Mini Mate de 2-3 TR Tecnico Sl-10535
Mini Mate de 2-3 TR Tecnico Sl-10535
5 kW) Capacity
Technical Data ManualAir, Water, Glycol, Chilled Water, 50 & 60Hz
TABLE OF CONTENTS
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 Designed to Match Computer and Electronic Equipment NeedsFrom Installation
to Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0 STANDARD FEATURES2 & 3 TON SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.1 Evaporator Section - Split Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2 Condensing Unit SectionSplit Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2.1 Indoor Centrifugal Fan Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2.2 Outdoor Prop Fan Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2.3 Indoor Water/Glycol Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.3 Chilled Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.4 System Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.4.1 Other Standard Control Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.0 OPTIONAL FACTORY-INSTALLED FEATURESEVAPORATOR/CHILLED WATER UNITS . . . . . .4
3.1 Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.2 Humidifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.3 Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.4 Switches and Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.5 Free-Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.6 Optional ConfigurationsProp Fan Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.7 Optional ConfigurationsWater/Glycol Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.8 Optional ConfigurationsChilled Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.0 SHIP-LOOSE ACCESSORIESFIELD-INSTALLED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
4.1 Remote Monitoring, Autochangeover, and Leak Detection Equipment . . . . . . . . . . . . . . . . . 6
5.0 FLEXIBLE CONFIGURATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
6.0 AIR-COOLED SYSTEMSCAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . .9
7.0 WATER/GLYCOL SYSTEMSCAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . 16
8.0 CHILLED WATER SYSTEMSCAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . 22
9.0 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
10.0 REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
11.0 GLYCOL LOOP PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
12.0 MODEL NUMBER NOMENCLATUREALL SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
GUIDE SPECIFICATIONS FOR LIEBERT MINI-MATE22- AND 3-TON SYSTEMS . . . . . . . . . . . . . . . . 43
1.0 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
2.0 PRODUCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3.0 EXECUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
i
FIGURES
Figure 1 Wall-box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 2 Free-cooling arrangement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 3 Air-cooled condensing unitssplit systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 4 Water/glycol condensing unitssplit systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 5 Chilled water units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 6 General arrangement, air-cooled split systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 7 Free-cooling arrangement, air-cooled units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 8 Dimensions, evaporator units with direct drive blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 9 Dimensions, evaporator units with optional belt drive blower assembly . . . . . . . . . . . . . . . . . . . 13
Figure 10 Dimensions, indoor air-cooled condensing unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 11 Cabinet and floor planning dimensional data, outdoor condensing unit . . . . . . . . . . . . . . . . . . . . 15
Figure 12 General arrangement, water/glycol split systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 13 General arrangement, free-cooling coil with water/glycol condensing units . . . . . . . . . . . . . . . . . 18
Figure 14 Dimensions, evaporator units with direct drive blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 15 Dimensions, evaporator units with optional belt drive blower assembly . . . . . . . . . . . . . . . . . . . 20
Figure 16 Cabinet dimensions and piping data, water/glycol indoor condensing module . . . . . . . . . . . . . . . 21
Figure 17 General arrangement, chilled water split systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 18 General arrangement, hot water reheat, chilled water units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 19 Dimensions, chilled water units with direct drive blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 20 Dimensions, chilled water units with optional belt drive blower assembly . . . . . . . . . . . . . . . . . 25
Figure 21 Single-point power kit - optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 22 Refrigerant piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 23 Heat rejection loop, multiple drycoolers and multiple indoor units. . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 24 Model number nomenclatureEvaporator units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 25 Model number nomenclatureAir-cooled, indoor condensing units . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 26 Model number nomenclatureOutdoor air-cooled prop fan condensing units . . . . . . . . . . . . . . . 41
Figure 27 Model number nomenclatureWater/glycol-cooled condensing units. . . . . . . . . . . . . . . . . . . . . . 41
Figure 28 Model number nomenclatureChilled water units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
ii
TABLES
Table 1 Air-cooled data, 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 2 Air-cooled data, 50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 3 Net weightssplit system evaporator units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 4 Net weight, high static blower module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table 5 Dimensions and net weights, indoor air-cooled condensing units . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 6 Dimensions and net weightsair-cooled outdoor condensing units . . . . . . . . . . . . . . . . . . . . . . . 15
Table 7 Water/glycol data, 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 8 Water/glycol data, 50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 9 Net weightssplit system evaporator units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 10 Net weight, high static blower module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 11 Net weight, indoor water/glycol-cooled condensing unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 12 Chilled water data, 60 and 50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 13 Capacity Correction Factors (based on 10F (5.6C) water rise) . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 14 Chilled water units with direct drive blower weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 15 Net weight, high static blower module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 16 Direct drive split system evaporator or chilled water unit electrical data, 60Hz . . . . . . . . . . . . . 26
Table 17 Belt drive split system evaporator or chilled water electrical data, with high static blower
box, 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 18 Direct drive split system evaporator or chilled water electrical data, 50Hz . . . . . . . . . . . . . . . . . 28
Table 19 Belt drive split system evaporator or chilled water electrical data, 50Hz. . . . . . . . . . . . . . . . . . . 28
Table 20 Indoor condensing unit electrical data, 60 and 50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 21 Outdoor condensing unit electrical data, 60 and 50Hz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 22 Electrical data, 60Hz air-cooled systems using single-point power kit, evaporator with
direct-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 23 Electrical data, 60Hz air-cooled systems using single-point power kit, evaporator with
belt-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 24 Electrical data, 50Hz air-cooled systems using single-point power kit, evaporator with
direct-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 25 Electrical data, 50Hz air-cooled systems using single-point power kit, evaporator with
belt-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 26 Electrical data, 60Hz water/glycol-cooled systems using single-point power kit, evaporator
with direct-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 27 Electrical data, 60Hz water/glycol-cooled systems using single-point power kit, evaporator
with belt-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 28 Electrical data, 50Hz water/glycol-cooled systems using single-point power kit, evaporator
with direct-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 29 Electrical data, 50Hz water/glycol-cooled systems using single-point power kit, evaporator
with belt-drive blowers and indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 30 Refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 31 Recommended refrigerant line sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 32 Pipe length and condenser elevation relative to evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 33 Line charges - refrigerant per 100 ft. (30m) of Type L copper tube . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 34 Refrigerant charge in Liebert pre-charged R-407C line sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Table 35 Equivalent lengths for various pipe fittings, ft (m). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
iii
iv
Introduction
1.0 INTRODUCTION
1 Liebert Mini-Mate2
Standard Features2 & 3 Ton Systems
2 Liebert Mini-Mate2
Standard Features2 & 3 Ton Systems
3 Liebert Mini-Mate2
Optional Factory-Installed FeaturesEvaporator/Chilled Water Units
3.1 Reheat
Electric Reheat includes 304/304 stainless steel finned tubular reheat elements, with high limit
safety switch.
