Professional Documents
Culture Documents
ANNEX 2. Bechman Purging System F-361
ANNEX 2. Bechman Purging System F-361
ANNEX 2. Bechman Purging System F-361
D-64625 Bensheim
Tel.: 06251/63736
FAX: 06251/63729
Client: Order no.: Code: Motor system no.: Sheet no.: of sheets:
Standard -- -- 1 43
Title:
Technical
documentation
Kmmerle
Pre rev.: Originator: Release:
Originate: (date / sign) Checked: (date / sign) Release: (date / sign)
27.11.2013 Bachmann
-- Description Ex px SYSTEM F-361.B4/B4M --
nd.:
Table of contents
To operate motors in hazardous areas some especially requirements are needed for
the electrical and mechanical equipment.
On the base of the Ex-protection p, internal overpressure, motors can operate in
these areas. For this the cabinet of the motors should be sealed in a way that the
leakage of compressed air is very low. Furthermore a pressure supply with sufficient
air supply has to be in reserve.
After the start of the functional sequence the air flow of the purge gas and the
thereby in the motor growing overpressure are monitored.
If a minimum of air flow streams through the motor enclosure (measure point
in the outlet valve) and a fixed motor enclosure overpressure has been
reached the purge time starts. After the purge time ran off, the motor can be
started.
If some faults appear the control sequence is set to the start point of the
functional sequence.
The safety device has to be combined with a main control system, which
prevents the start of the motor until the purging sequence has finished.
Combined with an enclosure which is suitable for use with overpressure the Ex
protection class
II 2G Ex px IIC T4
Clean the connected air pipe or tubing system of the installation plant to
ensure that the supplied air tube is free of dirt or small parts which will cause a
malfunction of the purging system, if no air filter is used.
Check outlet valve so all movable parts for ease of movement, before getting
started.
The internal volume of the motor enclosure must be purged with non-
explosive compressed air, to reduce a possible explosive gas concentration to
safe limits. The overpressure has to be monitored permanent.
If the pressure drops under the reference value an alarm signal is given and the
motor has to be switched off.
2 Main Parts
consists of: main air valve for pressure supply, purge valve, proportional valve
for operating pressure (leakage compensation), adjustment valves
for purge- and leakage volume, measure points (to acquire
leakage volume and the pressure inside the motor enclosure),
indicator for purge pressure, Ex d junction box GUB-02, Ex d box
GUB, main switch, control unit F-351.P (connected with terminals
in junction box) for the potential free signals:
PURGING IN PROGRESS
READY TO START
MOTOR SHUTDOWN
PURGE SEQUENCE FINISHED
MOTOR NOT PURGED
The purge unit in the control cabinet ST-200B/BM monitors the air flow of the
outlet valve and the pressure inside the motor enclosure. Simultaneous the
control automatic works in accordance with EN 60079-2 and ATEX 94/9.
The outlet valve with integrated particle and flame barrier opens during the
purging sequence to ensure the purging of the motor enclosure according to
EN 60079-2. The valve closes completely if the purging sequence is finished.
The built-in safety overpressure valve opens at approx. 30 mbar overpressure.
The sea water proof, corrosion free stainless steel enclosure, Splash water and
sandstorm protected air outlet can be mounted on an existing EN flange
connection of the enclosure in angle steps of 90 degrees with a standard gasket
sheet in between. Mounting of the valve is only allowed in an upright or
horizontal position. The orifice is adjustable even during valve operation and has
an easily accessible measuring point for measuring or check of the volume flow
through the outlet with suitable measuring devices even during operation.
