Professional Documents
Culture Documents
Comparison of Touch and Step Voltages Between PDF
Comparison of Touch and Step Voltages Between PDF
Abstract: A comparison of the safety criteria of two widely accepted standards, i.e. the IEEE Std 80
and the IEC 479-1 is proposed. The two standards differ in their definitions of permissible body
current and body resistance. Another difference is that the IEC 479-1 does not provide guidance on
human feeusoil contact impedances. It tacitly assumes that these impedances are computable by the
designer. A comprehensive study of permissible touch and step voltages by these two standards is
included for a wide range of conditions, which enables a direct comparison of the two standards. It is
shown that differences exist and these differences are quantified.
Table 1: Electrical shock model differences between IEEE Std 80 and IEC 479-1
IEEE Std 80 IEC 479-1
Body 100052 Voltage-dependent and
resistance Path-dependent (Figs. 5 and 6 )
Thevenin equivalent resistance 1.5cgSfor touch voltage no guidance
6.0c8,for step voltage
Thevenin equivalent voltage Simplified equations k; k, L l o r use no guidance
of computer models is suggested
Permissible body current O.116Adtfor 50kg person S-curves (Fig. 7) independent of
0.157Adtfor 70kg person human size
i8 4.0
.
3.5
0 1.o 2.0
D
Fig.3 Feet to soil resistances as a fwzction of feet separation and gravel
thickness
= 3925Rm. pyclt/
= 2108m, D = feet separation. ft
req
c s ( h s , k )= -
1.5Ps
The value of reg, and therefore cs(h,, k), depends on foot
size and spacing between feet. Using a foot model as shown
in Fig. 3, the IEEE Std 80 model is matched exactly for
uniform soil and assuming feet separation of D = 2 ft.
Fig. 3 also illustrates the effect of the mutual resistance
between the two plates representing the two feet. Note that
for the usual standing position D = 1-2 ft, the effect of the
mutual resistance is negligible. However, as the feet come The data of IEC 479-1 can be utilised in two ways: (a)
closer than 1 ft, the effect of the mutual resistance is such actual body currents can be computed for an individual
as to increase the value of req. subjected to a touch or step voltage in a specific system and
The computed values of c,(h,, k) are given in Fig. 4 specific conditions, and (b) permissible touch and step volt-
superimposed on the present values of the IEEE Std 80. ages can be computed for a specific system.
IEE Proc -Gener Trunsm Distrib , Vol 146, No 5, September 1999 595
Figs. 5 and 6. req,T is the feet to soil resistance for touch
voltage, i.e. the two feet to soil resistances are in parallel.
reqSis the feet to soil resistance for step voltage, i.e. the two
feet to soil resistances are in series.
The IEC 479-1 does not provide any data for r e , , or
req,* For this reason, we shall use the data of IEEE Std 80,
i.e. Eqns. 3 and 4.
Note that application of above equations to obtain the
permissible touch and step voltages is straightforward and
involves the following steps:
Step 1: For a given electric shock duration t and assumed
probability of ventricular fibrillation, determine the value
of permissible body current, ib,penn(t), from Fig. 7.
Step 2 For the current ib,penn(t), determine the body resist-
ances RbT and Rbs from the data of Figs. 5 and 6. For
touch voltage it is expedient to assume that the path will be
one hand to two feet (75% of the body resistance given in
Fig. 5), and for step voltage the path is foot to foot (100%
of the body resistance given in Fig. 5).
Step 3: Compute req,Tand reqSfor IEEE Std 80.
Step 4: Compute permissible touch and step voltages using
eqns. 6 and 7
For comparison purposes with the IEEE Std 80, the per-
missible body current ib,pem(t) is computed for probability
0.5'1/0 of ventricular fibnllation by proper interpolation
between the curves C1 and C2 of Fig. 7.
Pa' a
Fi .6 Internal i m p e k e of the human bo& as a fiction of the current
Numbers in brackets indicate current paths between both hands and corresponding
part of the body. Numbers without brackets indicate impedance of several paths in 4.2 Computation of actual body current
the body as percentage of hand to hand impedance. Data from IEC 479-1 (1984). For a given touch or step voltage, the computation of the
body current using the IEC data requires the solution of a
set of nonhear equations. This solution can be obtained
iteratively or with a graphical method described below.
a
E
3L
10-
zone 4
Step 1: Compute the Thevenin equivalent resistance, req, of
the electrocution circuit.
