Plumbing Engineering
Design Handbook
A Plumbing Engineers Guide to System Design and Specications
Volume 1
Fundamentals of
Plumbing Engineering
All rights reserved, including rights of reproduction and use in any form or by any means, including the making of copies
by any photographic process, or by any electronic or mechanical device, printed or written or oral, or recording for
sound or visual reproduction, or for use in any knowledge or retrieval system or device, unless permission in writing is
obtained from the publisher.
ISBN 1891255215
Printed in the United States of America
10 9 8 7 6 5 4 3 2 1
Plumbing Engineering Design Handbook
Volume 1
Fundamentals of Plumbing Engineering
Plumbing Engineering Design Handbook
Chairperson: Alan Otts, P.E., CIPE
ASPE Vice-Presidents, Technical: J. Joe Scott, CPD (2003-2004)
Technical and Editorial Review: Jill Dirksen & Jim Camillo
Chairperson: Richard Ellis
CONTRIBUTORS
Chapter 1 Chapter 8
Formulas, Symbols and Terminology Corrosion
C. David Hudson, CPD Jill Dirksen
Chapter 2 Chapter 9
Standards for Plumbing Materials and Equipment Seismic Protection of Plumbing Equipment
Julius Ballanco, P.E. Rich Lloyd
Chapter 3 Chapter 10
Specications Acoustics in Plumbing Systems
Joe Manning, CPD Ted Carnes
Bill Johnson
Chapter 4
Tom Rose
Plumbing Cost Estimation
Steven Skattebo, P.E. Chapter 11
Basics of Value Engineering
Chapter 5
Stanley Wolfson
Job Preparation, Drawings and Field Checklists
Steven Skattebo, P.E. Chapter 12
Green Design for Plumbing Systems
Chapter 6
J. Joe Scott, CPD
Plumbing for People (or Persons) with Disabilities
Patrick McClellan, CPD
Chapter 7
Energy and Resource Conservation in
Plumbing Systems
Aaron Kelly, CPD
About ASPE
The American Society of Plumbing Engineers (ASPE) is the international organization for professionals skilled in
the design and specication of plumbing systems. ASPE is dedicated to the advancement of the science of plumbing
engineering, to the professional growth and advancement of its members, and to the health, welfare, and safety of
the public.
The Society disseminates technical data and information, sponsors activities that facilitate interaction with
fellow professionals, and, through research and education programs, expands the base of knowledge of the plumbing
engineering industry. ASPE members are leaders in innovative plumbing design, effective materials and energy use,
and the application of advanced techniques from around the world.
WORLDWIDE MEMBERSHIP ASPE was founded in 1964 and currently has 7,500 members. Spanning the globe,
members are located in the United States, Canada, Asia, Mexico, South America, the South Pacic, Australia, and
Europe. They represent an extensive network of experienced engineers, designers, contractors, educators, code
ofcials, and manufacturers interested in furthering their careers, their profession, and the industry. ASPE is at the
forefront of technology. In addition, ASPE represents members and promotes the profession among all segments of the
construction industry.
ASPE MEMBERSHIP COMMUNICATION All members belong to ASPE worldwide and have the opportunity to
belong and participate in one of the 62 state, provincial or local chapters throughout the U.S. and Canada. ASPE
chapters provide the major communication links and the rst line of services and programs for the individual member.
Communications with the membership is enhanced through the Societys bimonthly magazine, Plumbing Systems
and Design, and the bimonthly newsletter ASPE Report which is incorporated as part of the magazine.
TECHNICAL PUBLICATIONS The Society maintains a comprehensive publishing program, spearheaded by the
professions basic reference text, the ASPE Plumbing Engineering Design Handbook. The Plumbing Engineering
Design Handbook, encompassing 47 chapters in four volumes, provides comprehensive details of the accepted practices
and design criteria used in the eld of plumbing engineering. New additions that will shortly join ASPEs published
library of professional technical manuals and handbooks include: Pharmaceutical Facilities Design Manual, Electronic
Facilities Design Manual, Health Care Facilities and Hospitals Design Manual, and Water Reuse Design Manual.
CONVENTION AND TECHNICAL SYMPOSIUM The Society hosts biennial Conventions in even-numbered years and
Technical Symposia in odd-numbered years to allow professional plumbing engineers and designers to improve their
skills, learn original concepts, and make important networking contacts to help them stay abreast of current trends
and technologies. In conjunction with each Convention there is an Engineered Plumbing Exposition, the greatest,
largest gathering of plumbing engineering and design products, equipment, and services. Everything from pipes to
pumps to xtures, from compressors to computers to consulting services is on display, giving engineers and speciers
the opportunity to view the newest and most innovative materials and equipment available to them.
CERTIFIED IN PLUMBING DESIGN ASPE sponsors a national certication program for engineers and designers of
plumbing systems, which carries the designation Certied in Plumbing Design or CPD. The certication program
provides the profession, the plumbing industry, and the general public with a single, comprehensive qualication of
professional competence for engineers and designers of plumbing systems. The CPD, designed exclusively by and for
plumbing engineers, tests hundreds of engineers and designers at centers throughout the United States biennially.
Created to provide a single, uniform national credential in the eld of engineered plumbing systems, the CPD program
is not in any way connected to state-regulated Professional Engineer (P.E.) registration.
ASPE RESEARCH FOUNDATION The ASPE Research Foundation, established in 1976, is the only independent,
impartial organization involved in plumbing engineering and design research. The science of plumbing engineering
affects everything from the quality of our drinking water to the conservation of our water resources to the building
codes for plumbing systems. Our lives are impacted daily by the advances made in plumbing engineering technology
through the Foundations research and development.
American Society of Plumbing Engineers
Plumbing Engineering Design Handbook
(4 Volumes 47 Chapters)
Volume 4 Plumbing Components and Equipment (Estimated revision date: Fall 2007)
Chapter 1 Plumbing Fixtures
2 Piping Systems
3 Valves
4 Pumps
5 Piping Insulation
6 Hangers and Supports
7 Vibration Isolation
8 Grease Interceptors
9 Cross Connection Control
10 Water Treatment
11 Thermal Expansion
12 Potable Water Coolers and Central Water Systems
13 Bioremediation Pretreatment Systems
(The chapters and subjects listed for these volume are subject to modication, adjustment and change.
The contents shown for each volume are proposed and may not represent the nal contents of the volume.
A nal listing of included chapters for each volume will appear in the actual publication.)
Table of Contents
Chapter 3, Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Construction Contract Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Denition of Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Project Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Uniformat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Masterformat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Masterformat 2004an Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Methods of Specication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Creating the Specication Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Part 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Part 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Part 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Use of Computers in Producing Specications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Appendix 3-A1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Appendix 3-A2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Appendix 3-A3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Division 1 General Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Division 2 Site Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Division 3 Concrete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Division 4 Masonry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
ii ASPE Plumbing Engineering Design Handbook Volume 1
Division 5 Metals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Division 6 Wood and Plastics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Division 7 Thermal and Moisture Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Division 8 Doors and Windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Division 9 Finishes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Division 10 Specialties. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Division 11 Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Division 12 Furnishings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Division 13 Special Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Division 14 Conveying Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Division 15 Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Division 16 Electrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Appendix 3-A4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Appendix 3-A5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Appendix 3-B1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
CSI Masterformat Divisions (2004 Edition) Procurement and
Contracting Documents Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Specications Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
General Requirements Subgroup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Facility Construction Subgroup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Facility Services Subgroup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Site and Infrastructure Subgroup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Process Equipment Subgroup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Appendix 3-B2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Appendix 3-B3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Appendix 3-B4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Appendix 3-B5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Appendix 3-C Section Shell Outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Part 1General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
1.1 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
1.2 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
1.3 Denitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
1.4 System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
1.5 System Performance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
1.6 Submittals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
1.7 Quality Assurance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
1.8 Delivery, Storage, and Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
1.9 Project Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
1.10 Sequencing and Scheduling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
1.11 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
1.12 Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
1.13 Extra Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Part 2Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
2.1 Manufacturers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
2.2 Materials [Product Name]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Table of Contents iii
Anthropometrics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Plumbing Elements and Facilities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
References. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Figures
Tables
Equation 1-3a
where D
V = Velocity of ow, ft/s (m/s) RHF = RFF = 4
n = Coefcient representing roughness of where
pipe surface, degree of fouling, and pipe D = Diameter of pipe, ft (m)
diameter RHF = Hydraulic radius, half-full condition, ft (m)
2 ASPE Plumbing Engineering Design Handbook Volume 1
W = Weight of body, lbf (kg) Equation 1-11, Flow rate in xture drain The
g = Gravitational acceleration, 32.2 ft/s2 (9.8 /s2) ow rate in a xture drain should equal the ow rate
gc = Gravitational constant, 32.2 lbm-ft/lbf-s2 at the xture outlet and is expressed as:
Equation 1-8, Flow at outlet Can be Equation 1-11
determined by using the following relationship: Q = 13.17 d2 h
Equation 1-8 where
Q = 29.87Cdd2 P Q = Discharge ow rate, gpm (L/s)
where d = Diameter of outlet orice, in. (mm)
Q = Flow at outlet, gpm (L/s) h = Mean vertical height of water surface above
Cd = Discharge Coefcient the point of outlet orice, ft (m)
d = Inside diameter of outlet, in. (mm) Equation 1-12, Pipe expansion and con-
P = Flow pressure, lbf/in2 (kPa) traction All pipes that are subject to temperature
The discharge coefcient (Cd) may be obtained from changes expand and contract. Piping expands with
Baumeister and Markss Handbook for Mechanical an increase in temperature and contracts with a de-
Engineers. crease in temperature. The rate of change in length
due to temperature is referred to as the expansion
Equation 1-9, Length of vent piping Can coefcient. The changes in length can be calculated
be determined by combining Darcys Friction
by using the following relation:
Formula (Equation 1-5) and the ow equation and
is expressed as: Equation 1-12
L2 L1 = CEL1 (T2 T1)
Equation 1-9
2226d5 where
L= fQ2 L2 = Final length of pipe, ft (m)
L1 = Initial length of pipe, ft (m)
where CE = Coefcient of expansion of material (A
L = Length of pipe, ft (m) materials expansion coefcient may be
d = Diameter of pipe, in. (mm) obtained from the ASHRAE Handbook of
f = Friction coefcient, dimensionless Fundamentals.)
Q = Rate of ow, gpm (L/s) T2 = Final temperature, F (C)
Equation 1-10, Stacks T1 = Initial temperature, F (C)
(a) Terminal velocity Equation 1-13, Various formulae for
Equation 1-10a areas and volumes, in ft (m ) and ft (m ),
2 2 3 3
respectively.
( Qd )
5
2
VT = 3
Equation 1-13a, Square (See Figure 1-1.)
where A = bh
VT = Terminal velocity in stack, ft/s (m/s)
Q = Rate of ow, gpm (L/s)
d = Diameter of stack, in. (mm)
(b) Terminal length
Equation 1-10b
LT = 0.052 VT2 Figure 1-1 Square
where Equation 1-13b, Rectangle (See Figure 1-2.)
LT = Terminal length below point of ow entry, ft A = bh
(m)
(c) Capacity
Equation 1-10c
Q = 27.8 r d
5 83
3
Equation 1-13c, Rhombus (See Figure 1-3.) Equation 1-13i, Ellipse (See Figure 1-9.)
A = bh A = ab
where
a=D
b=d
Equation 1-13o, Circle (See Figure 1-14.) The discharge coefcients (cD) may be obtained from
Baumeister and Markss Handbook for Mechanical
A = R2
Engineers.
Equation 1-15, Gravity circulation This prin-
ciple is used to keep the sanitary system free of foul
odors and the growth of slime and fungi. The circu-
lation is induced by the pressure difference between
Figure 1-14 Circle the outdoor air and the air in the vent piping. This
Equation 1-13p, Triangle (See Figure 1-15.)
3 pressure difference is due to the difference in tem-
perature (T) and density () between the two and
Known: 2 angles
the height (h) of the air column in the vent piping.
Required: Third angle
The gravity circulation is determined by using the
Solution: A = 180 (B + C)
following formula:
Equation 1-13q, Triangle (See Figure 1-15.)
3
Equation 1-15
Known: 3 sides P = 0.1925 (O I) hs
Required: Any angle where
Solution: cos A = b + c a
2 2 2
P = Natural draft pressure, in. (mm)
2bc O = Specic Weight of outside air, lbf/ft3 (N/m3)
Equation 1-13r, Triangle (See Figure 1-15.)
3
I = Specic Weight of air in pipe, lbf/ft3 (N/m3)
Known: 2 sides and included angle hs = Height of air column in stack, ft (m)
Required: Third side The outside and inside air densities (O and I) may
Solution: c = (a2 + b2 2ab cos C) be obtained from the ASHRAE Handbook of Fun-
Equation 1-13s, Triangle (See Figure 1-15.)
3 damentals.
Known: 2 sides and included angle Equation 1-16, Velocity head (h) When the water
Required: Third angle in a piping system is at rest, it has potential energy
Solution: tan A = a sin C (PE). When the water in a piping system is owing, it
b a cos C has kinetic energy (KE). For the water to ow, some
Equation 1-13t, Triangle (See Figure 1-15.)
3
of the potential energy (PE) must be converted to
Known: 2 sides and excluded angle kinetic energy (KE). The decrease in potential energy
Required: Third side (static head) is referred to as the velocity head (h)
Solution: c = b cos A (a2 b2 sin2 A) and is expressed as:
Equation 1-13u, Triangle (See Figure 1-15.)
3 Equation 1-16
V2
Known: 1 side and adjacent angles h = 2g
Required: Adjacent side where
Solution: c = asin
sin C
A
h = Height of the fall, ft (m)
V = Velocity at any moment, ft/s (m/s)
g = Gravitational acceleration, 32.2 ft/s2 (9.8
m/s2)
Equation 1-17, Bernoullis Equation Since ener-
gy cannot be created or destroyed, Bernoulli developed
a theorem to express this energy conservation. It is
represented by the following equation:
Figure 1-15 Triangle
Equation 1-14, Flow rate in outlet With Equa- Equation 1-17
ET = Zg + P + V
2
tion 1-11, we determined that the ow rate (Q) in the gc 2gc
outlet should be equal to the ow rate in the xture
( ET = Zg + + V
P
)
2
g = Gravitational acceleration, 32.2 ft/s2 (9.8 (a) The velocity of propagation of elastic vibration in
m/s2) the pipe can be dened as:
gc = Gravitational constant, 32.2 lbm-ft/lbf-s2
Equation 1-20a
(a) For two points in the system, Equation 1-17 can a= 4660
be expressed as: (1 + KB)
where
Equation 1-17a a = Propagation velocity, ft/s (m/s)
Z1g + P + V12 = Z2g + P2 + V22 4660 = Velocity of sound in water, ft/s (m/s)
1
( ) ( )
V = Velocity at outlet, ft/s (m/s) N1 Q H1 BHP
1
3
[ ]
barrier to ambient, BTU/h ft2 F (W/m2
(P12 P22) d 3
16
Q = 28.05 C)
SL
where SYMBOLS
Q = Flow rate, ft3/h (m3/h) The standardized plumbing and piping-related
P1 = Initial gas pressure, psi symbols in Tables 1-1 and 1-2 and the abbreviations
P2 = Final gas pressure, psi in Table 1-3 have been tabulated by the American So-
d = Diameter of pipe, in. (mm) ciety of Plumbing Engineers for use in the design and
S = Specic gravity preparation of drawings. Users of these symbols are
L = Length of pipe, mi (km) cautioned that some governmental agencies, industry
groups, and other clients may have a list of symbols
that are required for their projects. All symbols should
be applied with a consideration for drafting and clarity
if drawings are to be reduced.
8 ASPE Plumbing Engineering Design Handbook Volume 1
Angle valve AV
Ball valve BV
Check valve CV
Plug valve PV
Solenoid valve
(CONTINUED)
10 ASPE Plumbing Engineering Design Handbook Volume 1
Pressure-relief valve RV
Hose bibb HB
Pipe anchor PA
Pipe guide
Expansion joint EJ
Flexible connector FC
Tee
Concentric reducer
Eccentric reducer
Aquastat
Flow switch FS
Pressure switch PS
Riser up (elbow)
Air chamber AC
(CONTINUED)
Chapter 1 Formulas, Symbols and Terminology 11
Branchtop connection
Branchbottom connection
Branchside connection
Cleanout plug CO
a Hot water (140F) and hot water return (140F). Use for normal hot water distribution system, usually but not necessarily (140F). Change temperature
designation if required.
b Hot water (temp. F) and hot water return (temp. F). Use for any domestic hot water system (e.g., tempered or sanitizing) required in addition to the normal
system (see note a above). Insert system supply temperature where temp. is indicated.
c Compressed air and compressed air X#. Use pressure designations (X#) when compressed air is to be distributed at more than one pressure.