2
P A B
Ex p motor
10
4
5
6
7
9 3
4 Dimensions of ST-200B
(f-361c4.002xe.dwg)
640
170 30
600 805
100
p min A B
p
1355
220
A B p min
p
Kiemenblech
85 135+5
-5
compressed air inlet cable plate
air connection to motor earthing point M8
250
P A B Connection
for tube 10 mm
Cutting ring fitting 10 L
45 30
Measuring point
with M10 screw
locked
185
hole arrangement
according to
EN 1092-1:2007(D)
Type 05 PN16
NW50 and NW65
formerly
DIN 2527
NW50 PN16 and NW65 PN16
240
6 P&I diagram
(f-361x4_va-xxx-5_pi1_en.emf)
1
control unit F-351.P
p min p max
P P P P P P P P
23 p min/max A 22 B
prop. valve
16 18
19
1
18
1 3 5 7 9
PE PE
2 4 6 8 10
2 4 6 8 10
1 3 5 7 9
2
17
16
1 2
3 14
PE L1 N F1 PE
3 4 N
K2 K3
3
2 4
1 5
4
0
15
6
12 13
5 6
11
10
7
8 9
21 20 22 23
19
1
18
9 7 5 3 1
PE PE
10 8 6 4 2
10 8 6 4 2
9 7 5 3 1
2
17
16
2 1
14 3
PE F1 N L1 PE
N 4 3
K3 K2
3
4 2
5 1
4
6 0
15
12
13
6 5
11
10
7
9 8
8 Technical data
4: Protection cabinet
Type: ST-200B/BM
Material: sheet steel with color coating RAL7035
or stainless steel
All inside mounted modules with IP rating: IP 65
5: Earthing point M8
6: Cable plate
W x H x D: 160 x 120 x 10 mm
Cut out in cabinet: 80 x 60 mm
10: Ball valve with hand lever Main air valve, lockable
Material: stainless steel
8.4 Weight
Compressed air in the industry must always be in perfect condition, but that it is not
by nature. On the contrary, dust is everywhere in different concentrations. On cooling
the compressed air comes from humidity unwanted water. Air quality is measured
according to DIN ISO 8573-1-2010 and divided into the following three classes:
class max. residual dust content max. residual water content max. oil content
dust density dust size dew point residual water
mg/m3 m C g/m3 mg/m3
1 0,1 0,1 -70 0,003 0,01
2 1 1 -40 0,117 0,1
3 5 5 -20 0,88 1
4 8 15 +3 5,953 5
5 10 40 +7 7,732 25
6 - - +10 9,356 -
7 - - not specified not specified -
Attention!!
There may be greater demands on the quality of compressed air when sensitive
components or systems are installed within the air purged housing.
Pneumatic connectors
2(+) 3 1(-) - 1,2 differential pressure
- 3 enclosure overpressure
OK / INFO button
Switches the display
over between measuring
data and info menu.
Confirms selected
parameters or values.
Wheel Shuttle
Rotary switch, screwdriver-
activated. Switches over
between different
parametrizing menu,
submenus or selectable data.
Terminal rail
Cable glands
1 OK
OK OK
OK
0,05 mbar /
step
Parameter range:
0,80 - 25 mbar l
OK
3 1mbar / Standard setting: OK
OK 0,8 mbar
step
Parameter range:
OK 1-8
OK
6 Standard setting: 4
Select function:
- Purging - System Fault
- Bypass - Fault 1 min Select polarity:
- <no>reg.closed
7 OK - Fault / Bypass - Fault flash.
- Purge-fail. - Prealarm MIN
OK - <nc>reg.open
OK
- Isolation - Prealarm MAX Preset: <no>
Preset: Purging
Select function:
- Proportional
8 OK - Two-position OK
- pulsed
Preset: Proportional
Select function:
- Purging - System Fault 0,05 mbar /
- Bypass - Fault 1 min step
Parameter range:
0,80 - 25 mbar
9 OK - Fault / Bypass - Fault flash. OK OK
- Purge-fail. - Prealarm MIN 1mbar / Standard setting:
- Isolation - Prealarm MAX OK 0,95 mbar
step
Preset: Prealarm MIN
Select function:
- Purging - System Fault 0,05 mbar /
- Bypass - Fault 1 min step
Parameter range:
0,80 - 25 mbar
10 OK - Fault / Bypass - Fault flash. OK OK
- Purge-fail. - Prealarm MIN Standard setting:
OK 1mbar /
- Isolation - Prealarm MAX 22,50 mbar
step
Preset: Prealarm MAX
Select function:
- Purging
- Bypass
- System Fault
- Fault 1 min Only active with
OK - Fault / Bypass - Fault flash. OK
11
- Purge-fail.
