DWB
Molded Case Circuit Breaker
UL 489 Listed
Molded Case
Circuit Breaker
Summary
Introduction 04
Selection Guide 06
Accessories 08
Internal Accessories 11
External Accessories 13
Technical Data 17
Trip Curves 20
DWB
Molded Case Circuit Breaker
UL 489 Listed
DWB400
In 200...400
DWB250
In 80...250
DWB160
In 20...100
Introducing the WEG DWB Series of Molded Case Circuit Breakers now available with UL 489
certification. With its three compact frames, the DWB UL provides protection from 20 to 400
amperes in two versions: Standard 80% rated and Premium 100% rated.
The DWB UL also counts with two levels of short circuit interrupting capacity, and common1)
internal accessories that simplify field installation and minimize inventory variations.
Ir
80-100, 100-125, 120-150,
DWB250 Adjustable thermal (0.8...1 x In) Fixed magnetic (10 x In)
160-200, 200-250
Ir
160-200, 180-225, 200-250,
DWB400 220-275, 240-300, 260-325, Adjustable thermal (0.8...1 x In) Adjustable magnetic (510 x In)
280-350, 320-400
Im
Selection Guide
DWB160 for Distribution - Standard 80% Rated - Fixed Thermal and Fixed Magnetic Trip Unit
Interrupting ratings (kA) Reference code
Rated current (A) Magnetic trip point (A)
240 V ac 480Y/277 V ac 3 poles
DWB160CE
20 300 35 10 DWB160CE20-3DX
25 300 35 10 DWB160CE25-3DX
30 300 35 10 DWB160CE30-3DX
40 400 35 10 DWB160CE40-3DX
50 500 35 10 DWB160CE50-3DX
60 600 35 10 DWB160CE60-3DX
70 700 35 10 DWB160CE70-3DX
80 800 35 10 DWB160CE80-3DX
90 900 35 10 DWB160CE90-3DX
100 1000 35 10 DWB160CE100-3DX
DWB160JE
20 300 50 14 DWB160JE20-3DX
25 300 50 14 DWB160JE25-3DX
30 300 50 14 DWB160JE30-3DX
40 400 50 14 DWB160JE40-3DX
50 500 50 14 DWB160JE50-3DX
60 600 50 14 DWB160JE60-3DX
70 700 50 14 DWB160JE70-3DX
80 800 50 14 DWB160JE80-3DX
90 900 50 14 DWB160JE90-3DX
100 1000 50 14 DWB160JE100-3DX
DWB250 for Distribution - Standard 80% Rated - Adjustable Thermal and Fixed Magnetic Trip Unit
Interrupting ratings (kA) Reference code
Current range (A) Magnetic trip point (A)
240 V ac 480Y/277 V ac 3 poles
DWB250JE
80-100 1000 50 14 DWB250JE100-3DF
100-125 1250 50 14 DWB250JE125-3DF
120-150 1500 50 14 DWB250JE150-3DF
160-200 2000 50 14 DWB250JE200-3DF
200-250 2500 50 14 DWB250JE250-3DF
DWB250PE
80-100 1000 100 35 DWB250PE100-3DF
100-125 1250 100 35 DWB250PE125-3DF
120-150 1500 100 35 DWB250PE150-3DF
160-200 2000 100 35 DWB250PE200-3DF
200-250 2500 100 35 DWB250PE250-3DF
DWB400 for Distribution - Standard 80% Rated - Adjustable Thermal and Magnetic Trip Unit
Interrupting ratings (kA) Reference code
Current range (A) Magnetic trip point (A)
240 V ac 480 V ac 3 poles
DWB400JE
160-200 1600-2000 50 18 DWB400JE200-3DA
180-225 1800-2250 50 18 DWB400JE225-3DA
200-250 2000-2500 50 18 DWB400JE250-3DA
220-275 2200-2750 50 18 DWB400JE275-3DA
240-300 2400-3000 50 18 DWB400JE300-3DA
260-325 2600-3250 50 18 DWB400JE325-3DA
280-350 2800-3500 50 18 DWB400JE350-3DA
320-400 3200-4000 50 18 DWB400JE400-3DA
DWB400PE
160-200 1600-2000 100 35 DWB400PE200-3DA
180-225 1800-2250 100 35 DWB400PE225-3DA
200-250 2000-2500 100 35 DWB400PE250-3DA
220-275 2200-2750 100 35 DWB400PE275-3DA
240-300 2400-3000 100 35 DWB400PE300-3DA
260-325 2600-3250 100 35 DWB400PE325-3DA
280-350 2800-3500 100 35 DWB400PE350-3DA
320-400 3200-4000 100 35 DWB400PE400-3DA
Notes: Wiring terminals (lugs) built-in for DWB160 and supplied as standard with DWB250 and DWB400. Lugs are also available as an accessory for DWB250
and DWB400, see the section Accessories.