12 ASPE Plumbing Engineering Design Handbook Volume 1
Hydrants
Public hydrant, two hose outlets Indicate size,a type of thread, or connection.
Wall hydrant, two hose outlets Indicate size,a type of thread, or connection.
Nonsprinklered space
Chapter 1 Formulas, Symbols and Terminology 13
Upright sprinklerc
Pendent sprinklerc, d
Sidewall sprinklerc
Symbols for piping, valves, control devices,
and hangerse
This symbol is a diagonal stroke imposed on the
Pipe hanger
pipe that it supports.
Table 1-3 Abbreviations for Text, Drawings, and Computer Programs (cont)
Term Text Drawings Program Term Text Drawings Program
Frequency Hz HZ Medium-pressure steam mps MPS MPS
Gage or gauge ga GA GA, GAGE Medium-temperature hot mthw MTHW MTHW
Gallons gal GAL GAL water
Gallons per hour gph GPH GPH Mercury Hg HG HG
gph, standard std gph SGPH SGPH Miles per hour mph MPH MPH
Gallons per day gpd GPD GPD Minimum min. MIN MIN
Grains gr GR GR Noise criteria NC NC
Gravitational constant g G G Normally closed nc NC
Greatest temperature GTD GTD GTD Normally open no NO
difference Not applicable na N/A
Head hd HD HD Not in contract nic NIC
Heat HT Not to scale NTS
Heater HTR Number no. NO N, NO
Heat gain HG HG HG, HEATG Number of circuits NC
Heat gain, latent LHG LHG HGL Number of tubes NT
Heat gain, sensible SHG SHG HGS Ounce oz OZ OZ
Heat loss HL, HEATL Outside air oa OA OA
Heat transfer Q Parts per million ppm PPM PPM
Heat transfer coefcient U U U Percent % % PCT
Height hgt HGT HGT, HT Phase (electrical) ph PH
High-pressure steam hps HPS HPS Pipe PIPE
High-temperature hot water hthw HTHW HTHW Pounds lb LBS LBS
Horsepower hp HP HP Pounds per square foot psf PSF PSF
Hour(s) h HR HR psf absolute psfa PSFA PSFA
Humidity ratio W W W psf gage psfg PSFG PSFG
Humidity, relative rh RH RH Pounds per square inch psi PSI PSI
Incident angle INANG psi absolute psia PSIA PSIA
Indicated horsepower ihp IHP psi gage psig PSIG PSIG
International Pipe Std. IPS IPS Pressure PRESS PRES, P
Iron pipe size ips IPS Pressure, barometric baro pr BARO PR BP
Kelvin K K K Pressure, critical CRIP
Kilowatt kW kW KW Pressure drop or difference PD PD PD, DELTP
Kilowatt hour kWh KWH KWH Pressure, dynamic (velocity) vp VP VP
Latent heat LH LH LH, LHEAT Pressure, static sp SP SP
Least mean temp. differenced LMTD LMTD LMTD Pressure, vapor vap pr VAP PR VAP
Least temperature differenced LTD LTD LTD Primary pri PRI PRIM
Leaving air temperature lat LAT LAT Quart qt QT QT
Leaving water temperature lwt LWT LWT Radian RAD
Length lg LG LG, L Radiat(-e, -or) RAD
Linear feet lin ft LF LF Radiation RADN RAD
Liquid liq LIQ LIQ Radius R
Logarithm (natural) ln LN LN Rankine R R R
Logarithm to base 10 log LOG LOG Receiver rcvr RCVR REC
Low-pressure steam lps LPS LPS Recirculate recirc. RECIRC RCIR, RECIR
Low-temperature hot water lthw LTHW LTHW Refrigerant (12, 22, etc.) R-12, R-22 R12, R22 R12, R22
Mach number Mach MACH Relative humidity rh RH RH
Mass ow rate mfr MFR MFR Resist(-ance, -ivity, -or) res RES RES, OHMS
Maximum max. MAX MAX Return air ra RA RA
Mean effective temperature MET MET MET Revolutions rev REV REV
Mean temp. difference MTD MTD MTD Revolutions per minute rpm RPM RPM
(CONTINUED) (CONTINUED)
16 ASPE Plumbing Engineering Design Handbook Volume 1
Table 1-3 Abbreviations for Text, Drawings, and Computer Programs (cont)
Term Text Drawings Program Term Text Drawings Program
Revolutions per second rps RPS RPS Ton TON
Roughness rgh RGH RGH, E Tons of refrigeration tons TONS TONS
Safety factor sf SF SF Total TOT
Saturation sat. SAT SAT Total heat tot ht TOT HT
Saybolt seconds Furol ssf SSF SSF Transmissivity TAU
Saybolt seconds Universal ssu SSU SSU U-factor U
Sea level sl SL SE Unit UNIT
Second s s SEC Vacuum vac VAC VAC
Sensible heat SH SH SH Valve v V VLV
Sensible heat gain SHG SHG SHG Vapor proof vap prf VAP PRF
Sensible heat ratio SHR SHR SHR Variable var VAR VAR
Shading coefcient SC Variable air volume VAV VAV VAV
Shaft horsepower sft hp SFT HP SHP Velocity vel. VEL VEL, V
Solar SOL Velocity, wind w vel. W VEL W VEL
Specication spec SPEC Ventilation, vent vent VENT VENT
Specic gravity SG SG Vertical vert. VERT VERT
Specic heat sp ht SP HT C Viscosity visc VISC MU, VISC
sp ht at constant pressure cp cp CP Volt V V E, VOLTS
sp ht at constant volume cv cv CV Volt ampere VA VA VA
Specic volume sp vol SP VOL V, CVOL Volume vol. VOL VOL
Square sq. SQ SQ Volumetric ow rate VFR
Standard std STD STD Wall W, WAL
Standard time meridian STM Water WTR
Static pressure SP SP SP Watt W W WAT, W
Suction suct. SUCT SUCT, SUC Watt-hour Wh WH WHR
Summ(-er, -ary, -ation) SUM Weight wt WT WT
Supply sply SPLY SUP, SPLY Wet bulb wb WB WB
Supply air sa SA SA Wet-bulb temperature wbt WBT WBT
Surface SUR, S Width WI
Surface, dry SURD Wind WD
Surface, wet SURW Wind direction wdir WDIR WDIR
System SYS Wind pressure wpr WPR WP, WPRES
Tabulat(-e, -ion) tab TAB TAB Yard yd YD YD
Tee TEE Year yr YR YR
Temperature temp. TEMP T, TEMP Zone z Z Z, ZN
Temperature difference TD, t TD TD, TDIF Source: ASHRAE, 1997, Handbook of fundamentals.
a
Abbreviations of most proper names use capital letters in both text
Temperature entering TE TE TE, TENT
and drawings.
Temperature leaving TL TL TL, TLEA b
The asterisk (*) is used with ET, effective temperature.
Thermal conductivity k K K c
These are surface heat transfer coefcients.
Thermal expansion coeff. TXPC
d
The letter L is also used for logarithm of these temperature
differences in computer programming.
Thermal resistance R R RES, R
Thermocouple tc TC TC, TCPL
Thermostat T STAT T STAT T STAT
Thick(-ness) thkns THKNS THK
Thousand circular mils Mcm MCM MCM
Thousand cubic feet Mcf MCF MCF
Thousand foot-pounds kip ft KIP FT KIPFT
Thousand pounds kip KIP KIP
Time T T
(CONTINUED)
Chapter 1 Formulas, Symbols and Terminology 17
The gas industry usually considers 60F (15.6C) the Arterial vent A vent serving the building drain
temperature of standard air. and the public sewer.
Air test A test using compressed air or nitrogen ASHRAE Abbreviation for American Society
applied to a plumbing system upon its completion of Heating, Refrigerating and Air Conditioning
but before the building is sheetrocked. Engineers.
Alarm (FP) 1. Any audible or visible signal in- ASME Abbreviation for American Society of Me-
dicating existence of a re or emergency requiring chanical Engineers.
evacuation of occupants and response and emergency ASPE Abbreviation for American Society of Plumb-
action on the part of the reghting service. 2. The ing Engineers.
alarm device(s) by which re and emergency signals
are received. ASPERF Abbreviation for American Society of
Plumbing Engineers Research Foundation.
Alarm check valve (FP) A check valve, equipped
with a signaling device, that will annunciate a remote Aspirator A tting or device supplied with water
alarm when a sprinkler head(s) is discharging. or other uid under positive pressure that passes
through an integral orice or constriction, causing
Alloy A substance composed of two or more metals a vacuum.
or a metal and nonmetal intimately united, usually
fused together and dissolving in each other when ASSE Abbreviation for American Society of
molten. Sanitary Engineering or American Society of Safety
Engineers.
Alloy pipe A steel pipe with one or more elements,
other than carbon, that give it greater resistance to ASTM Abbreviation for American Society for Test-
corrosion and more strength than carbon steel pipe. ing and Materials.
Ambient temperature The prevailing tempera- Atmospheric vacuum breaker A mechanical
ture in the immediate vicinity of or the temperature device consisting of a check valve that opens to the
of the medium surrounding an object. atmosphere when the pressure in the piping drops
to atmospheric.
American standard pipe thread A type of screw
thread commonly used on pipe and ttings. Authority having jurisdiction (FP) The organi-
zation, ofce, or individual responsible for approving
Anaerobic (re: bacteria) Living or active in the equipment, materials, installation, or procedure.
absence of free oxygen.
AWWA Abbreviation for American Water Works
Anchor A device used to fasten or secure pipes to Association.
the building or structure.
Backll Material used to cover piping laid in an
Angle of bend In a pipe, the angle between radial earthen trench.
lines from the beginning and end of the bend to the
center. Backow The ow of water or other liquids, mix-
tures, or substances from any source(s) other than the
Angle stop Common term for right-angle valves one(s) intended into the distributing pipes of a potable
used to control water supplies to plumbing xtures. supply of water. See BACK-SIPHONAGE.
Angle valve A device, usually of the globe type, in Backow connection A connection in any arrange-
which the inlet and outlet are at right angles. ment whereby backow can occur.
ANSI Abbreviation for American National Stan- Backow preventer A device or means to prevent
dards Institute. backow into the potable water system.
Approved Accepted or acceptable under an appli- Backing ring A metal strip used to prevent melted
cable specication or standard stated or cited for the metal, from the welding process, from entering a pipe
proposed use under the procedures and authority of in the process of making a butt-welded joint.
the administrative authority.
Back-siphonage The owing back of used, con-
Approved testing agency An organization estab- taminated, or polluted water from a plumbing xture
lished for purposes of testing to approved standards or vessel into the potable water supply pipe due to a
and acceptable to the administrative authority. negative pressure in the pipe. See BACKFLOW.
Area drain A receptacle designed to collect surface Backup A condition where the waste water may
or rainwater from a determined or calculated open ow back into another xture or compartment but
area. not backow into the potable water system.
Chapter 1 Formulas, Symbols and Terminology 19
Backwater valve A device that permits drainage Branch vent A vent connecting one or more indi-
in one direction but has a check valve that closes vidual vents with a vent stack or stack vent.
against back pressure. Sometimes used conjunctively Brazing ends The ends of a valve or tting that
with gate valves designed for sewage. are prepared for silver brazing.
Bafe plate A tray or partition placed in process Bronze trim or bronze-mounted An indication
equipment or tanks to direct or change the direction that certain internal (water contact) parts of the
of ow. valves known as trim materials (stem, disc, seat rings,
Ball check valve A device used to stop the ow of etc.) are made of copper alloy.
media in one direction while allowing ow in an op- Btu Abbreviation for British thermal unit. The
posite direction. The closure member used is spherical amount of heat required to raise the temperature
or ball-shaped. of 1 pound (0.45 kg) of water 1 degree Fahrenheit
Ball valve A spherical gate valve providing very (0.565C).
tight shut-off; a quick-closing (quarter-turn) valve. Btu/h Abbreviation for British thermal units per
Barrier free See ACCESSIBLE, def. 2. hour.
Base The lowest portion or lowest point of a stack Bubble tight The condition of a valve seat that
of vertical pipe. prohibits the leakage of visible bubbles when the
Battery of xtures Any group of two or more simi- valve is closed.
lar, adjacent xtures that discharge into a common Building (house) A structure built, erected, and
horizontal waste or soil branch. framed of component structural parts designed for
Bell That portion of a pipe that, for a short distance, the housing, shelter, enclosure, or support of persons,
is sufciently enlarged to receive the end of another animals, or property of any kind.
pipe of the same diameter for the purpose of making Building (house) drain That part of the lowest
a joint. piping of a drainage system that receives the discharge
Bell-and-spigot joint A commonly used joint from soil, waste, and other drainage pipes inside the
in cast-iron soil pipe. Each piece is made with an walls of the building (house) and conveys it to the
enlarged diameter or bell at one end into which the building (house) sewer, which begins outside the
plain or spigot end of another piece is inserted. The building (house) walls.
joint is then made tight by cement, oakum, lead, or Building (house) drain, combined A building
rubber caulked into the bell around the spigot. See (house) drain that conveys both sewage and storm
also HUB-AND-SPIGOT. water or other drainage.
Black pipe Steel pipe that has not been galva- Building (house) drain, sanitary A building
nized. (house) drain that conveys only sewage.
Blank ange A solid plate ange used to seal off Building (house) drain, storm A building (house)
ow in a pipe. drain that conveys storm water or other drainage but
Boiler blow-off An outlet on a boiler to permit no sewage.
emptying or discharge of sediment. Building (house) sewer That part of the hori-
Boiler blow-off tank A vessel designed to receive zontal piping of a drainage system that extends from
the discharge from a boiler blow-off outlet and cool the end of the building (house) drain and receives
the discharge to a temperature that permits its safe the discharge from the building (house) drain and
discharge to the drainage system. conveys it to a public sewer, private sewer, individual
sewage-disposal system, or other approved point of
Bonnet That part of a valve that connects the valve disposal.
actuator to the valve body; in some valves, it may also
contain the stem packing. Building (house) subdrain That portion of a
drainage system below the building (house) sewer
Branch Any part of a piping system other than a that cannot drain by gravity in the building (house)
main, riser, or stack. sewer.
Branch interval A length of soil or waste stack Building (house) trap A device, tting, or assem-
corresponding, in general, to a story height, but in no bly of ttings installed in the building (house) drain
case less than 8 feet (2.4 m), within which the hori- to prevent circulation of air between the drainage of
zontal branches from one oor or story of a building the building (house) and the building (house) sewer.
are connected to the stack. It is usually installed as a running trap.
Branch tee A tee having one side branch.
20 ASPE Plumbing Engineering Design Handbook Volume 1
Bull head tee A tee in which the branch is larger Cesspool A lined excavation in the ground that
than the run. receives the discharge of a drainage system, or part
Burst pressure That pressure that can slowly be thereof, and is so designed to retain the organic matter
applied to a valve at room temperature for 30 seconds and solids discharged therein but permit the liquids
without causing rupture. to seep through the bottom and sides.
Bushing A pipe tting for connecting a pipe with Chainwheel-operated valve A device operated by
a female tting of a larger size. It is a hollow plug a chain-driven wheel that opens and closes the valve
with internal and external threads. Used in lieu of a seats. Usually required for larger valves.
reducer/increaser. Channel That trough through which any media
Buttery valve A device deriving its name from may ow.
the wing-like action of the disc, which operates at Chase A recess in a wall or a space between two
right angles to the ow. The disc impinges against the walls in which pipes can be run.
resilient liner with low-operating torque. Check valve A device designed to allow a uid to
Butt weld joint A welded pipe joint made with the pass through in one direction only.
ends of the two pipes butting each other, the weld Chemical waste system Piping that conveys cor-
being around the periphery. rosive or harmful industrial, chemical, or processed
Butt weld pipe Pipe welded along a seam butted wastes to the drainage system.
edge to edge and not scarfed or lapped. Circuit The directed route taken by a ow of media
Bypass An auxiliary loop in a pipeline intended from one point to another.
for diverting ow around a valve or other piece of Circuit vent A branch vent that serves two or more
equipment. traps and extends from in front of the last xture con-
Bypass valve A device used to divert the ow past nection of a horizontal branch to the vent stack.
the part of the system through which it normally CISPI Abbreviation for Cast Iron Soil Pipe
passes. Institute.