- Isolation
- Prealarm MIN
- Prealarm MAX
connected F-369
Preset: Fault flash.
opto relay
Select function:
12 OK -mbar OK
-pasc
Preset: mbar
13
OK
function
bypass All menus are closed,
OK <on> off
In conjunction with an enclosure (motor enclosure, junction box), the Ex-px system
F-361.x4 provides a pressurized motor that is in compliance with EN 60079-2. For
this purpose, it has all the facilities and sensors needed to monitor the necessary
purging phase and then to monitor and maintain an overpressure within the Ex-p
enclosure (motor cabinet).
1 Structure
The controlling system consists mainly of two components which must be installed
separately:
The controller F-351.Px itself monitors and regulates the overpressure in the
enclosure, while the digital/proportional valves doses the air quantity needed to
achieve the pressurized apparatus.
After a functional test and start-up, the controller F-351 in the control cabinet
ST-xxx monitors the flowrate of the compressed air or inert gas during the initial
purging process, and then monitors and regulates the internal pressure of the
Ex-p enclosure with regard to the surrounding atmosphere during normal
operation.
Display
In three lines of 12 characters each, the digital display shows the enclosures
internal pressure during normal operation, and the remaining purging time in
minutes and seconds during the initial purging process. During normal operation,
you can call up further information by pressing the button "OK / Info". Faults
which are detected during the self-check are shown here with a number.
OK-button
The button on the left side (OK / INFO) is used in normal operation to call up
the stored parameters Enclosure Pressure, Purging Time, Switchpoint of
Purge Start, Switchpoint of Minimum Pressure and Switchpoint of
Overpressure. During the parametrization, this button is used to select and
confirm the various parameters.
The right field (Menu) permits access to the Wheel Shuttle with a tool (e.g. a
screwdriver) for parametrizing the controller. With this Wheel Shuttle, you can
start the parametrization and set the individual parameter values.
Screw terminal
In the lower part of the cover (see page 1), the terminal assignment of the
Controller is shown. Terminals 1 to 3 are inputs; they provide electrical power to
the Controller. Terminals 4 to 19 are outputs, over which the monitoring unit
drives its peripherals, e.g. the digital/proportional controller.
Immediately after the compressed air supply is opened and the main voltage is
applied, the internal self-check of the controller begins automatically. Any fault
occurring during the self-check sequence is indicated by
Error
XXX
An explanation of the fault numbers (XX) is given in the manual, section 3.5 Faults
and Troubleshooting, Table 1: Faults detected during the self-check.
If the self-check is carried out successfully, the initial purging of the enclosure
commences, ending when at least five times the enclosure volume has been
circulated. The purging process is indicated by the message
Remain. time:
XX:XX min.
in the display. All the time, the remaining purging time is counted down to 00 min and
00 seconds.
After the end of the purging sequence, the Non-Ex units in the enclosure are
switched on. The overpressure in the enclosure then constantly monitored for
adherence to the setpoint value (factory setting: 2.0 mbar) and also for transgressing
of the MIN value (factory setting: 0.9 mbar) and exceeding of the MAX value (factory
setting: 20.0 mbar). Normal operation is indicated by the message
OPERATE
pressure is
XX.XX mbar
in the display.
For a reliable operation of the Ex p control system different states have to be fulfilled.
P P P P P P P P
ST-X00 L p A K B
min/max
prop. valve
H I
If all four conditions are fulfilled, hence it follows the state Minimum conditions to start
purge.