Selection Guide
DWB160 for Distribution - Premium 100% Rated - Fixed Thermal and Fixed Magnetic Trip Unit
Interrupting ratings (kA) Reference code
Rated current (A) Magnetic trip point (A)
240 V ac 480Y/277 V ac 3 poles
DWB160CH
20 300 35 10 DWB160CH20-3DX
25 300 35 10 DWB160CH25-3DX
30 300 35 10 DWB160CH30-3DX
40 400 35 10 DWB160CH40-3DX
50 500 35 10 DWB160CH50-3DX
60 600 35 10 DWB160CH60-3DX
70 700 35 10 DWB160CH70-3DX
80 800 35 10 DWB160CH80-3DX
90 900 35 10 DWB160CH90-3DX
100 1000 35 10 DWB160CH100-3DX
DWB160JH
20 300 50 14 DWB160JH20-3DX
25 300 50 14 DWB160JH25-3DX
30 300 50 14 DWB160JH30-3DX
40 400 50 14 DWB160JH40-3DX
50 500 50 14 DWB160JH50-3DX
60 600 50 14 DWB160JH60-3DX
70 700 50 14 DWB160JH70-3DX
80 800 50 14 DWB160JH80-3DX
90 900 50 14 DWB160JH90-3DX
100 1000 50 14 DWB160JH100-3DX
DWB250 for Distribution - Premium 100% Rated - Adjustable Thermal and Fixed Magnetic Trip Unit
Interrupting ratings (kA) Reference code
Current range (A) Magnetic trip point (A)
240 V ac 480Y/277 V ac 3 poles
DWB250JH
80-100 1000 50 14 DWB250JH100-3DF
100-125 1250 50 14 DWB250JH125-3DF
120-150 1500 50 14 DWB250JH150-3DF
160-200 2000 50 14 DWB250JH200-3DF
200-250 2500 50 14 DWB250JH250-3DF
DWB250PH
80-100 1000 100 35 DWB250PH100-3DF
100-125 1250 100 35 DWB250PH125-3DF
120-150 1500 100 35 DWB250PH150-3DF
160-200 2000 100 35 DWB250PH200-3DF
200-250 2500 100 35 DWB250PH250-3DF
DWB400 for Distribution - Premium 100% Rated - Adjustable Thermal and Magnetic Trip Unit
Interrupting ratings (kA) Reference code
Current range (A) Magnetic trip point (A)
240 V ac 480 V ac 3 poles
DWB400JH
160-200 1600-2000 50 18 DWB400JH200-3DA
180-225 1800-2250 50 18 DWB400JH225-3DA
200-250 2000-2500 50 18 DWB400JH250-3DA
220-275 2200-2750 50 18 DWB400JH275-3DA
240-300 2400-3000 50 18 DWB400JH300-3DA
260-325 2600-3250 50 18 DWB400JH325-3DA
280-350 2800-3500 50 18 DWB400JH350-3DA
320-400 3200-4000 50 18 DWB400JH400-3DA
DWB400PH
160-200 1600-2000 100 35 DWB400PH200-3DA
180-225 1800-2250 100 35 DWB400PH225-3DA
200-250 2000-2500 100 35 DWB400PH250-3DA
220-275 2200-2750 100 35 DWB400PH275-3DA
240-300 2400-3000 100 35 DWB400PH300-3DA
260-325 2600-3250 100 35 DWB400PH325-3DA
280-350 2800-3500 100 35 DWB400PH350-3DA
320-400 3200-4000 100 35 DWB400PH400-3DA
Notes: Wiring terminals (lugs) built-in for DWB160 and supplied as standard with DWB250 and DWB400. Lugs are also available as an accessory for DWB250
and DWB400, see the section Accessories.
Accessories
Overview of DWB160 and Accessories
10
2 3
1
11
5 6 8
9
Accessories
Overview of DWB250 and Accessories
2 3
7 8
5 6
Accessories
Overview of DWB400 and Accessories
2 3
8
7
5 6
Internal Accessories
Auxiliary Switches and Alarm Switches
The auxiliary switch and alarm switch have the function to signal remotely the status of circuit breakers power contacts.
There are 3 types of switches available:
JJ Offers provisions for audio or visual indication of the under the conditions described above
BCAL
Ensemble comprised of an auxiliary switch + alarm switch The BCAL switch makes
JJ
Reference code
Internal accessory Number of contacts
DWB160 DWB250 DWB400
1 changeover BC-1 DWB
Auxiliary switch BC
2 changeover BC-2 DWB
Alarm switch AL 1 changeover AL-1 DWB
Auxiliary switch and alarm switch BCAL 1BC + 1AL BCAL-2 DWB
Electrical characteristics
Rated voltage Type of load Switching capacity (A)
125 V ac Resistive 6
250 V ac Resistive 6
Notes: Use BCAL switches when applications require auxiliary switch and alarm switch fitted in the same circuit breaker.
Not applicable for motor switching.
Wiring Diagrams
ON OFF TRIP
12 12
11 22 11 22
BC
21 14 21 14
24 24
82 82
AL 81 81
84 84
Internal Accessories
Shunt and Undervoltage Release
Voltage releases function to trip remotely the circuit breaker. They are often used for remote emergency stop purpose.
BD Shunt Release
JJ
When energized by a pulse or maintained signal of voltage, the shunt release trips the
circuit breaker (trip position).
