Transformer Stability Test Calculation

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 14

Transformer Stability Calculation

Applied Test Voltage @ Primary Side

Transformer Ratings
Transforver Vector Group
Transformer KVA rating
Primary Voltage of Transformer (Line-Line) @ KVA rating
Secondary Voltage of Transformer (Line-Line) @ KVA rating
Transformer Impedance (Zt) @ KVA rating
Transformer Primary Full Load Current I (Line-Line) @ KVA rating
Transformer Secondary Full Load Current I (Line-Line) @ KVA rating
Transformer Ratio
Current Calculation
Transformer Primary Impedance
Transformer Primary Impedance Per Phase
Primary Side Injected Current Per Phase
Secondary Side Current Per Phase

Short Circuit Cable Calculation


Cable Length from Transformer to Main Panel
Type of Cable
No of Conductor/Phase
Size of Phase Conductor
Size of Neutral Conductor
Type of Race Way
Phase Conductor Constant (C1)
Neutral Conductor Constant (C2)
F1(L-L) [F(L-L)=(1.732 X Length X Isc)/(C1 X No of Conductor X Volt)]
F2(L-N) [F(L-L)=(1.732 X Length X Isc)/(C2 X No of Conductor X Volt)]
M1(L-L) [M=(1/(1+F1)]
M2(L-N) [M=(1/(1+F2)]
Fault Current at Main Panel Disconnection (L-L) [Isc X M1]
Fault Current at Main Panel Disconnection (L-N) [Isc X M2]
ulation
400 Volt Alu
Cu
Yes
Dyn No
164000 KVA No
170000 Volts
15750 Volts
12.76 %
556.99 Amperes
6011.95 Amperes
10.79

305.2122 Ohms
38.9451 Ohms
10.27 Amperes
110.86 Amperes

50 Meter
Cu 3 Core Cable
1
120 mm2
120 mm2
Non-Metalic
17483
17483
0.000
0.000
1.000
1.000
111 Amp
0 Amp
1 Core Cable Non-Metalic
3 Core Cable Metalic