SCR Electric Reheat uses an SCR controller and unit control software to provide full cooling with
modulating of the electric reheat elements to control air temperatures. Reheat capacity is up-sized to
offset the cooling capacity. (The SCR Electric Reheat is not available on chilled water, free-cooling or
575V units.)
Hot Water Reheat includes hot water coil, 2-way solenoid valve and Y-strainer.
NOTE
This option is available only on Chilled Water units, but not with other reheat options.
3.2 Humidifier
The Canister Humidifier includes a steam-generating type humidifier with automatic flushing
circuit, inlet strainer, drain, 1" (25.4mm) air gap on fill line and solenoid valves. Humidifier problem
alarm annunciates at the wall-mounted display panel.
Remote Humidifier Contact allows the units humidity controller to control a humidifier outside
the unit. Power to operate the remote humidifier does not come from the Liebert Mini-Mate2.
Available on units with or without internal humidifier.
3.3 Sensors
Smoke Sensor checks return air, shuts down the unit upon sensing smoke and activates visual and
audible alarms at the wall-box display. This smoke sensor is not intended to function as or replace
any smoke sensor system that may be required by local or national codes.
High-Temperature Sensor senses the return air temperature and shuts down unit if the
temperature reaches 125F (52C). This device is not meant to replace any fire detection system that
may be required by local or national codes.
3.5 Free-Cooling
Free-cooling option includes separate cooling coil, three-way slow-close valve and separate supply and
return piping. Free-cooling is activated when the water temperature reaches a field-adjustable
temperature, typically 45F (7C). The valve is rated for 300psi (2068kPa) working pressure.
Air-cooled condensing units can be matched with evaporators using free-cooling coils with chilled
water sources to serve as backup cooling. When matched with a water/glycol condensing unit, a
three-way water regulating valve is recommended for the condensing unit to simplify piping to the
main supply pipes. The coil is designed for closed-loop applications using properly treated and
circulated fluid. Not available with SCR reheat options.
4 Liebert Mini-Mate2
Optional Factory-Installed FeaturesEvaporator/Chilled Water Units
Water/Glycol
Condenser
Field Piping
NOTE
If free-cooling is applied to an open water tower, an optional cupro-nickel (CuNi) coil is
required to prevent premature corrosion, or a heat exchanger must separate the tower water
from the free-cooling loop. The cupro-nickel coil requires an extended lead time.
5 Liebert Mini-Mate2
Ship-Loose AccessoriesField-Installed
NOTE
Installing the remote sensors disables the sensors included in the wall box.
Field-Installed Kits available for filter clog, smoke sensor, high-temperature sensor, electric reheat
and humidifier. The kits include installation instructions and are designed to be added to the
evaporator unit before it is installed in the ceiling. Electric reheat kits cannot be installed in units
with free-cooling.
277-to-208V step-down transformer (37.5 amps) allows use of 277-1-60 supply power with a
208-1-60 Prop Fan Condensing unit. The transformer is coated with epoxy and contained in an
enclosed, non-ventilated electrical box with adaptable mounting brackets.
Single-Point Power Kit contains the necessary electrical components to interconnect the
high-voltage sections of a close-coupled evaporator and an MCD condensing unit.
Pre-Charged Refrigerant Line Set (R-407C) contains an insulated copper suction line and a
copper liquid line for interconnection of the indoor and outdoor sections. Available in 15-foot (4.5m)
and 30-foot (9m) sections.
The Refrigerant-Line Sweat Adapter Kit contains two suction and two liquid line fittings that
allow field-supplied refrigerant piping between the evaporator and condensing unit.
Liebert Mini-Mate2 6
Ship-Loose AccessoriesField-Installed
The Liebert AC8 is ideal for coordinated control of systems with redundant units. The Liebert
AC8 enables redundant devices during an alarm condition, balances usage of devices and tests
standby devices at programmable intervals. Supports four zones and can use the 4-20mA
temperature sensor (TW420) for temperature staging in each zone. Two programmable output control
relays are available for auxiliary control such as humidity lockout. Emergency power operation input
provided for device control during an emergency. Two common alarm relay outputs are available. A
built-in LCD and RS-232 port for direct PC/terminal connection provides two options for configuration
and monitoring of the product.
The Liebert ENV-DO interface card provides 16 discrete outputs, corresponding to status and
major alarm conditions of Environmental units. The Liebert ENV-DO-ENCL1 packages one
Environmental DO interface card in its own steel enclosure and the ENV-DO-ENCL2 packages two
Environmental DO interface cards in one enclosure for installation external to the Liebert
Mini-Mate2. The self-contained kit includes an external 120VAC-to-24VAC power transformer.
Wiring harnesses are not provided. Power and communication wiring is field-provided.
The Liebert Liqui-tect 410 Point Leak Detection Sensor detects the presence of conductive
liquid using a pair of corrosion-resistant, gold-plated probes mounted in a painted, height-adjustable
enclosure. Dual Form-C, dry contact common alarm relays (rated at 24VAC, 3A) signal a leak
detected as well as loss of power and cable fault. The Liebert Liqui-tect 410 requires an external
24VAC or 24VDC power source.
Liebert LT460 Zone Leak Detection Kits include one LT460 sensor, a specified length of
LT500-xxY cable (maximum length is 100 ft [30.5m]) and a corresponding number of hold-down clips.
The Liebert LT460 requires an external 24VAC, 0.12A power source, such as EXT-XFMR or XFMR24.
Liebert SiteScan is a monitoring solution that gives you decision-making power to effectively
manage the equipment critical to your business.
Liebert SiteScan enables communication from Liebert environmental and power units, as well as
many other pieces of analog or digital equipment, to a front-end software package that provides
real-time status and alarms so you can react quickly to changing situations.
Liebert SiteScan is designed with flexibility for both small systems and large, complex systems such
as those in computer rooms, telecommunications facilities or industrial process control rooms.
Contact your local Emerson representative for assistance with a Liebert SiteScan system.