The shunt release works from 70 to 110% of the rated voltage (0.70 x Un <Ue <1.1 x Un)
JJ
This release features a device to keep it not energized after the tripping pulse
BS Undervoltage Release
JJ
Trips the circuit breaker when the voltage drops below 35% of the rated voltage (Ue
<0.35 x Un)
JJ
When voltage is between 35 to 70% of the rate voltage, it may open the circuit breaker
(0.35 x Un <Ue <0.7 x Un)
JJ
After the operation of BS release, circuit breaker can only be closed if supply voltage is
above 85% of the rated voltage (Ue >0.85 x Un)
JJ
The BS undervoltage release along with an emergency stop push button makes possible
the fail-safe operation of the circuit breaker
To Complete the Reference Code, Replace " " with the Appropriate Voltage Code
E26 E27 E28 E10 E15
24 V ac/dc 48 V ac/dc 60 V ac/dc 110-130 V ac/dc 220-250 V ac/dc
C1 D1
BD BS
C2 D2
Maximum Configurations - Internal Accessories
Internal accessory DWB160 DWB250 DWB400
Auxiliary switch 2 11) 2 11) 2 11) 2 11) 2 11) 2 11)
Alarm switch 0 11) 0 11) 0 11) 0 11) 0 11) 0 11)
Shunt release 1 1 0 0 1 1 0 0 1 1 0 0
Undervoltage release 0 0 1 1 0 0 1 1 0 0 1 1
Note: 1) Use BCAL switches when applications require auxiliary switch and alarm switch fitted in the same circuit breaker.
External Accessories
Panel Door Operating Handles
The panel door operating handles allow external operation of a circuit breaker installed in an electrical panel. WEG has
3 options to better fit according to customer needs.
Reference code
Mechanism Suitable for
DWB160 DWB250 DWB400
MRH RH MRH DWB160 MRH DWB250 MRH DWB400
External Accessories
Panel Door Operating Handles
Reference code
Rotary handle Thermometry feature Degree of protection Handle color / background color
DWB160
Black / gray RHX DWB160
RHX Yes UL-type 4x (IP66)
Red / yellow RHX DWB160 E
Reference code
Mechanism Suitable for
DWB160
MRH RHX MRH DWB160
External Accessories
Panel Door Operating Handles
FH Flange Handles
JJ Degree of protection UL-type 1, 12, 3R, 4 and 4x available
JJ
When in ON position, panel door cannot be opened, unless a tool is used to bypass the panel door locking system,
allowing thermometry of the panel
JJ
Flexible cable length up to 72 inches (1828 mm)
JJ
Allows padlocking in OFF position using padlocks
JJ
Padlocks are not supplied
Reference code
Flange handle Thermometry feature Degree of protection
DWB160 DWB250 DWB400
FHU Yes UL-type 1, 12, 3R, 4 FHU DWB160-250 FHU DWB400
FHX Yes UL-type 4, 4x FHX DWB160-250 FHX DWB400
Reference code
Flexible cable Length (inch) Suitable for
DWB160 DWB250 DWB400
36 FC DWB160-250 36i FC DWB400 36i
48 FC DWB160-250 48i FC DWB400 48i
FC FHU, FHX
60 FC DWB160-250 60i FC DWB400 60i
72 FC DWB160-250 72i FC DWB400 72i
Reference code
Mechanism Suitable for
DWB160 DWB250 DWB400
MFH FHU, FHX MFH DWB160 MFH DWB250 MFH DWB400
External Accessories
Changeover Device
Manual-operated changeovers are used to make safe switching of two different circuits.
MP Escutcheons
JJ
Escutcheons are frames for cutouts in panel doors
JJ
It makes possible the external switching of the MCCB through the front door when the circuit
breakers is installed close to the panel door, maintaining the degree of protection
JJ
Degree of protection IP40
JJ
See section Dimensions for cutout details
Technical Data
Notes: 1) For DWB160: suitable for continuous operation at 100 percent of rating only if used in a circuit breaker enclosure in a cubicle space 23.6 by 15.7 by 7.9 inches
(600 by 400 by 200 mm) or equivalent.
For DWB250: suitable for continuous operation at 100 percent of rating only if used in a circuit breaker enclosure in a cubicle space 31.5 by 23.6 by 11.8 inches
(800 by 600 by 300 mm) or equivalent.
F
or DWB400: suitable for continuous operation at 100 percent of rating only if used in a circuit breaker enclosure in a cubicle space 47.2 by 23.6 by 15.8 inches
(1200 by 600 by 400 mm) or equivalent.
2) Use only 90 C rated wire with ampacity based on 75 C rated conductors.
DWB160
DWB250
DWB400
Recommended mounting distances (inch / mm)
90
90
90
Mounting position
90
DWB160/DWB250
0.78 (19.5)
0.3
3
(8.5
)
DWB250 70 / 8
0.37
0.3
(9.5)
3
) (8.5)
(8
31
0.
ax
M
0.47
(12)
Max 0.47
0.94
(24) (12)
Max
0.94
(24)
1.55 A/mm
1,000 A/in 95...240 mm
1.06 (27) 3/0 AWG...500 kcmil
0.3
5
DWB400 177 / 20 (9)
0.47
0.3
1
(8)
2)
(1
47
0.
