Professional Documents
Culture Documents
ADK Hospital - Operation Theater - Technical Sheet
ADK Hospital - Operation Theater - Technical Sheet
Unit
Unit type: ASU 622 A
Cooling capacity (total): 58.6 kW Airflow: 9,670 m/h
Cooling capacity (sensible): 40.0 kW Air velocity: 1.4 m/s
Net total cooling capacity: 57.0 kW Return air temperature: 24 C
Net sensible cooling capacity: 38.4 kW Return air humidity: 55 rel.%
Condensing temperature: 45 C Supply air temperature: 12 C
EER: 4.19 kW/kW Altitude above sea level: 0 m
AER: 0.17 W/(m/h) Height: 1,980 mm
Sound power level: 75.8 dB(A) Width: 2,200 mm
LpA (2m freefield): 56.3 dB(A) Depth: 890 mm
Number of refrigerant circuits: 2 Weight: 669 kg
Number of compressors: 2 Refrigerant: R407C
Power supply: 380-415/3/50
Condenser
Unit type: KSV057A31pC Weight: 168 kg
Ambient temperature: 35 C Current consumption (per fan): 3.10 A
Sound pressure group: Standard Power consumption (per fan): 0.71 kW
Required condenser capacity: 35.5 kW Height: 947 mm
Available condenser capacity: 41.4 kW Width: 2,360 mm
Difference: 16.6 % Depth: 770 mm
Number of fans: 3 Airflow: 16,800 m/h
Number of condensers: 2 LpA (5m freefield): 60.3 dB(A)
The above mentioned data are subject to the measuring tolerances of Eurovent. Unless otherwise stated, all data refer to a product in basic version. Page 1 of 1
StulzSelect Vers. 3.0.0 - New Project: 1 x ASU 622 A