Capacity 1. The maximum or minimum flow Clamp gate valve A gate valve whose body and
obtainable under given conditions of media, tempera- bonnet are held together by a U-bolt clamp.
ture, pressure, velocity, etc. 2. The volume of media
that may be stored in a container or receptacle. Cleanout A plug or cover (joined to an opening in a
pipe) that can be removed for the purpose of cleaning
Capillary The action by which the surface of a or examining the interior of the pipe.
liquid, where it is in contact with a solid, is elevated
or depressed, depending on the relative attraction Clear-water waste Cooling water and condensate
of the molecules of the liquid for each other and for drainage from refrigeration and air-conditioning
those of the solid. equipment; cooled condensate from steam-heating
systems; cooled boiler blowdown water; waste-water
Cathodic protection 1. The control of the elec- drainage from equipment rooms and other areas
trolytic corrosion of an underground or underwater where water is used without an appreciable addition
metallic structure by the application of an electric of oil, gasoline, solvent, acid, etc.; and treated efu-
current in such a way that the structure is made to ent in which impurities have been reduced below a
act as the cathode instead of the anode of an electro- minimum concentration considered harmful.
lytic cell. 2. The use of materials and liquid to cause
electricity to ow to avoid corrosion. Close nipple A nipple with a length twice the
length of a standard pipe thread.
Caulking The method of rendering a joint tight
against water or gas by means of applying plastic sub- Cock An original form of valve having a hole in a
stances such as lead and oakum; a method of sealing tapered plug that is rotated to provide passageway
between xtures and adjacent surfaces. for uid.
Cavitation A localized gaseous condition (usually Code Those regulations, subsequent amendments
involving air) that is found within a liquid stream. thereto, and any emergency rule or regulation that the
department having jurisdiction may lawfully adopt.
CDA Abbreviation for Copper Development As-
sociation. Coefcient of expansion The increase in unit
length, area of volume for a 1-degree rise in tem-
Cement joint The union of two ttings by the inser- perature.
tion of material. Sometimes this joint is accomplished
mechanically, sometimes chemically.
Chapter 1 Formulas, Symbols and Terminology 21
Coliform group of bacteria All organisms con- Corporation cock A stopcock screwed into the
sidered in the coli aerogenes group as set forth by the street water main to supply the house service con-
American Water Works Association. nection.
Combination xture A xture that combines one Coupling A pipe tting with female threads used
sink and tray or a two- or three-compartment sink only to connect two pipes in a straight line.
and/or tray in one unit. CPVC Abbreviation for chlorinated polyvinyl-
Combined waste and vent system A specially chloride.
designed system of waste piping, embodying the hori- Critical level The point on a backow-preven-
zontal wet venting of one or more sinks, oor sinks, tion device or vacuum breaker that determines the
or oor drains by means of a common waste and vent minimum elevation above the ood level rim of the
pipe, adequately sized to provide free movement of xture or receptacle served at which the device may
air above the ow line of the drain. be installed; the point conforms to approved standards
Combustion efciency The rated efciency of a and is established by the recognized (approved) test-
water heater or boiler determined by the equipments ing laboratory (usually stamped or marked CL or C/L
ability to completely burn fuel, leaving no products on the device by the manufacturer). When a backow-
of combustion in the ue gas. prevention device does not bear critical-level marking,
Common vent A vent that connects at the junction the bottom of the vacuum breaker or combination
of two xture drains and serves as a vent for both valve or the bottom of any such approved device shall
xtures. Also known as a DUAL VENT. constitute the critical level.
Companion ange A pipe ange to connect with Cross A pipe tting with four branches in pairs,
another ange or with a anged valve or tting. It is each pair on one axis, and the axis at right angles.
attached to the pipe by threads, welding, or another Cross-connection Any physical connection or ar-
method and differs from a ange that is an integral rangement between two otherwise separated piping
part of a pipe or tting. systemsone of which contains potable water and the
Compression joint A multi-piece joint with cup- other of which contains water or another substance of
shaped, threaded nuts that, when tightened, compress unknown or questionable safetywhereby ow may
tapered sleeves so they form a tight joint on the pe- occur from one system to the other, the direction of
riphery of the tubing they connect. ow depending on the pressure differential between
the two systems. See BACKFLOW and BACK-SI-
Compressor A mechanical device for increasing the PHONAGE.
pressure of air or gas.
Crossover A pipe tting with a double offset, or
Condensate Water that has liqueed (cooled) from shaped like the letter U with the ends turned out,
steam. used to pass the ow of one pipe past another when
Conductor The piping from the roof to the build- the pipes are in the same plane.
ing storm drain, combined building sewer, or other Cross valve A valve tted on a transverse pipe so as
approved means of disposal; it is located inside the to open communication between two parallel pipes.
building.
Crown That part of a trap in which the direction of
Conduit A pipe or channel for conveying media. ow is changed from upward to horizontal.
Conuent vent A vent serving more than one Crown vent A vent pipe connected at the topmost
xture vent or stack vent. point in the crown of a trap.
Contaminator A medium or condition that spoils CS Abbreviation for Commercial Standards.
the nature or quality of another medium.
Curb box A device at the curb that contains a
Continuous vent A vent that is a continuation of valve is used to shut off a supply line, usually of gas
the drain to which it connects. or water.
Continuous waste A drain from two or three x- Dampen 1. To check or reduce. 2. To deaden vibra-
tures connected to a single trap. tion.
Control A device used to regulate the function of Dead end A branch leading from a soil, waste, or
a component or system. vent pipe; building (house) drain; or building (house)
Controller (FP) The cabinet containing motor sewer that is terminated at a developed distance of
starter(s), circuit breaker(s), disconnect switch(s), and 2 feet (0.6 m) or more by means of a plug or other
other control devices for the control of electric motors closed tting.
and internal-combustion-engine-driven re pumps.
22 ASPE Plumbing Engineering Design Handbook Volume 1
Department having jurisdiction The adminis- the seating faces in the valve, force them against the
trative authorityand any other law enforcement body seats to shut off the ow.
agencyaffected by any provision of a code, whether Double offset Two changes of direction installed
such agency is specically named or not. in succession, or series, in continuous pipe.
Detector, smoke (FP) Listed device for sensing Double-ported valve A valve having two ports to
visible or invisible products of combustion. overcome line-pressure imbalance.
Developed length The length along the center line Double-sweep tee A tee made with easy (lon-ra-
of the pipe and ttings. dius) curves between body and branch.
Dewpoint The temperature of a gas or liquid at Double wedge A device used in gate valves that is
which condensation or evaporation occurs. similar to a double disc, in that the last downward
Diameter Unless specically stated otherwise, the turn of the stem spreads the split wedges, and each
nominal diameter as designated commercially. seals independently.
Diaphragm A exible disc that is used to separate Down Term referring to piping running through
the control medium from the controlled medium and the oor to a lower level.
actuates the valve stem. Downspout The rainleader from the roof to the
Diaphragm-control valve A control valve having building storm drain, combined building sewer, or
a spring-diaphragm actuator. other means of disposal; it is located outside of the
Dielectric tting A tting having insulating parts building.
or material that prohibits the ow of electric current. Downstream Term referring to a location in the
Used to separate dissimilar metals. direction of ow after passing a referenced point.
Differential The variance between two target val- Drain Any pipe that carries waste water or water-
ues, one of which is the high value of conditions, the borne wastes in a building drainage system.
other of which is the low value of conditions. Drain eld The area of a piping system arranged
Digestion That portion of the sewage treatment in troughs for the purpose of disposing unwanted
process where biochemical decomposition of organic liquid waste.
matter takes place, resulting in the formation of Drainage tting A type of tting used for drain-
simple organic and mineral substances. ing uid from pipes. The tting makes possible a
Disc That part of a valve that actually closes off smooth and continuous interior surface for the pip-
the ow. ing system.
Dishwasher An appliance for washing dishes, Drainage system The drainage piping within
glassware, atware, and some utensils. public or private premises (usually to 5 feet outside
Displacement The volume or weight of a uid, such building walls) that conveys sewage, rainwater, or
as water, displaced by a oating body. other liquid wastes to an approved point of disposal
but does not include the mains of a public sewer
Disposer A motor-driven appliance for reducing system or a private or public sewage-treatment or
food and other waste by grinding so that it can ow disposal plant.
through the drainage system.
Drift The sustained deviation in a corresponding
Domestic sewage The liquid and waterborne controller resulting from the predetermined rela-
wastes derived from ordinary living processes that tion between values and the controlled variable and
are free of industrial wastes and of such a character positions of the nal control element. Also known as
as to permit satisfactory disposal, without special WANDER.
treatment, into the public sewer or by means of a
private sewage disposal system. Droop The amount by which the controlled variable
pressure, temperature, liquid level, or differential
Dosing tank A watertight tank in a septic system pressure deviates from the set value at minimum
placed between the septic tank and the distribution controllable ow to the rated capacity.
box and equipped with a pump or automatic siphon
designed to discharge sewage intermittently to a dis- Drop Term referring to piping running to a lower
posal eld. This is done so that rest periods may be elevation within the same oor level.
provided between discharges. Drop elbow A small elbow having wings cast on
Double disc A two-piece disc used in the gate valve. each side, the wings having countersunk holes so they
The wedges between the disc faces, upon contact with may be fastened by wood screws to a ceiling, wall, or
framing timbers.
Chapter 1 Formulas, Symbols and Terminology 23
Drop tee A tee having wings of the same type as Elbow (Ell) A tting that makes an angle between
the drop elbow. adjacent pipes. The angle is 90, unless another angle
Dross 1. The solid scum that forms on the surface is specied.
of a metal, as lead or antimony, when it is molten or Electrolysis The process of producing chemical
melting, largely as a result of oxidation but some- changes by passage of an electric current through an
times because of the rising of dirt and impurities to electrolyte (as in a cell), the ions present carrying the
the surface. 2. Waste or foreign matter mixed with a current by migrating to the electrodes where they may
substance or left as a residue after that substance has form new substances (as in the deposition of metals
been used or processed. or the liberation of gases).
Dry-bulb temperature The temperature of air as Elutriation A process of sludge conditioning in
measured by an ordinary thermometer. which certain constituents are removed by successive
Dry-pipe valve (FP) A valve used with a dry-pipe decontaminations with fresh water or plant efu-
sprinkler system where water is on one side of the ent, thereby reducing the demand for conditioning
valve and air is on the other side. When a sprinkler chemicals.
heads fusible link melts, releasing air from the sys- End connection A reference to the method of con-
tem, this valve opens, allowing water to ow to the necting the parts of a piping system, e.g., threaded,
sprinkler head. anged, butt-weld, socket-weld.
Dry-weather ow Sewage collected during the Engineered plumbing system Plumbing system
summer that contains little or no ground water by designed by use of scientic engineering design cri-
inltration and no storm water at the time of col- teria other than design criteria normally given in
lection. plumbing codes.
Dry well See LEACHING WELL. Erosion The gradual destruction of metal or other
Dual vent See COMMON VENT. material by the abrasive action of liquids, gases, solids,
or mixtures of these materials.
Durham system A term used to describe soil or
waste systems where all piping is of threaded pipe, Evapotranspiration Loss of water from the soil
tubing or, other such material of rigid construction, by both evaporation and transpiration from the plants
and where recessed draining ttings corresponding growing thereon.
to the type of piping are used. Existing work A plumbing system, or any part
Durion A high-silicon alloy that is resistant to thereof, that was installed prior to the effective date
practically all corrosive wastes. The silicon content is of an applicable code.
approximately 14.5 percent, and the acid resistance Expansion joint A joint whose primary purpose is
is in the entire thickness of the metal. to absorb longitudinal thermal expansion in the pipe
Dwelling A one-family unit with or without acces- line due to heat.
sory buildings. Expansion loop A large radius bend in a pipe line
DWV Abbreviation for drainage, waste, and vent. to absorb longitudinal thermal expansion in the line
A name for copper or plastic tubing used for drain, due to heat.
waste, or venting pipe. Extra heavy Description of piping material, usu-
Eccentric ttings Fittings where the openings are ally cast-iron, indicating piping that is thicker than
offset, allowing liquid to ow freely. standard pipe.
Effective opening The minimum cross-sectional Face-to-face dimensions The dimensions from
area at the point of water-supply discharge, measured the face of the inlet port to the face of the outlet port
or expressed in terms of the diameter of a circle or, of a valve or tting.
if the opening is not circular, the diameter of a circle Female thread Internal thread in pipe ttings,
of equivalent cross-sectional area. (This is applicable valves, etc., for making screwed connections.
to an AIR GAP.) Filter A device through which uid is passed to
Efuent Sewage, treated or partially treated, ow- separate contaminants from it.
ing out of sewage-treatment equipment. Filter element or media A porous device that
Elastic limit The greatest stress that a material performs the process of ltration or ltering.
can withstand without permanent deformation after Fire alarm system (FP) A functionally related
the release of the stress. group of devices that, when automatically or manually
24 ASPE Plumbing Engineering Design Handbook Volume 1
activated, will sound audio or visual warning devices Pressure maintenance (jockey) pump
on or off the protected premises, signaling a re. (FP) Pump with controls and accessories used
Fire department connection (FP) A piping con- to maintain pressure in a re protection system
nection for re department use to supplement in without the operation of the re pump. Does
supplying water for standpipes and sprinkler systems. not have to be a listed pump.
See STANDPIPE SYSTEM. Vertical shaft turbine pump (FP) A
Fire hazard (FP) Any thing or act that increases, centrifugal pump with one or more impellers
or will cause an increase of, the hazard or menace discharging into one or more bowls and a ver-
of re to a degree greater than what is customarily tical educator or column pipe used to connect
recognized as normal by persons in the public service the bowl(s) to the discharge head on which the
regularly engaged in preventing, suppressing, or ex- pump driver is mounted.
tinguishing re; or that will obstruct, delay, hinder, or Fitting The connector or closure for uid lines and
interfere with the operations of the re department passages.
or the egress of occupants in the event of re. Fitting, compression A tting designed to join
Fire hydrant valve (FP) A valve that, when closed, pipe or tubing by means of pressure or friction.
drains at an underground level to prevent freezing. Fitting, ange A tting that utilizes a radially
Fire line (FP) A system of pipes and equipment extending collar for sealing and connection.
used exclusively to supply water for extinguishing Fitting, welded A tting attached by welding.
res.
Fixture branch A pipe connecting several
Fire pump types xtures.
Can pump (FP) A vertical-shaft, turbine-type Fixture carrier A metal unit designed to support
pump in a can (suction vessel) for installation an off-the-oor plumbing xture.
in a pipeline to raise water pressure.
Fixture carrier ttings Special ttings for wall-
Centrifugal pump (FP) A pump in which mounted xture carriers. Fittings have a sanitary
the pressure is developed principally by the drainage waterway with a minimum angle of 30 45
action of centrifugal force. degrees so that there are no fouling areas.
End-suction pump (FP) A single-suction Fixture drain The drain from the trap of a xture
pump having its suction nozzle on the opposite to the junction of that drain with any other drain
side of the casing from the stufng box and hav- pipe.
ing the face of the suction nozzle perpendicular
to the longitudinal axis of the shaft. Fixture, plumbing See PLUMBING FIXTURE.
Excess pressure pump (FP) UL-listed and/ Fixture supply A water supply pipe connecting
or FM-approved, low-ow, high-head pump for the xture to the xture branch or directly to a main
sprinkler systems not being supplied from a water supply pipe.
re pump. The pump pressurizes the sprinkler Fixture unit, drainage (dfu) A measure of prob-
system so that the loss of water-supply pressure able discharge into the drainage system by various
will not cause a false alarm. types of plumbing xtures. The drainage xture unit
Fire pump (FP) UL-listed and/or FM-approved value for a particular xture depends on its volume
pump with driver, controls, and accessories used rate of drainage discharge, on the time duration of a
for re protection service. Fire pumps are of the single drainage operation, and on the average time
centrifugal or turbine type and usually have an between successive operations. Laboratory tests have
electric-motor or diesel-engine driver. shown that the rate of discharge of an ordinary lava-
tory with a nominal 1.2-inches (31.8-mm) outlet, trap,
Horizontal pump (FP) A pump with the and waste is about 7.5 gpm (0.5 L/s). This gure is so
shaft normally in a horizontal position. near to 1 ft3/min (0.5 L/s) that 1 ft3/min (0.5 L/s) has
Horizontal split-case pump (FP) A cen- become the accepted ow rate of one xture unit.
trifugal pump characterized by a housing that Fixture unit, supply (sfu) A measure of the prob-
is split parallel to the shaft. able hydraulic demand on the water supply by various
In-line pump (FP) A centrifugal pump in types of plumbing xtures. The supply xture unit
which the drive unit is supported by the pump, value for a particular xture depends on its volume
having its suction and discharge anges on ap- rate of supply, the time duration of a single supply
proximately the same center line. operation, and the average time between successive
operations.
Chapter 1 Formulas, Symbols and Terminology 25
Flange In pipe work, a ring-shaped plate on the prime by preventing pumped liquid from draining
end of a pipe at right angles to the end of the pipe away from the pump.
and provided with holes for bolts to allow fastening French drain A drain consisting of an under-
the pipe to a similarly equipped adjoining pipe. The ground passage made by lling a trench with loose
resulting joint is a anged joint. stones and covering with earth. Also known as
Flange bonnet A valve bonnet having a ange RUBBLE DRAIN.
through which bolts connect it to a matching ange Fresh-air inlet A vent line connected with the
on the valve body. building drain just inside the house trap and extend-
Flange ends A valve or tting having anges for ing to the outer air. It provides fresh air at the lowest
joining to other piping elements. Flange ends can point of the plumbing system, and with the vent
be plain-faced, raised-face, large male-and-female, stacks, provides a ventilated system. A fresh-air inlet
large tongue-and-groove, small tongue-and-groove, is not required where a septic-tank system of sewage
or ring-joint. disposal is employed.