ax
M
0.47
(12)
Max 0.43
0.94
(24) (11)
Max
0.91
(23)
Thermal Dissipation
Distribution MCCB
Rated current - In A 20 25 30 40 50 60 70 80 90 100 125 150 200 250 275 300 325 350 400
Watts/pole
DWB160 1 2 4 4 5 8 4 5 6 7
Power loss
DWB250 14 19 17 14 20
DBW400 14 20 20 19 19 30 30
Deratings
50 F / 59 F / 68 F / 77 F / 86 F / 95 F / 104 F / 113 F / 122 F / 131 F / 140 F /
Temperature derating
10 C 15 C 20 C 25 C 30 C 35 C 40 C 45 C 50 C 55 C 60 C
DWB160 (x In) 1.16 1.12 1.09 1.07 1.02 1.02 1 0.97 0.95 0.91 0.88
DWB250 (x In) 1.15 1.13 1.10 1.08 1.05 1.02 1 0.98 0.95 0.92 0.88
DWB400 (x In) 1.16 1.13 1.10 1.08 1.05 1.02 1 0.98 0.94 0.90 0.88
Altitude derating 6500 ft / 2000 m 9800 ft / 3000 m 13100 ft / 4000 m 16400 ft / 5000 m
Rated current - In % 100 98 93 90
Rated operational voltage - Ue V ac 4801) 4801) 4801) 4001)
Trip Curves
DWB160 - Fixed Thermal and Fixed Magnetic (20100 A)
20000
20,000
Characteristic trip curve.
DWB160
DWB160 Characteristic trip curve.
The curves shown are for cold state and three pole
10000
10,000 The curves shown are for cold state and three pole
loaded. For hot state the time values are
loaded. For hot 25%
approximately stateofthe time
the values are
presented onapproximately
the cold
state25% of the presented on the cold state curve.
curve.
5000
5,000
ForFor
oneone pole
pole load,
load, thethe
timetimemay
mayrise
rise up
up to
to 20%.
20%.
ForFor
twotwo
polepole
load,load,
thethe
timetime mayrise
may riseup
uptoto10%.
10%
2000
2,000
1000
1,000
500
500
200
200
100
100
50
50
20
20
t t(s)
(s)
10
10
55
22
11
0.5
0.5
0.2
0.2
A: 12
25 A: 12 xx In
In 20 A:
A: 15
15 xx In
In
20
0.1
0.1
0.05
0.05 From 30
From 30 to
to 100
100 A:
A :10
10xxIn
In
0.02
0.02
0.01
0.01
11 1.3
1.3 22 33 44 55 66 7
7 8
8 10
10 12
12 15
15 20
20 30
30 40
40 50
50
xx InIn
Trip Curves
DWB250 - Adjustable Thermal and Fixed Magnetic (80250 A)
20000
20,000
DWB250
DWB250 Characteristic
The
Thecurves
trip curve.trip curve.
Characteristic
curvesshown
shownarearefor
for cold state
state and
andthree
threepole
pole
10000
10,000
loaded.loaded.
For hotForstate
hotthe time
state thevalues are are
time values
approximately 25%
approximately 25%of of
thethepresented
presentedononthe
thecold
cold
state curve.
5000
5,000
For For
oneone
polepole
load,
load,
state curve.
thethe
timetimemay
mayrise up to
rise up to 20%.
20%.
For For
twotwo
polepole
load, thethe
load, timetimemay
mayrise up to 10%.
rise up 10%.
2000
2,000
1000
1,000
500
500
200
200
Maximum
Maximum current adjustment:11xxInIn
current adjustment:
100
100
50
50
20
20
t(s)
t (s)
10
10
Minimum
Minimum current adjustment:0.8
current adjustment: 0.8x xInIn
55
22
11
0.5
0.5
0.2
0.2
10
10 xx In
In
0.1
0.1
0.05
0.05
0.02
0.02
0.01
0.01
1 1 1.3
1.3 2
2 33 44 55 66 77 88 10
10 20
20 30
30 40
40 50
50
x xIn
In
Trip Curves
DWB400 - Adjustable Thermal and Magnetic (200...400 A)
20000
20,000
Characteristic trip curve.
10000
10,000
DWB400
DWB400 The
Characteristic trip curve.
curves shown are for cold state and three pole
The curves shown are for cold state and three pole
loaded. For hot state the time values are
loaded. For hot state the time values are approximately
approximately 25% of the presented on the cold
25% of the presented on the cold state curve.
5000
5,000 state
Forcurve.
one pole load, the time may rise up to 20%.
For For
onetwo
pole load, the time may rise up 20%.
pole load, the time may rise up to 10%
For two pole load, the time may rise up 10%.