The NIC-ENCL1 and NIC-ENCL2 package one or two Liebert IntelliSlot Web/485 Cards with
Adapters, respectively, in one steel enclosure for installation external to the Liebert Mini-Mate2. The
Liebert IntelliSlot Web/485 Card with Adapter provides communication with Liebert Mini-Mate2 via
SNMP, HTTP, RTU Modbus 485 and BACnet IP. The self-contained kit includes an external
120VAC-to-24VAC transformer as a power source. Wiring harnesses are not provided. Power and
communication wiring is field-provided.
7 Liebert Mini-Mate2
Flexible Configurations
Air Ducted
Air Plenum
Liebert Mini-Mate2 8
Air-Cooled SystemsCapacities and Dimensions
Liebert Mini-Mate2 9
Air-Cooled SystemsCapacities and Dimensions
Liebert Mini-Mate2 10
Air-Cooled SystemsCapacities and Dimensions
Condenser
Coil
High Pressure
Scroll Switch
Compressor
Liquid Injection
Valve Bulb
Hot Gas Bypass
Solenoid Valve 3/8" SAE 45 Male Flare
Suction Line Male Quick (MCD) or Atmospheric (PFH)
Connect Coupling Pressure Relief Valve
ad
ay He
Suction Line Female Quick 3 - W re
su
Connect Coupling Pres Valve Check
* e lief Valve Sight Glass
R
pass
as By
Sensing Bulb Hot G Valve
l
Contro
External Equalizer
Liquid Injection
Valve
Liquid Line Lee - Temp
Service Access Solenoid Valve Receiver
Receiver
Ports Heater
* Liquid Line Male Quick Pressure
Connect Coupling Limiting Pressure Balancing
Switch Valve
Liquid Line Female Quick
Connect Coupling
DPN000191
Rev. 2
Evaporator Coil
Free-Cooling
Control
Fluid
Valve
Fluid Return
Supply From Unit Free Cooling
To Unit Coil
Shutoff
Valves * Temperature Stat
Liebert Mini-Mate2 11
Air-Cooled SystemsCapacities and Dimensions
Removable panel on
side of plenum.
Minimum clearance
30" (762mm) for flter
access and removal
6" (152mm)
5"
(127mm)
48" 3-1/4"
(1219mm) (83mm)
24"
Overall
(610mm)
Air Discharge out Dimension
Overall
sides of plenum Dimension
Air Discharge out
Sides of Plenum
Liebert Mini-Mate2 12
Air-Cooled SystemsCapacities and Dimensions
Figure 9 Dimensions, evaporator units with optional belt drive blower assembly
29-7/8" (759mm)
Threaded
Rod Centers 57-13/16" (1468mm)
16-13/16" (427mm) Overall Dimension
Threaded Rod Centers
30" (762mm)
Blower Box
Dimension 55-13/16" (1418mm)
19" (483mm) Threaded Rod Centers
Blower Box
Dimension High Static
Blower
Module
9-3/4" Outlet Evaporator
(248mm)
Unit
5-7/8" 24" (610mm)
(149mm) Cabinet
Dimension
6-7/8" (175mm)
6-5/16" (160mm) Outlet
4-29/32" (125mm)
Threaded Rod 3-7/32"
To Threaded Rod (82mm)
Base to 4-29/32" (125mm)
Base Cabinet to Cabinet
54" (1372mm)
Cabinet Dimension 30" (762mm)
Cabinet
14"
Dimension
(356mm)
Outlet
Dimension
18 "
(457mm)
Outlet
Dimension
DPN000194
Rev. 3
Liebert Mini-Mate2 13
Air-Cooled SystemsCapacities and Dimensions
Customer Supplied
22-3/4" (578mm) Threaded Rods
50-1/4" (1276mm) Overall Dimension
Overall Dimension for Module Support
21-1/2 " (546mm) from Ceiling (typ. 4)
46-1/2" (1181mm) Cabinet Dimension
Cabinet Dimension 19-1/2" (495mm) C
48- 1/4" (1225mm) Threaded Rod
Threaded Rod Centers Centers
1/2" (13mm)
D Air Outlet
20-3/4" Duct Connection
(527mm)
22-1/2" 20-7/16"
(572mm) (519mm)
Cabinet Coil Inlet
Dimension B Air Outlet
Duct Conn. Duct Dimension
30-1/8" A
(765mm) Blower Motor Service Access
Holes for Module Coil Inlet Panel on Bottom of Unit
Duct Connection Minimum Clearance 33" (838mm)
Rigging (typ. 2 each end)
Duct Flange for Component Access and Removal.
Integral 1"
(25.4mm)
Hanging Bracket 2-1/4"
Minimum Clearance 33" (838mm) (57mm)
This End for Component Access
and Removal Note: Unit is evenly spaced in
reference to threaded rod centers.
7/8" (22.2mm) Dia. DIMENSIONAL DATA
Electrical Entrance
for Line Voltage
Connection.
7/8" (22.2mm) Dia.
Electrical Entrance
for Low Voltage
Connection.
Suction Line
Male Quick
Connect
Liebert Mini-Mate2 14
Air-Cooled SystemsCapacities and Dimensions
Figure 11 Cabinet and floor planning dimensional data, outdoor condensing unit
Shaded area
indicates a minimum
B
clearance of 18" (457mm)
for proper air flow.
Shaded area
indicates a recommended
C
clearance of 24" (610mm)
for component access and
Shaded area removal.
indicates a minimum Removable panel for access
clearance of 18" (457mm) to high-voltage and low-voltage
for proper air flow connections and refrigeration DPN000130
components Rev. 1
Liebert Mini-Mate2 15
Water/Glycol SystemsCapacities and Dimensions
Liebert Mini-Mate2 16
Water/Glycol SystemsCapacities and Dimensions
Liebert Mini-Mate2 17
Water/Glycol SystemsCapacities and Dimensions
High Pressure
Scroll Switch
Scroll Tube in Tube
Compressor Condenser
Liebert Mini-Mate2 18
Water/Glycol SystemsCapacities and Dimensions
Removable panel on
side of plenum.