Step 2 For a given (or computed) touch (or step) voltage
and equivalent resistance re from step 1, the actual body
current is computed with t i e graphical method shown in
Fig. 8. Specifically, the actual body current is determined
by the simultaneous solution of the following two equa-
10
zone2 '--. tions:
&ouch v b $- r e q i b (8)
1 2 3 4
10 10 10 10
duration of current-flow, ms Ib = V b / r b = T/b/f(Vb) (9)
Fig.7 Permissible bo4 currentfor IEC 479-1 where the function rb = V b ) represents the nonlinear char-
acteristics of the body resistance as a function of body volt-
4. I Permissible touch and step voltage - age determined with the data of Fig. 5. Note that eqn. 9
IEC 479-1 represents a nonlinear function whch is illustrated in Fig. 8
The permissible (or allowable) touch, VTa,and step, Vf, as curve 1.
voltages are computed from the following equations
v$ = i b , p e r m ( t ) [RF ( i b , p e r m ( t ) ) $- r e q , ~ ] (6) 350
r1-
v: = i b , p e r m ( t ) [Rf ( i b , p e r m ( t ) ) $- Teq,S] (7) CUNe 1
where ibgem(t) is the permissible body current for IEC 479-
1 for an electric shock duration t. This current is obtained
from the data of Fig. 7. &T(ib,pem(t)) is the body resistance
for the path specified by the touch voltage (typically hand
to two feet) and for a body current equal to ibpem(t). This 50
value can be obtained from the data of Figs. 5 and 6. B(Vtouch/req, 0)
I 1
0
R,,s(ib,pem(t)) is the body resistance for the path specified by 0 50 100 150 200 250 300 350 400
the step voltage (foot to foot) and for a body current equal body current, mA
to ibgem(t). This value can be obtained from the data of Fig.8 Graphical methodof computing a c t d b o r f v current
596 IEE Proc-Cener. Transm. Distrib., Vol. 146, No. 5, September 1999
Table 2: Permissible touch voltages per IEEE Std 80,1986 edition 50kg person, probability of
ventricular fibrillation 0.5%
Table 3: Permissible step voltages per IEEE Std 80,1986 edition, 50 kg person, probability of
ventricular fibrillation 0.5%
Table 4 Permissible touch voltages per IEC 479-1,5% body resistance values, probability of
ventricular fibrillation 0.5%, hand to two feet
IEE Proc-Gener. Transm. Distrib., Vol. 146. No. 5. September 1999 591
Table 5: Permissibletouch voltages per IEC 479-1,50% body resistancevalues, probability of
ventricular fibrillation 0.5%, hand to two feet
Table 6: Permissible step voltages per IEC 479-1,5% body resistance values, probability of
ventricular fibrillation 0.5%, hand to two feet
Table 7: Permissible step voltages per IEC 479-1,50% body resistance values, probability of
ventricular fibrillation 0.5%. hand to two feet
Figs. 9-12 provide the data of Tables 2-7 in graphical diagonal represent cases where the IEEE Std 80 is more
form. The coordinates are the permissible touch or step conservative than the IEC 479-1. Note that the points are
voltages of the two standards, respectively. Each point rep- about evenly distributed around the diagonal. Finally,
resents permissible voltages, as allowed by the two stand- Figs. 13 and 14 compare the body resistance value used for
ards computed for the same parameters of soil resistivity the computation of the permissible touch and step voltages
and shock duration. By construction, then, each point on with the two standards. Note that for the usual shock dura-
the diagonal of the graph represents a case where the two tions 0.25-0.5s, the 5% body resistance of the IEC 479-1
standards yield the same permissible voltages. Points above standard is near 100052 or higher. Ths is useful informa-
the diagonal represent cases where the IEC 479-1 is more tion for persons questioning the use of 100OQ in the IEEE
conservative than the IEEE Std 80, whde points below the Std 80.