2000
2,000
1000
1,000
500
500
200
200
Maximumcurrent
Maximum currentadjustment:
adjustment:1 x1lnxIn
100
100
50
50
20
20
t (s)t (s)
10
10
Minimumcurrent
Minimum currentadjustment:
adjustment:0.80.8
x lnxIn
55
22
11
Maximum magnetic
Maximum magnetic
Minimum
Minimum magnetic
magnetic
0,5
0.5
adjustment:
adjustment: 55xxIn
ln
adjustment:10
adjustment: 10xxIn
ln
0,2
0.2
0,1
0.1
0,05
0.05
0,02
0.02
0,01
0.01
11 1,3
1.3 2
2 33 44 55 66 7
7 8
8 10
10 20
20 30
30 40
40 50
50
xx IIn n
Trip Curves
DWB160 - Short-Circuit Limiting Curves @ 240 V ac
50
50
40
40
DWB160
DWB160 -- UL
UL240
240V V
30
30
20
20
10
10
(k)
IpIp (k)
77
55
44
33
22
11
11 22 33 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100
IsIs(kA)
(kA)
Trip Curves
DWB160 - Short-Circuit Limiting Curves @ 480Y/277 V ac
30
30
DWB160 - UL
DWB160 - UL480Y/277
480Y/277 Vac V ac
20
20
J
C
10
10
77
Ip Ip(k)
(k)
55
44
33
22
11
11 22 33 4
4 55 77 10
10 20
20
IsIs(kA)
(kA)
Trip Curves
DWB250 - Short-Circuit Limiting Curves @ 240 V ac
50
50
40
40 DWB250 - UL 240 V
30
30
P
J
20
20
10
10
IpIp(k)
(k)
77
55
44
33
22
11
11 22 33 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100 200
200
IsIs(kA)
(kA)
Trip Curves
DWB250 - Short-Circuit Limiting Curves @ 480Y/277 V ac
50
50
40
40
DWB250
DWB250 UL
- UL-480Y/277
480Y/277 Vac V ac
30
30
20
20
10
10
Ip Ip(k)
(k)
77
55
44
33
22
11
11 22 33 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100
IsIs(kA)
(kA)
Trip Curves
DWB400 - Short-Circuit Limiting Curves @ 240 V ac
50
50
P
40
40 DWB400
DWB400 --UL
UL240240V
V
J
30
30
20
20
10
10
Ip (k)
Ip (k)
77
55
44
33
22
11
11 22 3
3 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100 200
200
IsIs(kA)
(kA)
Trip Curves
DWB400 - Short-Circuit Limiting Curves @ 480 V ac
50
50
40
40
DWB400
DWB400 -- UL
UL480
480V
V
30
30
20
20
P
10
10
Ip Ip(k)
(k)
77
55
44
33
22
11
11 22 33 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100
Is Is(kA)
(kA)
Trip Curves
DWB160 - I2t @ 240 V ac
1000
1,000
700
700
DWB160
DWB160 -- UL
UL240
240V V
J
500
500 C
400
400
300
300
200
200
100
100
70
70
50
50
I t (10 AAs)
40
40
2 s)
30
It (10
3
30
2
20
20
10
10
77
55
44
33
22
11
11 22 33 44 55 77 10
10 20
20 25
25 30
30 40
40 50
50 70
70
IsIs(kA)
(kA)
Trip Curves
DWB160 - I2t @ 480Y/277 V ac
1000
1,000
700
700
DWB160 - -UL
DWB160 UL 480Y/277
480Y/277 V acV ac
J
500
500 C
400
400
300
300
200
200
100
100
70
70
50
50
t (10 A As)
40
40
2 s)
30
It I(10
30
3
2
20
20
10
10
77
55
44
33
22
11
11 22 33 44 55 77 10
10 14
14 20
20
IsIs(kA)
(kA)
Trip Curves
DWB250 - I2t @ 240 V ac
2000
2,000
DWB250
DWB250 -- UL
UL240
240V V
1000
1,000 P
J
700
700
500
500
400
400
300
300
200
200
100
100
70
70
I t (10 AAs)
50
s)
50
2
It (10
40
3
40
2
30
30
20
20
10
10
77
55
44
33
22
11
11 22 33 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100 150
150
IsIs(kA)
(kA)
Trip Curves
DWB250 - I2t @ 480Y/277 V ac
2000
2,000
P
DWB250 - UL
DWB250 - UL480Y/277
480Y/277 VacV ac
1000
1,000
J
700
700
500
500
400
400
300
300
200
200
100
100
70
70
I t (10 AAs)
50
s)
50
2
It (10
40
3
40
2
30
30
20
20
10
10
77
55
44
33
22
11
11 22 33 44 55 77 10
10 14
14 20
20 30
30 35
35 50
50
Is Is(kA)
(kA)
Trip Curves
DWB400 - I2t @ 240 V ac
5000
5,000
DWB400
DWB400 --UL
UL240
240V
V
P
2000
2,000 J
1000
1,000
700
700
500
500
400
400
300
300
