

6.8. Installation

6.8.1. For installation of all the systems,


installer shall strictly follow design listed
and certified systems including illustrations
therein and manufacturers installation
instructions.

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 52


People with complete trust
in the compartmentation

Fire with successful


compartmentation

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 53


Questions.?

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 54


THANK YOU

(Protect Yourself & Others)

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 55


ASTM 2307 EN 1364-3 EN 1364-4 BS 8414-1 BS 8414-2

Curtain Wall Full Full Part Part Part


Assembly
Glazing Non-Fire Fire-Rated Fire Rated & N/A Non-Fire
Rated Non-Fire Rated
Rated
Internal Curtain Wall, Curtain Wall Curtain Wall Not Not
exposure Insulation & & Gap Seal & Gap seal Evaluated as Evaluated as
Gap Seal (partially) a full system a full system

External Curtain Wall, Curtain Wall Evaluated curtain Wall, Curtain Wall,
Exposure Glazing, Partially Over- Glazing,
insulation or cladding & Composite
Composite insulation Panel
Panel

Movement Cycling N/A N/A N/A N/A


requirements
Equipments Internal & Internal OR Internal OR Internal OR Internal
External External External External Burner
Burners Burner Burner Burner

www.hilti.com Safety Design in Buildings Forum Abu Dhabi 2012 56