1 No.
PRESENTATION ENTRY
SHROUDING
ALL LIVE PARTS ALL DIMENSIONS ARE IN mm
TYPE OF CONSTRUCTION
BUS BARS FORM - 2 AUXILIARIES SUPPLY CIRCUIT MARKING
VOLTAGE WIRING >
DIMENSION 230V AC
HEIGHT : 800 WIDTH : 600 DEPTH : 250
30X10MM DEGREE OF PROTECTION
IP-65
IP-41
MOUNTING LABELS
ORIGIN FACIA LEGEND PLATES OF 1.5mm THICK
WALL
TRIFOLIATE ENGRAVED WITH
FROM THE INCOMER
STRIP DANGER LABELS WITH WHITE LETTERS
ON RED BACKGROUND
SURFACE TREATMENT
ANTI CORROSION COATING FOR COMPLETE
ENVIRONMENTAL PROTECTION WITH WIRING
THERMAL POLYMENSED POLYESTER CONTROL 1.5 Sqmm
EPOXY POWDER COATED COLOUR-RAL 7032
COLOUR THICKNESS <50 MICRON
PANEL SUPPLIER :
R Y B SB S
SEA BREEZE ELECT SWITCHGEAR IND L.L.C
P.O BOX - 73539, SHARJAH
UNITED ARAB EMIRATES
TEL - 06 5355993 * FAX - 06 5355994
E-mail :- seabreezeuae yahoo.com
Q1 - Q8
R Y B N
WARNNING
750
800
CF1-4
800
TH1
Q0 415V
X1 (TERMINALS)
QO
E
GLAND PLATE
PANEL FACIA
RIGHT SIDE VIEW INTERNAL LAYOUT
1 1 1
1 3 5 7
Q0 1 1 1 1 1 1 1 1
32A,4P Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8
MCCB,36KA 16A,SP 16A,SP 16A,SP 16A,SP 16A,SP 16A,SP 16A,SP 16A,SP
INCOMER
2 4 6 8
MCB MCB MCB MCB MCB MCB MCB MCB
10kA 2
10kA 2
10kA 2
10kA 2
10kA 2
10kA 2
10kA 2
10kA 2
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
R
N
Y
B
X1
9
EARTH
LOC.-132KV BASEMENT
LOC.-11KV BASEMENT
BUSBAR
TO COMMON POWER
TO COMMON POWER
TO COMMON POWER
(ASP-19 TO ASP-23)
(ASP-13 TO ASP-18)
LOC.-FIRST FLOOR
(ASP-7 TO ASP-12)
(ASP-1 TO ASP-6)
R Y B N E
SUPPLY UNIT-4
SUPPLY UNIT-1
SUPPLY UNIT-3
(2C X 4SQ.MM)
SPARE
SPARE
SPARE
(2C X 4SQ.MM)
SUPPLY UNIT-2
(2C X 4SQ.MM)
(2C X 4SQ.MM)
(2C X 4SQ.MM)
INCOMER FROM
LVAC SWITCHBOARD
(BUS-2,FEEDER NO.6Q12)
(DWG. NO. 026-COMN-E-10-160)
(CABLE SIZE :- 4CX6Sqmm+
1CX6Sqmm)
NOTE:
POWER DIAGRAM # ASP : AIR SAMPLING PANEL
JOB NO : SBS/L&T-001/002-2/17
SCHNEIDER ALFANAR
MSD1/418/D1/026
R R
Y Y
B B
N N
CF4
6A
2
NOTE:
1) SINGLE FEEDER IS FEEDING TO TWO ASP PANELS IN BASEMENT FLOOR AREA & GROUND FLOOR AREA. IF ONE ASP PANEL NEED TO MAINTAIN , THAN PARTICULAR FUSE TO REMOVE.
AND IF BOTH ASP PANELS REQUIRED TO MAINTAIN ,THAN PARTICULAR MCB NEED TO OFF.
2) TYPICAL SETUP IS PROVIDED FOR ASP PANEL LOCATED IN BASEMENT & GROUND FLOOR AREA.
3) SINGLE FEEDER IS FEEDING THE SUPPLY FOR EACH ASP PANEL IN FIRST FLOOR AREA AS PER EACH ROOM WISE REQUIREMENT.
JOB NO : SBS/L&T-001/002-2/17
SCHNEIDER ALFANAR
MSD1/418/D1/026