Minimum clearance
30" (762mm) for flter
access and removal
6" (152mm)
5"
(127mm)
48" 3-1/4"
(1219mm) (83mm)
24"
Overall
(610mm)
Air Discharge out Dimension
Overall
sides of plenum Dimension
Air Discharge out
Sides of Plenum
Liebert Mini-Mate2 19
Water/Glycol SystemsCapacities and Dimensions
Figure 15 Dimensions, evaporator units with optional belt drive blower assembly
29-7/8" (759mm)
Threaded
Rod Centers 57-13/16" (1468mm)
16-13/16" (427mm) Overall Dimension
Threaded Rod Centers
30" (762mm)
Blower Box
Dimension 55-13/16" (1418mm)
19" (483mm) Threaded Rod Centers
Blower Box
Dimension High Static
Blower
Module
9-3/4" Outlet Evaporator
(248mm)
Unit
5-7/8" 24" (610mm)
(149mm) Cabinet
Dimension
6-7/8" (175mm)
6-5/16" (160mm) Outlet
4-29/32" (125mm)
Threaded Rod 3-7/32"
To Threaded Rod (82mm)
Base to 4-29/32" (125mm)
Base Cabinet to Cabinet
54" (1372mm)
Cabinet Dimension 30" (762mm)
Cabinet
14"
Dimension
(356mm)
Outlet
Dimension
18 "
(457mm)
Outlet
Dimension
DPN000194
Rev. 3
Liebert Mini-Mate2 20
Water/Glycol SystemsCapacities and Dimensions
Figure 16 Cabinet dimensions and piping data, water/glycol indoor condensing module
8-7/8" (225mm) 14" (356mm)
3-7/8" (98mm) 50-1/4" (1276mm) Overall Cabinet
Overall Dimension Dimension
48-1/4" (1225mm) 12" (305mm)
8-7/16" Threaded Rod Centers Threaded Rod
(214mm) Centers
46-1/2" (1181mm)
Cabinet Dimension
20-3/4"
(527mm)
22-1/2"
Customer-Supplied (572mm) Cabinet
Threaded Rods for Dimension
Module Support Outlet
from Ceiling (typ. 4) Inlet
Minimum Clearance
33" (838mm) this side
for component access
Holes for Module
and removal.
Rigging (typ. 2 each end) Note:
Integral Unit is spaced evenly in
Hanging reference to threaded rod centers
Bracket
DIMENSIONAL DATA
7/8" (22.2mm) OD CU
Water/Glycol Inlet Connection
Extends 3-1/2" (88.9mm) beyond
7/8" (22.2mm) OD CU panel exterior
Water/Glycol Outlet Connection 7/8" (22mm) Dia.
Extends 3-1/2" (88.9mm) beyond Electrical Entrance
panel exterior for High Voltage
Connection
Suction Line
Male Quick
Connect
Liquid Line
Male Quick
Connect
Liebert Mini-Mate2 21
Chilled Water SystemsCapacities and Dimensions
Liebert Mini-Mate2 22
Chilled Water SystemsCapacities and Dimensions
Bleed Valve
Chilled Water
Chilled Control Valve
Water 3 - Way Chilled Water
Chilled Supply Control Valve
Water (Optional)
Return Chilled Water Coil
Shutoff Valves *
Hose Bibs *
FIELD PIPING
** Components are not supplied by FACTORY PIPING
Emerson but are recommended for
proper circuit operation and
maintenance. DPN000191
Rev. 2
Figure 18 General arrangement, hot water reheat, chilled water units
Bleed Valve
Hot Water
Reheat
Control
Water Valve
Water Supply
Return To Unit Hot Water
From Unit Reheat
Coil
Shutoff
Valves * Y-Strainer
FIELD PIPING
Hose FACTORY PIPING
Bibs *
NOTE: Hot water reheat only available
* Components are not supplied on chilled water units.
by Liebert but are recommended
DPN000197
for proper circuit operation and
maintenance. Rev. 2
23 Liebert Mini-Mate2
Chilled Water SystemsCapacities and Dimensions
Removable panel on
side of plenum.
Minimum clearance
30" (762mm) for flter
access and removal
6" (152mm)
5"
(127mm)
48" 3-1/4"
(1219mm) (83mm)
24"
Overall
(610mm)
Air Discharge out Dimension
Overall
sides of plenum Dimension
Air Discharge out
Sides of Plenum
Liebert Mini-Mate2 24
Chilled Water SystemsCapacities and Dimensions
Figure 20 Dimensions, chilled water units with optional belt drive blower assembly
29-7/8" (759mm)
Threaded
Rod Centers 57-13/16" (1468mm)
16-13/16" (427mm) Overall Dimension
Threaded Rod Centers
30" (762mm)
Blower Box
Dimension 55-13/16" (1418mm)
19" (483mm) Threaded Rod Centers
Blower Box
Dimension High Static
Blower
Module
9-3/4" Outlet Evaporator
(248mm)
Unit
5-7/8" 24" (610mm)
(149mm) Cabinet
Dimension
6-7/8" (175mm)
6-5/16" (160mm) Outlet
4-29/32" (125mm)
Threaded Rod 3-7/32"
To Threaded Rod (82mm)
Base to 4-29/32" (125mm)
Base Cabinet to Cabinet
54" (1372mm)
Cabinet Dimension 30" (762mm)
Cabinet
14"
Dimension
(356mm)
Outlet
Dimension
18 "
(457mm)
Outlet
Dimension
DPN000194
Rev. 3
Liebert Mini-Mate2 25
Electrical Data
Liebert Mini-Mate2 26
Electrical Data
Table 17 Belt drive split system evaporator or chilled water electrical data, with high static blower box,
60Hz
208/230 - 1 Ph - 60Hz 277 - 1 Ph - 60Hz 208/230 - 3 Ph - 60Hz 460 - 3 Ph - 60Hz
Base Evaporator
Model Number MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E
Cooling Only
FLA 9.2 9.2 6.4 6.4 4.8 2.1
WSA 11.5 11.5 8.0 8.0 6.0 2.6
OPD 20 20 15 15 15 15
with Electric Reheat
FLA 34.2 34.2 28.1 28.1 21.6 10.5
WSA 42.8 42.8 35.1 35.1 27.0 13.1
OPD 45 45 40 40 30 15
5
with SCR Reheat
FLA 38.4 50.9 31.7 42.5 28.9 14.2
WSA 48.0 63.6 39.6 53.1 36.1 17.8
OPD 50 70 40 60 40 20
with Humidifier
FLA 15.6 15.6 12.1 12.1 11.2 5.5
WSA 19.5 19.5 15.1 15.1 14.0 6.9
OPD 25 25 20 20 15 15
with Electric Reheat and Humidifier
FLA 40.6 40.6 33.8 33.8 28.0 13.9
WSA 50.8 50.8 42.3 42.3 35.0 17.4
OPD 60 60 45 45 40 20
5
with SCR Reheat and Humidifier
FLA 44.8 57.3 37.4 48.2 35.3 17.6
WSA 56.0 71.6 46.8 60.3 44.1 22.0
OPD 60 80 50 70 45 25
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from unit.
