EM1000/EM1200/EM1220 Power and Energy Meter Introduction Power and Energy Meter Physical Description

Quick Start Guide Models and Parameters


C60000243-04 English The power and energy meter ships in three different configurations.
06/2015 Parameter EM1000 EM1200 EM1220
VLL - V12 V23 V31
VLN - V1 V2 V3
A A1 A2 A3

RMS F
PF PF1 PF2 PF3

W W1 W2 W3 /
VA VA1 VA2 VA3 /
VAR VAR1 VAR2 VAR3

KWh / KVAh / KVARh

Run.h
INTG & OLD
On.h

INTR
Input current terminals
A1, A2, A3
POP 50mA to 6A
RS-485 communication
Class 0.5 Accuracy

Class 1.0 Accuracy


S1 1 2 S2 S1 3 4 S2 S1 5 6 S2 7
A1 A2 A3

D0
D1D1D1

to 6Ato 6A CURRENT INPUTS: 50mA to 6A


50mA50mA RS-485 terminals for EM1200/EM1220

ZAR
S N:
S/N: XXXXXX/XXXXXX- XX Acc
XXXXXX/XXXXXX-XXXX Acc Acc
Cl:Cl: Cl: X.X
X.XX.X
power and energy meters

RS 485
NOTE: Standard Option specified while ordering VER:XX.XX.XX ITEM CODE:XXXXXXXX
VER:XX.XX.XX

44 - 277 V < 4VA


Or
80 to 480
VOLTAGE 480 Vac
Vac :LL
INPUT LL80 to 480 Vac LL 4450
to Hz Vac 50/60Hz
277 Vac 50/60Hz << 3VA
3VA
POP terminals for EM1000 energy meters
The power/energy parameters are user-programmable. Only one power related parameter L ND0D0D0

D1
8 V1 9 V2 10 V3 11 VN 12 13 14

will be available at a time in the meter.

DAN
One (1) EM1000/EM1200/EM1220 power and energy meter.
One (1) quick start guide (QSG). Input voltage Aux supply
To download user manuals and other documentation, visit www.schneider-electric.co.in. terminals (control power)
One (1) test and calibration certificate for the power and energy meter.
Type the device model (For e.g., EM1220) in the search field. V1, V2, V3, VN 44 to 277 VAC/DC
80 to 480 VAC LL

3-phase 3-wire delta connection


Dimensions L1
L2
L3
LINE
Wire size Temperature Rating 90.0
System type Meter configuration
3.54 LOAD
2
0.82 - 3.31 mm Star/Wye StAr
(18 - 12 AWG)
2 Delta, open delta dLtA
> 7.5 A 2.08 - 3.31 mm
(14 - 12 AWG) 2-phase 2 ph S1 1 A1 2 S2 S1 3 A2 4 S2 S1 5
A3 6 S2
D1
7

> 75 C (167 F) INPUTS:- 50mA


CURRENT INPUTS: 5A NOM / 6A MAX
to 6A
Auxiliary supply 0.82 - 3.31 mm2 Single-phase 1 ph

RS 485
S/N:XXXXXX/XXXXXX-XXXX Acc Cl: 1.0
> 0.1 A
(control power) (18 - 12 AWG)
VER:XX.XX.XX ITEM CODE:XXXXXXXX

44 - 277 V < 4VA

0.33 - 3.31 mm2


VOLTAGE INPUT
VOLTAGE INPUT ::-80
80to
to480
480Vac
VacLL
LL 44 to 277 Vac 50/60Hz < 3VA
50 Hz
D0
RS-485 8 V1 9 V2 10 V3 11 VN 12
L N
13
D0
14
(22 - 12 AWG)

0.25 A
80.0
PT
3.15

Fuse (Slow blow)