200
200
I t (10 As)
100
100
2 A s)
70
3
It (10
70
2
50
50
40
40
30
30
20
20
10
10
77
55
44
33
22
11
11 22 33 44 55 77 10
10 20
20 30
30 40
40 50
50 70
70 100
100 150
150
Is Is(kA)
(kA)
Trip Curves
DWB400 - I2t @ 480 V ac
10000
10,000
DWB400 - UL
DWB400 - UL480V
480 V
P
2000
2,000
1000
1,000
700
700
500
500
400
400
300
300
200
200
I t (10 AAs)
2 s)
100
100
It (10
3
70
2
70
50
50
40
40
30
30
20
20
10
10
77
55
44
33
22
11
11 22 33 44 55 77 10
10 18
18 30
30 35
35 50
50
Is (kA)
Is (kA)
0.984
(25)
2x
M4
6.25 (158.8)
4.01 (102)
1.77 (45.2)
3.93 (100)
1.49 (38.1)
0.883
(22.4)
2.62 (66.8)
0.984 0.984
(25) (25) 2.58 (65.7)
2.77 (70.4)
3.06 (77.9)
2.91 (74)
3.04 (77.4)
3.63 (92.4)
1.37
(35)
2xM
4
5.31 (135)
0.886
(22.5)
7.79 (198.1)
1.77 (45)
2.38 (60.6)
3.28 (83.6)
4.88 (124)
1.37 1.37
(35) (35) 2.68 (68.3)
4.16 (105.8) 2.94 (74.8)
3.07 (78)
3.26 (83)
4.20 (106.8)
4x 1,38
M5
38 35
5 44xx 1.38
1,38
MM5 (35)
5 35
7,83
199
103,2
4,06
(51.6)
(103.2)
2.03
2,03
51,6
12,72
323
(323)
4.06103,2
(199)
7.83
4,06
7,83
199
103,2
2,03
51,6
12,72
4,06
323
12.72
12,72
323
(168.5)
6.63
168,5
6,63
3,31
84,1
168,5
6,63
(84.1)
3.313,31
84,1
3,31
84,1
3.90
3,90
(99.1)
99,1
4.33
4,33
(109.9)
109,9
3,90 4.50
4,50
99,1 (114.4)
114,4
4.19
(106.5) 5.07
5,07
4,33 (128.8)
128,8
109,9
4,50
114,4
5,07
128,8
DWB - Molded Case Circuit Breaker - UL 489 Listed 35
www.weg.net
4.13 (105)
0.984 (25)
4x
M4
6.25 (158.8)
3.93 (100)
1.06
3.06 (77.9) (27.1) 4.04 (102.6)
7.20 (182.9)
(35)
x
M
4
7.79 (198.1)
4.88 (124)
0.760
4.16 (105.8) (19.3)
9.09 (230.9)
1
4.61
4,61
(117)
117
44xxM 1.38
1,38
M5
5 (35)
35
103,2
4,06
(51.6)
12,72
2.03
323
2,03
51,6
(168.5)
(103.2)
6.63
168,5
103,2
4.06
6,63
4,06
(199)
7.83
7,83
199
12.72
116,9
(323)
4,60
12,72
323
2,03
51,6
0.10
168,5
6,63
0,10 3.90
3,90
(2.5)
2,5 (99.1)
99,1
(116.9)
116,9
4.60
4.33
4,60
4,33
(109.9)
109,9
4.50
4,50
(114.4)
114,4
5.07
5,07
(128.8)
128,8
8.79 0,10 3,90
5.63
5,63
(223.3) 2,5 99,1 (142.9)
142,9
4,33
109,9
4,50
114,4
36 DWB - Molded Case Circuit Breaker - UL 4895,07Listed
128,8
5,63
142,9
www.weg.net
1.90 (48.5)
0.965
(24.5)
86
0.8 2.5)
2
(
16.93
(430)
0.984...1102
2.05 (52.3) (25...28)
1.22 (31)
2.09 (53)
16.93 (430) 45
1.77 (45)
25.4...127 97
(1...5) 0.1 5)
x
(2
7.79 (198.1)
(41.7)
1.64
1.22 (31)
2.08 (53)
16.93
(430)
45
1.77 (45)
323 (323)
199
103,2
4,06
12,72
323
7,83
199
(84.1) 4.06103,2
4,06
12.72
12,72
(168.5)
6.63 168,5
6,63
3,31
84,1
168,5
6,63
3.313,31
84,1
3.90 (99.1)
3,90
99,1
11
34,8
34,8
www.weg.net
194,1
194,1
A
X X
Y
11
108
Y
11
322,1
100,1
124
A
Y X X
322,1
108
Dimensions - Inch (mm)
17,4
124
A
B X X X
108
out - DWB250
X X
201
201
Accessories Y
Y
FH - Flange Handle B
A UP
7,87
7
49,3
Lenghts 36", 48", 60", 72".
26,6
75,7
2.98 (75.7)
A DOWN
49,3
1.94 (49.3)
Y
26,6
1 (26.6)
Y
Y
11
B MAX
Y
194,1
X X
108
119
194,1 (194.1)
41,8
7.64
322,1
Y
11
Y 0.99
X
41,8
(41.8)
(322.1)
(100.1)
12.68
(11)
3.94
201
0
100,1
322,1
(17.4)
0.69
0.43
A
76
17,4
X X
108
11
119
MENSION
YY
XX XX
7.9201(201)
4.25108(108)
119 (119)
24.79 29.79
AA
Y
23.79 28.79 B XX XX
kg kg
4.69
SWD - A2
Table 2 MAXIMUM "B" DIMENSION DT LIBER/REL DT 07.08.2014 FOL/SHEET 1 2
Enclousure Propriedade da WEG. Proibida reproduo sem autorizao prvia./ WEG's property. Forbidden reproduction without previous authorization.
