Professional Documents
Culture Documents
CA Cooling Tower
CA Cooling Tower
LEVEL: 500
COOLING TOWER
WRITTEN BY:
N NAMES MATRICULE
COURSE FACILITATOR :
CONTENTS
CONTENTS .............................................................................................................................. ii
TABLE OF TABLE .................................................................................................................. iii
TABLE OF FIGURES .............................................................................................................. iii
INTRODUCTION ......................................................................................................................4
I- GENERALITIES ON COOLING TOWERS .......................................................................4
I-1- Principle [1] ..................................................................................................................4
I-2- Classification of cooling tower. [2] ...............................................................................5
I-2-1- Air ow generation methods ..................................................................................5
I-2-2- Categorization by air-to-water ow ........................................................................6
II- COMPONENTS & MATERIALS OF COOLING TOWER [2] ...........................................8
II-1-1- Components of cooling tower .............................................................................8
II-1-2- Materials of cooling tower [4] .......................................................................... 10
III- DESIGN AND SIZING OF COOLING TOWER [5] ...................................................... 11
III-1- Heat Balance ........................................................................................................... 11
III-2- Pressure Drops in Cooling Tower ............................................................................ 12
III-3- Motor Power Sizing ................................................................................................. 13
III-4- Fan Components & Sizing ....................................................................................... 14
III-4-1- Fan Coverage ................................................................................................... 14
III-4-2- Fan Sizing ........................................................................................................ 14
III-5- Air-Water Distribution System Design .................................................................... 14
III-5-1- Recirculation of Exit Air .................................................................................. 14
III-5-2- Evaporation ...................................................................................................... 14
III-5-3- Cycles of concentration [1] ............................................................................... 15
IV- MAINTENANCE [4] ..................................................................................................... 15
IV-1- System Concerns ..................................................................................................... 15
IV-1-1- Corrosion: ........................................................................................................ 15
IV-1-2- Scaling: ............................................................................................................ 15
IV-1-3- Biological Activity ........................................................................................... 16
IV-2- Typical problems and troubleshooting for cooling towers ........................................ 17
CONCLUSION ......................................................................................................................... 18
REFERENCES ......................................................................................................................... 19
ii
COOLING TOWER
TABLE OF TABLE
Table 1: Advantages and disadvantages of cooling tower ............................................................7
Table 2: Troubleshooting for cooling tower ............................................................................... 17
TABLE OF FIGURES
iii
COOLING TOWER
INTRODUCTION
Cooling towers are an integral component of many refrigeration systems, providing
comfort or process cooling across a broad range of applications. They are the point in the system
where heat is dissipated to the atmosphere through the evaporative process, and are common in
industries such as oil refining, chemical process-ing, power plants, steel mills, and many different
manufacturing processes where process cooling is required. They are also commonly used to
provide comfort cooling for large commercial buildings including airports, office buildings.
4
COOLING TOWER
o/blowndown (D) for disposal. Fresh water make-up (M) is supplied to the tower basin to
compensate for the loss of evaporated water, the windage loss water and the draw-o water.
5
COOLING TOWER
A distribution or hot water basin consisting of a deep pan with holes or nozzles in its bottom
is located near the top of a crossow tower. Gravity distributes the water through the nozzles
uniformly across the ll material.
6
COOLING TOWER
b) Counter ow
In a counter ow design, the air ow is directly opposite to the water ow (see diagram at
left). Air ow rst enters an open area beneath the ll media, and is then drawn up vertically. The
water is sprayed through pressurized nozzles near the top of the tower, and then ows downward
through the ll, opposite to the air ow.
7
COOLING TOWER
The basic components of a cooling tower include the frame and casing, fill, cold-water
basin, drift eliminators, air inlet, louvers, nozzles and fans. These are described below.
Frame and casing. Most towers have structural frames that support the exterior
enclosures (casings), motors, fans, and other components. With some smaller designs, such as
some glass fiber units, the casing may essentially be the frame.
8
COOLING TOWER
Fill. Most towers employ fills (made of plastic or wood) to facilitate heat transfer by
maximizing water and air contact. There are two types of fill:
Splash fill: water falls over successive layers of horizontal splash bars, continuously
breaking into smaller droplets, while also wetting the fill surface. Plastic splash fills promote better
heat transfer than wood splash fills.
