Professional Documents
Culture Documents
SUCO Incident Investigation: Area Authority
SUCO Incident Investigation: Area Authority
SUCO Incident Investigation: Area Authority
Description of Incident Losses (Circle all relevant): Injury - Health - Environment - Process loss Damage - Other
Date: 21/04/2006 Time: 10;00 AM Duration: days Staff Involved: Gas plant Description of Actual Losses:
Description of Event:
- LPG = 40 Tons X 250 $
On 21/04/2006 a sudden decrease of tail gas feed from AGIBA side which led - Cond. = 150 BBLS X 60 $
to tail gas comp. to operate in surge mode and the anti-surge control valve
can not Total. = 19000 $
Area
functioning properly due to sudden decrease in the feed gas immediately
Authority stopped
the tail gas comp. TR/2 due to the following reasons :-
1. Gas leak from 2nd stage comp. end flange.
2. Gas leak from the buffer gas flange on the 2nd stage comp.
3. Unavailability of sufficient tail gas feed.
Losses Category: M
Reporting Guidelines
Serious or Potential Serious LTIs, Strains, $5000 to $50000 Leads to immediate environmental damage A/I written report faxed to MDs/O-1/HSE
Accident or Incident MTCs lasting for up to 2 years and costing $5000 to within 1 day.
Serious Cuts $50000 in immediate clean up or control costs.
Non-compliance with legal requirement.
Minor Accident or Incident Small cuts self treated Less than $5000 Monitoring or clean up costs less than $5000 A/I written report sent to O-1/HSE within
Accident-W.
without Lost Time 3 days