Enclosure Integrity Verification Form

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Enclosure Integrity verification form

Building
Room
Testing technician
Witness
Date and time of test

Check Section in Name on


What to look for
off Software Computer Screen

1 __ yes Is the pressure gauge calibration certificate up to date?


N/A N/A (less than 1 year old)
__ no

2 __ yes Is the door fan system calibration certificate up to date?


N/A N/A
__ no (less than 5 years old)

3 __ yes Does the technician have the correct level of training?


N/A N/A
__ no Ask for certificate

4 __ yes Test and Has the correct test type been selected? If mixing is
Technician Test type chosen, verify that mixing will occur.
__ no details

5 __ yes Building and Elevation above


Is it correct within 600 ft or 200 m?
__ no Agent details sea level

6 __ yes Building and Protected enclosure This is used to calculate the initial concentration and
__ no Agent details volume hold time. It must be measured, was it?

7 __ yes Building and Was it measured from floor slab to highest point that is
Enclosure height
__ no Agent details flooded with agent?

8 __ yes Was the height from the floor slab to the equipment
Building and Minimum being protected properly measured? Only applies if
__ no
Agent details protected height there is no mixing but it is useful to have it recorded
__n/a either way.

9 __ yes Was the minimum anticipated temperature entered? If


Building and Operating that information was unavailable it is ok to enter the
__ no Agent details temperature
current room temperature.

10 __ yes Building and


Agent Have they selected the correct agent?
__ no Agent details
Check Section in Name on
What to look for
off Software Computer Screen

11 Options are mass, volume, or concentration. Have they


__ yes Building and selected the appropriate method? Volume for inert
Agent quantity by
__ no Agent details agents, mass for halocarbon agents. Concentration
should not be used unless no mass or volume is known.

12 __ yes Building and Did they enter a correct quantity (mass or volume) and
Agent quantity read it from the labels on the tanks?
__ no Agent details

13 __ yes Do you agree that the value recorded will prevent re-
Building and Minimum ignition at the end of the retention period? Only applies
__ no
Agent details concentration if there is mixing but it is useful to have it recorded
__n/a either way.

14 __ yes Is the correct design concentration entered from the


Building and Design
__ no system design specs? Only applies for extended discharge
Agent details concentration
__n/a systems.

15 __ yes Building and Specified hold Do you agree with the time shown?
__ no Agent details time

16 __ yes Remove all temporary tape or get sufficient assurance it


N/A N/A
__none will be replaced with a permanent seal.

17 __ yes Leakage Area:


Total Enclosure If untested values were entered, do you agree with their
__ no Tested/Enter validity? It would be unusual to have untested values.
Leakage
__ n/a untested

18 __ yes Total Enclosure Bias pressure Did you observe the bias pressure measurement at the
__ no Leakage during fan test time of the Door Fan test?

19 __ yes Total Enclosure


N/A Was the enclosure tested in both directions?
__ no Leakage

20 __ yes Was the enclosure tested at 10Pa and 50Pa in both


Total Enclosure directions? If 50Pa could not be achieved, are you
Induced pressure
__ no Leakage
comfortable with the highest pressure reached?

21 Were the pressures checked across each wall or was


__ yes Total Enclosure there sufficient return path from the Door Fan to the
N/A
__ no Leakage enclosure leaks to ensure the pressure was the same
across all enclosure boundaries.
Check Section in Name on
What to look for
off Software Computer Screen

22 __ yes Total Enclosure Was the range used verified? A picture of the ranges will
Fan range
__ no Leakage pop up in FanTestic Integrity when the range is selected.

23 __ yes Was the flow pressure accurately recorded while the


Total Enclosure
Fan pressure Door Fan was running without FanTestic Integrity
__ no Leakage
warning of the pressure being too low?

24 __ yes Total Enclosure Must be between 0.45 and 0.9 to be acceptable (shown
Flow exponent in the Detailed Results)
__ no Leakage

If BCLA test is not done, skip ahead to 33

25 __ yes
BCLA Test N/A Was a Total Enclosure Leakage test completed first?
__ no

26 __ yes Bias pressure Was the bias pressure re-measured at the time of the
BCLA Test
__ no during fan test BCLA test?

27 __ yes Leakage Area:


If untested values were entered, do you agree with their
__ no BCLA Test Tested/Enter validity? It would be unusual to have untested values.
__n/a untested

28 __ yes Was the enclosure tested at 10Pa and 50Pa in both


BCLA Test Induced pressure directions? If 50Pa could not be achieved, are you
__ no comfortable with the highest pressure reached?

29 Were the pressures checked across each wall or was


__ yes there sufficient return path from the Door Fan to the
BCLA Test N/A
__ no enclosure leaks to ensure the pressure was the same
across all enclosure boundaries.

30 __ yes Was the range used verified? A picture of the ranges will
BCLA Test Fan range
__ no pop up in FanTestic Integrity when the range is selected.

31 __ yes Was the flow pressure accurately recorded while the


BCLA Test Fan pressure Door Fan was running without FanTestic Integrity
__ no warning of the pressure being too low?

32 __ yes Must be between 0.45 and 0.9 to be acceptable (shown


BCLA Test Flow exponent in the Detailed Results)
__ no
Check Section in Name on
What to look for
off Software Computer Screen

33 This is the hold time given all the variables input into
__ pass FanTestic Integrity. If this is greater or equal to the
Retention Time,t
__ fail Specified hold time in the Building and Agent details
section, the room PASSES.
Note any other concerns
you had about the test ->