100% Limiting values Based on the values given in 7671:2008

Circuit Breakers BS 3871 or BS


Fuses
60898 or RCBOs 61009
NominalBS 88 'gG' Type
BS 1361 or Type Type Type Type
Rating Parts 2 BS 3036 3 and
1362 1 2 B D
(A) and 5 C

0.4S 5s 0.4S 5s 0.4S 5S 0.4 and 5 s


5 10.45 16.40 9.5817.70 12 6.86
6 8.52 13.50 10 5.71 7.67 3.83 1.92
10 5.11 7.42 6 3.43 4.60 2.30 1.15
13 2.42 3.83
15 3.28 5.00 2.555.35 4 2.29
16 2.70 4.18 3.75 2.14 2.87 1.44 0.72
20 1.77 2.91 1.70 2.80 1.773.83 3 1.70 2.30 1.15 0.57
25 1.44 2.30 2.4 1.37 1.84 0.92 0.46
30 1.15 1.84 1.092.64 2 1.14
32 1.04 1.84 1.88 1.07 1.44 0.72 0.36
40 1.35 1.5 0.86 1.15 0.57 0.29
45 0.96 1.59 1.33 0.76
50 1.04 1.2 0.69 0.92 0.46 0.23
60 0.70 1.12
63 0.82 0.95 0.73 0.36 0.18
80 0.57 0.50 0.57 0.29 0.14
100 0.42 0.36 0.53 0.46 0.23 0.11
125 0.33 0.09
160 0.25
200 0.19

Typical breaking values for common overcurrent protective devices


Fuses 3871/60898
BS 88 'Gg'
Parts 2 BS 1361 BS 3036 BS 1362 All domestic types
and 6
Type 1 Type 2
Typical
Breaking 80 kA 16.5 kA33 kA 4 kA 6 kA 6 kA 6 kA 6 kA
Capacity