NOTICE 8.00
0.31
0.25 A
Aux supply
Communication
(Control Power)
44 to 277 VAC/DC
Use PT,
if VAC LL > 480 V
DAMAGE TO THE DEVICE
Mounting angle
Use only the specified tool for tightening and loosening the screw Potential transformer (PT) 3-phase 3-wire open delta connection
Do not over-torque the screw above the specified range 90 90
L1
L2
Failure to follow these instructions can result in equipment damage. 3-phase 4-wire star/wye connection L3
LINE
L1 LOAD
L2

Tools and Equipment Requirements L3

Mounting N
LINE LOAD

Driver Torque driver preferred; may use hand screwdriver. S1 3 5 6 S2

1 2 3
S1 1 A1 2 S2
A2 4 S2 S1
A3 D1
7

Tip Phillips tip preferred, but you can also use flat. INPUTS:- 50mA
CURRENT INPUTS: 5A NOM / 6A MAX
to 6A
Do not use Pozidriv tip.

RS 485
S/N:XXXXXX/XXXXXX-XXXX Acc Cl: 1.0
VER:XX.XX.XX ITEM CODE:XXXXXXXX
Screw head diameter 3.5 mm(0.14 in.) 5 6 S2
S1 1 A1 2 S2 S1 3 A2 4 S2 S1
A3 D1 7 44 - 277 V < 4VA
Shaft diameter < 5 mm (0.2 in.). Diameter 5 mm (0.2 in.) will get stuck in the cover. INPUTS:- 50mA
CURRENT INPUTS: to 6A
5A NOM / 6A MAX
VOLTAGE
VOLTAGE INPUT
INPUT ::-80
80to
to480
480Vac
VacLL
LL 44 to 277 Vac 50/60Hz < 3VA
50 Hz
L N D0
D0
V1 V2 V3 VN

RS 485
S/N:XXXXXX/XXXXXX-XXXX Acc Cl: 1.0 8 9 10 11 12 13 14
Torque Tightening Torque: 0.25 to 1 N.m (2.21 to 8.85 lb-in) VER:XX.XX.XX ITEM CODE:XXXXXXXX

0.25 A
44 - 277 V < 4VA PT
If the torque is more than 1 N.m (8.85 lb-in), then it may damage the VOLTAGE INPUT :-
: 80 to
to 480
480 Vac
Vac LL
LL 44 to
50277
L
Hz Vac 50/60Hz < 3VA
N D0
D0
screw or the screw head. 8 V1 9 V2 10 V3 11 VN 12 13 14

Communication

0.25 A
Loosening Torque: 1.2 N.m PT
Aux supply
(Control Power)
0.25 A
44 to 277 VAC/DC
Aux supply Communication Use PT,
0.25 A (Control Power) if VAC LL >
480 V
NOTE: Installation should include a disconnecting device, like a switch or circuit breaker, with 44 to 277 VAC/DC

clear ON/OFF markings, to turn-off the auxiliary supply (control power). The disconnecting Use PT,
if VAC > 480 V LL
/ 277 V LN
device should be within the reach of the equipment and the operator.
2-phase 3-wire connection Keys and Operation PROG Menu -
Setup Enter Setup Menu in Edit Mode
Keys Description The PROG menu setup gives the complete list of user-programmable parameters.
L1
The EM1000/EM1200/EM1220 power and energy meter has four keys. The keys and their ?You must set up the power and energy meter to match the application settings before use.
L2
descriptions are explained in the following table : Otherwise, readings will be wrong.
N
LINE ?All the setup parameters can be re-programmed, using SET. However, the following
Keys and Description settings critically determine the scaling of the measured readings: SYS (star or delta),
LOAD

OK key:
Vpri, Vsec, Apri, Asec.
OK To navigate forward to the sub-parameter pages. ?The scaling may be used to minimize the errors in reading due to Instrument
Transformer errors. However, wrong settings will introduce errors in readings on other
S1 1 A1 2 S2 S1 3 A2 4 S2 S1 5
A3 6 S2
D1 7 running systems.
CURRENT
CURRENT INPUTS:
INPUTS:- 50mA to 6A
5A NOM / 6A MAX ESC key:
ESC