While the power supply is switched off and the adjustment of the secondary pressure
(pressure after the pressure regulator is p2 = 3,5 4 bar, the operate
pressure/leakage compensation is adjusted by the leakage valve . Herewith the first
condition overpressure > 50 Pa is fulfilled. The value is in a range of 80 Pa and 1000
Pa (it depends on the construction of the motor enclosure). So the second condition
max. overpressure not exceeded is also fulfilled. The purge flow is smaller than the
adjusted minimum, while the purge valve is closed and in the outlet valve (VA-xxx) no
air flow can be measured. The third condition is fulfilled. The fourth condition is fulfilled,
while the system is not powered.
Standard signal conditions at the terminals in the connection box GUB at this time:
Signal* Relay Terminal* Condition
Motor shutdown K2 + K3 12 Contact opened
Purging in progress K4 34 Contact opened
Motor not purged K2 56 Contact closed
Purge sequence finished K2 78 Contact opened
Ready to start K2 + K3 9 10 Contact opened
*Variations of the used signals or in the order of the terminals are possible on customer request
P P P P P P P P
( f-361x4-va-xxx-5_pi1_s2_en.emf)
ST-X00 L p min/max A K B
prop. valve
H I
If all four conditions are fulfilled, hence it follows the state Purging.
Condition 1 and 2 are fulfilled from state 1. If the control unit is powered now the prop.
valve opens. While the external command motor start purge is active the purge
valve is open. Now the outlet valve (VA-xxx) opens. The compressed air streams
through the Ex p system and a part of it expands in the motor enclosure. A little
overpressure subsists in the motor enclosure. Through the opened outlet valve (VA-
xxx) the compressed air streams in the environment. In the outlet valve a measuring
point for pressure difference is installed. If the air volume at the end of the outlet valve
is measured with an additional instrument, the start point for the purging can be fixed
by the measured air flow and the differential pressure at this point of time. The air flow
is at this point of time higher than the adjusted value in the control unit. So the third
condition is fulfilled. Hence it follows combined with the condition Purge time
incomplete the state Purging. The purge time starts.
Standard signal conditions at the terminals in the connection box GUB at this time:
Signal* Relay Terminal* Condition
Motor shutdown K2 + K3 12 Contact opened
Purging in progress K4 34 Contact closed
Motor not purged K2 56 Contact closed
Purge sequence finished K2 78 Contact opened
Ready to start K2 + K3 9 10 Contact opened
*Variations of the used signals or in the order of the terminals are possible on customer request
To prevent a false alarm, as a result of pressure oscillations through the motor housing
during the purging sequence, a drop-out time delay of ca. 5 sec is programmed in the
control unit. This prevents a prompt reset of the purge time to the start value. The
purge time is stopped, if the adjusted diff. pressure is reached within the 5 sec, the
purge time starts at the stopped time. Otherwise the purge time will be resetted.
The required purging time depends on the setting of the purge volume (normally 10
times the free volume of the motor cabinet) and the presetted inlet pressure at the
pressure regulator .
P P P P P P P P
ST-X00 L p A K B
min/max
prop. valve
H I
If all three conditions are fulfilled, hence it follows the state Purging complete. After
the regular purging the Ex [p] system switches automatically the power. The purge
valve only closes, if the command motor start purge is deactivated. Likewise the
outlet valve is closing. Leakage compensation (operating overpressure) in the motor
enclosure is performed by the adjustment valve leakage compensation and if
needed with the proportional valve . The start sequence of the motor can be initiated.
Standard signal conditions at the terminals in the connection box GUB at this time:
Signal* Relay Terminal* Condition
Motor shutdown K2 + K3 12 Contact closed
Purging in progress K4 34 Contact opend
Motor not purged K2 56 Contact opened
Purge sequence finished K2 78 Contact closed
Ready to start K2 + K3 9 10 Contact closed
*Variations of the used signals or in the order of the terminals are possible on customer request
During the operating time of the motor the enclosure can be leaking. This is corrected
by the proportional valve . The deviation control is supervised by the control unit to
the adjusted operating pressure. The operating pressure can also be readjusted with
the manual valve .