Flange faces Pipe anges that have the entire Frostproof closet A hopper that has no water in
surface of the ange faced straight across and use the bowl and has the trap and control valve for its
either a full-face or ring gasket. water supply installed below the frost line.
Flap valve A non-return valve in the form of a FS Abbreviation for federal specications.
hinged disc or ap, sometimes having leather or Galvanic action When two dissimilar metals
rubber faces. are immersed in the same electrolytic solution and
Flash point The temperature at which a uid rst connected electrically, there is an interchange of
gives off sufcient ammable vapor to ignite when atoms carrying an electric charge between them.
approached with a ame or spark. The anode metal with the higher electrode potential
Float valve A valve that is operated by means of a corrodes; the cathode is protected. Thus magnesium
bulb or ball oating on the surface of a liquid within will protect iron; iron will protect copper. See also
a tank. The rising and falling action operates a lever, ELECTROLYSIS.
which opens and closes the valve. Galvanizing A process where the surface of iron or
Flooded The condition when liquid rises to the ood steel piping or plate is covered with a layer of zinc.
level rim of a xture. Generally accepted standard A document re-
Flood level rim The top edge of a receptacle or ferred to in a code that covers a particular subject and
xture from which water overows. is accepted by the administrative authority.
Flow pressure The pressure in the water supply Grade The slope or fall of a line of pipe in reference
pipe near the water outlet while the faucet or water to a horizontal plane. In drainage, it is expressed as
outlet is fully open and owing. the fall in a fraction of an inch or percentage slope
per foot (mm/m) length of pipe.
Flue An enclosed passage, primarily vertical, for
removal of gaseous products of combustion to the Grease interceptor An automatic or manual device
outer air. used to separate and retain grease, with a capacity
greater than 50 gal (227.3 L), and generally located
Flush valve A device located at the bottom of a outside a building.
tank for the purpose of ushing water closets and
similar xtures. Grease trap An automatic or manual device used
to separate and retain grease, with a capacity of 50
Flushing-type oor drain A oor drain that is gallons (227.3 L) or less, and generally located inside
equipped with an integral water supply, enabling a building.
ushing of the drain receptor and trap.
Grinder pump A special class of solids-handling
Flushometer valve A device that discharges a pre- pump that grinds sewage solids to a ne slurry, rather
determined quantity of water to xtures for ushing than passing through entire spherical solids.
purposes and is actuated by direct water pressure.
Halon 1301 (FP) Halon 1301 (bromtrifluoro-
Footing The part of a foundation wall or column methane CBrF3) is a colorless, odorless, electrically
resting on the bearing soil, rock, or piling that trans- non-conductive gas that is an effective medium for
mits the superimposed load to the bearing material. extinguishing res.
Foot valve A check valve installed at the base of a Halon system types (FP) There are two types of
pump-suction pipe. Its purpose is to maintain pump systems recognized in this standard: Total ooding
systems and local application systems.
26 ASPE Plumbing Engineering Design Handbook Volume 1
Total ooding system Consists of a supply of Liquid waste The discharge from any fixture,
Halon 1301 arranged to discharged into, and ll appliance, or appurtenance in connection with a
to the proper concentration, an enclosed space plumbing system that does not receive fecal matter.
or enclosure around the hazard. Listed Term describing equipment and materi-
Local application system Consists of a sup- als included in a list published by an organization
ply of Halon 1301 arranged to discharge directly acceptable to the authority having jurisdiction and
on the burning material. concerned (a listing agency).
Hangers See SUPPORTS. Listing agency An agency accepted by the adminis-
Hub-and-spigot Piping made with an enlarged trative authority that lists or labels certain models of a
diameter or hub at one end and being plain or having product and maintains a periodic inspection program
a spigot at the other end. The joint is made tight by on the current production of listed models. It makes
oakum and lead or by use of a neoprene gasket caulked available a published report of its listing, including
or inserted in the hub around the spigot. information indicating that the products have been
tested, comply with generally accepted standards, and
Hubless Soil piping with plain ends. The joint is are found safe for use in a specied manner.
made tight with a stainless steel or cast-iron clamp
and neoprene gasket assembly. Load factor The percentage of the total connected
xture unit ow that is likely to occur at any point in
Indirect waste pipe A pipe that does not connect the drainage system. The load factor represents the
directly with the drainage system but conveys liquid ratio of the probable load to the potential load and is
waste by discharging into a plumbing xture or recep- determined by the average rates of ow of the various
tacle directly connected to the drainage system. kinds of xtures, the average frequency of use, the
Individual vent A pipe that is installed to vent a duration of ow during one use, and the number of
xture trap and connects with the vent system above xtures installed.
the xture served or terminates in the open air. Loop vent See VENT, LOOP.
Induced siphonage Loss of liquid from a xture Main The principal artery of a system of continuous
trap due to pressure differential between the inlet piping to which branches may be connected.
and outlet of a trap, often caused by the discharge of
another xture. Main vent A vent header to which vent stacks are
connected.
Industrial waste All liquid or waterborne waste
from industrial or commercial processes except do- Malleable Capable of being extended or shaped by
mestic sewage. beating with a hammer, or by the pressure of rollers.
Most metals are malleable. The term malleable iron
Insanitary A condition that is contrary to sanitary also has the older meaning (still universal in Great
principles or injurious to health. Britain) of wrought iron, abbreviated Mall.
Interceptor A device designed and installed so as Master plumber An individual who is licensed
to separate and retain deleterious, hazardous, or un- and authorized to install and assume responsibility
desirable matter from normal wastes and to permit for contractual agreements pertaining to plumbing
normal sewage or liquid wastes to discharge into the and to secure any required permits. The journeyman
disposal terminal by gravity. plumber is allowed to install plumbing only under the
Invert Term referring to the lowest point on the responsibility of a master plumber.
interior of a horizontal pipe. MSS Abbreviation for Manufacturers Standardiza-
Labeled Term describing equipment or materials tion Society of the Valve and Fittings Industry, Inc.
bearing a label of a listing agency. NFPA Abbreviation for National Fire Protection
Lateral sewer A sewer that does not receive sew- Association.
age from any other common sewer except house NSF Abbreviation for National Sanitation Founda-
connections. tion Testing Laboratory.
Leaching well A pit or receptacle having porous Offset A combination of pipe(s) and/or ttings that
walls that permit the contents to seep into the ground. join two approximately parallel sections of a line of
Also known as DRY WELL. pipe.
Leader The water conductor from the roof to the Outfall sewers Sewers receiving the sewage from a
building (house) storm drain. Also known as DOWN- collection system and carrying it to the point of nal
SPOUT. discharge or treatment. They are usually the largest
sewers of an entire system.
Chapter 1 Formulas, Symbols and Terminology 27
Oxidized sewage Sewage in which the organic such wastes into the drainage system to which they
matter has been combined with oxygen and become may be directly or indirectly connected. Industrial
stable in nature. or commercial tanks, vats, and similar processing
PB Abbreviation for polybutylene. equipment are not plumbing xtures but may be
connected to or discharged into approved traps or
PDI Abbreviation for Plumbing and Drainage plumbing xtures.
Institute.
Plumbing inspector Any person who, under the
PE Abbreviation for polyethylene. supervision of the department having jurisdiction, is
Percolation The ow or trickling of a liquid down- authorized to inspect plumbing and drainage systems
ward through a contact or ltering medium; the liquid as dened in the code for the municipality and com-
may or may not ll the pores of the medium. plying with the laws of licensing and/or registration
Pitch The amount of slope or grade given to hori- of the state, city, or county.
zontal piping and expressed in inches or vertically Plumbing system All potable water supply and
projected drop per foot (mm/m) on a horizontally distribution piping, plumbing xtures and traps,
projected run of pipe. drainage and vent pipe, and building (house) drains;
Plumbing The practice, materials, and xtures including their respective joints, connections, devices,
used in the installation, maintenance, extension, receptacles, and appurtenances within the property
and alteration of all piping, xtures, appliances, and lines of the premises. Additional components in the
appurtenances in connection with any of the follow- system include: Potable water-treating or water-us-
ing: Sanitary drainage or storm drainage facilities; ing equipment, fuel gas piping, water heaters, and
venting systems and public or private water-supply vents for same.
systems, within or adjacent to any building, structure, Polymer A chemical compound or mixture of com-
or conveyance; water supply systems and/or the storm pounds formed by polymerization and consisting
water, liquid waste, or sewage system of any premises essentially of repeating structural units.
to their connection with any point of public disposal Pool A water receptacle used for swimming or as a
or other acceptable terminal. plunge or other bath, designed to accommodate more
Plumbing appliance A plumbing xture that than one bather at a time.
is intended to perform a special plumbing func- Potable water Water that is satisfactory for drink-
tion. Its operation and/or control may be dependent ing, culinary, and domestic purposes and meets the
upon one or more energized components, such as a requirements of the health authority having jurisdic-
motor, control, heating element, or pressure or tem- tion.
perature-sensing element. Such xtures may operate
automatically through one or more of the following Precipitation The total measurable supply of
actions: A time cycle, a temperature range, a pressure water received directly from the clouds as snow, rain,
range, a measured volume, or weight; or the xture hail, and sleet. It is expressed in inches (mm) per day,
may be manually adjusted or controlled by the user month, or year.
or operator. Private sewage disposal system A septic tank
Plumbing appurtenances A manufactured de- with the efuent discharging into a subsurface dis-
vice, prefabricated assembly, or on-the-job assembly posal eld, one or more seepage pits, or a combination
of component parts that is an adjunct to the basic pip- of subsurface disposal eld and seepage pit, or of
ing system and plumbing xtures. An appurtenance such other facilities as may be permitted under the
demands no additional water supply, nor does it add procedures set forth in a code.
any discharge load to a xture or the drainage system. Private sewer A sewer that is privately owned and
It is presumed perform some useful function in the not directly operated by public authority.
operation, maintenance, servicing, economy, or safety Private use Applies to plumbing xtures in resi-
of the plumbing system. dences and apartments, private bathrooms in hotels
Plumbing engineering The application of scientif- and hospitals, and rest rooms in commercial estab-
ic principles to the design, installation, and operation lishments containing restricted-use single xtures
of efcient, economical, ecological, and energy-con- or groups of single xtures and similar installations,
serving systems for the transport and distribution of where the xtures are intended for the use of a family
liquids and gases. or an individual.
Plumbing xtures Installed receptacles, devices, Public sewer A common sewer directly operated
or appliances are supplied with water or that re- by public authority.
ceive liquid or liquid-borne wastes and discharge
28 ASPE Plumbing Engineering Design Handbook Volume 1
Public use Applies to toilet rooms and bathrooms Sand lter A water-treatment device for remov-
used by employees, occupants, visitors, or patrons, ing solid or colloidal material with sand as the lter
in or about any premises, and locked toilet rooms or medium.
bathrooms to which several occupants or employees Sanitary sewer A conduit or pipe carrying sanitary
on the premises possess keys and have access. sewage. It may include storm water and inltrated
Putrefaction Biological decomposition of organic ground water.
matter with the production of ill-smelling products; Seepage pit A lined excavation in the ground that
usually takes place when there is a deciency of receives the discharge of a septic tank that is designed
oxygen. to permit efuent from the tank to seep through its
PVC Abbreviation for polyvinyl chloride. bottom and sides.
PVDF Abbreviation for polyvinyl-uoridine. Septic tank A watertight receptacle that receives
Raw sewage Untreated sewage. the discharge of a drainage system, or part thereof,
and is designed and constructed to separate solids
Receptor A plumbing xture or device of such from liquids and digest organic matter over a period
material, shape, and capacity that it will adequately of detention.
receive the discharge from indirect waste pipes and,
so constructed and located, that it can be readily Sewage Any liquid waste containing animal, vege-
cleaned. table, or chemical wastes in suspension or solution.
Reduced size vent Dry vents that are smaller than Sewage ejector A mechanical device or pump for
those allowed by model plumbing codes. lifting sewage.
Reducer 1. A pipe tting with inside threads that Siamese (FP) A hose tting for combining the ow
is larger at one end than at the other. 2. A tting so from two or more lines into a single stream. See FIRE
shaped at one end that it can receive a larger size pipe DEPARTMENT CONNECTION.
in the direction of ow. Side vent A vent connected to the drain pipe
Reecting pool A water receptacle used for decora- through a tting at an angle not greater than 45
tive purposes. degrees to the vertical.
Relief vent A vent designed to provide circulation Sludge The accumulated, suspended solids of sew-
of air between drainage and vent systems or to act age deposited in tanks, beds, or basins, mixed with
as an auxiliary vent. water to form a semiliquid mass.
Residual pressure (FP) Pressure less than static Soil pipe Any pipe that conveys the discharge
that varies with the ow discharged from outlets. of water closets, urinals, or xtures having similar
functions, with or without the discharge from other
Return offset A double offset installed to return xtures, to the building (house) drain or building
the pipe to its original alignment. (house) sewer.
Revent pipe That part of a vent pipe line that con- Special wastes Wastes that require some special
nects directly with an individual waste pipe or group method of handling, such as the use of indirect waste
of waste pipes, underneath or at the back of the x- piping and receptors; corrosion-resistant piping; sand,
ture, and extends either to the main or branch vent oil, or grease interceptors; condensers; or other pre-
pipe. Also known as INDIVIDUAL VENT. treatment facilities.
Rim An unobstructed open edge of a xture. Sprinkler system (FP) An integrated system of
Riser 1. A water supply pipe that extends vertically underground and overhead piping designed in ac-
one full story or more to convey water to branches or cordance with re-protection engineering standards.
xtures. 2. (FP) A vertical pipe used to carry water The installation includes one or more automatic water
for re protection to elevations above or below grade, supplies. The portion of the sprinkler system above
such as a standpipe riser, sprinkler riser, etc. ground is a network of specially sized or hydraulically
Roof drain A drain installed to remove water col- designed piping installed in a building, structure, or
lecting on the surface of a roof and discharge it into area, generally overhead, and to which sprinklers are
the leader (downspout). attached in a systematic pattern. The valve control-
ling each system riser is located in the system riser or
Roughing in The installation of all parts of a its supply piping. Each sprinkler system riser includes
plumbing system that can be completed prior to the a device for actuating an alarm when the system is in
installation of xtures. This includes drainage, water operation. The system is activated by heat from a re
supply and vent piping, and the necessary xture and discharges water over the re area.
supports.
Chapter 1 Formulas, Symbols and Terminology 29
Quick-response sprinklers A type of sprin- Class II For use primarily by the building oc-
kler that is both a fast-response and a spray cupants until the arrival of the re department
sprinkler. (1-inch hose).
Recessed sprinklers Sprinklers in which Class III For use either by re departments
all or a part of the body, other than the shank and those trained in handling heavy hose
thread, is mounted within a recessed housing. streams (2-inch hose) or by the building oc-
Residential sprinklers Sprinklers that cupants (1-inch hose).
have been specically listed for use in residen- Standpipe system types (FP)
tial occupancies. Dry standpipe A system having no perma-
Sidewall sprinklers Sprinklers having nent water supply, maybe so arranged through
special deectors that are designed to discharge the use of approved devices as to admit water
most of the water away from a nearby wall in a to the system automatically by the opening of
pattern resembling a quarter of a sphere, with a hose valve.
a small portion of the discharge directed at the Wet standpipe A system having the supply
wall behind the sprinkler. valve open and water pressure maintained in
Special sprinklers Sprinklers that have the system at all times.
been tested and listed as having special limita- Stop valve A valve used for the control of water
tions. supply, usually to a single xture. Can be a straight
Upright sprinklers Sprinklers designed to or angle conguration.
be installed in such a way that the water spray Storm sewer A sewer used for conveying rainwater,
is directed upward against the deector. surface water, condensate, cooling water, or similar
Stack The vertical main of a system of soil, waste, or liquid wastes, exclusive of sewage and industrial
vent piping extending through one or more stories. waste.
Stack group The location of xtures in relation to Strain Change of the shape or size of a body pro-
the stack so that, by means of proper ttings, vents duced by the action of stress.
may be reduced to a minimum. Stress Reactions within a body resisting external
Stack vent The extension of a soil waste stack forces acting on it.
above the highest horizontal drain connected to the Subsoil drain A drain that receives only subsur-
stack. Also known as WASTE or SOIL VENT. face or seepage water and conveys it to an approved
Stack venting A method of venting a xture or place of disposal.
xtures through the soil or waste stack. Submain sewer A sewer into which the sewage
Stale sewage Sewage that contains little or no from two or more lateral sewers is discharged. Also
oxygen and is free from putrefaction. known as BRANCH SEWER.