RS 485
S/N:XXXXXX/XXXXXX-XXXX Acc Cl: 1.0
To navigate back to the main parameter pages. Press OK four times
VER:XX.XX.XX ITEM CODE:XXXXXXXX
You can enter PROG menu setup in
VOLTAGE
VOLTAGEINPUT
INPUT::-80
80toto480
480Vac
VacLL
LL
44 - 277 V < 4VA
44 to 277 Vac 50/60Hz < 3VA
50 Hz
L N D0
D0
?View mode: To view the set parameters.
V1 V2 V3 VN
8 9 10 11 12 13 14
Up Key: ?Edit mode: To view or edit the set parameters.
0.25 A

PT Used to scroll up through the display pages of same level, within the same function.
0.25A In Set mode, used to increase the value by one .
Aux supply Communication
(Control Power)
Use PT, if 44 to 277 VAC/DC
Down Key:
NOTE:
VAC > 480 V LL
/ 277 V LN
Used to scroll down through the display pages of same level, within the same function. HAZARD OF UNINTENDED OPERATION - Means blinking.
In Set mode, used to decrease the value by one.
Single-phase connection Only qualified personnel are authorized to set up the power and energy meter. 2 - Means 2 is blinking.

L1 Failure to follow this instruction can result in injury or equipment damage.


N
NOTE: The following symbols are used to represent the different keys operations.
/ - OK operation. 1. Press from RMS. The display shows SET.
LINE LOAD 2. Press . The display shows SET VIEW.
OK

/ - ESC operation. Enter Setup Menu in View Mode 3. Press . The display shows SET EDIT. You are required to enter CODE to enter into
setup in Edit mode.
/ - operation. 4. Press .The display shows CODE 2000 with blinking 2.The factory set CODE is 1000.
OK

5. Press . The display shows CODE 1000 with blinking 1.


S1 1 2 S2 S1 3 4 S2 S1 5 6 S2 7
/ - operation. 6. Press four times. The display flashes PASS and then Ed A.PRI 100.0.
OK
A1 A2 A3 D1

CURRENT INPUTS:
INPUTS:- 50mA to 6A Keys Operation
This indicates that you have successfully entered the setup menu in edit mode.
RS 485

S/N:XXXXXX/XXXXXX-XXXX Acc Cl: 1.0


VER:XX.XX.XX ITEM CODE:XXXXXXXX The following example explains how to navigate from the RMS page to the KWh display
page and back to the RMS page.
VOLTAGE INPUT ::- 80
80 to
to480
480Vac
VacLL
LL
44 - 277 V < 4VA
44 to 277 Vac 50/60Hz < 3VA
50 Hz NOTE: If you enter a wrong CODE, the display flashes FAIL and then shows SET EDIT.
D0
8 V1 9 V2 10 V3 11 VN 12
L N D0
13 14
1. Press from RMS. The display shows INTG page. Repeat the steps and make sure that you enter the correct CODE.
0.25 A

PT 0.25 A 2. Press OK
from INTG. The display shows KWh. 1. Press from RMS. The display shows SET.
3. Press ESC
to return to INTG page. 2. Press . The display shows SET VIEW.
OK
RMS 4. Press to return to RMS page.
Aux supply
Communication 3. Press . The display shows VI A.PRI 100.0. Use
OK and to view the setup parameters
Use PT, if
VAC > 480 V LL
(Control Power) and their default values.
/ 277 V LN 44 to 277 VAC/DC
INTG NOTE:
KWh
Use to go forward to the sub parameter pages.
OK

Use to go back to the main parameter pages.


ESC

Use and to scroll up and down through the display


pages.