2. Use MM*36E electrical data for MM*40C chilled water units.
3. For units with Hot Water Reheat (available only on MM*40C units), use appropriate values from Cooling only or with Humidifier
categories.
4. Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
5. SCR Reheat not available with MM*24K, MM*36K or MM*40C.
Liebert Mini-Mate2 27
Electrical Data
Table 18 Direct drive split system evaporator or chilled water electrical data, 50Hz
220 - 1Ph - 50Hz 380/415 - 3Ph-50Hz
Base Evaporator Model Number MM*35E MM*35E
Cooling Only
FLA 2.8 1.4
with Electric Reheat
FLA 27.8 11.1
with SCR Reheat 4
FLA 44.6 15.3
with Humidifier
FLA 9.2 5.1
with Electric Reheat and Humidifier
FLA 34.2 14.8
4
with SCR Reheat and Humidifier
FLA 50.9 19.0
* Specify disconnect or no disconnect
Notes:
1. Use MM*35E electrical data for MM*39C chilled water units.
2. For units with Hot Water Reheat (available only on MM*39C units), use appropriate values from Cooling only or with Humidifier
categories.
3. Use MM*35E for MM*35K, except with SCR reheat.
4. SCR Reheat not available with MM*35K or MM*39C.
Table 19 Belt drive split system evaporator or chilled water electrical data, 50Hz
220 - 1 Ph - 50Hz 380/415 - 3 Ph - 50Hz
Base Evaporator Model Number MM*35E MM*35E
Cooling Only
FLA 7.0 2.6
with Electric Reheat
FLA 32.0 12.3
with SCR Reheat 5
FLA 48.7 16.5
with Humidifier
FLA 13.4 6.3
with Electric Reheat and Humidifier
FLA 38.4 16.0
5
with SCR Reheat and Humidifier
FLA 55.1 20.2
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from unit.
2. Use MM*35E electrical data for MM*39C chilled water units.
3. For units with Hot Water Reheat (available only on MM*39C units), use appropriate values from Cooling only or with Humidifier
categories.
4. Use MM*35E for MM*35K, except with SCR reheat.
5. SCR Reheat not available with MM*35K or MM*39C.
Liebert Mini-Mate2 28
Electrical Data
Liebert Mini-Mate2 29
Electrical Data
Close Coupled
Centrifugal Air-Cooled or
Water/Glycol-Cooled Condenser
Electric Service
(not by Emerson)
Condenser
Evaporator
Evaporator Unit
Electric Box
Line Voltage
Electrical Power (Optional Field-Installed
Supply Entrance Single Point Power Kit)
Liebert Mini-Mate2 30
Electrical Data
Table 22 Electrical data, 60Hz air-cooled systems using single-point power kit, evaporator with
direct-drive blowers and indoor condensing unit
208/230 - 1 Ph - 60Hz 277 - 1 Ph - 60Hz 208/230 - 3 Ph - 60Hz 460 - 3 Ph - 60Hz
Base Evaporator
Model Number MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E
Condensing Unit
Model Number MC*24A MC*36A MC*24A MC*36A MC*24A MC*36A MC*24A MC*36A
Cooling Only
FLA 17.1 23.6 15.0 18.9 18.5 9.2
WSA 20.1 27.9 17.6 22.5 21.5 10.8
OPD 30 40 25 35 30 15
with Electric Reheat
FLA 42.1 48.6 36.7 40.6 35.3 17.6
WSA 51.4 59.1 44.7 49.6 42.5 21.3
OPD 60 60 45 50 50 25
2
with SCR Reheat
FLA 46.3 65.3 40.3 55.0 42.6 21.3
WSA 56.6 80.0 49.2 67.6 51.6 25.9
OPD 60 80 50 70 50 30
with Humidifier
FLA 23.5 30.0 20.7 24.6 24.9 12.6
WSA 26.5 34.3 23.3 28.2 27.9 14.2
OPD 35 50 30 40 35 20
with Electric Reheat and Humidifier
FLA 42.1 48.6 36.7 40.6 35.3 17.6
WSA 51.4 59.1 44.7 49.6 42.5 21.3
OPD 60 60 45 50 50 25
2
with SCR Reheat and Humidifier
FLA 52.7 71.7 46.0 60.7 49.0 24.7
WSA 63.0 86.4 54.9 73.3 58.0 29.3
OPD 70 90 60 80 60 30
* Specify disconnect or no disconnect
Note:
1. Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
2. SCR Reheat not available with MM*24K or MM*36K.
Liebert Mini-Mate2 31
Electrical Data
Table 23 Electrical data, 60Hz air-cooled systems using single-point power kit, evaporator with belt-drive
blowers and indoor condensing unit
208/230 - 1 Ph - 60Hz 277 - 1 Ph - 60Hz 208/230 - 3 Ph - 60Hz 460 - 3 Ph - 60Hz
Base Evaporator
Model Number MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E
Condensing Unit
Model Number MC*24A MC*36A MC*24A MC*36A MC*24A MC*36A MC*24A MC*36A
Cooling Only
FLA 23.5 30.0 19.1 23.0 20.5 9.9
WSA 26.5 34.3 21.7 26.6 23.5 11.5
OPD 35 50 30 40 35 15
with Electric Reheat
FLA 48.5 55.0 40.8 44.7 37.3 18.3
WSA 57.8 65.5 48.8 53.7 44.5 22.0
OPD 60 70 50 60 50 25
3
with SCR Reheat
FLA 52.7 71.7 44.4 59.1 44.6 22.0
WSA 63.0 86.4 53.3 71.7 53.6 26.6
OPD 70 90 60 80 60 30
with Humidifier
FLA 29.9 36.4 24.8 28.7 26.9 13.3
WSA 32.9 40.7 27.4 32.3 29.9 14.9
OPD 40 50 35 45 40 20
with Electric Reheat and Humidifier
FLA 48.5 55.0 40.8 44.7 37.3 18.3
WSA 57.8 65.5 48.8 53.7 44.5 22.0
OPD 60 70 50 60 50 25
3
with SCR Reheat and Humidifier
FLA 59.1 78.1 50.1 64.8 51.0 25.4
WSA 69.4 92.8 59.0 77.4 60.0 30.0
OPD 70 100 60 80 70 35
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from evaporator unit.
2. Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
3. SCR Reheat not available with MM*24K or MM*36K.
32 Liebert Mini-Mate2
Electrical Data
Table 24 Electrical data, 50Hz air-cooled systems using single-point power kit, evaporator with
direct-drive blowers and indoor condensing unit
220 - 1 Ph - 50Hz 380/415 - 3 Ph - 50Hz
Base Evaporator Model Number MM*35E MM*35E
Condensing Unit Model Number MC*35A MC*35A
Cooling Only
FLA 22.9 9.2
with Electric Reheat
FLA 47.9 18.9
2
with SCR Reheat
FLA 64.6 23.1
with Humidifier
FLA 29.3 12.9
with Electric Reheat and Humidifier
FLA 47.9 18.9
2
with SCR Reheat and Humidifier
FLA 71.0 26.8
* Specify disconnect or no disconnect
Notes:
1. Use MM*35E for MM*35K, except with SCR reheat.
2. SCR Reheat not available with MM*35K.
Table 25 Electrical data, 50Hz air-cooled systems using single-point power kit, evaporator with belt-drive
blowers and indoor condensing unit
220 - 1 Ph - 50Hz 380/415 - 3 Ph - 50Hz
Base Unit Model Number MM*35E MM*35E
Condensing Unit Model Number MC*35A MC*35A
Cooling Only
FLA 27.1 10.4
with Electric Reheat
FLA 52.1 20.1
3
with SCR Reheat
FLA 68.8 24.3
with Humidifier
FLA 33.5 14.1
with Electric Reheat and Humidifier
FLA 52.1 20.1
with SCR Reheat and Humidifier 3
FLA 75.2 28.0
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from evaporator unit.
2. Use MM*35E for MM*35K, except with SCR reheat.
3. SCR Reheat not available with MM*35K.
33 Liebert Mini-Mate2
Electrical Data
Table 26 Electrical data, 60Hz water/glycol-cooled systems using single-point power kit, evaporator with
direct-drive blowers and indoor condensing unit
208/230 - 1 Ph - 60Hz 277 - 1 Ph - 60Hz 208/230 - 3 Ph - 60Hz 460 - 3 Ph - 60Hz
Base Unit
Model Number MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E
Condensing Unit
Model Number MC*26W MC*38W MC*26W MC*38W MC*26W MC*38W MC*26W MC*38W
Cooling Only
FLA 14.8 19.9 12.7 16.6 14.8 7.8
WSA 17.8 24.2 15.3 20.2 17.8 9.4
OPD 25 40 25 30 25 15
with Electric Reheat
FLA 39.8 44.9 34.4 38.3 31.6 16.2
WSA 49.1 55.4 42.4 47.3 38.8 19.9
OPD 50 60 45 50 45 20
2
with SCR Reheat
FLA 44.0 61.6 38.0 52.7 38.9 19.9
WSA 54.3 76.3 46.9 65.3 47.9 24.5
OPD 60 80 50 70 50 25
with Humidifier
FLA 21.2 26.3 18.4 22.3 21.2 11.2
WSA 24.2 30.6 21.0 25.9 24.2 12.8
OPD 35 45 30 40 35 15
with Electric Reheat and Humidifier
FLA 39.8 44.9 34.4 38.3 31.6 16.2
WSA 49.1 55.4 42.4 47.3 38.8 19.9
OPD 50 60 45 50 45 20
2
with SCR Reheat and Humidifier
FLA 50.4 68.0 43.7 58.4 45.3 23.3
WSA 60.7 82.7 52.6 71.0 54.3 27.9
OPD 70 90 60 80 60 30
* Specify disconnect or no disconnect
Notes:
1. Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
2. SCR Reheat not available with MM*24K or MM*36K.
34 Liebert Mini-Mate2
Electrical Data
Table 27 Electrical data, 60Hz water/glycol-cooled systems using single-point power kit, evaporator with
belt-drive blowers and indoor condensing unit
208/230 - 1 Ph - 60Hz 277 - 1 Ph - 60Hz 208/230 - 3 Ph - 60Hz 460 - 3 Ph - 60Hz
Base Evaporator
Model Number MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E MM*24E MM*36E
Condensing Unit
Model Number MC*26W MC*38W MC*26W MC*38W MC*26W MC*38W MC*26W MC*38W
Cooling Only
FLA 21.2 26.3 16.8 20.7 16.8 8.5
WSA 24.2 30.6 19.4 24.3 19.8 10.1
OPD 35 45 25 35 30 15
with Electric Reheat
FLA 46.2 51.3 38.5 42.4 33.6 16.9
WSA 55.5 61.8 46.5 51.4 40.8 20.6
OPD 60 70 50 60 45 20
3
with SCR Reheat
FLA 50.4 68.0 42.1 56.8 40.9 20.6
WSA 60.7 82.7 51.0 69.4 49.9 25.2
OPD 70 90 60 70 50 30
with Humidifier
FLA 27.6 32.7 22.5 26.4 23.2 11.9
WSA 30.6 37.0 25.1 30.0 26.2 13.5
OPD 40 50 35 40 35 15
with Electric Reheat and Humidifier
FLA 46.2 51.3 38.5 42.4 33.6 16.9
WSA 55.5 61.8 46.5 51.4 40.8 20.6
OPD 60 70 50 60 45 20
3
with SCR Reheat and Humidifier
FLA 56.8 74.4 47.8 62.5 47.3 24.0
WSA 67.1 89.1 56.7 75.1 56.3 28.6
OPD 70 90 60 80 60 30
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from evaporator unit.
2. Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
3. SCR Reheat not available with MM*24K or MM*36K.
35 Liebert Mini-Mate2
Electrical Data
Table 28 Electrical data, 50Hz water/glycol-cooled systems using single-point power kit, evaporator with
direct-drive blowers and indoor condensing unit
220 - 1 Ph - 50Hz 380/415 - 3 Ph - 50Hz
Base Evaporator Model Number MM*35E MM*35E
Condensing Unit Model Number MC*37W MC*37W
Cooling Only
FLA 19.9 7.8
with Electric Reheat
FLA 44.9 17.5
2
with SCR Reheat
FLA 61.6 21.7
with Humidifier
FLA 26.3 11.5
with Electric Reheat and Humidifier
FLA 44.9 17.5
2
with SCR Reheat and Humidifier
FLA 68.0 25.4
* Specify disconnect or no disconnect
Notes:
1. Use MM*35E for MM*35K, except with SCR reheat.
2. SCR Reheat not available with MM*35K.
Table 29 Electrical data, 50Hz water/glycol-cooled systems using single-point power kit, evaporator with
belt-drive blowers and indoor condensing unit
220 - 1 Ph - 50Hz 380/415 - 3 Ph - 50Hz
Base Evaporator Model Number MM*35E MM*35E
Condensing Unit Model Number MC*37W MC*37W
Cooling Only
FLA 24.1 9.0
with Electric Reheat
FLA 49.1 18.7
with SCR Reheat 3
FLA 65.8 22.9
with Humidifier
FLA 30.5 12.7
with Electric Reheat and Humidifier
FLA 49.1 18.7
3
with SCR Reheat and Humidifier
FLA 72.2 26.6
* Specify disconnect or no disconnect
Notes:
1. Belt drive data includes externally mounted high static blower box, powered from evaporator unit.
2. Use MM*35E for MM*35K, except with SCR reheat.
3. SCR Reheat not available with MM*35K.
36 Liebert Mini-Mate2
Refrigerant Piping
Table 33 Line charges - refrigerant per 100 ft. (30m) of Type L copper tube
R-407C, lb/100 ft. (kg/30m)
Line Size,
O.D., in. Liquid Line Suction Line
3/8 3.7 (1.7)
1/2 6.9 (3.1)
5/8 11.0 (5.0 0.4 (0.2)
3/4 15.7 (7.1) 0.6 (0.3)
7/8 23.0 (10.4) 1.0 (0.4)
1-1/8 1.7 (0.7)
1-3/8 2.7 (1.1)
37 Liebert Mini-Mate2
Refrigerant Piping
Evaporator
Suction Line Piping
Condensing Unit Above Evaporator
Traps recommended at the base of riser exceeding
5 ft (1.5m) and every 20 feet (6m) of vertical rise.
Pitch down 1/2" (13mm) per 10 ft. (3m)
Liebert Mini-Mate2 38
Glycol Loop Piping
Figure 23 Heat rejection loop, multiple drycoolers and multiple indoor units
Expansion Tank
______ Gal. (L)
HP GPM (l/s) ft.
Total
____(kW) ____ Per Pump @ ____(kPa)
GPM
PUMP PACKAGE FS (L/s): _____
Pipe
Drycooler No. 1 Model ______ Cooling Unit # Diam.: _____ In. (mm)
GPM (l/s) ____ P: ___ ft (kPa) Model P: _____ Ft. (kPa)
GPM (l/s)
P ft (kPa): Cooling Unit #
Model
Cooling Unit # GPM (l/s)
Model P ft (kPa):
GPM (l/s)
P ft (kPa): Cooling Unit #
See Note 3 Model
Cooling Unit # GPM (l/s)
Model P ft (kPa):
GPM (l/s)
P ft (kPa): Cooling Unit #
Model
Cooling Unit # GPM (l/s)
Model P ft (kPa):
Drycooler No. 2 Model ______ GPM (l/s)
GPM (l/s) ____ P: ___ ft (kPa) Cooling Unit #
P ft (kPa):
LEGEND Model
Gate Valve Cooling Unit # GPM (l/s)
Model P ft (kPa):
Check Valve
GPM (l/s)
Butterfly Valve P ft (kPa): Cooling Unit #
Model
Relief Valve GPM (l/s)
Cooling Unit #
Union Model P ft (kPa):
GPM (l/s)
Ball or Flow Control Valve P ft (kPa): Cooling Unit #
FS Flow Switch Model
GPM (l/s)
P: Pressure Drop
P ft (kPa):
Strainer/Filter
Notes:
1. Pressure and temperature gauges (or ports for same) are
recommended to monitor component pressure drops and performance.
2. Flow measuring devices, drain and balancing valves to be supplied
by others and located as required.
3. See product literature for installation guidelines and clearance dimensions.
4. Drawing shows dual pump package. Alternate pump packages with more DPN000991
pumps may be considered; consult supplier Rev. 0
39 Liebert Mini-Mate2
Model Number NomenclatureAll Systems
MM D 36 E 7 A H E D A
Refrigerant Reheat Type
7 = R-407C 0 = No Reheat
Supply Power E = Electric Reheat
P = 208/230V - 1 ph - 60Hz S = SCR Reheat (not available
X = 277V - 1 ph - 60Hz with free-cooling)
S = 220V - 1 ph - 50Hz (3-ton only)
A = 460V - 3 ph - 60Hz (3-ton only)
Humidification
Y = 208/230V - 3 ph - 60Hz (3-ton only)
H = Canister Humidifier
M = 380/415V - 3ph - 50Hz (3-ton only)
0 = No Humidifier
R = Remote Humidifier Contact
J = Canister Humidifier and Remote
Humidifier Contact
Sensor Packages
0 = None
A = Filter Clog
B = Smoke Sensor
C = High-Temperature Sensor
D = Filter Clog & Smoke Sensor
E = Filter Clog & High-Temperature Sensor
F = Smoke Sensor & High-Temperature Sensor
G = Filter Clog, Smoke Sensor & High-Temperature Sensor
MC D 36 A L A H 7
Head Pressure Controls
L = Liebert Lee-Temp Receiver H = Hot Gas
Bypass
Liebert Mini-Mate2 40
Model Number NomenclatureAll Systems
PFH 0 37 A P L 7
= Standard Coil
L = 95F Ambient,
C = Coated Coil P = 208/230V - 1ph - 60Hz Liebert Lee-Temp
Y = 208/230V - 3ph - 60Hz (3-ton only) H = 105F High Ambient,
A = 460V - 3ph - 60Hz (3-ton only) Liebert Lee-Temp
B = 575V - 3ph - 60Hz (3-ton only)
S = 220V - 1ph - 50Hz (3-ton only)
M = 380/415V - 3ph - 50Hz (3-ton only)
MC D 38 W 2 A H 7
Head Pressure Controls Refrigerant
2 = 2-Way Standard Pressure Water Reg Valve 7 = R-407C
3 = 3-Way Standard Pressure Water Reg Valve
D = 2-Way High-Pressure Water Reg Valve H = Hot Gas Bypass
T = 3-Way High-Pressure Water Reg Valve
41 Liebert Mini-Mate2
Model Number NomenclatureAll Systems
MM D 40 C 3 A H E D A
Supply Power
P = 208/230V - 1 ph - 60Hz Reheat Type
X = 277V - 1ph - 60Hz Humidification 0 = No Reheat
S = 220V - 1ph - 50Hz H = Canister Humidifier E = Electric Reheat
A = 460V - 3ph - 60Hz 0 = No Humidifier H = Hot Water Reheat
Y = 208/230V - 3ph - 60Hz R = Remote Humidifier Contact
M = 380/415V 3ph-50Hz J = Canister Humidifier and Remote
Humidifier Contact Sensor Packages
0 = None
A = Filter Clog
B = Smoke Sensor
C = High-Temperature Sensor
D = Filter Clog & Smoke Sensor
E = Filter Clog & High-Temperature
Sensor
F = Smoke Sensor & High
Temperature Sensor
G = Filter Clog, Smoke Sensor & High-
Temperature Sensor
Liebert Mini-Mate2 42
Guide Specifications for Liebert Mini-Mate22- and 3-Ton Systems
1.0 GENERAL
1.1 Summary
These specifications describe requirements for an environmental control system. The system shall be
designed to control temperature and relative humidity conditions within the room.