Standpipe A vertical pipe generally used for the stor- Sump A tank or pit that receives sewage or liquid
age and distribution of water for re extinguishing. waste, is located below the normal grade of the gravity
Standpipe system (FP) An arrangement of pip- system, and must be emptied by mechanical means.
ing, valves, hose connections, and allied equipment Sump pump A mechanical device for removing
installed in a building or structure with the hose liquid waste from a sump.
connections located in such a manner that water Supervisory (tamper) switch (FP) A device at-
can be discharged in streams or spray patterns tached to the handle of a valve that, when the valve
through attached hose and nozzles, for the purpose is closed, annunciates a trouble signal at a remote
of extinguishing a re and so protecting a building location.
or structure and its contents as well as its occupants.
This is accomplished by connections to water supply Supports Devices for supporting and securing pipe
systems or by pumps, tanks, and other equipment and xtures to walls, ceilings, oors, or structural
necessary to provide an adequate supply of water to members.
the hose connections. Swimming pool A structure, basin, or tank con-
Standpipe system class of service (FP) taining water for swimming, diving, or recreation.
Class I For use by fire departments and Tempered water Water ranging in temperature
those trained in handling heavy re streams from 85 to 110F (29 to 43C) thermal efciency.
(2-inch hose).
Chapter 1 Formulas, Symbols and Terminology 31
Thermal efciency The ratio of the energy output Waste pipe The discharge pipe from any xture,
from the system to energy input to the system. appliance, or appurtenance in connection with the
Trailer park sewer That part of the horizontal plumbing system that does not contain fecal matter.
piping of a drainage system that begins 2 feet (0.6 Water-conditioning or treating device A device
m) downstream from the last trailer site connection, that conditions or treats a water supply to change
receives the discharge of the trailer site, and conveys it its chemical content or remove suspended solids by
to a public sewer, private sewer, individual sewage dis- ltration.
posal system, or other approved point of disposal. Water-distributing pipe A pipe that conveys
Trap A tting or device designed and constructed to potable water from the building supply pipe to the
provide, when properly vented, a liquid seal that will plumbing xtures and other water outlets in the
prevent the back passage of air without signicantly af- building.
fecting the ow of sewage or waste water through it. Water hammer The forces, pounding noises, and
Trap primer A device or system of piping to main- vibration that develop in a piping system when a
tain a water seal in a trap. column of noncompressible liquid owing through a
Trap seal The maximum vertical depth of liquid pipeline at a given pressure and velocity is stopped
that a trap will retain, measured between the crown abruptly.
weir and the top of the dip of the trap. Water hammer arrester A device, other than an
Turbulence Any deviation from parallel ow in a air chamber, designed to provide protection against
pipe due to rough inner wall surfaces, obstructions, excessive surge pressure.
or directional changes. Water main The water supply pipe for public or
Underground piping Piping in contact with the community use. Normally under the jurisdiction of
earth below grade. the municipality or water company.
Upstream Term referring to a location in the direc- Water riser A water supply pipe that extends
tion of ow before reaching a referenced point. vertically one full story or more to convey water to
branches or xtures.
Vacuum Any pressure less than that exerted by
the atmosphere. Also known as NEGATIVE PRES- Water-service pipe The pipe from the water
SURE. main or other source of water supply to the building
served.
Va c u u m b r e a k e r See BACKFLOW PRE -
VENTER. Water supply system The building supply pipe,
the water distributing pipes, and the necessary
Vacuum relief valve A device to prevent excessive connecting pipes, ttings, control valves, and all ap-
vacuum in a pressure vessel. purtenances carrying or supplying potable water in,
Velocity Time rate of motion in a given direction or adjacent to, the building or premises.
and sense. Wet vent A vent that also serves as a drain.
Vent, loop Any vent connecting a horizontal branch Yoke vent A pipe connecting upward from a soil or
or xture drain with the stack vent of the originating waste stack to a vent stack for the purpose of prevent-
waste or soil stack. ing pressure changes in the stacks.
Vent stack A vertical vent pipe installed primarily
for the purpose of providing circulation of air to and
from any part of the drainage system.
Vertical pipe Any pipe or tting installed in a
vertical position or that makes an angle of not more
than 45 degrees with the vertical.
Vitried sewer pipe Conduit made of red and
glazed earthenware installed to receive waste or sew-
age or sewerage.
Waste The discharge from any xture, appliance,
area, or appurtenance that does not contain fecal
matter.
32 ASPE Plumbing Engineering Design Handbook Volume 1
Non-SI Units and Symbols for Use with SI Units Style and Use
the SI System
1. Multiples and submultiples of SI units are to be
There are several (non-SI) units that are traditional formed by adding the appropriate SI prexes to
and acceptable for use in the SI system of units due to such units.
their signicance in specic and general applications.
2. Except for the kilogram, SI prexes are not to be
These units are as follows:
used in the denominator of compound numbers.
Quantity Unit Symbol
Area hectare ha 3. Double prexes are not to be used.
Energy kilowatt-hour kWh 4. Except for exa (E), peta (P), teca (T), giga (G),
Mass metric ton t and mega (M), SI prexes are not capitalized.
Temperature degree celsius C
Time minute, hour, year min, h, y 5. The use of units from other systems of measure-
(respectively) ment is to be avoided.
Velocity kilometer per hour km/h
Volume liter L 6. Except when the SI unit is derived from a proper
name, the symbol for SI units is not capitalized.
7. SI unit symbols are always denoted in singular
SI Unit Prexes and Symbols
form.
The SI unit system is based on multiples and sub- 8. Except at the end of a sentence, periods are not
multiples. The following prexes and corresponding used after SI unit symbols.
symbols are accepted for use with SI units.
9. Digits are placed in groups of three numbers,
Factor Prex Symbol
separated by a space to the left and to the right
1018 exa E of the decimal point. In the case of four digits,
1015 peta P
spacing is optional.
1012 tera T
109 giga G 10. A center dot indicates multiplication, and a slash
106 mega M indicates division (to the left of the slash is the
103 kilo k numerator and to the right of the slash is the
102 hectoa h
101 dekaa da denominator).
10-1 decia d 11. When equations are used, such equations are to
10-2 centia c be restated using SI terms.
10-3 milli m
10-6 micro 12. All units are to be denoted by either their sym-
10-9 nano n bols or their names written in full. Mixed use of
10-12 pico p symbols and names is not allowed.
10-15 femto f
10-18 atto a
Heat
Btu-inch per second-foot squared-F = 519.2 W/mK W/m.K = 0.002 Btu-in/s-ft2F
Btu-inch per hour-foot squared-F = 0.144 W/mK W/m.K = 6.94 Btu-in/h-ft2F
Btu per foot squared = 11 357 J/m2 J/m2 = 0.000088 Btu/ft2
Btu per hour-foot squared-F = 5.678 W/m2K W/m2.K = 0.176 Btu/h-ft2F
Btu per pound-mass = 2326 J/kg J/kg = 0.00043 Btu/lbm
Btu per pound-mass-F = 4186.8 J/kgK J/kg.K = 0.000239 Btu/lbm F
F-hour-foot squared per Btu = 0.176 Km2/W Km2/W = 5.68 F-h-ft2/Btu
Length
inch = 0.0254 m m = 39.37 in
foot = 0.3048 m m = 3.28 ft
yard = 0.914 m m = 1.1 yd
mile = 1609.3 m m = 0.000621 mi
Light (illuminance)
footcandle = 10.764 lx lx = 0.093 ftcd
Mass
ounce-mass = 0.028 kg kg = 35.7 ozm
pound-mass = 0.454 kg kg = 2.2 lbm
Mass per unit area
pound-mass per foot squared = 4.882 kg/m2 kg/m2 = 0.205 lbm/ft2
Mass per unit length
pound-mass per foot = 1.488 kg/m kg/m = 0.67 lbm/ft
Mass per unit time (ow)
pound-mass per hour = 0.0076 kg/s kg/s = 131.58 lbm/h
Mass per unit volume (density)
pound-mass per cubic foot = 16.019 kg/m3 kg/m3 = 0.062 lbm/ft3
pound-mass per cubic inch = 27 680 kg/m3 kg/m3 = 0.000036 lbm/in3
pound-mass per gallon = 119.8 kg/m3 kg/m3 = 0.008347 lbm/gal
Moment of inertia
pound-foot squared = 0.042 kg.m2 kg.m2 = 23.8 lb-ft2
Plane angle
degree = 17.453 mrad mrad = 0.057 deg
minute = 290.89 rad rad = 0.00344 min
second = 4.848 rad rad = 0.206 s
Power
Btu per hour = 0.293 W W = 3.41 Btu/h
foot-pound-force per hour = 0.38 mW mW = 2.63 ft-lbf/h
horsepower = 745.7 W W = 0.00134 hp
Pressure (stress), force per unit area
inches water column = 25.4 mm water mm water = 0.0394 in. wc
atmosphere = 101.325 kPa kPa = 0.009869 atm
inch of mercury (at 60F) = 3.3769 kPa kPa = 0.296 in. Hg
inch of water (at 60F) = 248.8 Pa Pa = 0.004 in. H2O
pound-force per foot squared = 47.88 Pa Pa = 0.02 lbf/ft2
pound-force per inch squared = 6.8948 kPa kPa = 0.145 lbf/in2 (psi)
Chapter 1 Formulas, Symbols and Terminology 37
mile 1.609 km
ft h F/Btu (thermal
2
0.176 m2 K/W
resistance, R) mile, nautical 1.852 a
km
ft /s (kinematic viscosity, v)
2
92.900 mm /s 2
mph 1.609 km/h
0.447 m/s
ft
3
28.32 L
0.02832 m3 millibar 0.100a kPa
ft /min, cfm
3
0.4719 L/s mm of mercury (60F) 0.133 kPa
ft3/s, cfs 28.32 L/s mm of water (60F) 9.80 Pa
To Obtain By Divide To Obtain By Divide
(CONTINUED)
40 ASPE Plumbing Engineering Design Handbook Volume 1
(CONTINUED)
Chapter 2 Standards for Plumbing Materials and Equipment 47
(CONTINUED)
Chapter 2 Standards for Plumbing Materials and Equipment 51
(CONTINUED)
52 ASPE Plumbing Engineering Design Handbook Volume 1
(CONTINUED)
54 ASPE Plumbing Engineering Design Handbook Volume 1
(CONTINUED)
Chapter 2 Standards for Plumbing Materials and Equipment 55
MSS Manufacturers Standardization Society of the Valve & Fittings Industry, Inc.
127 Park Street, N.E.
Vienna, VA 22180
www.mss-hq.com
(703) 281-6613
(703) 281-6671 facsimile
SP-6-2001 Standard Finishes for Contact Faces of Pipe Flanges and Connecting-End Flanges of Valves and
Fittings
SP-58-2002 Pipe Hangers and SupportsMaterials, Design and Manufacture
SP-69-2002 Pipe Hangers and Supports-Selection and Application
SP-70-1998 Cast Iron Gate Valves, Flanged and Threaded Ends
SP-72-1999 Ball Valves with Flanged or Butt-Welding Ends for General Service
SP-80-2003 Bronze Gate, Globe, Angle and Check Valves
(CONTINUED)
Chapter 2 Standards for Plumbing Materials and Equipment 57
(CONTINUED)
58 ASPE Plumbing Engineering Design Handbook Volume 1
ANSI AWWA
American National Standards Institute American Water Works Association
25 West 43rd Street, Fourth Floor 6666 West Quincy Avenue
New York, NY 10036 Denver, CO 80235
www.ansi.org www.awwa.org
(212) 642-4900 (800) 926-7337
(212) 398-0023 facsimile (303) 347-0804 facsimile
ARI CISPI
Air-Conditioning & Refrigeration Institute Cast Iron Soil Pipe Institute
4100 North Fairfax Drive, Suite 200 5959 Shallowford Road, Suite 419
Arlington, VA 22203 Chattanooga, TN 37421
www.ari.org www.cispi.org
(703) 524-8800 (423) 892-0137
(703) 528-3816 facsimile (423) 892-0817 facsimile
ASHRAE CGA
American Society of Heating, Refrigerating and Air-Condi- Compressed Gas Association
tioning Engineers, Inc. 4221 Walney Rd., 5th Floor
1791 Tullie Circle, NE Chantilly, VA 20151-2923
Atlanta, GA 30329-2305 www.cganet.com
www.ashrae.org (703) 788-2700
(404) 636-8400 (703) 961-1831 facsimile
(404) 321-5478 facsimile CSA
ASME Canadian Standards Association
American Society of Mechanical Engineers 178 Rexdale Blvd.
Three Park Avenue Toronto, Ontario, Canada M9W 1R3
New York, NY 10016-5990 www.csa-international.org
www.asme.org (416) 747-4000 or 866-797-4272
800-THE-ASME (843-2763) (416) 747-4149 facsimile
(973) 882-1717 facsimile (Inquiries) DOTn
(212) 591-7674 facsimile (NY) Department of Transportation
ASSE 400 Seventh St. SW
American Society of Sanitary Engineering Washington, DC 20590
901 Canterbury Road, Suite A www.dot.gov
Westlake, OH 44145 (202) 366-4000
www.asse-plumbing.org FS*
(440) 835-3040 Federal Specication
(440) 835-3488 facsimile 1941 Jefferson Davis Highway, Suite 104
ASTM Arlington, VA 22202
ASTM International * Standards are available from the Supt. of Documents,
100 Barr Harbor Drive U.S. Government Printing Ofce, Washington, DC 20402-
P.O. Box C700 9325
West Conshohocken, PA 19428-2959 IAPMO
www.astm.org International Association of Plumbing and Mechanical
(610) 832-9585 Ofcials
(610) 832-9555 facsimile 5001 E. Philadelphia St.
AWS Ontario, CA 91761-2816
American Welding Society www.iapmo.org
550 N.W. LeJeune Road 909-472-4100
Miami, FL 33126 909-472-4150 facsimile
www.aws.org
(800) 443-9353
(305) 443-5951 facsimile
(CONTINUED)
Chapter 2 Standards for Plumbing Materials and Equipment 59
ICC UL
International Code Council Underwriters Laboratories, Inc.
5203 Leesburg Pike, Suite 600 333 Pngsten Road
Falls Church, VA 22041 Northbrook, IL 60062-2096
www.iccsafe.org www.ul.com
703-931-4533 (847) 272-8800
703-379-1546 facsimile (847) 272-8129 facsimile
ISEA
Industry Safety Equipment Association
1901 N. Moore Street, Suite 808
Arlington, VA 22209-1762
www.safetyequipment.org
(703) 525-1695
(703) 528-2148 facsimile
MSS
Manufacturers Standardization
Society of the Valve & Fittings Industry, Inc.
127 Park Street, N.E.
Vienna, VA 22180
www.mss-hq.com
(703) 281-6613
(703) 281-6671 facsimile
NFPA
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02269
www.nfpa.org
(617) 770-3000
(617) 770-0700 facsimile
NSF
National Sanitation Foundation
789 N. Dixboro Road
P.O. Box 130140
Ann Arbor, MI 48113-0140
www.nsf.org
800-NSF-Mark
(734) 769-0109 facsimile
PDI
Plumbing and Drainage Institute
800 Turnpike Street, Suite 300
North Andover, MA 01845
www.pdionline.org
(978) 557-0720
(978) 557-0721 facsimile
PHCC-NA
Plumbing Heating and Cooling
Contractors National Association
180 S. Washington St.
P.O. Box 6808
Falls Church, VA 22040
www.phccweb.org
(800) 533-7694
(703) 237-7442 facsimile
60 ASPE Plumbing Engineering Design Handbook Volume 1
3
INTRODUCTION
Specications
ments. The correct term when describing all of the or subcontractors, as well as certicates of
documents, with the exception of the drawings, is compliance with applicable codes, laws, and
project manual. regulations.