The overpressure in the motor enclosure is supervised by the pressure sensors "Min"
and "Max" in the control unit F-351.P. Drops the overpressure below the adjusted
value of "Min", or increases the overpressure over the adjusted value of "Max", the
operating releases (READY TO START 1 + 2) are cancelled.
In this Ex d box are all needed relays and terminals mounted, which are required for
wiring the electrical system. The relays are wired together, that the signals READY
TO START, MOTOR SHUTDOWN, PURGE SEQUENCE FINSHED and MOTOR
NOT PURGED are built. These signals are cabled to the Ex d box GUB. The
connection for the power supply is wired to this box (terminal L1 and N), the
terminals for the control signals are located in the Ex d box GUB.
(f-361.x4_gub02_iv1.emf)
12 11 10 9 C 12 11 10 9 C
O O
41 31 21 11 M 41 31 21 11 M
1 2 8 7 6 5 N 8 7 6 5 N F1 PE
PE 4 6
44 34 24 14 O 44 34 24 14 O
L1 N 4 3 2 1 N 4 3 2 1 N 7
3 5 42 32 22 12 C 42 32 22 12 C
K2 K3
3 5
4 6 C C
14 13 O 14 13 O
I I
A2 A1 L A2 A1 L
PE
For the power supply a cable with a diameter of max. 17 mm can be installed.
It has to be secured that the installed cable through the Ex d cable gland is accurate
sealed, because of the direct wiring in the Ex d box. Not used bore holes have to be
closed with certified plugs.
11.1 Terminals
(f-361.x4_gub02_ter.emf)
12 11 10 9 C 12 11 10 9 C
O O
41 31 21 11 M 41 31 21 11 M
1 2 8 7 6 5 N 8 7 6 5 N F1 PE
PE 4 6
44 34 24 14 O 44 34 24 14 O
L1 N 4 3 2 1 N 4 3 2 1 N 7
3 5 42 32 22 12 C 42 32 22 12 C
K2 K3
3 5
4 6 C C
14 13 O 14 13 O
I I
A2 A1 L A2 A1 L
Terminals for power feeder are suitable for cable size of 4 mm.
(f-361.x4_gub10w_en.emf)
2 4 6 8 10
PE PE
1 3 5 7 9
1 3 5 7 9
2 4 6 8 10
12.1 Terminals
(f-361.x4_gub10w_en.emf)
2 4 6 8 10
PE PE
1 3 5 7 9
1 3 5 7 9
2 4 6 8 10
Terminals for signal cable are suitable for cable size of 4 mm.
13 Wiring plan
(f-361x4_wp1_en.emf)
power supply
GUB 02
-X1 L1 N PE 1 2
F1:
230 VAC = 200 mA
115 VAC = 400 mA
24 VDC = 1,6 A 12 22
K3
11 21
purging in F1
13 23 progress K2 K3 spare
A1 A2
PE 3 4 PE 7 PE 5 6 PE
A2 A1 gn/ye bl br gn/ye bl br
14 24
main
switch PE 1 2
F1
F-351.P
1 2 3 4 5 6 7 8 9 10
purging in Ex p
progress release
K1 N L
PE L N control
power supply
Ex d enclosure GUB
-X2 PE 1 2 3 4 5 6 7 8 9 10 PE
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
44 22 14 34
K2
41 21 11 31
3 4
44 31
K3
41 34
Ex d enclosure GUB02
14 Type Code
.L.B. EX-GERTE
EEx-p System Type F-361.B4
TV 02 ATEX 1801
Operating voltage: VAC/48-62 Hz VDC
For the identification of the system a stainless steel plate is fixed at the enclosure
of the control cabinet.