Setup Parameters in View and Edit Modes (EM1000) Setup Parameters in View and Edit Modes (EM1200/EM1220) Edit Set Parameters Save New Value to the Setup

This section explains how to edit the setup parameter A.PRI from 100.0 to 5000 in the
A.PRI = Current primary winding (CT); Input range 1 A to A.PRI = Current primary winding (CT); Input range 1 A to EM1000/EM1200/EM1220 power and energy meter.
99 kA. Default value is 100.0 99 kA. Default value is 100.0
For better understanding, the editing is explained in two parts: Edit and Accept Setup, Save
A.SEC = Current secondary winding (CT); Default value is A.SEC = Current secondary winding (CT); Default value is New Value to the Setup. NOTE:
5.000. 5.000. - Means blinking.
V.PRI = Voltage primary winding (PT), line to line; V.PRI = Voltage primary winding (PT), line to line; Edit and Accept Setup
Input range 100 V to 999 kV; Default value is 415.0. Input range 100 V to 999 kV; Default value is 415.0.
y - Means y is blinking.
1. After you edit and accept the parameter as previously described, press ESC. The display
V.SEC = Voltage secondary winding (PT), line to line; V.SEC = Voltage secondary winding (PT), line to line;
Input range 50 V to 600 V; Default value is 415.0. Input range 50 V to 600 V; Default value is 415.0.
shows SAVE y with blinking y.
2. Press . The display flashes PASS and shows SET EDIT.
OK

SYS = System configuration; Select from StAR, dLtA, 2 ph, SYS = System configuration; Select from StAR, dLtA, 2 ph, 3. Press . The display shows SET.
ESC

1 ph; Default value is StAR. 1 ph; Default value is StAR. Press OK four times
NOTE:
St.A = Starting current; 1 to 200 mA St.A = Starting current; 1 to 200 mA 1.If you do not want to save the new value, press to change SAVE y to SAVE n in
Default value is 005. Default value is 005. Press four times step 1. Press . The display flashes FAIL and shows SET EDIT. Proceed to step 3.
OK

PF.STD = PF standard; Select from IEC, IEEE, TRIG PF.STD = PF standard; Select from IEC, IEEE, TRIG
2.If you want to go back to the ED A.PRI 5.000 page from SAVE y in step 1,
Default value is TRIG. Default value is TRIG. then press . ESC

VA.FN = VA function selection; Select between 3D and Arth; VA.FN = VA function selection; Select between 3D and Arth;
Default value is 3D. Default value is 3D. Edit ID
NOTE:
*PAR = Parameter selection ; Select from Wh, VAh, VARh; *PAR = Parameter selection ; Select from Wh, VAh, VARh;
Default value is Wh. Default value is Wh.
- Means blinking.

E.POP = Energy POP


Baud = Baud rate; Select from 4800, 9600, 19200; 2 - Means 2 is blinking.
Default value is 1.00K Press OK
four times
Default value is 19200.
POP.ON = POP on time
Default value is 50 millie secs PRTY = Parity and stop bit settings; Select from EVN.1, 1. After you have successfully entered the setup in Edit mode (See Enter Setup Menu in Edit NOTE:
ODD.1, no.2; Default value is EVN.1. Mode for more information), press OK . The display shows ED A.PRI 100.0 with blinking 1. - Means blinking.
2. Press four times. The display shows ED A.PRI 500.0 with blinking 5.
ID = RS 485 device ID number; 001 to 247; Default value is
001.
3. Press OK four times. The display shows ED A.PRI 500.0 with blinking .. 2 - Means 2 is blinking.
4. Press once. The display shows ED A.PRi 5.000 with blinking . and k indicator.
NOTE:
The value 5000 is represented as 5.00 with k indicator. 1. Press from RMS. The display shows SET.
*Parameters such as Wh,VAh, and VARh are User selectable.
See Indicators on page 3 for more information. 2. Press . The display shows SET VIEW.
OK
If a parameter is changed in setup, the integrator will get reset. The following integrators NOTE: 5. Press OK . The new value is accepted. 3. Press . The display shows SET EDIT.
will be reset: *Parameters such as Wh, VAh, and VARh are User selectable.
- VA h/ Wh/ VAR h If a parameter is changed in setup, the integrator will get reset. The following integrators 4. Press . OK