Film fill: consists of thin, closely spaced plastic surfaces over which the water
spreads, forming a thin film in contact with the air. These surfaces may be flat, corrugated,
honeycombed, or other patterns. The film type of fill is the more efficient and provides
Cold-water basin. The cold-water basin is located at or near the bottom of the tower,
and it receives the cooled water that flows down through the tower and fill. The basin usually has
a sump or low point for the cold-water discharge connection. In many tower designs, the cold
water basin is beneath the entire fill. In some forced draft counter flow design, however, the water
at the bottom of the fill is channeled to a perimeter trough that functions as the cold-water basin.
Propeller fans are mounted beneath the fill to blow the air up through the tower. With this design,
the tower is mounted on legs, providing easy access to the fans and their motors.
Drift eliminators. These capture water droplets entrapped in the air stream that
otherwise would be lost to the atmosphere.
Air inlet. This is the point of entry for the air entering a tower. The inlet may take up
an entire side of a tower (cross-flow design) or be located low on the side or the bottom of the
tower (counter-flow design).
Louvers. Generally, cross-flow towers have inlet louvers. The purpose of louvers is to
equalize air flow into the fill and retain the water within the tower. Many counter flow tower
designs do not require louvers.
Nozzles. These spray water to wet the fill. Uniform water distribution at the top of the
fill is essential to achieve proper wetting of the entire fill surface. Nozzles can either be fixed and
spray in a round or square patterns, or they can be part of a rotating assembly as found in some
circular cross-section towers.
Fans. Both axial (propeller type) and centrifugal fans are used in towers. Generally,
propeller fans are used in induced draft towers and both propeller and centrifugal fans are found
9
COOLING TOWER
in forced draft towers. Depending upon their size, the type of propeller fans used is either fixed or
variable pitch. A fan with non-automatic adjustable pitch blades can be used over a wide kW range
because the fan can be adjusted to deliver the desired air flow at the lowest power consumption.
Automatic variable pitch blades can vary air flow in response to changing load conditions.
Frame and casing. Wooden towers are still available, but many components are made
of different materials, such as the casing around the wooden framework of glass fiber, the inlet air
louvers of glass fiber, the fill of plastic and the cold-water basin of steel. Many towers (casings
and basins) are constructed of galvanized steel or, where a corrosive atmosphere is a problem, the
tower and/or the basis are made of stainless steel. Larger towers sometimes are made of concrete.
Glass fiber is also widely used for cooling tower casings and basins, because they extend the life
of the cooling tower and provide protection against harmful chemicals.
Fill. Plastics are widely used for fill, including PVC, polypropylene, and other polymers.
When water conditions require the use of splash fill, treated wood splash fill is still used in wooden
towers, but plastic splash fill is also widely used. Because of greater heat transfer efficiency, film
fill is chosen for applications where the circulating water is generally free of debris that could
block the fill passageways.
Nozzles. Plastics are also widely used for nozzles. Many nozzles are made of PVC,
ABS, polypropylene, and glass-filled nylon.
Fans. Aluminum, glass fiber and hot-dipped galvanized steel are commonly used fan
materials. Centrifugal fans are often fabricated from galvanized steel. Propeller fans are made from
galvanized steel, aluminum, or molded glass fiber reinforced plastic.
10
COOLING TOWER
HEATin = HEATout
The difference between L2 (entering water flow rate) and L1 (leaving water flow rate) is a
loss of water due to the evaporation in the direct contact of water and air.
This evaporation loss is a result of difference in the water vapor content between the inlet
air and exit air of cooling tower. Evaporation Loss is expressed in G x (w2 -w1) and is equal to
L2- L1. Therefore, L1 = L2 - G x (w2 -w1) is established.
11
COOLING TOWER
Let's replace the term of L1 in the right side of Eq. III-1 with the equation of L1 = L2 - G x
(w2 -w1) and rewrite. Then, Cw L2 tw2 + G ha1 = Cw [L2 - G x (w2 - w1)] x tw1 + Gha2 is
obtained. This equation could be rewritten in Cw x L2 x (tw2 - tw1) = G x (ha2 - ha1) - Cw x tw1
x G x (w2 - w1). In general, the 2nd term of right side is ignored to simplify the calculation under
the assumption of G x (w2 - w1) = 0.
Finally, the relationship of Cw x L2 x (tw2 - tw1) = G x (ha2 - ha1) is established and this
can be expressed to Cw x L x (tw2 - tw1) = G x (ha2 - ha1) again. Therefore, the enthalpy of exit
air, ha2 = ha1 + Cw x L / G x (tw2 - tw1) is obtained. The value of specific heat of water is Eq.
III-1.
