The most important advantage of the modified control is the lower level of pressure the system
is operated with. The long 360bar permanent pressure at the pump is avoided so that the
lifetime of the pump is prolonged considerably. Furthermore all system components are less
stressed as 170bar pressures are achieved at a maximum.
At the beginning of a grease cycle, voltage is applied to the hydraulic valve of the pump by
means of the PLC, and the hydraulic pump starts pumping in line 1 until the initiator 1 switches
over (lamp 1 Ini on, lamp 2 Ini off). After a follow time of 22 sec and 4 sec of switching over
(pump switches off during 4 s) the pump in line 2 starts pumping until initiator switch no. 2
switches over (lamp Ini 2 on, lamp Ini 1 off). The hydraulic valve and thus the pump are
switched off after pumping for 22sec. During a greasing cycle the lamps of the initiators must
switch on at least once (first initiator no.1!).
A complete grease cycle (time for greasing and a pause) is always started after the time set in
the PLC has expired. At the beginning of a greasing period the greasing cycle begins again.
Time can be changed by the BCS and should be pre-set to 20 and 30 min, i.e. 1200-1800 sec,
the minimum value being 5 min (300 sec), the maximum time 40 min (2400 sec). Settings are
made on the 2nd BCS level of access PLC options.
Time is counted only when the machine is in operation, i.e. when boom, stick or bucket are
operated (pressure switch load /DSL is enabled). The travel times of the excavator are not
counted, there is no greasing during breaks. Thus the supply of grease is adapted to demand
and any unnecessary greasing during production breaks is avoided. Moreover it is guaranteed
that grease breaks are made at regular intervals. The automatic change from summer to
winter operation is a further advantage. Upon higher lubricant viscosity in winter, grease is
automatically pumped for a longer time.
Upon any start of the engine, a new cycle is started.
Operation time
BCS fault messages (without grease pump being switched off) superstructure:
When a cable of the pressure sensor is broken
When a cable of the grease level sensor is broken
BCS fault messages (without grease pump being switched off) undercarriage:
When cable of the pressure sensor is broken
t0 t1 t2 t3 t4 t5 t6
Pump status
Relief valve
- A new grease cycle starts as soon as pause time (t0) has elapsed.
- At (t1) the End of Line initiators at the stick indicate that the movement of the control piston towards
direction A is finished.
- Now an additional greasing time of 22sec is passing in the system. This time guarantees that even
possibly slower pistons have enough time to reach final position A.
- The pump is switched off after further pumping during (t2) is over and the switch valve is operated.
- After a 4s break the pump is re-activated (t3) and pumps grease into line B.
- At (t1) the End of Line initiators at the stick indicate that the movement of the control piston towards
direction B is finished.
- Now an additional greasing time of 22sec is operating in the system. This time guarantees that even
possibly slower pistons have enough time to reach final position B
- The pump is switched off after trailing off time (t2) is over and the switch valve is operated and 5sec
later the relief valve is switched off.
Measurements in the system showed that the control pistons of the stick grease distributor
reach their final position at a pressure of approx. 40 bar (at the pump). After ca. 7sec this
pressure is attained.
Due to further pumping, however, pressure continues rising.
grease pressure
200
grease pressure at the
150
pump [bar]
100
50
0
0 5 10 15 20 25
follow time [s] Reihe1
The control is set to a 22sec follow time so that a pressure of c. 170bar is attained at the
pump.
In the BCS, the sequence of a grease cycle is indicated by means of a red bar in the control
field of the greasing system. In case the pressure switch charge is activated, the bar turns
green from the left to the right. When the bar has completely changed to green time has
elapsed and greasing and a grease cycle start anew.
During greasing the background of the pictogram is displayed in yellow. In the BCS, the
grease pressure is indicated by means of an analogue signal.
Time can be changed via the BCS and should be pre-set to 20 to 30 min, i.e. 1200-1800 sec,
the minimum value being 5 min (300 sec), the maximum time 40 min (2400 sec). Settings are
made on the BCS level of access.
It must also be set if the machine is equipped with a grease drum and/or a greasing system for
the undercarriage.