Depth FHU/FHX - 36'' FHU/FHX - 48'' FHU/FHX - 60'' FHU/FHX - 72''
10 15.79 10.79 25.79 30.79 Panel door
Panel door cutout
Cutout - DWB160
- DWB160
12 14.79 12.79 Y 24.79
Y 29.79
Lenghts 36", 48", 60",1672". 13.79 16.79 23.79 28.79
Lenghts 36, 48, 60, 72 MASSA BRUTA/GROSS WEIGHT kg MASS
18 12.79 18.79 22.79 27.79
20 - 20.79 21.79 Table 226.79 MAXIMUM "B" DIMENSION
24Table 1 - Maximum "A" Dimension- 20.79 25.79
Enclousure
30
Enclousure 36" - 48" 60"- 72 19.79 Depth24.79 FHU/FHX - 36'' FHU/FHX - 48'' FHU/FHX - 60'' FHU/FHX - 72'' ECM LOC
RESUMO DE MODIFICAES
SUMMARY OF MODIFICATIONS
36Depth Up Down- Up Down Up Down - Up Down 18.79 23.79 EXEC RODRIGOGL
10 15.79 10.79 25.79 30.79 FH Flange Handles
10 10 21 11 25 17 31 20 34 12 14.79 12.79 24.79 29.79 VERIF/CHECKED
12Table 110 23 12 26 17 31 19 33 16 13.79
Maximum A dimension (inches)
16.79 23.79 28.79 LIBER/RELEASED
16 10 20 12 23 17 28 36
19 30 18
48
12.79 18.79
60
22.79 27.79
72
DT LIBER/REL DT 07.08.2014
Enclousure depth
18 10 20 12 23 Up17 28 19 30 Down 20 Up - Down 20.79 Up 21.79 Down 26.79 UpPropriedade da WEG. Proibida reproduo
Down sem autorizao prvia./ WEG's property. Forbidden reproduction witho
20 10 - - 11 21 1016 26 18 28 21 24 11 - 25 - 17 20.79 31 25.79 20 34
24 12 - - - - 1014 26 16 28 23 30 12 - 26 - 17 19.79 31 24.79 19 33
30 16 - - - - 1011 24 13 26 20 36 12 - 23 - 17 18.79 28 23.79 19 30
36 18 - - - - 10 6 21 8 22 20 12 23 17 28 19 30
20 - - 11 21 16 26 18 28
24 - - - - 14 26 16 28
30 - - - - 11 24 13 26
36 - - - - 6 21 8 22
www.weg.net
194,1
Y
11
100,1
322,1
17,4
124
A
X X
108
119
X X
5 Y 6 7 8 9 10
FH - Flange Handle 7,87
A UP
75,7 Frame 250 + FH DWB160-250
49,3 1 2 3 4 5 6 7
26,6 2.98
75,7
(75.7)
A DOWN
Y 1.94 (49.3)
49,3
1 (26.6)
26,6
A
Y
Y
B MAX
194,1 (194.1)
194,1
1.37
34,8
(34.8)
(11)
7.64
41,8
0.43
YY
100,1
11
322,1
3.94100,1(100.1)
B
17,4
12.68322,1(322.1)
11
Y
0.6917,4(17.4)
4.88124 (124)
X X
108
119
4.25108(108)
4.69119 (119)
201
XX XX
AA
A
76
X X
108
XX XX
119
7.9 (201)
201
7,87
Y Y
Y
B
C B
B
- - 6 21 8 22 FH Flange Handles
12 10 23 12 26 17 31 19 33 12 14.79 VERIF/CHECKED 12.79 24.79 29.79
00
16 10 20 12 23 17 28 19 30 16 13.79 LIBER/RELEASED
16.79 07.08.2014
23.79 28.79 1 2
DT LIBER/REL DT FOL/SHEET
18 10 20 12 23 17 28 19 30 18 12.79 Propriedade da WEG. Proibida reproduo
18.79 22.79
sem autorizao prvia./ WEG's property. Forbidden reproduction without previous authorization. 27.79
20 - - 11 21 16 26 18 28 20 - 20.79 21.79 26.79
24 - - - - 14 26 16 28 24 - - 20.79 25.79
E 30 - - - - 11 24 13 26 30 - - 19.79 24.79
194,1
36 - - - - 6 21 8 22 36 - - 18.79 23.79
1,831
46,5
322,1
17,4
11
2,362
60 1,16
0,2 1,831 Y
68 X
46,5 X 29,5
6,8
0,433
11
201
F 1.8311,831
(46.5) 9,17
2.362
46,5 R233 1.16
A
2,362
(60)
76
X X 60 1,16
(29.5)
108
0,2 29,5
68
119
6,8
9 7
0,433
(RR229,.1
11
31 0.