598 IEE Proc.-Gener. Transm. Distrib., Vol. 144, No. 5, September 1999
1600 -
1400 -
IEC 479-1 more
1200 -
d
5
c
.I
p!
1000 -
800 -
- - IEEEStd 80
A
U
600 -
IEEE Std 80 more
conservativethan 13 400-
200 -
0.5 1.0 1.5 2.0 2.5 3.0 01
0
I
0.10
I
0.20
I
0.30
I
0.40
0.50
permissible touch voltage, kV (IEC 479-1)
electric shock duration, s
Fi 9 Permissible touch voltages er IEEE Std 80 against IEC 479-1; 5%
bog resistunce values, probability ofvenntricular fibrillation 0.5% hand to two Fi . I 3 Body resistance against electric shock duration at mwcimm permis-
feet sib! touch voltage; 5% body resistance values, hund to two@et
11
10 IEC 479-1 more IEC 479-1
g 1000
1
IEEE Std 80
2 800
x5 600
400
3 IEEE Std 80 more
conservativethan
2
IEC 479-1
A 0 0.10 0.20 0.30 0.40 0.50
1 2 3 4 5 6 7 8 9 1011 electric shock duration, s
permissible step voltage, kV (IEC 479-1)
Fi . I 4 Body resistance aguinst electric shock h a t i o n at mm permis-
Fig. 10 Permissible step voltages per IEEE Std 80 vs IEC 479-1; 5% body sib!! t a c h voltage; 50Y( I body resistance values, hand to twofeet
resistme values, probubility of ventriculrufbrilhtion 0.596, hund to two feet
6
3.0
2.5 -
r IEC 479-1 more
conservativethan
The safety criteria of the IEC 479-1 and IEEE Std 80 have
been compared and their differences have been quantified.
B IEEE Std EO There are cases in whch the IEEE Std 80 is more conserv-
86 ative than the IEC 479-1 and vice versa. The IEC 479-1
m 2.0 -
co
SQ safety criteria are rather complex, while the safety criteria
1.5- of IEEE Std 80 are simplified. The opinion of the authors
2g is that simplicity is important. Given the fact that the safety
.g 2 1.0 - x x / ,LEE Std 80 more criteria include comfortable safety margins, one can con-
Conservativethan clude that the simplicity of the IEEE Std 80 does not com-
0.5 IEC 479-1 promise safety in grounding system design. Another major
difference is that the IEC 479-1 does not address all rele-
0.5 1.0 1.5 2.0 2.5 3.0
vant computational issues, while the IEEE Std 80 provides
permissible touch voltage, kV (IEC 479-1)
approximate equations and formulas which are useful to a
Fi .I1 Permissible touch voltagesper IEEE Std 80 ugaht IEC 479-1; 50% designer. The IEEE Std 80 also provides useful procedures
b a resistance values, probability of ventricular fbrilhtion 0.5%, hand to two
feet for grounding systems safety assessment.
References
11
ANSVIEEE Std 80-1986: IEEE guide for safety in AC substation
IEC 479-1 more grounding. 1986
conservativethan SAKIS MELIOPOULOS, A.P.: Power system grounding and tran-
IEEE Std 80 sients: an introduction (Marcel Defier, Inc., New York, 1988), pp.
7 119-133
International Electrotechnical Commission IEC Report: Effects of
6 current passing through the human body, part 1: general aspects. 479-
5 t / x
1, IEC 1984
SAKIS MELIOPOULOS, A.P., XIA, F., JOY, E.B., and COKKI-
IEEE Std 80 more NIDES, G.J.: An advanced computer model for grounding system
conservativethan analysis, IEEE Trans. Power Deliv., 1993, 8, (l), pp. 1%23
IEC 479-1
Appendix: Analytical expressions of body
1 2 3 4 5 6 7 8 9 10 11 resistance vs. body voltage
permissible step voltage, kV (IEC 479-1)
Fi .I2 Peimirsible step voltages er IEEE Std 80 against IEC 479-1; 50% This Appendix presents analytic expressions for the volt-
bo!y resistance values, probability of ventricularfibrillation 0.5%, hund to two age-dependent body resistance which closely match the IEC
feet 479-1 data. These formulae can be used in lieu of the
IEE Proc.-Gener. Transm. Distrib., Vol. 146, No. 5, September 1999 599
\
Table 8 Total body impedance, per IEC 479-1 (data from IEC tabular data of the IEC 479-1. Table 8 presents a reproduc-
479-1 (1984)) tion of body resistance data in the IEC 479-1. The Table
contain three sets of data corresponding to the stafistical
Values for the total body impedance (9)that are not values of 5%, 50% and 95% of population (see IEC 479-1).
