F302 Ref.7sj80

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Protective Relaying

High Impedance Restricted Earth Fault 7SJ801


Commissioning certificate 12/2011
Customer : EETC

Plant : Maghagha 500 kV S/S Contract-No.:

Feeder : B08+R1

MLFB - No.: 7SJ80125EB001FA0

Serial.-No.: 1512516190 In 1 A f= 50 Hz UH = 220 V Un = 100 V


= dc
UN= UN=
UN
Remarks:
=
Setting and parameter printouts produced by DIGSI Program are attached

High impedance R.E.F.


Setting : I = 20.0 mA
R =6 K
V calculated = 120 Volt

Calculated pick up voltage 120 volt

measured pick up voltage 119.37 volt

Measured Current (IEE) at trip 20 mA

Trip time measured = 38 msec

Tested by Witnessed by
Sie mens S.A.E Client :EETC Client :EETC
Name: Ahmed Salim Name Name:
Date: 20 -10-2016 Date: Date:
Signature Signature Signature

Page 1 of 6
LEDs Operation Tested According to setting OK
I/P Function Tested N/A
O/P Function Tested : OK

Test Switch Facility:


Current Transformer shorting facility. OK
Isolating alarm and trip signals. OK

Tested by Witnessed by
Sie mens S.A.E Client :EETC Client :EETC
Name: Ahmed Salim Name Name:
Date: 20 -10-2016 Date: Date:
Signature Signature Signature

Page 2 of 6
Tested by Witnessed by
Sie mens S.A.E Client :EETC Client :EETC
Name: Ahmed Salim Name Name:
Date: 20 -10-2016 Date: Date:
Signature Signature Signature

Page 3 of 6
Stability test for HV side (500 KV) and Neutral side for High
impedance R.E.F.

Simulation of External Fault.

Inject primary current as shown in fig (1). The next Table for the
result measured.

Measured Values
Injected primary CB
Fault
current (A) Current in (mA) at the TRIP
device
R 200 0 NO

S 200 0 NO

T 200 0 NO

Tested by Witnessed by
Sie mens S.A.E Client :EETC Client :EETC
Name: Ahmed Salim Name Name:
Date: 20 -10-2016 Date: Date:
Signature Signature Signature

Page 4 of 6
Simulation of Internal Fault.

Inject primary current as shown in fig (2). The next Table for the
result measured.

Measured Values
Injected primary CB
Fault
current (A) Current in (mA) at TRIP
the device
R 50 20 OK

S 50 20 OK

T 50 20 OK

Tested by Witnessed by
Sie mens S.A.E Client :EETC Client :EETC
Name: Ahmed Salim Name Name:
Date: 20 -10-2016 Date: Date:
Signature Signature Signature

Page 5 of 6
Stability test for LV side (220 KV) and Neutral side for High
impedance R.E.F.

Simulation of External Fault.

Inject primary current as shown in fig (1). The next Table for the
result measured.

Measured Values
Injected primary CB
Fault
current (A) Current in (mA) at the TRIP
device
R 200 0 NO

S 200 0 NO

T 200 0 NO

Simulation of Internal Fault.

Inject primary current as shown in fig (2). The next Table for the
result measured.

Measured Values
Injected primary CB
Fault
current (A) Current in (mA) at TRIP
the device
R 50 20 OK

S 50 20 OK

T 50 20 OK

Tested by Witnessed by
Sie mens S.A.E Client :EETC Client :EETC
Name: Ahmed Salim Name Name:
Date: 20 -10-2016 Date: Date:
Signature Signature Signature

Page 6 of 6

You might also like