- Run.h will be reset: You are required to enter CODE to enter into setup in Edit mode.
- On.h - VA h/ Wh/ VAR h 5. Press .The display shows CODE 2000 with blinking 2.The factory set CODE is 1000.
OK

- No. of INTR - Run.h 6. Press . The display shows CODE 1000 with blinking 1.
- On.h 7. Press OK
four times. The display flashes PASS and then Ed A.PRI 100.0.
- No. of INTR 8. Press . The display shows ED ID 001.
To edit the values, press and set the values as required.
OK

9. Press , the display shows SAVE y with blinking y.


ESC

2 10.Press . The display flashes PASS and shows SET EDIT.


OK
CLR INTG Energy Integrator INTG, OLD, Overflow Integrator Overflow kVA Measurement
The EM1000/EM1200/EM1220 power and energy meters are equipped with an energy
integrator INTG where the energy parameters are accumulated. Energy Integrator INTG
EM1000/EM1200/EM1220 power and energy meter has two different kVA measurements
Your EM1000/EM1200/EM1220 power and energy meter is equipped with an V.PRI x A.PRI Max Reading Minimum time to overflow
3D and arithmetic. These are available in the setup parameter VA.FN and can be edited
energy integrator function which provides several parameters for Energy x 1.732 (Wh/VAh/VARh) at full scale (in months)
upon entering the SET.
Management: VAh, Wh, VARh, RUN.h, ON.h, INTR.
Press four times All the values stored in INTG are direct readings and have high resolution. < 1000 k 9999999.0 k 13.88 ?
OK

3D measurement (factory-set): Advanced method which provides most accurate and


A few of these need explanation: predictable measurement under unbalanced as well as distorted waveform conditions .
RUN.h: Indicates the period the load is ON and has run. This counter gets accumulated as < 1000 M 9999999.0 M 13.88
?
Arithmetic measurement: Used when the energy meter needs to match the readings of
the older or simpler meters.
long as the load is ON.
NOTE: ON.h: The period for which the input voltage is ON.
< 1000 G 9999999.000 G 13.88 kVA measurement selection
- Means blinking. INTR: The number of input voltage interruptions or input voltage outages.

y - Means y is blinking. Integrator Overflow OLD Data Register kVA function Formula Other names Which one?

The energy values stored in INTG are based on V.Pri x A.Pri; they are independent of When the integrator is cleared (manually or due to overflow), the energy values stored in
3D
kVA3 D =W2 +
VAR 2 +
D2 U, Apparent vector Best all around
1. Press from RMS page. The display shows SET. secondary values of V and A. the integrator will be transferred to the OLD register.
where D = Distortion power per kVA
2. Press . The display shows CLR. The energy value readings will overflow based on V.Pri x A.Pri of the primary settings in Thus the old energy values are not lost even after the integrator is cleared and can be IEEE 100
You are required to enter CODE to clear the INTG values. setup. viewed with the OLD parameter.
2. Press OK . The display shows 2000 with blinking 2. The factory set CODE is 1000. The energy parameter is user selectable (Wh, VARh or VAh) through setup. By
3. Press . The display shows 1000 with blinking 1. Arth kVA Arth =
kVA1 +
kVA2 +
kVA3 Arithmetic scalar kVA Good under low
default it is Wh. NOTE: For energy studies clear the Integrator at the end of each observation. This transfers unbalance, to match
4. Press OK four times to accept the new CODE value. The display flashes PASS and then
shows CLR INTG. all the stored energy values to the OLD register, where they are held while the integrator simple meters
begins accumulating data for the next observation. without 3D capability.
5. Press OK . The display shows CLR INTG y with blinking y.
6. Press OK to clear the INTG values. The display flashes PASS and then shows CLR INTG. When the integrator is cleared next time, the OLD values will be overwritten.
7. Press ESC . The display shows CLR.
8. Press twice. The display shows RMS.