16 Timing diagrams
T1: Switching on power supply and opening air pressure supply the control unit begins with a self test and the purging sequence
of the Ex p motor enclosure starts. With an air flow which is higher than the adjusted value min air flow and the air flow is
adequate the adjusted purge volume (min. 10-fold inner free motor volume), the motor enclosure is purged.
T2: The purging sequence is finished. The adjusted motor enclosure overpressure is controlled by the leakage compensation
(see chapter 5 of main manual). The Non- Ex units can be powered.
T1: The purging sequence is finished. The adjusted motor enclosure overpressure is controlled by the leakage compensation
(see chapter 5 of main manual). The Non- Ex units can be powered.
T2: Normal operation starts. The internal enclosure overpressure is regulated to the set point value.
T4: The increased overpressure is controlled down with the proportional valve.
T1: Switching on power supply and opening air pressure supply the control unit begins with a self test and the purging sequence
of the Ex p motor enclosure starts. With an air flow which is higher than the adjusted value min air flow and the air flow is
adequate the adjusted purge volume (min. 10-fold inner free motor volume), the motor enclosure is purged.
T2: During the purging sequence the internal overpressure increases to an excessively high value.
T3: During the purging sequence the minimum air volume flow falls. The purging sequence is resetted.
T1: The purging sequence is finished. The adjusted motor enclosure overpressure is controlled by the leakage compensation
(see chapter 5 of main manual). The Non- Ex units can be powered.
T2: Normal operation starts. The internal enclosure overpressure is regulated to the set point value.
T3: The internal enclosure pressure drops. If the pressure value falls below the switch point Minimum pressure in relation to
the external pressure, the Non- Ex units are switched off.
T6: The internal enclosure pressure rises. The increased internal enclosure pressure cannot controlled down.
T7: If the internal pressure value exceeds the switch point Overpressure, the Non- Ex units are switched off. The purge valve
is powered, so the outlet valve opens. The increased overpressure sinks to operation values.
T8: After the pressure decrease, normal operation begins without purging.
17 Options
17.1 Option: Outlet valve VA-65-3H
Mounting example:
(f-361c4.001xe.dwg)
P
2
A B
Ex p motor
10
4
5
6
7
9 3
Not to scale
1: Control cabinet ST-xxx
2: Outlet valve VA-xxx-3H
3: Measure point motor inside pressure
4: Pilot line to outlet valve
5 and 6: Measure points air volume A - B
7: Measure line motor inside pressure
8: Compressed air connector for supply (Flanges as option)
9: Compressed air connector to motor (Flanges as option)
10: Motor enclosure
120 450
240
130
390
50 45
450.0
Please notice that retroactive the overpressure in the motor enclosure rises.
(VA-65-3H_iv_en.emf)
A B
The VA-xxx-3H types of the outlet valve are available in a mirrored version e.g. to
avoid the crossing of the pipes to the valve or if you need to place it at the other side of
the motor.
Mounting example:
(f-361x4_va-xxx-m_me_en.emf)
2
B A P
Ex p Motor
4 10
5
6
9
8
Not to scale
1: control cabinet ST-xxx
2: outlet valve VA-xxx-3HM
3: measure point motor inside pressure
4: pilot line to outlet valve
5 and 6: measure points air volume A - B
7: measure line motor inside pressure
8: compressed air connector for supply (Flanges as option)
9: compressed air connector to motor (Flanges as option)
10: motor enclosure
450 120
240
130
390
45 50
450.0
Depending on your project you can order various flanges and drilling assembly can be adjusted
according to your needs.
