Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 3

Resolucin de tuberias por Mtodo de Hardy Cross

500 m
8"
50 lts/s A (I)

6"
600 m

Circuito Tubera L(km) C Qo S(m/km) ho(m) ho/Qo e


AB 8" 0.5 100 35 9.70 4.85 0.14 -1.34
I BC 6" 0.5 100 10 4.00 2.00 0.20 -2.98
AC 6" 0.6 100 -15 -8.60 -5.16 0.34 -1.34
1.69 0.68

AB 8" 0.5 100 33.7 9.00 4.50 0.13 0.18


I BC 6" 0.5 100 7.0 2.10 1.05 0.15 0.52
AC 6" 0.6 100 -16.3 -9.60 -5.76 0.35 0.18
-0.21 0.64

AB 8" 0.5 100 33.84 9.00 4.50 0.13 0.05


I BC 6" 0.5 100 7.54 2.40 1.20 0.16 0.20
AC 6" 0.6 100 -16.16 -9.60 -5.76 0.36 0.05
-0.06 0.65
B

700 m

8"
6" (II) D 50 lts/s
500 m
8"

600 m

Qi Circuito Tubera L(km) C Qo S(m/km) ho(m)


33.66 BD 8" 0.7 100 25 5.40 3.78
7.02 II BC 6" 0.5 100 -10 -4.00 -2.00
-16.34 CD 8" 0.6 100 -25 -5.40 -3.24
-1.46

33.84 BD 8" 0.7 100 26.64 6.00 4.20


7.54 II BC 6" 0.5 100 -7.02 -2.10 -1.05
-16.16 CD 8" 0.6 100 -23.36 -4.80 -2.88
0.27

33.89 BD 8" 0.7 100 26.30 6.00 4.20


7.74 II BC 6" 0.5 100 -7.54 -2.40 -1.20
-16.11 CD 8" 0.6 100 -23.70 -4.80 -2.88
0.12
ho/Qo e Qi Error (%)
0.15 1.64 26.64
0.20 2.98 -7.02 42.445064
0.13 1.64 -23.36
0.48
Cuando el error
0.16 -0.34 26.30 sea cercano al
0.15 -0.52 -7.54 6.865981 1% podemos
0.12 -0.34 -23.70 considerar como
0.43 solucin

0.16 -0.15 26.16


0.16 -0.20 -7.74 2.5505278
0.12 -0.15 -23.84
0.44

You might also like