NOTE: If you do not want to clear the INTG, press to change the value from CLR INTG
y to CLR INTG n in step 5. Press OK . The display flashes FAIL and then shows CLR INTG.
Proceed to step 7.

Features EM1000/EM1200/EM1220 Series Power and


Energy Readings 1
Auto-scroll Energy Meter Menu Hierarchy
?
Auto-scroll allows you to view a group of display pages sequentially every five seconds Energy Reading, Range As shown in the Display 1
3-Phase
without manual key operation.
?
During auto-scroll, the meter displays parameter name and value for four seconds. 00001.0000 to 9999999.00 K to RMS = RMS value display pages are in sub level DIAG MDL DIAG = Represents diagnostic pages. The values contained
A V LL PF
Active(Wh) / in these pages are for factory testing only
?
Auto-scroll is possible only within the page groups. i.e., the parameters within the page
10000.0000 to 9999999.00 M to RMS VER
Apparent(VAh) / A V F MDL = Product model number
groups like RMS or INTG or DIAG will be auto-scrolled sequentially. Reactive(VARh) A = Current average
?
The following table explains the auto-scroll operation in RMS parameter pages in VLL = Phase to phase voltage average C.SUM
10000.0000 to 9999999.00 G to VER = Product version number
W A PF PF = Power factor average

Applicable for EM1220


EM1000/EM1200/EM1220 power and energy meter. C.SUM = Check sum
M.ON
A = Current average
A V = Phase to neutral average M.ON = Energy meter power ON hours
F = Frequency average M.INT
Auto-scroll Default Display Page M.INT = Energy meter power interruptions
V LL
Step Perform Output W = Active power total 001 EVN1 19.2k*
A = Current average Communication settings*
The default display page feature enables you to select any display page as user-set display V
PF = Power factor average A. Rev A. Rev = CT reverse indication
*

1 Press OK from RMS. The display shows W PF or A VLL PF(For EM1220) page. You can scroll to other pages, when the default display page is active. The default
display page will be displayed two minutes after you stop the manual key operation. W W = Active power total No. Ain No.Ain = No current input
2 Press and hold or for The display flashes AUTO and scrolls through the PF = Power factor average
three seconds. RMS parameter pages. No.Vin = No voltage input
To LOCK default display page: PF No. Vin
W1 = Active power, phase 1
Go to the desired page you want to set as default display page. W2 = Active power, phase 2
E.RST = Energy reset status
Press and together until the display shows LOCK and the display page is locked. E.RST
NOTE: W PF W3 = Active power, phase 3 All the segments glow
RMS
Press any key to revert to manual scrolling. PF1 = Power factor, phase 1 All Display Seg Glow
CLR = Clears INTG values.
To unlock default display page: W1 W2 W3
Auto scrolling is not possible in setup parameters. PF2 = Power factor, phase 2
Once the default display page is active, press and together until the display shows
PF3 = Power factor, phase 3
UN LOCK and the default display page is unlocked. PF1 PF2 PF3 CLR SET = PROG menu setup. Has two modes to View and Edit
INTG = Integrator setup parameters.
NOTE: kWh = Kilo active energy SET VIEW = To view the setup parameters.
Indicators Entry to SET EDIT and CLR is possible only when the default display page is unlocked. INTG KWh
SET SET VIEW SET EDIT = To edit the setup parameters.
Run.h = Duration for which input voltage and current is ON.
run.h
Kilo: When lit, indicates that the reading is in Kilo (10^3). The value 1000 is displayed as SET EDIT
1.00 K and 10,000 is displayed as 10.0 K. On.h = Duration for which input voltage is ON.
on.h
INTR = Number of input voltage interruptions.
Mega: When lit, indicates that the reading is in Mega (10^6). The value 1000 k is displayed Intr
as 1.00 M and 10,000 K is displayed as 10.0 M. OLD INTG = OLD integrator
Giga: When both K and M are lit, indicates that the reading is in Giga (10^9). kWh = OLD Kilo active energy
The value 1000 M is displayed as 1.00 G and 10,000 M is displayed as 10.0 G. OLD KWh
INTG Run.h = OLD Run hours 2
Negative: When lit, indicates that the reading is in negative as per IEEE 100 and
run.h
industry standard. On.h = OLD Duration for which input voltage is ON.
When power factor(PF) is lead (capacitive load): Both PF and VAR will be negative NOTE:
When current is reversed, W will be negative. on.h INTR = OLD Number of input voltage interruptions. * Communication setting is available only for EM1200/EM1220 power and
INTR
energy meter.