Touch exceeded for a percentage (percentile rank) of Each one of the sets can be approximated with one analytic
voltage (v) 5% of the 50% of the 95% of the function of the form
population population population
Rb,model(Z) = R b , m o d e l (a1> b l >c 1 , 210)
25 1750 3250 6100
50 1450 2625 4375
75 1250 2200 3500
1200 1875 3200
&,model (z)= &,model ( ~ 2b ,2 ~ 2 ~ 2 0 )
100
125 1125 1625 2875 = U 2 -k bzib -k C2 *
220 1000 1350 2125 The coefficients a l , bl, c1 and vo or the vector X = [al, bl,
700 750 1100 1550 c1, vo] and the coefficients q,b2, c2 and i,, or the vector X =
[a2,b2, c2, io] will be different for each one of the three sets
1000 700 1050 1500
of data. For each data set, the unknown vectors x = [al, bl,
2000 677 1084 1464 c1, volT and x = [a2, b2, c2, &IT are computed by the
weighted least squares method, i.e. by solving the following
Table 9: Computed coefficients of the analytic expressions optimisation problem.
for body resistance m
Minimise J = wir: = rTWr
5% of the 50% of the 95% of the
i= 1
population population population
where r = w iis weight for the resid-
- Rb,mode,(~),
a1 668.381 1080.02 1 1427.296
ual ri, and W is a diagonal matrix, the diagonal elements
bl 15344.426 7751.063 73049.270 being the weights w i
C1 515.588 2552.197 21 19.462 The solution to the above nonlinear estimation problem
Vn 311.673 80.182 131.727 is obtained with the following algorithm
5"" = X u - (HTWH)-lWTWIRb,modei(Zu)
- b]
Table IO: Computed coefficients of the analytic expressions
for body voltage where b = Rb,mpanued,
Rb(xV+')- R&") + H.(x"+~
- x"), and
H = dRb(X)/aXIX=XO
5% of the 50% of the 95% of the The computed analytic expression for the three sets of
population population population data, using the above algorithm with wi = 1.0 for all i, are
a2 140.6 63.1 77.8 listed in Tables 9 and 10.
9 0.6 1.o 1.4 The accuracy of the derived analytic expressions as com-
pared to the IEC 479-1 data is illustrated in Tables 11 and
Q -130.1 -50.5 -68.0
12. For all practical purposes, the analytic expressions can
io 241.1 48.1 26.9 be used in lieu of the data of Table 8.
Table 11: Comparison of the proposed formula for resistance to the IEC 479-1
data
Values for the total body impedance (a)that are not exceeded for a percentage
(percentilerank) of
Touch
voltage 5% of the population 50% of the population 95% of the population
.-.
IVI
Proposed
Proposed IEC 479-1 Proposed
IEC 479-1 formula formula IEC 479-1 formula
25 1750 1758.0 3250 3258.6 6100 6102.3
50 1450 1414.4 2625 2603.1 4375 4338.3
75 1250 1278.3 2200 2185.0 3500 3600.7
100 1200 1195.9 1875 1890.8 3200 3149.8
125 1125 1136.4 1625 1678.9 2875 2832.2
220 1000 992.7 1350 1279.4 2125 2158.3
700 750 744.9 1100 1091.5 1550 1542.1
1000 700 704.6 1050 1087.8 1500 1501.4
2000 677 668 1084 1080.0 1464 1427.0
600 IEE Proc-Gener. Transm. Distrib., Vol. 146, No. 5, September 1999
Table 12: Comparison of the proposed formula for body current vs. body voltage to the IEC 479-1 data
Values for the body voltage (V) that are not exceeded for a percentage (percentile rank) of