Professional Documents
Culture Documents
Analogue Load Share Lines Interface: Genset
Analogue Load Share Lines Interface: Genset
CONFIGURATION VIBRATION
DSE123 SWITCH POSITION BS EN 60068-2-6
The table shows how the TYPE Ten sweeps in each of three major axes
DSE123 interface needs to be kW SHARE SETTINGS V Ar SHARE SETTINGS
5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @
configured depending on the 2gn
DEIF* 0 1 8 0 1 8
SHOCK
BS EN 60068-2-27
SELCO 2 2 8 0 1 1 Three shocks in each of three major axes
15gn in 11mS
WOODWARD 6 8 1 0 1 1
BARBER COLMAN
DSE123 DEIF*
SELCO
WOODWARD
7
kW kV Ar
ISSUE 1
dseGenset
dse123 SPECIFICATION
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
and supply recovers to 5 V. This is
achieved without the need for internal
batteries. LEDs and backlight will not be
maintained during cranking.
DIMENSIONS
OVERALL
161 mm x 78 mm x 76 mm
6.3 x 3.1 x 3.0
MOUNTING
DIN Rail
RELATED MATERIALS
TITLE PART NOS
DSE5510 Data Sheet 055-039
DSE5510 Operators Manual 057-015
DSE7510 Data Sheet 055-065
DSE7510 Operators Manual 057-088
DSE8610 Data Sheet 055-083
DSE8610 Operators Manual 057-115
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-044/02/13 (4)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457