(f-361x4_flanges.emf)
B 5 D 5
A 5 C
D 5
C
Our standards:
F-361.A4 F-361.B4 F-361.C4 F-361.F4
A: 260 mm 260 mm 300 mm
B: 177 mm 177 mm
C: 170 mm 220 mm 220 mm 240 mm
D: 110 mm 135 mm 135 mm 135 mm
E: 80 mm 90 mm 90 mm 115 mm
22 21 20 19
18
1
17
Pos. 2 16
Ex d enclosure
not mounted 15
14
13
12
3
11
10
4 5
9
6 7
Wiring plan
(f-361f4.022xe.dwg)
power supply GUB 02
-X1 L1 N PE 1 2
purging in Start/Stop
progress
3 4 5 6
21 12 12
K2 K2 K3
11 11
24 F1
13 23 21
K2 K3
A1 A2
PE K3 PE 7 PE PE
24
A2 A1
14 24 gn/ye bl br
main
switch PE 1 2
F1
F-351.P
1 2 3 4 5 6 7 8 9 10
EEx p
purging in
release
progress
K1 N L
PE L N control
power supply
Minimum required signals are the purging in progress and the Start/Stop signals.
The Ex d junction box GUB is not needed anymore, all cables have to be wired to the
Ex d control box GUB 02.
-X2 PE 1 2 3 4 PE -X3 PE 1 2 3 4 5 6 7 8 9 10 PE
44 22 14 34
K2
41 21 11 31
-X1 3 4
44 31
K3
41 34
GUB-02 (-X1)
(f-361c4_iv_2gub_en.emf)
23 22 20 21
19
1
18
1 3 1 3 5 7 9
PE PE PE PE
2 4 2 4 6 8 10
2 4 2 4 6 8 10
1 3 1 3 5 7 9
2a, 2b
17
16
1 2
14
PE L1 N PE
3
F1
3 4 N
K2 K3
3
2 4
1 5
4
0
15
6
12 13
5 6
11
10
7
8 9
22 21 20 19
18
1
F-3 6 9
17
16
Pos. 2
Ex d enclosure 15
with F-369
14
13
12
3
11
10
4 5
9
6 7
The function of each relay is programmable as listed (menu plan page 14):
L1 N PE 1 2
11
K3 K2 K3 F1 11 21
14 24
34 A1 A2
PE PE PE 13 PE PE
31
A2 A1 gn/ye bl bn
main
switch gn/ye bl bn
-Y2 -Y1
PE 1 2
F1
-A3
leakage valve purge valve
F-369 9 10 7 5 3 1 14 15 16
Adjustment F-369:
12 12 12
K2 = pre-alarm MIN -A1 F-351.PC
K3 = pre-alarm MAX 1 2 3 4 5 6 7 8 9 10
K4 = fault Ex p
all DIP switches "ON" 11 11 11 release
K4 K3 K2
bn ye wh gy
K1 N L
12 10 8 6 PE L N control C
GUB 0 power supply
The opto-relay F-369 is mounted together with the option minimum required signals.
All signals are wired to terminals in the Ex d box GUB02.
Using the Ex p system with temperatures higher than + 40C the proportional valve
(Pos. 14) has to be interchanged with a proportional valve suitable for +60C.
Technical data
17.8 Option: F-361.x4M with extended ambient temperature range down to -40C
(f-361f4.025xe.dwg)
21 20 22 23
19
1
18
9 7 5 3 1
PE PE
10 8 6 4 2
25
10 8 6 4 2
9 7 5 3 1
2
17
16
24
14 3
PE F1 2 1 N L1 P E
N 4 3
K3 K2
3
4 2
5 1
15 4
6 0
12 26
13
6 5
11
10
7
9 8
To operate the Ex p purging system below an ambient temperature of -20 C down to -40 C
heaters will be added inside the control cabinet of system F-361. The heaters and the junction
box (for power supply) are mounted inside the door. The heater is switched on, if the cabinet
temperature drops below +10C to additionally avoid condensation etc.. The Ex p system is
powered while temperature in the cabinet is higher than - 15C.