(11)
(620,268
17
0,3 ,4
8 7,87
33)
33 2,362
60 1,16
.86,8)68 29,5
0.433
4,252
3,819
4,685
0,433
31
108
119
11
97
0,3 ,4
7,874
8
200
9,17
F
R233 Y
4,252
3,819
4,685
119
108
119
(200)
97
B
31
F
0.30,338.1,44)
108(108)
119(119)
97 (97)
( 8
(281.6)
7,874
200
11.09
11,09
281,6
7.874
11,09
281,6
4.2524,252
3,819
4,685
3.819
4.685
FF
E
Table 2 MAXIMUM "B" DIMENSION
4xTable 1NUNC
410U-24
C
Maximum "A" Dimension
4x 10 -2 36" 48" 60"
EE
72
Enclousure
Depth FHU/FHX - 36'' FHU/FHX - 48'' FHU/FHX - 60'' FHU/FHX - 72''
Enclousure
Depth Up Down Up Down Up Down Up Down 10 15.79 10.79 25.79 30.79
10 10 21 11 25 17 31 20 34 12 14.79 12.79 24.79 29.79
12 10 23 12 26 17 31 19 33 16 13.792 16.79 23.79 (inches) 28.79
Table
16 1 10 20Maximum 12 23 17E28dimension
19 30 (inches) Table Maximum F dimension E MAX MASSA BRUTA/GROSS WEIGHT
18 12.79 18.79 22.79 27.79
Enclousure
18 10 20 12 23 17 28 19 30 20 Enclousure
- 62 20.79
cable 72
21.79cable 26.79
20 - - 11FHU-60 21 16 26 18 28 FHU-72
H depth
24 - - - - 14 26 16 28
24 depth- Up - Down Up20.79 Down 25.79
HX - 72'' 30 - - 19.79 24.79 F UP ECM
10
30 - - - 25 - 11 24 13 26 30 36 10 - 17 - 31 2018.79 34 23.79 EXEC R
30.79 36
12 - - - 24 - 6 21 8 22 29 12 17 31 19 33 VERIF/CHECKED
29.79 16 23 28 16 17 28 19 30 LIBER/RELEASED
28.79
F DOWN
2x
23 ) M4
0.3 8.2
x
(3
6.25 (158.8)
3.93 (100)
3.06 (77.9) 3.68 (93.6)
1.49 (38)
1.37
2
(35)
xM
4
23 )
0.3 8.2
x
(3
4.88 (124)
4.16 (106)
4.08 (104)
44xxM 1.38
1,38
M5 5 (35)
35
7,83
199
103,2
4,06
12,72
323
(51.6)
2.03
2,03
51,6
(103.2)
4.06
103,2
(199)
4,06
7.83
7,83
12.72
199
(323)
103,2
12,72
4,06
323
(168.5)
12,72
2,03
51,6
323
6.63
168,5
6,63
3,31
84,1
168,5
6,63
(84.1)
3.31
3,31
84,1
3,31
84,1
3.903,90
(99.1)
99,1
4,33
4.33 109,9
(109.9)
4,50
4.50114,4
(114.4)
5,07
4.19 (106.5) 3,90 5.07128,8
(128.8)
99,1
4,33
109,9
4,50
40 DWB - Molded Case Circuit Breaker
114,4
5,07
- UL 489 Listed
128,8
www.weg.net
MP - Escutcheons
MP DWB160 1.22
(31)
1.97
(50)
(46.7)
2.48
1.84
(63)
2.99
(76)
0.12
(2.8
0.11
(3)
MP DWB250 )
1.44
2.19 (36.50)
(55.5)
2.99
(46.7)
2.48
(76)
(63)
1.84
7
3 0.12
(2.8
0.11
(3)
)
1,47
MP DWB400
37,3
1.47
1,47
(37.3)
37,3
3,15
80
(120.5)
3,15
3.15
143,6
120,5
4.74
3,80
96,5
5,65
4,74
3,15 (80)
80 80
(143.6)
(96.5)
143,6
120,5
3.80
5.65
3,80
96,5
5,65
4,74
143,6
120,5
3,80
96,5
5,65
4,74
(6.1)
6,1
0.24
0,24
0.32
0,32
6,1
(8.2)
0,24
8,2
0,32
8,2
1 2 3 4 5
BFR DWB160 3P UL
1,78
45,2
3 4 5 6
1,78
45,2
1,78
45,2
(1.78)
45.2
100,1
3,94
117,5
4,62
100,1
100,1
(100.1)
3,94
3,94
117,5
117,5
3.94
(117.5)
4,62
4,62
4.62
1,78
45,2
0,05
0,98 1,27
24,90
0,25
6,3
117,5
4,62
0,05
0,38 0,05
(0.05)
0,98
(0.98) 0,98 1,27
9,7 1,27
1.27
24,90
24.90 24,90
0,25 0,25
(0.25)
6,3 6,3
6.3
0,38 0,38
(0.38)
9,7 9.7
9,7
2,76
(2.76) 0,05
70
70 1,27
0,25
6,3
2,76 2,76 0,38
70 70 9,7 BFR DWA160
BFR DWA160
The Global Solution with electric machines and automation for industry
and energy systems
WEG, one of the largest global manufacturers of Electric Motors with Quality and Efficiency recognized
in different industrial areas worldwide, is also present in Energy, Transmission and Distribution, Coatings
and Industrial Automation sectors, and produces and offers a wide range of electric components for
Motor Control and Protection and Electric Circuit Protection.
JJ Double pushbutton
JJ
Easy network module change via exclusive drawer
Electrical Connections system (Modbus, DeviceNet, Profibus modules)
JJ Terminal blocks with screw type connection JJ USB communication
JJ Terminal block with spring type connection
JJ Free WLP programming software
JJ Terminal blocks for fuses
Capacitors JJ
Multifunction three-phase monitoring relays
JJ Power factor compensation and timer relays
JJ Lighting
JJ Motor-run