5. The Agreement is the written document signed by
PROJECT MANUAL the owner and the contractor, or by the contractor
The project manual is an accurate and descriptive and a subcontractor or a material supplier, that is
term to describe the collection of documents other the legal instrument binding these parties to the
than the drawings. This manual consists of the fol- contract. The agreement denes the relationships
lowing documents: as well as the obligations between the signing
1. Pre-bid Information advises those prospective parties.
bidders about the proposed project. Private work 6. General Conditions are the general clauses that
going out for bid is usually advertised to the establish how the project is to be administered.
bidders by mail or by telephone. The Architect, These clauses contain provisions that are common
Engineer, or the Owner invites these bidders, practice in the United States. The American Insti-
and bidding is restricted to those bidders invited. tute of Architects, AIA, has developed Document
This method is usually referred to as Bid by In- A201, General Conditions of the Contract for
vitation. Pre-bid information for public work is Construction. A printed copy of which is usually
required by law to be advertised in all newspapers included into the project manual and referenced
of general subscription in the immediate area by the other documents included in the manual.
where the work is to be bid. These public notices, General conditions documents are available from
which are governed by local ordinances, are pub- other organizations such as the National Society
lished for a predetermined period of time. of Professional Engineers (NSPE), the Ameri-
2. Instructions to Bidders are written to inform the can Consulting Engineers Council (ACEC), the
prospective bidders how to prepare their bid so American Society of Civil Engineers (ASCE), and
that all bids are in the same format and can be the Construction Specications Institute (CSI).
easily and fairly compared after the bid open- 7. Supplementary Conditions are the clauses that
ing. modify or supplement the general conditions, as
3. Bid Forms are prepared by the Architect/Engineer needed, to provide for requirements specic to
to provide uniform bid submittals by the bidders that project. They consist of modications and/or
and to facilitate the comparison and evaluation substitutions such as insurance requirements,
of the bids received. prevailing wage rates, etc. It is important to
remember that these are not standardized docu-
4. Bonds and Certicates are the legal documents ments like AIA A201 and must be prepared based
that bind a third party into the contract as a on the requirements of the specic project.
surety that the bidder and the owner will perform
as agreed. This could also be used to insure that 8. Specications verbally describe the required mate-
the contractor and subcontractors will perform as rials and equipment, the level of quality required
agreed. The types of bonds commonly used are: for installation and equipment, and the methods
by which the materials and equipment are as-
(a) Bid Bond Assures that the bidder will enter
sembled and installed, and how they interface
into a contract with the owner or the contrac-
within the project as a whole. The specications
tor if the bidder is selected during the bidding
also set the administrative requirements for the
phase;
contract. All items pertaining to the work under
(b) Performance Bond Assures that the work, contract should be included in the specications.
once a contract has been signed, will be The plumbing drawings graphically illustrate
completed in compliance with the contract the scope of the design, the equipment location,
documents; the routing of piping, the quantity of materials
(c) Labor and Materials Payment Bond Assures required, and the interface with the other trades
that workers on this project will be paid in involved.
full, and that all suppliers that have provided 9. Addenda are the written or graphic documents
materials for the project will be paid in full that are issued prior to the bid to clarify, revise,
prior to the project closeout; add to, or delete information in the original bid-
(d) Guaranty Bond Guarantees that the ding documents or in previous addenda. It should
contractor will be paid in full for all work be noted that while an addendum is typically is-
performed to construct the project; sued prior to the bid opening, AIA document A201
allows for the issuance of an addendum any time
(e) Certicates Certicates of insurance, or up to the execution of the contract. This feature
proof of insurance from the contractors and/
Chapter 3 Specications 63
allows for the negotiated adjustment of a selected Last-minute changes were extremely difcult to ac-
bid after the bid opening. In contrast, the similar complish.
document by the Engineers Joint Contract Docu- Specications can be generated in as many ways.
ments Committee (EJCDC) restricts the issuance They may be produced by the designer as part of the
of addenda pre-bid opening. design process or by a specic individual within the
10. Modications are the written or graphic docu- rm who is employed full time to writing project
ments that are issued after the construction specications. Large rms may even have a full-time
agreement has been signed to allow for additions specications department.
to, deletions from, or modications of the work The rst thing the designer must have is as much
to be performed. These changes are accomplished information as possible that pertains to the section
by the use of change orders, construction change to be written. This includes any reference materials
directives, work change directives, eld orders, that describe products and methods of construction
architects supplemental Instructions (ASI), and to be described within the specication section. The
written amendments to the construction agree- project information would include the drawing set as
ment. These changes or modications can be prepared by the designer, the project notebook, the
issued anytime during the contract period. project scope of work and any applicable laws and/or
Each of the above listed documents is a separate building codes. Information for the products can be
document, but when grouped together, they are col- obtained through a variety of sources, which include:
lectively referred to as the Front End Documents. (1) previous project specications; (2) manufacturers
Although the specications document usually com- information; (3) handbooks, pamphlets, etc for the
prises the bulk of the project manual, it is only one various trade associations; (4) information from
of the required documents. If the project is primar- the manufacturers representatives; (5) reference
ily plumbing, then the plumbing engineer/designer standards from national standards organizations,
may be responsible for the preparation of the entire governmental agencies, and trade associations; (6)
project manual. technical and professional societies; (7) commer-
cially prepared guide specications; (8) information
SPECIFICATIONS obtained from the trades, contractors, etc.; and (9)
Originally all documentation for a given project was personal experience.
placed upon the drawings, but as the amount of Never edit previous specications for use in the
information increased to where it would not t the new project, as they may not contain required lan-
drawing, another way was needed to present this guage, the standards cited may have changed, the
information. The designers simply started compiling products specied may not be available any more, or
all the notes that would not t onto the drawings and the codes and/or laws may have changed since those
over time designers have added additional informa- specications were rst written.
tion, product requirements, contractual provisions, as Once the information that will be needed has been
well as construction methods and systems to create a gathered the designer must now decide what type of
written document. The specication is used to dene format will be used as the basis of the specications
the qualitative requirements for products, materials to be written.
and workmanship that will be used to construct a Depending on the size of the project or the project
given project. phase that the specication is being prepared for, the
As the popularity of the specication grew among designer may choose a short abbreviated format such
design professionals, so did the problems this new as Uniformat developed by the CSI. For the larger,
idea created. Among these problems, there were no more complex projects the designer may choose the
universal guidelines to insure a uniform document. full format as is found in the Masterformat devel-
Each designer wrote specications using their own oped by the CSI. Both Uniformat and Masterformat
style according to what they thought was important. were developed in the early 1970s and 1960s, respec-
Even the specications that came from large rms tively.
were lacking in consistency between documents. In addition to the Uniformat and Masterformat
Materials, methods or items that were related were specication format listed above, there are also speci-
not grouped together in a logical manner but were cations developed by the Engineers Joint Contract
scattered throughout the document in a seemingly Documents Committee (EJCDC), American Institute
random manner. This practice caused great dif- of Architects (AIA), National Society of Professional
culty when the contractor tried to prepare a specic Engineers (NSPE), as well as various governmental
bid, making it very easy to overlook important and agencies such as the Corps of Engineers (USACOE),
costly items. Also, coordination between the various the armed services, NASA, etc.
trades and the contractor would be difcult at best.
64 ASPE Plumbing Engineering Design Handbook Volume 1
The designer needs to become knowledgeable of is the five-digit numbers and titles that arrange
the different specications that are available so they construction/project data into an organized order
can decide which specication is best suited for the of sequence. By having this universal standardized
phase of the project being designed. system, the placement and retrieval of information
is greatly facilitated, and communication throughout
UNIFORMAT the entire construction phase also is greatly improved.
Uniformat is the specication system that was devel- Under this format, group numbers and titles are
oped during the early 1970s and is a system-based organized under these headings: (1) introductory in-
format. This format is used primarily during the formation; (2) bidding requirements; (3) contracting
schematic phase as well as the preliminary or budget- requirements; (4) facilities and spaces; (5) systems
ary cost estimates. The Construction Specications and assemblies; and (6) construction products and
Institute (CSI) and the Construction Specications activities (divisions 1-16). The rst ve groups, while
Canada (CSC) recommend the organization of project they are not specications, are usually included in the
data during the preliminary project phases. project manual. The last group forms the construction
Uniformat is divided into eight broad categories specications.
or sections: (A) substructure; Under the heading (6) construction products
(B) shell; (C) interiors; (D) services; (E) equipment and activities, there are four levels of detail for each
and furnishings; (F) other building construction; (G) division. Level One consists of the titles for the 16
sitework; and (Z) general. For more information and divisions (see Appendix 3-A2). The Level Two titles
the subcategories found within each of the eight (or sections) are referred to as broad scope because
categories of this format, refer to Appendix 3-A1. Ad- they provide the widest scope in describing the work
ditional information on Uniformat may be obtained to be performed or the products to be utilized (see
from CSIs publication Manual of Practice. Appendix 3-A3). Level Three titles are sometimes
One of the best features of Uniformat is that each referred to as medium scope since they cover work
category or sub-category can be easily expanded as that is more limited in scope than under the level two
more information is accumulated during the ongo- titles. Level Three takes the titles listed under Level
ing design process. As more information is added to Two and further divides them in order to add a more
the Uniformat, provides the estimator with valuable denitive scope (see Appendix 3-A4). The titles found
information to prepare an informed preliminary cost under Level Four are the most limited in scope and
estimate. are often referred to as narrow scope. These titles
Once the project progresses from the preliminary cover elements of the work that are very specic (see
or schematic phase (where the Uniformat provides the Appendix 3-A5).
necessary information) to the design development or In the progression from Level One to Level Four,
DD phase, more detailed information is required the titles (or sections) become more narrow or special-
that Uniformat is not designed to handle. At this ized. For example, using the spec for nitrogen piping,
stage of the project, outline specications are usually at Level One it would be 15000-Mechanical. Then, at
introduced to organize the required information. In Level Two the title is further dened to 15200-Pro-
some projects, the use of the outline specication cess piping. At Level Three, this section is dened as
may be required as part of the agreement between 15210-Process Air and Gas Piping. Finally, at Level
the owner and the architect/engineer (A/E). Refer to Four, the title is further dened to 15215-Nitrogen
AIA document B141 and ESCDC document 1910-1 Piping.
for additional information.
Drawings that are prepared during the design MASTERFORMAT 2004AN
development phase contain more detail, both general OVERVIEW
and specic, than the schematic phase drawings. Since last being updated in 1995, CSIs Master-
Format has been the staple of the architectural and
MASTERFORMAT engineering community. This document, while it was
Some designers organize their outline specications good, began to show some problems with respect to
at this point around CSIs Masterformat because supporting the entire construction industry and it
this format can be used from the design development had very limited room for any future expansion. In
phase through to the construction documents (CD). 2001 a seventeen-member task force known as the
Masterformat is a master list of the divisions MasterFormat expansion task team (MFETT) was
numbers and titles that was developed during the formed by CSI to address problems of the document
Washington, D.C., conferences in 1962 and 1963 currently in use. Three years and many drafts later,
and later became the industry standard in both the the revised document known as MasterFormat 2004 is
United States and Canada. The core of this system
Chapter 3 Specications 65
now ready and will be available in late autumn 2004 ing and HVAC items have been moved to Division
through CSI at their website (www.CSINet.org) . 23-Heating, Ventilation and Air Conditioning. Fire
Signicant changes have been made in the organi- Suppression items that were located to Division 13
zation of this document. The rst signicant change to have been relocated to Division 21-Fire Suppression.
be made in the organization of the MasterFormat 95 Refer to Appendix 3-B2 for a listing of sections found
is the reduction of the six groups to only two groups in Division 21-Fire Suppression. For a more detailed
(Procurement and Contracting Requirements Group breakdown of subjects listed in this Division refer to
and Specications Group). The Procurement and Appendix 3-B3. Appendix 3-B4 contains a listing of
Contracting Requirements Group known, by the more the sections found in Division 22-Plumbing, while
familiar name front end documents, contains the bid- Appendix 3-B5 contains a more detailed breakdown
ding information, project forms, contract conditions, of the sections and subjects.
etc. Essentially this is the same material, just with a In conclusion, the changes discussed above and
new name and different location. The Specications any others made to MasterFormat 2004 were made
Group contains the administrative and technical to facilitate use in the Architectural and Engineering
requirements that govern a project. This group is elds for years to come. As when anything changes,
divided into ve subgroups, which are further divided there will be those who love, hate, use or ignore
into a total of forty-nine divisions. The ve subgroups the new. However, MasterFormat 2004 deserves a
comprising the Specications Group are: (1) General chance.
Requirements (Division 01), (2) Facility Construction While Masterformat provides standardization as
(Divisions 02-19), (3) Facility Services (Divisions 20- well as the titles to be used in the project manual, it
29), (4) Site and Infrastructure (Divisions 30-39), and does not address the way in which information will
(5) Process Equipment (Divisions 40-49). Appendix be organized. This need for standardization within a
3-B1 contains a complete list of subgroups and divi- section prompted the development of Sectionformat.
sions and a short description of any changes. This format or outline produces organization, appear-
The original numbering system consisted of a ance, and completeness that is consistent from one
ve-digit number (began in 1978) that organized the section to the next. It may be used as a checklist to
information throughout the sixteen divisions. The gather information for each section.
new system utilizes a six-digit number that consists A good specication section will provide the an-
of three pairs of two digit numbers. For example, swer to the following three questions: (1) How does
03200 found in MasterFormat 95 was replaced by 03 the work dened in the section relate to the work
20 00 (the new number for Concrete Reinforcement). dened for the rest of the project? (2) What materials
Level four numbers have been removed. However, and/or products are to be used to complete the work
recommendations for their use have been included in under this section? (3) How are these materials and/
the supporting documents should the specier wish or products to be incorporated into the work under
to include level four. It should be noted that each this section and the project as a whole? The answers
level has two digits and this alone allows ten times to these questions are grouped into three parts to
as many subjects as was possible under the old ve form the outline for a given section. These parts are:
digit format. Part IGENERAL, Part 2PRODUCTS, and Part
Site construction was located in Division 2 under 3EXECUTION. Refer to Appendix 3-C1 for the
the old system and is now listed as Division 02-Ex- shell outline developed by the American Institute
isting Conditions and all site construction subjects of Architects (AIA) that conforms to the manual of
have been relocated to the Civil and Infrastructure practice as prepared by the Construction Specica-
Subgroup. Division 02 now contains subjects dealing tions Institute (CSI). The order in which these parts
with items and conditions on the job site at the start of are used within a section is xed in both name and
the project including selected demolition, subsurface order, providing a consistent format throughout all
and site investigation, surveying, site decontamina- sections. This, in turn, simplies the designers job
tion and site remediation, etc., and makes the nding of information by the reader
Beginning with this edition, there will be sections much easier.
included to classify information for facility operations Masterformat and Sectionformat, when used
and maintenance, repairs and commissioning. This together, will produce specications that are clear,
information will be located in each division instead complete, accurate, and coordinated. This allows the
of being placed in its own division. information to ow from the divisions to the sections
Another change is the relocation of certain items to the parts and vice versa.
from one Division to other Divisions. Division 15 has
now been reserved for future expansion. Plumbing
items have been relocated to Division 22-Plumb-
66 ASPE Plumbing Engineering Design Handbook Volume 1
This standard describes the procedure for making ments of the cited reference standards. Another clause
capillary (sweat) joints using solder, copper tube, should state that should a conict or discrepancy arise
and copper or copper alloy ttings. between the reference standard and another cited
Test method standards establish the minimum reference and the specications, the more stringent
requirements of what is being tested and how to requirement shall apply. Once the standard has been
test systems for compliance to the standard. Test specied, it becomes necessary for the designer to be
standards such as ASTM E53-02, Standard Test able to enforce the requirements of that particular
Methods for Determination of Copper in Alloyed standard once the project begins. The most com-
Copper by Gravimetry, describe the test procedures mon means to ensure compliance of the standard
and protocols required to obtain a chemical analysis is to check the shop drawings and other submittals
of copper having a minimal purity of 99.75% by gravi- (including manufacturers literature, samples, and
metric analysis. A code standard contains regulations test reports) and make regular site visits to insure
that govern materials to be used, how they are to be compliance of the workmanship standards.
installed, etc. Code standards, such as the National The last method of specifying is the use of the
Standard Plumbing Code published by the National proprietary specication. This method identies the
Association of Plumbing-Heating-Cooling Contrac- products to be used by manufacturers name, brand
tors is a body of code regulations adopted by local name, the model number, type designation, or unique
municipalities as their plumbing code. characteristics. A specication is considered propri-
When a designer wants to refer to or cite a etary if the product to be specied is available from
standard, it is not necessary to include the entire a single source.
text of the referenced standard into the body of the The use of this type of specication has both
specication to be written. The desired standard can advantages and disadvantages. Advantages include:
be included in the document by referring to its num- allowing for closer control in the selection of the
ber, title, or other designation. The most common product; having more detailed and complete drawings
form is to cite it with the initials of the organization due to the more precise information from the product
that sponsors it and the number of the standard, supplier; having shorter specications which result
such as ASTM B88-03. The last digits separated by in shorter production time; allowing for removal of
the hyphen are the date the standard was written product pricing as a major variable; and narrowing
or last revised. Sometimes the standard will be seen of the competition which will simplify the bidding
with a lower case a after the date. This indicates an process. Disadvantages to the use of this method
amendment to the standard. These cited standards include: the elimination or narrowing down of the
become part of the document just as surely as if the competition (preferential treatment might be shown
standards entire text were included. for one product over another and resentment might be
When using the reference standard, the designer directed back to the designer); forcing the contractor
needs to remember certain things. First, there are to do work with a product with which they have very
bad reference standards as well as good ones. Next, little or no prior experience (this could result in poor
the indiscriminate use of these standards within the performance by the contractor); and possibly specify-
document can result in duplication, contradiction, ing a product to be provided by a manufacturer that
and general chaos for designer, contractor, and the no longer exists.