Technical data
24: Temperature switch
Ex-protection class: II 2 G Ex d IIC T6
Protection class: IP 68
Temperature range: - 50C + 180C
Certified by: PTB 03 ATEX 1136X
Switch point: -15 3 C
25: Ex - heater
Ex-protection class: II 2 GD Ex dm IIC T3
Protection class: IP 68, NEMA 4X
Temperature range: -50C ... +80C
Certified by: PTB 02 ATEX 1041 X
Certified by: IECEx PTB 07.0052X
Rated power: 3x 100W = T4 or
2x 200 W = T3
Temperature limiter: built-in, automatically working
26: Ex - junction box
Ex-protection class: II 2 G Ex e II T5
Protection class: IP 66
Temperature range: - 20C + 55C
Certified by: PTB 99 ATEX 3103
Certified by: IECEx PTB 06.0026
Due to the type of construction, the heater requires no maintenance. Performance and
safety tests can be conducted at intervals to be determined by the operator in
compliance with current regulations.
Repair work must only be carried out by the manufacturer.
Safety instructions
Wiring plan
for temperature class T3
(f-361x4_wp_+heaterT3_en.emf)
-X1 L1 N PE
(+) (-) PE PE 2 3
12 22
K3
11 21
purging in F1
1 13 23 K3
progress K2 A1 A2
PE 4 5 PE 6 PE PE
T>
-15 C 3 A2 A1
14 24 gn/ye bl br gn/ye bl br
temperature main
switch switch PE 1 2
F1
Ex e junction box
+10 C +10 C
T> T>
F-351.P
1 2 3 4 5 6 7 8 9 10
Ex p
purging in
release
progress
T> T>
K1 N L
PE L N control
power supply
Ex e junction box
NOTE: If Tamb is lower than -15 3C then a delay time may occur until the power
to the control system is switched on.
The below mentioned function is understood as an additional feature, all other features
remain unchanged:
Prologue:
In addition to the standard the pressurization system is extended with an externally
adjustable additional Ex i pressure sensor. This Ex i sensor has a large wheel adjuster
with an adjusting range between 2.0 and 20.0 mbar The maximum switching
hysteresis is stated at 0.4 mbar. The measure connection of this additional, external
sensor is already connected to the outside of the control box and operates to supervise
a second pressurized chamber of the main Ex px protected motor engine.
a. To initiate the pre-purging sequence it is essential that even the pressure in the
second supervised chamber of the motor is at least over the adjusted setting of
the additional Ex i sensor.
b. If this internal pressure is not sufficiently the message "waiting for external
release" appears on the LCD of the control unit F-351.
c. If the pressure in the second Ex p chamber is permanently below the set value
of the external sensor, the message "external monitoring Error" appears with a
delay time of 10 sec on the LCD of the control unit and at the same time the
operation authorization for the Ex px motor engine expires (motor stop
condition).
e. The pressure conditions in the main chamber have priority, i.e. a pressure drop
in the main chamber leads in each case to an expiration of the authorization for
safe operation (motor stop condition) and with sufficient air supply to a new pre-
purging sequence.
OK
Function
bypass
?
OK
Enter
password
xxxx
OK
OK
Select function:
- Bypass For use with option F-290.A
- Release Purge Start
- Printer Door
- Temperature Sensor
purge start + cont.
- Release purge contin
- Release operate is preseleted
- Rel. purge start+cont
Preset: Bypass
OK
1
F-290.A control unit F-351.PF
p p max
min
Ex-i
P P P P P P P
21
7
8
10 9
L1 N PE 1 2
F1:
230 VAC = 200 mA
115 VAC = 400 mA
wired to GUB 24 VDC = 1,6 A 12 22
terminals 3 and 4 K3
13 23
PURGING IN
K2 K3 F1 11 21
PROGRESS A1 A2
PE 3 4 PE 5 PE PE
14 24
A2 A1 gn/ye bl br
gn/ye bl br
main
switch
PE 1 2
F1
F-290.A F-351.P
1 2 3 4 5 6 7 8 9 10
Ex p
release
3 K1 N L
gn gr PE L N control C
power supply