The term of tw2 (entering water temperature) - tw1 (leaving water temperature) is
called the cooling range. And the term L/G is Liquid to Gas ratio. Simply,
Consequently, the enthalpy of exit air is a summation of the enthalpy of entering air and
the addition of enthalpy from water to air (this is a value of L/G x Range).
Most of air pressure drops at all the areas excepting fill section can be easily calculated as
per the well-known formula of:
=
= { =
=
12
COOLING TOWER
In cooling tower, these pressure losses are called "Static Pressure Loss", just "Static
Pressure", or "System Resistance.
Total Static Pressure = PD @Air Inlet + PD @Fill + PD @Drift Eliminator + PD @Fan Inlet
The fan BHP shown on the fan rating sheet is the net fan brake horsepower based on the
ideal conditions of fan test. The actual operating conditions of cooling tower is quite different from
the test conditions of fan maker and the actual fan efficiency will be different from the
environmental factor like the inlet and exit air flow conditions, tip clearance, obstructions to air
flow, plenum geometry, etc. Therefore, a proper environmental correction factor should be
considered to both total pressure and horsepower.
Fan BHP = Air Volume at Fan in ACFM x Total Pressure in inch Aq. / (Fan Total
Efficiency x 6356), or = Air Volume at Fan in ACFM x Static Pressure in inch Aq. / (Fan
Static Efficiency x 6356)
Actual Fan BHP = Net Fan BHP / System Environmental Correction Factor
Motor Shaft BHP = Actual Fan BHP / Efficiency of Power Transmission of Gear
Reducer
13
COOLING TOWER
From the mathematical standpoint recirculation can be expressed as the percent of the
exhaust air which reenters the tower at the air inlets. Thus, considering a heat balance on the air
around the tower:
III-5-2- Evaporation
When water is cooled in a direct contact cooling tower of air and water, some of the heat
is removed by the sensible heat of air in contact with the water. Most of the heat is removed by
evaporation of a portion of the circulating water.
Evaporation Loss Rate = (Absolute Humidity @ Tower Exit - Absolute Humidity @ Tower
14
COOLING TOWER
M=E+D+W
Since the evaporated water (E) has no salts, a chloride balance around the system is:
M XM = D XC + W XC = XC ( D + W ) and, therefore:
XC M M E
= concentration of Cycles = = =1+
XM ( D + W) ( M E ) (D + V)
IV-1-2- Scaling:
Scaling is the precipitation of dissolved minerals components that have become saturated
in solution. Scale formation reduces the heat exchange ability of the system because of the
insulating properties of scale, making the entire system work harder to meet the cooling demand.
15
COOLING TOWER
16
COOLING TOWER
17
COOLING TOWER
1. Float-valve not at
Adjust the make-up valve
Loss of water from correct level
basins/pans 2. Lack of equalising Equalise the basins of towers
connections operating in parallel
1. Water flow below the Regulated the flow by means in of
design valve the valves
Check the direction of rotation of the
2. Irregular airflow or
fans and/or belt tension (broken belt
lack of air
possible)
3a. Recycling of humid
Check the air descent velocity
Lack of cooling and discharge air
hence increase in 3b. Intake of hot air from
Install deflectors
temperatures owing to other sources
increased temperature 4a. Blocked spray nozzles
range (or even blocked spray Clean the nozzles and/or the tubes
tubes)
4b. Scaling of joints Wash or replace the item
Clean or replace the material
(washing with inhibited aqueous
5. Scaling of the fill pack
sulphuric acid is possible but long,
complex and expensive)
CONCLUSION
A cooling tower is a heat rejection device which rejects waste heat to the atmosphere
through the cooling of a water stream to a lower temperature. Cooling towers may either use the
evaporation of water to remove process heat and cool the working uid to near the wet-bulb air
temperature. The classication is based on the type of air induction into the tower: the main types
of cooling towers are natural draft and induced draft cooling towers.
18
COOLING TOWER
REFERENCES
[2] Edward, Kku, Ronz and Bogdangiusca, "Cooling tower," 21 09 2016. [Online]. Available:
https://en.wikipedia.org/wiki/Cooling_tower?oldid=738863870.
[3] D. A. C. Ltd., "Cooling Tower Thermal Design Manual," 10 05 2004. [Online]. Available:
http://myhome.hanafos.com/~criok/english/publication/thermal/thermallisteng.html.
[4] UNEP, "Electrical Energy Equipment: Cooling Towers," 23 09 2016. [Online]. Available:
www.energyefficiencyasia.org .
19