Basic Operating Principles Design Guide

3.5 Wiring Schematic

130BD599.10
3-phase
power
91 (L1)
92 (L2)
93 (L3)
(U) 96
(V) 97
(W) 98
3 3
input
95 PE (PE) 99
Motor

88 (-) Switch Mode


DC bus
Power Supply
89 (+)
10 V DC 24 V DC (R+) 82 Brake
15 mA 130/200 mA resistor
50 (+10 V OUT) + - + -
+10 V DC (R-) 81
S201
0/-10 V DC-
53 (A IN)
1 2

ON

+10 V DC relay1
ON=0/4-20 mA
0/4-20 mA S202 03
OFF=0/-10 V DC -
1 2

0/-10 V DC - +10 V DC
ON

54 (A IN) 240 V AC, 2 A


+10 V DC 02
0/4-20 mA
55 (COM A IN) 01
* relay2
12 (+24 V OUT) 06
240 V AC, 2 A
13 (+24 V OUT) P 5-00 05
400 V AC, 2 A
24 V (NPN)
18 (D IN) 04
0 V (PNP)
24 V (NPN)
19 (D IN) 0 V (PNP) (COM A OUT) 39 Analog Output
0/4-20 mA
(A OUT) 42
20 (COM D IN)
24 V (NPN)
27 (D IN/OUT) 0 V (PNP) S801
24 V ON=Terminated
1 2

ON

OFF=Open

0V 5V
* 24 V (NPN)
29 (D IN/OUT) 0 V (PNP)
24 V
S801 0V
0V
RS-485 RS-485
(N RS-485) 69
24 V (NPN) Interface
32 (D IN) 0 V (PNP) (P RS-485) 68
24 V (NPN) **
33 (D IN) 0 V (PNP) (COM RS-485) 61
: Chassis

* : Ground
37 (D IN)

Figure 3.2 Basic Wiring Schematic

A=Analog, D=Digital
*Terminal 37 (optional) is used for Safe Torque Off. For Safe Torque Off installation instructions, refer to the Safe Torque Off
Instruction Manual for Danfoss VLT Adjustable Frequency Drives. Terminal 37 is not included in FC 301 (except enclosure type
A1). Relay 2 and terminal 29 have no function in FC 301.
**Do not connect cable shield.

MG33BF22 Rev. 2014-04-04 All rights reserved. 17