owner. Finally, some of the standards may contain There are two types of proprietary specications:
hidden choices that the designer may not know even closed and open. The difference between them lies
exists, and their inclusion into the document may in how the subject of substitutions of the specied
cause a myriad of problems with the enforcement of products is handled. Open specifications usually
the contract conditions. These standards often only allow substitution of the products, while closed speci-
meet the minimum requirements. cations usually do not allow any substitutions but
Before writing a reference based specication, the restrict the selection to a limited number of choices.
designers should thoroughly familiarize themselves The closed proprietary specication allows the
with the standards they plan to use and how to incor- design to be completed with higher-level detail while
porate these standards into the document correctly, reducing the variables, thus promoting more accurate
as well as how to enforce the requirements of the bids. It will not, however, provide protection against
standard once it has been included. higher costs caused by a supplier of a specied product
Due to possible conicts between the language of taking an unfair advantage of his proprietary posi-
the written standard and the general conditions of the tion and increasing the price. The closed proprietary
contract, the designer should include a clause in the specication may either list one product or multiple
supplementary conditions of the contract that states products as the designer sees t, and there are no
the contract conditions shall govern over the require- substitutions allowed. The designer can control the
68 ASPE Plumbing Engineering Design Handbook Volume 1
product selection through the use of the instructions from manufacturers and suppliers will not be con-
found in section 01630-(Product Substitution Pro- sidered. (2) The setting of a denite deadline for the
cedures), which provides requirements for the use submission of substitution requests by the bidder.
of the product or products specied. Under a closed This deadline should be a minimum of ten (10) days
proprietary specication, when only a single product prior to the bid opening. (3) All requests for substitu-
is specied, the substitution of another product is tions shall be submitted with the request for approval.
not allowed, and the bids submitted will be based Submissions without supporting documentation shall
upon this product only. When a product is specied not be considered. (4) The designer shall review all
by naming several manufacturers, the substitution submissions and issue notication of any accepted
of other products shall not be allowed, and the bids substitutions to all bidders by addendum. The time
submitted will be based on the products specied. The period between the deadline for requests and the
successful bidder is usually required to submit a list addendum is at the discretion of the designer, but
of the product or products they intend to use; within should not be less than three (3) days to allow proper
a specied time following the bid for approval, but examination of the submitted materials.
prior to purchase and installation. If there are at least The federal government and other public au-
three products named and competition is achieved in thorities forbid the use of the proprietary or other
the bid process, it is up to the designer to make sure exclusionary specications except under special con-
the products are equal and acceptable for the purpose ditions.
to which they are being specied.
The open proprietary specication species or CREATING THE SPECIFICATION
names products or materials in the same manner as SECTION
the closed specication. The difference is that alterna- Having examined the methods by which products,
tives for the specied products or materials are also materials, or workmanship are specied, we shall
listed. The bidder must bid on those specied items now look at how these methods are used to create
and may also provide prices for the alternative items a specication section for the project manual. Refer
specied. These prices are usually included on the to Appendix 3-C1, Section Shell Outline, to help il-
bid form in the spaces provided. To clarify bidding lustrate a specication section, in conformance with
processes, the designer might include instructions to the Manual of Practice.
the bidder such as the following: When the product Beginning at the top, the rst item to be com-
is specied to only one manufacturer, substitution of pleted is the section number. The section number is
products will not be allowed. If alternates to the base a ve-digit number corresponding to MasterFormat.
bid are requested, then the bidder may submit bids for This number may refer to any level from Level Two
the alternate items. These bid prices shall include the to Level Four, depending on how specic this section
amount required to incorporate the alternate product will be. Following the section number is the section
into the project. Requests for additional monies for title. The designer should keep this to a maximum of
alternate products or materials shall not be consid- one line, 6-8 words.
ered after the agreement has been executed. The Under Sectionformat as discussed earlier, a speci-
open proprietary specication removes the problem of cation section is divided into three parts. These are
overpricing, which is common in sole-source product (1) PART 1GENERAL; PART 2PRODUCTS;
or material bids. It also allows for the selection of al- PART 3EXECUTION. The section number is usu-
ternate items and price quotations for those items. ally either Level Two or Level Three. Level Four
The major problem with proprietary specica- section numbers are not assigned. This provides the
tions is the attempts by some bidders to introduce user with greater exibility by allowing a location for
products or materials inferior in quality to those that the designer to add specications if necessary.
were specied originally. This problem is the greatest PART 1GENERAL includes: the scope of and,
when the bidder is allowed to specify substitutions any necessary references to the related work, codes,
after the award of the contract. This leads to the and standards that are to be in force during the
practice known as bid shopping. This is unfair to project; qualications for both manufacturers and
those who submitted bids originally and pressure is workmanship; required submittals, including the
put on the designer to accept these inferior product format required for submission of the submittals; any
substitutions. samples required for examination by the designer;
In order to prevent this situation, the designer required information on product manufacturing and
must maintain control over the bidding process by shipping schedules; receiving and storage require-
including requirements in the specications similar ments; as well as any other information found to be
to the following: (1) All substitution requests are to necessary.
be in writing from the bidders, only and any requests
Chapter 3 Specications 69
PART 2PRODUCTS includes those products to be have been cited in this section are listed alphabeti-
used on the project that are part of the work described cally. Standards are usually written in the following
by this specication section. These products should manner: (1) Standard number; (2) Standard title;
be described as accurately, completely, and, above all, (3) Standard society or agency; and (4) Date of the
briey as possible to give the reader the facts needed last revision. For example: ASME B16.22, Wrought
in least amount of text. Any descriptions of these Copper and Copper Alloy Solder Joint, Pressure
products shall be to describe the product to be used Fittings, American Society of Mechanical Engineers
and present any pertinent data required for the use of (ASME), 2002. When there are multiple references
that product. The designer should not include instal- by the same organization those references are ar-
lation instructions and like information in this part, ranged in ascending numerical order.
but should include it in PART 3EXECUTION. Section 1.3 Denition
PART 3EXECUTION contains the detailed in- After the references, any special denitions re-
structions of how the products listed in PART 2 are to quired to explain the work or products used are
be used or installed in the work being performed. Each listed alphabetically.
product listed in PART 2 should have information as
Section 1.4 System Description
to its use in this part. Also, included in this section:
any testing that is to be performed (be sure to include The system description is used by some designers
instructions on who pays for the testing, as well as and omitted by others. This is usually a brief but
what tests and the number required); instructions accurate description of how this spec section ts
for the coordination between the various trades; the into the work.
acceptance of the substrate; and any required toler- Section 1.5 System Performance Criteria
ances for installations. The system performance requirements give the
PART 1 performance criteria, if necessary, for this work.
This section is usually omitted unless a performance
Section 1.1 Summary specication is desired.
The rst section of Part 1 is the summary. In this Section 1.6 Submittals
section, there is the description of the work to
The next portion of PART 1 is probably one of
be performed, the listing of any products to be
the most important ones because it governs the
furnished but not installed, and products that are
submittals. It tells what is required for all prod-
not furnished but are to be installed. This also is
ucts used in the project. The designer must decide
sometimes a clause referred to as owner furnished,
what information will be submitted for review and
contractor installed. The next item found in PART
approval. On some government projects the sub-
1 is the listing of the related sections. It is here
mittal process will be under governmental control
that other sections in the specications contain-
not the designer. The information required for the
ing requirements related to this particular section
submittal can include: (1) Product data as prepared
are listed. Some designers choose to omit this part
by the manufacturer or third-party organization;
because during last-minute changes, this often
(2) Shop drawings from either the manufacturer
fails to get updated resulting in a confusing, awed
or the contractor; (3) Coordination drawings; (4)
document. Also found in the summary are allow-
Wiring or piping diagrams from the manufacturer
ances, unit prices, and alternates. An allowance is a
or contractor; (5) Product certication from manu-
predetermined monetary amount agreed to by both
facturers that these products have been tested and
the designer and the owner to be inserted into the
are compliant with the appropriate standard cited
bid for certain items such as art work, furniture or
by the manufacturer; (6) Test reports from an inde-
even plumbing xtures. A unit price is a xed bid
pendent (or third party) test laboratory certifying
price amount for an item such as a water closet,
those products; (7) Qualication data for manufac-
lavatory, and per-foot price on a four-inch cast iron
turers, rms, or individuals as required in Section
pipe, etc. An alternate is a dened portion of the
1.7 Quality Assurance; and (8) Maintenance data for
work that is priced separately and provides the
the materials and products used for inclusion into
owner an option for to select for the nal scope of
the operation and maintenance (O&M) manuals for
the work. Alternates usually allow choices among
the owner (if required).
the products to be used or to add or delete portions
of the work from the project. Section 1.7 Quality Assurance
Section 1.2 References This is the quality control for the project. In this
section the designer can include what he feels
Another item found in the rst section is the refer-
is needed to assure the project is completed cor-
ences. It is here that the reference standards that
70 ASPE Plumbing Engineering Design Handbook Volume 1
does not mean they cannot be used if the designer regard to the start up and shut down of equipment,
feels they are needed. troubleshooting, servicing, and maintenance; and
(4) Reviewing the data in the O&M manuals with
PART 3 the maintenance staff.
Section 3.1 Examination
USE OF COMPUTERS IN
This section is concerned with the installation of the
products or materials into the project. The rst part
PRODUCING SPECIFICATIONS
involves instructions to the contractor to examine Very few plumbing specications today are written
the sites, plans, existing or constructed walls, oors as an original document, otherwise known as from
and ceilings that must be installed. This section scratch. In most cases, the project specications are
should also instruct the contractor not to proceed created using an ofce prepared master specica-
with the work until all unsatisfactory items have tion, or a set of commercially prepared specications
been corrected. Following sections deal with the that have been published by various industry organi-
general and specic installation requirements of zations such as Masterspec or Spectext. The American
the products and/or materials being used. Often Institute of Architects (AIA) publishes Masterspec.
included, but not mandatory by CSI standards, is Spectext is published by the Constructed Science
a section on connections (shown as Section 3.5). It Research Foundation, which is afliated with the
is in this section that connection requirements for Construction Specications Institute (CSI). The use
owner furnished, contractor installed (often seen as of a master specication to prepare a project speci-
OFCI or GFCI on government projects) are found. cation is certainly more cost efcient than starting
A good example of this would be in the case of a from scratch with each new project.
commercial kitchen where the kitchen equipment The process begins with the designer or speci-
supplier sets the equipment but the plumber con- er choosing the sections that will be needed for the
nects them to the utilities. project manual. This list is then given to the word-
processing department to put together the copy for
Section 3.6 Field Quality Control each section and return it to the designer. It is then re-
The designer deals with testing laboratory services viewed and rewritten as required to suit the projects
(including who pays for it), which tests are to be particular requirements. The revised master copy is
made, and which standard(s) must be met. Also then returned to the word-processing department to
included is what remedy must be made if the tests make the necessary rewrite to the master copy. This
prove that the products and/or materials are not revised copy will be returned to the designer, who will
compliant with the standard set forth in the speci- proofread it and make any further changes that might
cation section. In addition, if a piece of equipment be required. This process continues until the project
that is assembled onsite appears to be complicated, is nalized. As you see, this method of specication
etc., this is where the designer could put a require- is very labor intensive.
ment for the services of a factory-authorized service Fortunately for specication writers, there are
technician to supervise the assembly. computerized or computer assisted specication pro-
Section 3.7 Adjusting and Cleaning grams to aid in the writing of specications. These
programs do for specication writing what computer
A section that covers the adjustment, cleaning, and
aided drafting and design (CADD) did for drafting.
calibration of the products included in this project
One of the rst computer aids was utilizing word-pro-
is well advised. One of the most common sections
cessing programs to write, edit, and more importantly,
would probably be the cleaning and disinfection of
store nished documents in an electronic format.
the potable water system.
This allows documents to be copied instantaneously
Section 3.8 Commissioning instead of spending a lengthy time at the typewriter
Another section that is not mandated by the cur- and/or copy machine. Another benet that came with
rent CSI format, but is gaining in use and will the use of computers is the size of space required to
probably be included as part of the new CSI format store the specications. A specication that might
(tentatively scheduled for release late 2004) is Com- require an entire le cabinet drawer of information
missioning or placing the building into service for can be reduced to one or two oppy disks or one CD-
the owner to use. Items that should be addressed ROM disk.
include: (1) Equipment start up by factory autho- The specication programs that have evolved over
rized service technicians; (2) Testing and adjusting past years and are available today have merged word
of controls and safeties with the replacement of processing, data storage, and acquisition programs
all malfunctioning parts; (3) Providing adequate into single powerful programs that allow specications
training to the owners maintenance staff with to be produced by a single person. This is a drastic
72 ASPE Plumbing Engineering Design Handbook Volume 1
change from the past when it took the designer(s) and CPD (Certied Plumbing Designer) when citing
several other personnel to produce the specication. their professional credentials.
One of the best features of the new master specica- In this world of continually changing work places
tion programs is that there are periodic updates with and corporate restructuring, the plumbing designer
new sections being added and obsolete sections being who demonstrates the ability to produce a clear, con-
deleted. Also, in these updates, the reference stan- cise set of specication documents is a valuable asset
dards that are included in each section are updated to to the project design teams.
the latest standard. For any specier who has spent
several hours searching these standards, this feature
is worth the price of the program.
Computer programs continue to improve at
a dizzying speed. What was cutting edge technol-
ogy ve years ago is now obsolete. These programs
have evolved beyond just being a specialized word
processing program to an interactive program that
contains checklists or interactive input dialogue for
the specier to utilize. Also, there are programs be-
ing written and developed that will interface with
the CADD systems to produce the specications and
even estimates.
CONCLUSION
Writing good, effective specications requires broad
experience as a plumbing designer. In most engi-
neering ofces, specications are prepared by the
project engineer or team leader. The designer must
remember that the essence of plumbing specica-
tions is communication between the persons involved
with the project. Plumbing speciers must develop
skills to communicate the project requirements in a
clear, concise, and easy-to-understand manner. This
requires the ability to write in a clear, precise, tech-
nical style and a precise legal style combined into a
single style.
The one thing that probably has changed the least
in specication writing is the amount of time allotted
by the project managers to complete the specications.
The amount of time given is never enough.
Like most plumbing engineering skills, specica-
tion writing is learned on the job. This is because
university level courses in specication writing are
rare (actually almost non-existent). Classes may be
available as continuing education programs offered by
the Construction Specications Institute (CSI) at both
the national and local level. Local chapter members
of CSI teach local courses. Interested parties should
contact their local CSI chapters for more information
about what is available.
Plumbing designers who have at least ve years
of specication writing experience can demonstrate
their prociency and understanding by taking the
Certied Construction Specier (CCS) Examination
that is given by CSI. Successful completion of this
exam will earn the designer the title of Certied Con-
struction Specier (CCS). There is a growing number
of plumbing engineers that can include CCS after
Chapter 3 Specications 73
H. Wiring diagrams from manufacturer for electri- G. UL Standard: Provide [products] complying with
cally operated equipment. UL [designation, title].
I. Wiring diagrams detailing wiring for power, sig- H. Electrical Component Standard: Provide com-
nal, and control systems, differentiating between ponents complying with NFPA 70 National
manufacturer and eld-installed wiring. Electrical Code and which are listed and labeled
by UL where available.
J. Material certificates signed by manufacturer
certifying that each material item complies with I. UL and NEMA Compliance: Provide [compo-
requirements, in lieu of laboratory test reports, nents] required as part of [product or system]
when permitted by architect. which are listed and labeled by UL and comply
with applicable NEMA standards.
K. Product certicates signed by manufacturers
of [products] certifying that their products J. ASME Compliance: Fabricate and stamp [prod-
comply with requirements. uct] to comply with ASME Boiler and Pressure
Vessel Code, Section VIII, Division 1.
L. Welder certicates signed by contractor certifying
that welders comply with requirements of qual- K. Single Source Responsibility: Obtain [system]
ity-assurance article. components from single source having responsi-
bility and accountability to answer and resolve
M. Qualications data for rms and persons specied problems regarding proper installation, compat-
in quality-assurance article to demonstrate ibility, performance, and acceptance.
their capabilities and experience. Include list of
completed projects with project name, addresses, L. Manufacturer and Product Selection: The draw-
name of architects and owners, plus other infor- ings indicate sizes, profiles, and dimensional
mation specied. requirements of [product or system]. A [product
or system] having equal performance character-
N. Test reports from, and based on tests performed istics with deviations from indicated dimensions
by, qualified independent testing laboratory and proles may be considered, provided devia-
evidencing compliance of [product] with require- tions do not change the design concept or intended
ments based on comprehensive testing. performance. The burden of proof of equality is
O. Maintenance data for [materials and products], on the proposer.
for inclusion in operating and maintenance manu- 1.8 DELIVERY, STORAGE, AND
als. HANDLING
1.7 QUALITY ASSURANCE
A. Deliver materials and equipment to site in such
A. Installer Qualications: Engage an experienced quantities and at such times to ensure continu-
installer who has successfully completed [unit of ity of installation. Store them at site to prevent
work] similar in material, design, and extent to cracking, distortion, staining, and other physical
that indicated for project. damage and so that markings are visible.