The manufacturer shall design and furnish all equipment in the quantities and configurations shown
on the project drawings.
System shall be supplied with CSA Certification to the harmonized U.S. and Canadian product safety
standard CSA C22.2 No 236/UL 1995 for Heating and Cooling Equipment and marked with the CSA
c-us logo (60Hz only).
The system model number(s) shall be:
Evaporator: _______________________
Condensing Unit: _______________________
Chilled Water Unit:__________________
1.2 Design Requirements
The environmental control system shall be a Liebert Mini-Mate2 factory assembled unit. On direct
expansion models, the refrigeration system shall be split, with the compressor located in a remote or
close-coupled condensing unit.
The evaporator section shall be designed for above dropped-ceiling installation. Condensing units
shall be designed for either outdoor or above-dropped-ceiling installation.
The system shall have a total cooling capacity of _______ BTU/hr (kW) and a sensible cooling capacity of
________ BTU/hr (kW), based on the entering air condition of _____F (C) dry bulb and _____F (C) wet bulb.
The unit is to be supplied for operation on a ______ volt, ______ phase, ______ Hz power supply.
1.3 Submittals
Submittals shall be provided with the proposal and shall include: Dimensional, Electrical and
Capacity data; and Piping and Electrical Connection Drawings.
1.4 Quality Assurance
The specified system shall be factory-tested before shipment. Testing shall include, but shall not be
limited to: Quality Control Checks, Hi-Pot Test (two times rated voltage plus 1000 volts, per NRTL
agency requirements), and Metering Calibration Tests. The system shall be designed and manufactured
according to world-class quality standards. The manufacturer shall be ISO 9001 certified.
2.0 PRODUCT
2.1 Standard Features/All Systems
2.1.1 Evaporator Cabinet Construction
The cabinet and chassis shall be constructed of heavy gauge galvanized steel, and shall be serviceable
from one side. Mounting brackets shall be factory-attached to the cabinet. Internal cabinet insulation
shall meet ASHRAE 62.1 requirements for Mold Growth, Humidity & Erosion, tested per UL 181 and
ASTM 1338 standards.
2.1.2 Air Distribution
The air distribution system shall be constructed with a quiet, direct-drive fan assembly equipped with
double-inlet blower, self-aligning ball bearings and lifetime lubrication. Fan motor shall be
permanent-split capacitor, high-efficiency type, equipped with two speeds for airflow modulation.
Dehumidification shall utilize the lower fan speed.
Each system shall be capable of delivering ____CFM (____ CMH) at high fan speed. The
circulating-air fan shall be two-speed for precise dehumidification control. The fan motor shall be
____ HP (____ W).
System shall be suitable for plenum or ducted air distribution. Refer to 2.5.2 - Air Filter Box, 2.5.3 -
Air Distribution Plenum and 2.5.4 - High Static Blower Assembly.
43 Liebert Mini-Mate2
Guide Specifications for Liebert Mini-Mate22- and 3-Ton Systems
2.1.3.1 Monitoring
The LCD shall provide On/Off indication, operating mode indication (cooling, heating, humidifying,
dehumidifying), fan speed indication and current day, time, temperature and humidity (if applicable)
indication. The monitoring system shall be capable of relaying unit operating parameters and alarms
to the Liebert SiteScan monitoring system.
Liebert Mini-Mate2 44
Guide Specifications for Liebert Mini-Mate22- and 3-Ton Systems
2.1.4 Alarms
2.1.4.1 Unit Alarm
The control system shall monitor unit operation and activate an audible and visual alarm in the event
of the following factory preset alarm conditions:
High Temperature
Low Temperature
High Humidity
Low Humidity
High Water Alarm - Lockout Unit Operation
High Head Pressure
Loss of Power
Compressor Short Cycle
45 Liebert Mini-Mate2
Guide Specifications for Liebert Mini-Mate22- and 3-Ton Systems
Liebert Mini-Mate2 46
Guide Specifications for Liebert Mini-Mate22- and 3-Ton Systems
47 Liebert Mini-Mate2
Guide Specifications for Liebert Mini-Mate22- and 3-Ton Systems
Liebert Mini-Mate2 48
Guide Specifications for Liebert Mini-Mate22- and 3-Ton Systems
3.0 EXECUTION
3.1 Installation of Air Conditioning Unit
3.1.1 General
Install air conditioning unit in accordance with manufacturer's installation instructions. Install unit
plumb and level, firmly anchored in location indicated, and maintain manufacturer's recommended
clearances.
3.1.2 Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be
factory-mounted. Furnish copy of manufacturers electrical connection diagram submittal to electrical
contractor.
3.1.3 Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory-mounted.
Furnish copy of manufacturers piping connection diagram submittal to piping contractor.
3.1.4 Supply and Drain Water Piping
Connect water supply and drains to air conditioning unit. Unit drain shall be trapped internally.
3.1.5 Field-Supplied Pan
A field-supplied pan with drain shall be installed beneath cooling units installed without air
distribution plenum and beneath water/glycol condensing units.
3.1.6 Field Quality Control
Startup air conditioning unit in accordance with manufacturer's start up instructions. Test controls
and demonstrate compliance with requirements.
49 Liebert Mini-Mate2
Technical Support / Service
Web Site
www.liebert.com
Monitoring
liebert.monitoring@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
While every precaution has been taken to ensure the accuracy Fax: +39 049 5841 257
and completeness of this literature, Liebert Corporation assumes no Asia
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
29/F, The Orient Square Building
2013 Liebert Corporation F. Ortigas Jr. Road, Ortigas Center
All rights reserved throughout the world. Specifications subject to change Pasig City 1605
without notice. Philippines
Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks +63 2 687 6615
or registered trademarks of their respective owners. Fax: +63 2 730 9572
SL-10535_REV8_10-13
www.EmersonNetworkPower.com