Professional Documents
Culture Documents
Cable Pull1 41eng
Cable Pull1 41eng
Calculations should be made to indicate whether the pull looks easy or impossible,
making the decision to pull an obvious choice. When a marginal situation is
encountered, the entire pull should be reviewed. This review may include more rigorous
calculations or trial pulls. A final decision should be made based on installation factors
known to the end user and installer.
The sizes of the conduit are determined based on the calculations of the clearances,
jamming, and fill. Pulling tensions may then be evaluated by determining the maximum
tension based on the pulling device used and the maximum tension that can be applied
to the conductors. The lesser of these two values is the maximum allowable tension (Tm).
The pulling tension (T) required to pull the cable through the conduit is then calculated
and compared to the maximum allowable tension. If the pulling tension exceeds the
allowable tension or sidewall pressure, then conditions should be changed to ensure a successful pull.
How to enter a cable pull into the calculator.
First, enter the wires going in the conduit. Next, enter the conduit type and size.
Example: 3/C SIMpull CU THHN Size 350, with a 4/0 SIMpull THHN ground wire: in GRC (Galv Rigid Conduit) size 3''.
It is assumed that it takes approx. 25 lbs of force to pull the wire off the reel. Thus, incoming tension is set at 25 lb and can
be changed if needed.
A segment has two parts that needs to be captured. The straight section and the bend section.
2. Up, Down or N/A : how the wire enters the vertical part of the bend?
Wire is going UP through the bend, Down through the bend, or N/A (horizontally).
This first segment will show Tension of 115 lb. and Sidewall Pressure of 74 lb.
Product sheets for:
http://www.southwire.com/ProductCatalog/XTEInterfaceServlet?contentKey=prodcatsheet276
http://www.southwire.com/ProductCatalog/XTEInterfaceServlet?contentKey=prodcatsheet5
http://www.southwire.com/ProductCatalog/XTEInterfaceServlet?contentKey=prodcatsheet7
http://www.southwire.com/ProductCatalog/XTEInterfaceServlet?contentKey=prodcatsheet327
http://www.southwire.com/ProductCatalog/XTEInterfaceServlet?contentKey=prodcatsheet3
http://www.southwire.com/ProductCatalog/XTEInterfaceServlet?contentKey=prodcatsheet12
http://www.southwire.com/processChannel.do?channelId=2dd91dc51235df00VgnVCM1000004c026564RCRD
Wire pull with 6 90's, 2 60's and elevation changes
Configuration Complex COF 0.14 COF 0.35 COF 0.14 COF 0.35
Wt.correction factor 1.40 Recommended Not Recommended Recommended Not Recommended
This spreadsheet enables the user to perform basic calculation for cable tensions when pulled in conduit.
Conduit system should be clean and free of debris. It uses formulas and methods found in the public domain. It
is not intended to be nor should it be used as authority for design, construction, use or installation of cable into
conduit systems. The design, construction, use and installation cable into conduit systems should only be
undertaken by competent professionals in light of currently accepted design and engineering practices.
While great care has been employed to ensure that the applications, tables, standards and references and other
information contained herein are free of errors, absolutely no warranties, either expressed or implied, are made
as to the accuracy or completeness of any such tables and formulas contained herein.
Neither Southwire nor anyone else who has been involved in the creation, production or delivery of this
publication shall be liable for any direct, indirect, consequential, or incidental damages arising out of the use, the
results of the use, or inability to use such publication, even if Southwire has been advised of the possibility of
such damages or claim. Some states do not allow the exclusion or limitation for consequential incidental
damages, so the above limitation may not apply to you.
1 Copyright Southwire Company 2009. Enter Voltage Drop Info SIMpull CU THHN Phase Wire Attributes
1 All rights reserved.
in purple areas Single Phase Three Phase Attributes can change based on wire type, size and Mfg
Amperage @ load 0 0 Acceptable Megger Readings 0
System Voltage 120 480 Dielectric Constant (SIC) 0
Enter wire info in purple areas that will go into the conduit Circuit Length 0 0 Max Oper Temp for Dry Use 0
# of wires Wire Type Wire Size Wire OD Wire Wt/ ft. Voltage Drop % 0.0% 0.0% Max Oper Temp for Wet Use 0
Phase Wires SIMpull CU1 THHN
N/A 1 0.000 0.00 Volts at Load 120.00 480.00 Min Bend Radius (in.) 0
Neutral Wire SIMpull CU1 THHN
N/A 1 0.000 0.00 Voltage Drop Calculator Min Installation Temp 0
Ground Wire N/A
SIMpull CU1 THHN 1 0.000 0.00 http://www.southwire.com/productcatalog/voltdrop.jsp Vertically Support every 0
Total Cables 0 Cable Pull Calculated Values Riser MC Requires No Vertical Supports
Maximum Pulling Force (lb.) 0 Sunlight Resistant 0
Max Sidewall Pres. (lb.) 0 CT Rated 0
CU 3/0 CU Jam Probability 0.00 Very Small UL 0
GW sizing (NEC 250.122) w/o VD 1200 amps
considerations AL 250 AL Phase Wire Ampacity Considerations NEMA 0
Short Circuit Current (amps) 8 cycles
4 0 sec.
/ .1333 RoHS Compliant 0
Enter conduit info in purple areas Adjust for Ambient Temp 26-30C (78-86F)
2 0 75 C Ampacity (310.16) 0
Conduit Type 1 #DIV/0! Adjust for # of Current 1 90 C ampacity (310.16) 0
Conduit Size 1 Min Conduit #N/A Carrying Conductors
1-3 0
Coefficient Of Friction 0
Max Allowable Ampacity for this Scenario
Conduit ID 0.000 (310.16) 0 0
Stranding
8/30/2009
Bend Section Notation: HZTL = Horizontal Bend; VCUP = Verticle Concave Up Bend; VCDN = Verticle Concave Down Bend