Load Test Procedure For Coflex Hanger......
Load Test Procedure For Coflex Hanger......
2. Load Test
Rig up: - The load cell is suspended via shackles and
links to the crane hook and attached to the test plate.
To the bottom face of the test plate is attached the
water bag.
Connect the water hoses and zero the load cell reader.
With the completed assembly suspended overboard,
the water bag is gradually filled with water up to 12MT.
Ensure the water bag is not fouled in any way and the
area below is clear.
Communicate with signal man and have crane operator
gradually move water bag and lower bag in position on
the coflex hanger with securing pins until reading on
the load cell reader displays zero.
Observe the assembly in place for about 15 minutes.
After 15minutes of observation, test assembly is lifted
off hanger and water discharged.
With the load cell reader turned off, the test assembly is
put on deck and assembly rigged down.