Surface box set in HYDRANT CHAMBER

concrete

Spacer blocks where Spacer blocks


HYDRANT CHAMBER DIMENSIONS
required where required VALVE DIA. CHAMBER WIDTH CHAMBER LENGTH DEPTH OF COVER TO CLEAR OPE. SURFACE
R.C. Roof slab R.C. Roof slab (mm) (W) (L) PIPE (H) BOX (mm)
215 blockwork 50 390 720 900 375x225
Precast lintel
80 460 960 900 575x300

From TEE on main 100 460 960 900 575x300


line
150 920 1500 900 900x600
Concrete grade 25n
PLAN ON COVER SLAB
SECTION X-X SECTION Y-Y
400

Surface box set in


concrete

R.C. Roof slab SCOUR SIZES


900

150
215 215 MAIN PIPE DIA SCOUR PIPE DIA.
150

(mm) (mm)

215 blockwork 80 100 150 80


Gate valve 200 100
100

Watermain 250 300 350 150 NOTES:


To watercourse or
sump 400 450 500 200 1. FIGURED DIMENSIONS ONLY TO BE TAKEN
D.I. or C.I. Flanged tee FROM THIS DRAWING.
600 REFER TO SPEC. 2. ALL DRAWINGS TO BE CHECKED BY THE
CONTRACTOR ON SITE.
3. ENGINEER/EMPLOYERS REPRESENTATIVE, AS
APPROPRIATE, TO BE INFORMED BY THE
150

Concrete grade 25n CONTRACTOR OF ANY DISCREPANCIES


BEFORE ANY WORK COMMENCES.
4. THE CONTRACTOR SHALL UNDERTAKE A
THOROUGH CHECK FOR THE ACTUAL
TYPE 1 SCOUR CHAMBER LOCATION OF ALL SERVICES/UTILITIES,
ABOVE AND BELOW GROUND, BEFORE ANY
WORK COMMENCES.
5. ALL LEVELS SHOWN RELATE TO ORDNANCE
SURVEY DATUM AT MALIN HEAD.
Surface box set in AIR VALVE CHAMBER
concrete

Spacer blocks where Spacer blocks


AIR VALVE CHAMBER DIMENSIONS
required where required
PIPE DIA CHAMBER WIDTH CHAMBER LENGTH DEPTH OF COVER TO A Dec. '15 PLANNING ISSUE MN DC
R.C. Roof slab R.C. Roof slab (mm) (W) (L) PIPE (H)
Rev Date Description By Chkd.
LENGTH 150 510 690 900
900

WIDTH
215 blockwork 250 510 690 900
Precast lintel Client:
300 600 720 1050

400 800 800 1050

450 800 800 1050

PLAN ON COVER SLAB 500 1000 1000 1050


Project:
Concrete grade 25n 600 1200 1200 1300

SECTION X-X SECTION Y-Y WEST DUBLIN


220 / 110 kV SUBSTATION
& ASSOCIATED WORKS

Title:

SLUICE VALVE CHAMBER


STANDARD
SLUICE VALVE CHAMBER DIMENSIONS WATERMAIN DETAILS
Surface box set in
400

concrete VALVE DIA. CHAMBER WIDTH CHAMBER LENGTH DEPTH OF COVER TO


(mm) (W) (L) PIPE (H)

R.C. Roof slab R.C. Roof slab Scale @ A1: 1:20


Depth "h"

80 280 560 900


Prepared by: Checked: Date:
215 Length "l" 215 215 Width "w" 215 100 310 560 900 M. Nolan D. Conneran October 2015
150

215 blockwork 215 blockwork 150 410 610 900 Project Director: D. Grehan
Vj coupling Precast lintel PLAN ON COVER SLAB 200 460 610 900 Drawing Status: Planning
250 510 690 900

Note 300 600 720 1060


Patrick J. Tobin & Co. Ltd.
Concrete floor to chamber
Concrete grade 25n not to be provided when 400 800 800 1060 TOBIN Consulting Engineers, AECOM,
150

Concrete grade 25n Class 1 watermains are Block 10-4, Blanchardstown Kingswood Drive,
used. Corporate Park, Dublin 15, City West Business Campus,
SECTION X-X SECTION Y-Y Ireland. Dublin 24,
tel: +353-(0)1-8030406 Ireland.