Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

1/4

SITE TEST REPORT


Project name: 765/400KV GIS PGCIL, WARDHA. DATE:01-04-17
Bay/Location: 416-4R1B, ALLAHABAD LINE-1 WITH REACTOR.

TEST REPORT FOR 21M2-DISTANCE RELAY

BASIC RELAY & OBJECT DATA:

Object : ALLAHABAD LINE-2


Make : Alstom
Relay Model : REL-670
Serial No. : I1553040
Aux voltage : 110-250 V DC/100-240 V AC
Nominal current : 1A
CT Ratio : 2000/1A
PT Ratio : 400000/110V

ENABLED PROTECTION FUNCTIONS:

1. DISTANCE (21)
2. ZCOM (85)
3. SOTF (50/27)
4. VOLTAGE (59)
5. DIRECTIONAL EARTH FAULT (67N)
6. STUB PROTECTION
7. BRC (46)

ENABLED PROTECTION RELATED FUNCTIONS:


POWER SWING (78)
VT FISE FAIL

A.MEASURMENTS:

Measured Measured
Applied Applied Measured
Phase PH-N
Current(A) Voltage (V) Current(A) PH-PH
Voltage(KV)
Voltage(KV)

R 1.000 63.510 19990 230.10 399.830

Y 1.00240 63.51240 1995240 230.9240 399.9-90

B 1.00120 63.51120 1999120 230.9120 399.9150

1) Distance protection :

OMICRON Kit reach test report attached with annexure-I.

TESTED BY WITNESSED BY WITNESSED BY


M/S GE T&D CHENNAI M/S GE T&D NOIDA M/S PGCIL
SUBRAMANIAN.R SHRI RAM PANDEY SUNIL KUMAR
2/4

SITE TEST REPORT


Project name: 765/400KV GIS PGCIL, WARDHA. DATE:01-04-17
Bay/Location: 416-4R1B, ALLAHABAD LINE-1 WITH REACTOR.

2) ZCOM TRIP :
Carrier aided trip checked when fault in zone-2 and operating time 35.7ms.

3) SOTF TRIP :
SOTF Protection checked with zone1&2 triping and operated within 28.4 ms.

4) OVER V:OTAGE :
Pickup :
Stage-I

PU
Set Voltage Time set
Phase Voltage Operated Time
(V) (Sec)
(V) (Sec)
RN 70.0 69.90 7 7.027
YN 70.0 69.95 7 7.015
BN 70.0 69.90 7 7.013

Stage-II

PU
Set Voltage Time set
Phase Voltage Operated Time
(V) (Sec)
(V) (Sec)
RN 95.26 95.30 0.100 0.135
YN 95.26 95.35 0.100 0.137
BN 95.26 95.35 0.100 0.124

Drop off voltage :

Stage-1
Phase Drop off Voltage
(V)
RN 69.55
YN 69.60
BN 69.60

TESTED BY WITNESSED BY WITNESSED BY


M/S GE T&D CHENNAI M/S GE T&D NOIDA M/S PGCIL
SUBRAMANIAN.R SHRI RAM PANDEY SUNIL KUMAR
3/4

SITE TEST REPORT


Project name: 765/400KV GIS PGCIL, WARDHA. DATE:01-04-17
Bay/Location: 416-4R1B, ALLAHABAD LINE-1 WITH REACTOR.
5) Directional Earth Fault:

SET CURRENT (I) =0.1 A, SET TMS=0.46, CURVE= IEC Normal Inverse.

Set current(A) Pickup Optd. Time(Sec)


Phase
*2 *5 *10 current(A) *2 *5 *10
N 0.2 0.5 1.0 0.102 4.755 2.012 1.402
Cal
time 4.613 1.969 1.366
(Sec)

PHASE Theoritical angle Operating angle

R 40---0---230 39---0---229
Y 110---240---280 109---240---278
B 160---120---350 158---120---349
6) STUB Protection:

PU
Set Current Time set
Phase Current Operated Time
(A) (Sec)
(A) (Sec)
RN 1.5 1.500 0.100 0.133
YN 1.5 1.505 0.100 0.121
BN 1.5 1.500 0.100 0.127

7) Brocken conductor alarm :

Pickup
Set Current
Phase Current Set Time Operated Time
I2/I1 ratio
I2/I1 ratio (Sec) (Sec)
R 0.2 0.198 15 15
Y 0.2 0.195 15 15
B 0.2 0.197 15 15

TESTED BY WITNESSED BY WITNESSED BY


M/S GE T&D CHENNAI M/S GE T&D NOIDA M/S PGCIL
SUBRAMANIAN.R SHRI RAM PANDEY SUNIL KUMAR
4/4

SITE TEST REPORT


Project name: 765/400KV GIS PGCIL, WARDHA. DATE:01-04-17
Bay/Location: 416-4R1B, ALLAHABAD LINE-1 WITH REACTOR.
8) Fuse fail check :

Phase Applied Volage(V) Applied Current(A)

R 24.51 63.51 63.51 1 1 1


Y 63.51 24.51 63.5 1 1 1
B 63.51 63.51 24.51 1 1 1
RYB 30.0 30.0 30.0 1 1 1

Alarm received after 5 sec for all phases.


Under VT fuse fail condition distance protection blocking checked.

9) FUNCTION CHECK:

CARRIER SEND CHECKED WHEN ZONE-1 OPERATED OK.


DT CHECKED WHEN EARTH FAULT & OVER VOLATGE OPERATED STAGE-1 & 2
CHECKED OK.
DR CHECKED OK.
POWER SWING BLOCK CHECKED OK.
TRIPING RELAY OPERATION CHECKED OK.

REMARKS:

INPUTS & OUTPUTS CHECKED OK.


LED CHECKED OK.
RELAY FIT FOR SERVICE.

TESTED BY WITNESSED BY WITNESSED BY


M/S GE T&D CHENNAI M/S GE T&D NOIDA M/S PGCIL
SUBRAMANIAN.R SHRI RAM PANDEY SUNIL KUMAR

You might also like