1
3
Technical Specifications
Description Specification
Sensing/measurement True RMS, two quadrant power and energy, one second
update time.
Accuracy % of Full Scale
1
Applicable for CL 1.0 CL 0.5
Voltage LN and LL +
per phase and average -1.0% +
- 0.5%
2 EM1220 +
Measurement Amp per phase and average +
- 1.0% - 0.5%
Accuracy Frequency +
- 0.2% +
- 0.2%
(3 Phase) Active power (kW) & +
Active energy (kWh) - 1.0% +
- 0.5%
Apparent power (kVA)& EM1220
EM1200 +
- 1.0% +
- 0.5%
Apparent energy (kVAh)
Reactive power (kVAR) & EM1000
+
- 2.0% +
-1.0%
Reactive energy ( kVARh)
Power Factor +
- 0.05 (5 count)
Auxiliary supply (control power) AC: 44 to 277 V LN ~ 50/60Hz + - 5% DC: 44 to 277 V
Input voltage Three voltage inputs (V1, V2, V3)
110 or 415 VLL nominal (operating range 80 to 480 VLL) ~50/60Hz +
- 5%
Input current (energy measurement) 50 mA to 6 A (5 mA starting current) ~ 50/60Hz + - 5%
Voltage and current input < 0.2 VA per phase
Burden Auxiliary supply (control power):
AC burden: < 4 VA at 277 V LN
DC burden: < 2 W at 277 V DC
Overload 10 A max continuous
Display and resolution Backlight LCD display;
Resolution: RMS Three digits (phase wise, average values);
Energy Nine digits.
Safety - Measurement
Pollution degree 2
- Double insulation at user-accessible area
Communication (EM1200/EM1220) RS 485 serial channel connection industry standard Modbus
RTU protocol
Environmental Operating temperature: -10 C to 60 C (14 F to 140 F)
Storage temperature: -25 C to 70 C (-13 F to 158 F)
Humidity 5 % to 95 % non-condensing
1
Altitude
2000 m For 1-Ph and 2-Ph system configuration, accuracy is applicable with additional error of 0.5%
2
Weight 400 gms approx, unpacked In delta system configuration, the accuracy for ampere per phase would be 1.0%
500 gms approx, shipping 3
Front display: IP 51 As per IEC 61326-1
IP degree of protection
Meter body: IP 40 (excluding terminals)
EM1000/EM1200/EM1220 Emission : CISPR11 class A;
3
conform to ESD: IEC 61000-4-2 ; 3
Fast Transient: IEC 61000-4-4 ; 3
Surge withstand: IEC 61000-4-5 ;
Impulse voltage: IEC 60060-1;

Schneider Electric India Pvt Ltd


44 P, Electronics City East Phase, Electrical equipment should be installed,
Hosur Road, operated, serviced, and maintained only by
Bangalore - 560 100, India qualified personnel. No responsibility is assumed
by Schneider Electric for any consequences
email: customercare.in@schneider-electric.com arising out of the use of this material.
Toll Free Help desk Number:
1800 425 4272, 1800 103 0011 SEI/EM1000-EM1200-EM1220/0615/V03.d09
www.schneider-electric.co.in 2015 Schneider Electric. All Rights Reserved.

You might also like