B. Installers Field Supervision: Require installer
to maintain an experienced full-time supervisor
90 ASPE Plumbing Engineering Design Handbook Volume 1
B. [Description] Standard: Provide [product or B. Examine rough-in drawings for [name] piping
material] which complies with [standard designa- systems to verify actual locations of piping connec-
tion]. tions prior to installation.
C. [Kind of Performance] Characteristics: [Insert C. Examine walls, oors, roof, and [description] for
requirements for kind of performance involved suitable conditions where [name of products or
and test method as applicable unless require- system] are to be installed.
ments included under Part 1 Article (System D. Do not proceed until unsatisfactory conditions
Description).] have been corrected.
D. [Kind of Performance] Characteristics: [Insert 3.2 PREPARATION
requirements for kind of performance involved
and test method as applicable unless require- A. Protection:
ments included under Part 1 Article (System 3.3 INSTALLATION, GENERAL
Description).] [APPLICATION, GENERAL]
2.4 EQUIPMENT [NAME OF A. [Description] Standard: Install [name of
MANUFACTURED UNIT] product, material, or system] to comply
A. [Equipment or Unit Name]: [Nonproprietary with [standard designation].
description of] complying with [standard des- 3.4 INSTALLATION {OF [NAME]}
ignation] (for type, grade, etc.). {APPLICATION OF [NAME]}
B. [Equipment or Unit Name]: [Nonproprietary A. Install [name of unit of work] level and plumb, in
description of] complying with [standard des- accordance with manu-facturers written instruc-
ignation] (for type, grade, etc.). tions, rough-in drawings, the original design, and
C. [Equipment, Unit, or Product Name]: [standard referenced standards.
designation], (type, grade, etc. as applicable to 3.5 CONNECTIONS (NOT A CSI
referenced standard). ARTICLEBUT USEFUL FOR
D. [Equipment, Unit, or Product Name]: [standard DIVISION 15)
designation], (type, grade, etc. as applicable to A. Piping installation requirements are specied
referenced standard). in other sections. Drawings indicate general ar-
2.5 COMPONENTS rangement of piping, ttings, and specialties. The
following are specic connection requirements:
A. [Component Name]: [Nonproprietary descrip-
tion of] complying with [standard designation] B. Install piping adjacent to equipment to allow
(for type, grade, etc.). servicing and maintenance.
B. [Component Name]: [Nonproprietary description 3.6 FIELD QUALITY CONTROL
of] complying with [standard designation] (for A. Testing Laboratory: Owner will employ and pay
type, grade, etc.). an independent testing laboratory to perform eld
2.6 ACCESSORIES quality control testing.
A. Manufacturers standard factory nish. B. Testing Laboratory: Provide the services of an
independent testing laboratory experienced in
2.7 MIXES the testing of [unit of work] and acceptable to
2.8 FABRICATION the engineer, to perform eld quality control test-
ing.
2.9 SOURCE OF QUALITY CONTROL
C. Extent and Testing Methodology: Arrange for
PART 3EXECUTION testing of completed [unit of work] in successive
stages in areas of extent described below; do not
3.1 EXAMINATION proceed with [unit of work] of next area until
test results for previously completed work verify
A. Examine [substrates] [areas] [and] [conditions] compliance with requirements.
[with Installer present] for compliance with
requirements for [maximum moisture content], D. Testing laboratory shall report test results
installation tolerances, [other specic conditions], promptly and in writing to contractor and engi-
and other conditions affecting performance of neer.
[unit of work of this section]. Do not proceed with E. Repair or replace [unit of work] within areas
installation until unsatisfactory conditions have where test results indicate [unit of work] does
been corrected. not comply with requirements.
92 ASPE Plumbing Engineering Design Handbook Volume 1
example, one plumber and one apprentice, each with Table 4-5 shows the time for one laborer to hand
their own wage, can install so many feet of 3-inch [75 backll and mechanically hand-tamper medium back-
mm] PVC pipe per day. ll (a trench 3 feet [0.91 m] deep 100 feet [30.5 m]
long) is 17 hours. The same table shows the time to
PRODUCTIVITY RATES do it by machine is 1.8 hours. However, 12 additional
Tables 4-2 through 4-8 provide labor units for es- hours are required for hand tamping the rst layer
timating a plumbing project. Table 4-9 provides some of a 4-inch [100 mm] pipe and 0.8 hours of labor to
modiers for various job conditions. The information assist the backlling. If certain types of ll material
was originally derived from the National Association are used, such as - to 1-inch [19 to 25 mm] stone,
of Plumbing-Heating-Cooling Contractors (NAPHCC) compacting the ll is not required.
based on surveys solicited of 150 plumbing contractors Notice in Table 4-6 that a single 4-inch [100 mm]
from all areas of the United States. brazed joint takes the most time (1.11 hours), and a
Notice the cost difference between hand trench- single hubless joint takes the least time (0.4 hours).
ing and machine trenching in Table 4-2. For example, Example 2
a trench 3 feet [0.91 m] deep 100 feet [30.5 m] long
takes 2 or 3 hours by machine and up to 48 man-hours Using Tables 4-2 and 4-5, estimate the cost to
by hand. Four hours of additional time is applied to excavate and backll a trench 5 feet [1.52 m] deep 210
the machine method if hand grading is required. The
Table 4-3 To Sawcut 100 Feet
trench width and material volume are revised in Table [30.5 m] of ConcreteTrench
2 from earlier Data Book editions to reect excava-
Depth
tion with trench boxes and other shoring methods. For
handwork, the volume should be adjusted to reect a Inches 3 4 5
typical 24-inch trench width for excavation and backll mm 75 100 125
volumes. For exterior work or other clear spaces ac-
commodating larger machinery, hours may be reduced Hours 5 6 7
substantially from that indicated. Sawcutting may be
faster than as shown in Table 4-3 if space allows for Table 4-4 To Break 100 Feet [30.5 m] of Pavement
larger equipment. Breaking pavement with heavier Method Pavement Width Hours
pneumatics or removing whole pieces of sawcut con- Hand Concrete 24 in. 10
crete will reduce the times shown in Table 4-4. Pneumatic [600 mm]
96 ASPE Plumbing Engineering Design Handbook Volume 1
12 178 73 91 119 8 12 5 b
13 192 80 99 130 8 12 6 b
Conversion factors: 1 in. = 25.4 mm, 1 ft. = 0.3048 m, 1 yd3 = 0.7646 m3, 1 ft3 = 0.037 yd3
Notes:
a Must add for stand-by hand laborer.
b Call equipment company for hours to compact backll.
23. Select location and spacing of cleanouts. Conrm 34. Review and coordinate natural-gas connections
compliance with local authority having jurisdic- for water heaters, food-service equipment, and
tion. other equipment as required.
24. Locate re standpipes and hose connections. 35. Select size and design of oor drains and recep-
25. Locate alarm panels and motor controllers. tors to meet requirements. If required, segregate
clearwater wastes from sanitary wastes. Connect
26. Locate roof leaders, main stacks, and supply clearwater system to the storm-drain system.
risers. Coordinate wall thicknesses, beam clear-
ances, and footing clearances with the architect 36. Identify infrequently used drains and provide
and structural engineer. with trap primers.
27. Coordinate structural penetrations and house- 37. Offset roof drains and vent terminals 12 to 18
keeping pads with the architect and structural inches [0.3 to 0.5 m] away from parapet walls,
engineer. Review weight of water heater and other roof openings, and other roong elements.
equipment with the structural engineer. 38. Review canopies and porte-cocheres for adequate
28. Select xtures and xture trim, including faucets, drainage.
shut-off valves, ush valves, carriers, strainers, 39. Provide cross-connection control for potable wa-
drains, traps, and wall anges. Send xture cut ter supply connections to building equipment and
sheets to the architect. Include dimensioned systems, for all xtures, and for appurtenances
drawings of xtures and xture trim. as required. In particular, provide air gaps or
29. Select sprinkler-head designs including es- approved backow preventers for connections
cutcheons or covers, nish type or color. Send to boilers and to sprinkler supplies. Provide air
sprinkler-head cut sheets to the architect. gaps for relief ports of backow preventers, for
pressure-relief valves, and generally for xture
30. Determine medical gas outlet types, shut-off faucet outlets.
valve box designs, and alarm panel layouts. Send
equipment cut sheets to the architect. Include 40. Provide interceptors as required, including sub-
dimensioned drawings and selection of options. soil receivers, exterior-pavement catch basins,
garage catch basins, grease interceptors, oil and
31. Review plans for mop-basin, drinking fountain, sand interceptors, laundry interceptors, plaster
and oor-drain requirements. interceptors, acid and caustic dilution or neutral-
32. Provide oor drains for public toilet rooms, at ization basins, and special industrial treatment
least one oor drain at the lowest oor level of systems.
the building, and in pits such as elevator pits.
PLUMBING-DRAWINGS CHECKLIST
33. Review and coordinate water-supply connection
Modify checklist to suit client requirements and the
and drain requirements for:
policy of your rm. Initial checked items. Label NA
Backow preventers (adequate drain for relief
port) where not applicable.
Beverage machines Plans
Boilers
1. Is it evident that the architectural back-
Chillers
grounds are current? Check at phases of job or
Compressors
other increments to be established.
Cooling towers
Cooling coils (drain only) 2. Does the title block have correct format,
Emergency eyewash/shower proper date, and proper nouns spelled correct-
Fire sprinklers and re pumps ly?
Food-service areas, including dishwashers, 3. Are the drawings legible and of sufcient
walk-in refrigerators and scale?
freezers, steam kettles, scullery sinks
High-efciency burners (drain only) 4. Are arrangements coordinated so that
Humidiers drawing sheet index and project-manual table of
Ice machines contents match the nal set of drawing sheets and
Laboratory equipment the nal sections of the plumbing specication,
Laundry respectively?
Pressure relief valves (drain only) 5. Are more recent requirements coordinated
Sterilizers with the architect, electrical engineer, HVAC
Vacuum pumps engineer, and structural engineer?
Other equipment
102 ASPE Plumbing Engineering Design Handbook Volume 1
6. Do pipes clear structural members, high 7. Does the re-riser design meet require-
ceilings, skylights, and clerestories? ments?
7. Do all pipes show sizes? Are xture units 8. Are detail references coordinated with the
shown? Are invert elevations shown? plans?
8. Are valves and cleanouts accessible? Schedules and Specications
9. Are all xtures connected to supply, waste, 1. Is the inclusion of xtures and equipment
and vent piping? consistent in both the drawings and the specica-
10. Do toilet rooms have oor drains where tions?
required? Lowest level, elevator pit, and other 2. Are xtures and equipment consistently
pits? referenced on plans, risers, schedules, and speci-
11. Is piping kept out of elevator shafts, electric cations?
and data-communication rooms, similar restricted 3. Are pumps selected for proper ow and
rooms, stairs, and exit-discharge corridors? Are head?
pipes clear of ductwork?
4. Is voltage and other electric data consistent
12. Are stacks, conductors, and risers within with schedules, the equipment supplier, and the
interior partitions of sufcient thickness? electrical engineer?
13. Are ceiling spaces and similar concealed 5. Does the schedule of supply and drainage-
spaces prone to freezing? xture units show the original total, removed
14. Is cutting and patching addressed clearly? total, and new total?
15. Do roof-drain locations coordinate with 6. Is a water-supply uniform-pressure calcula-
architectural requirements? tion or other sizing method included? Is the street
pressure correct? Is the controlling-xture pres-
16. Are drawing notes complete and edited for sure correct? Is the maximum length accurate?
the specic job?
7. Do faucets and ush valves meet water-
17. Are plumbing vents spaced sufciently from conservation requirements? Does the xture trim
air intakes and operable windows? meet requirements for handle design, strainer
18. Is the mechanical room coordinated and design, and spout height? Does the client accept
well laid out with sufcient access to service the vendor selection?
equipment, including equipment removal? Are 8. Are legends, symbols, and abbreviations
equipment connections and drains coordinated? included?
19. Does the direction of the north arrow agree
with the architects plans? FIELD CHECKLIST
Risers and Details Field visits can be broken down into three phases:
Underground, rough-in, and nal. Important items
1. Are risers legible? Are references, such as to observe when visiting a job site are listed as fol-
drawing references, room numbers and xture lows and shall be in reference to requirements of the
tags, clearly presented? Are xture traps oriented construction documents. Initial observed items. Label
correctly? NA where not applicable. Add comments regarding
2. Are all vents properly connected? Are vent deciencies.
stacks, relief vents, and yoke vents shown where Building Drains
required?
1. General alignment and conformity to
3. Are pipe sizes consistent between risers and
plans
plans?
2. Workmanship of joints, general compactness
4. Are details shown for accessible xtures,
of soil below, and around pipe
interceptors, backow preventers, water heat-
ers, water-treatment systems, sump pumps, and 3. General slope of piping
sewage ejectors? 4. Spacing and accessibility of cleanouts
5. Are pipe supports, sleeves and re-stopping 5. Vent connections
systems detailed properly?
6. Branch to building drain not connected near
6. Is the water-service design detailed properly base of stack or conductor
and coordinated with the utility?
7. Pipe sleeves and water stopping
8. Pipe sizes and invert elevations
Chapter 5 Job Preparation, Drawings and Field Checklists 103
9. Manholes, sumps, receivers, grease intercep- 15. Branch to stack offset not connected near
tors, sand and oil interceptors, trench drains, and upstream end of offset
other structures; workmanship, specied size, 16. Pipe labeling and valve tags
invert elevations, and rim elevations
17. Installation of pipe insulation, including
10. Trap-primer connections covers over valves and ttings.
11. Temporary terminations covered or capped 18. Adequacy of cooling-coil-condensate drains,
to prevent entry of foreign material combustion-condensate drains, relief-valve drains,
12. Acid-waste and vent piping and acid-dilution and indirect waste pipes; supported properly and
tank air break or air gap as required
Water and Gas Services 19. Adequacy of oor slope to oor drains and
oor sinks; rims of indirect waste receptors are
1. Compliance with water-service require-
elevated to prevent entrance of debris
ments, including service location, pipe depth,
thrust blocks, and shut-off valves 20. Installation of small interceptors
2. Compliance with natural-gas-service re- 21. Vent terminals properly ashed, located
quirements, such as service location and shut-off away from air intakes and operable windows
valves 22. Motor starters, magnetic and manual
Above Grade Rough-in 23. Connection of plumbing to other building
1. Compliance with water-service require- equipment, including boilers, chillers, cooling
ments such as location, shut-off valves, meters, towers, air handlers or fan coils, food service,
meter registers, pressure-reducing valves, by- medical, laundry, and similar equipment; arrange-
passes, backow preventers, pressure gauges, and ment of piping, valves, cross-connection control,
testing ports and drainage.
2. Compliance with natural-gas-service re- Final
quirements such as location, shut-off valves, 1. Adequacy of hot water at remote xture
meters, meter registers, pressure-reducing valves,
vent ports, and bypasses 2. ADA accessibility requirements
3. Piping at booster pumps, water heaters, and 3. Fixture support
water-treatment devices 4. Water-closet bowl type and seat design
4. Fire-protection-system piping 5. Flush-valve performance
5. Medical-gas-system piping, valves, outlets, 6. Strainers and traps
panels, and source equipment such as cryogenic
7. Faucet handles, outlet ow rating, outlet air
systems, high-pressure manifolds, vacuum pumps,
gap
air compressors as well as attendant dew-point
and carbon-monoxide monitors, air dryers, and 8. Fixture supply-stop location
inlet, discharge, or relief piping to the exterior 9. Fixture mixing-valve location and tempera-
6. Adequacy of sump pumps, sub-soil receivers, ture setting
and sewage ejectors 10. Mop-basin accessories
7. General alignment, arrangement, and sizes 11. Caulking at xture
of piping in conformity to plans
12. Access panels for valves and cleanouts
8. Workmanship of joints
13. Cross-connection control type, application,
9. Installation of pipe supports, expansion installation, approval, product listing, drainage
joints or expansion loops, and pipe swing joints
14. Sprinkler heads and standpipe hose connec-
10. Location of valves tions
11. Clearances around pipes within sleeves 15. Medical-gas valves, outlets, panels
12. Spacing and accessibility of cleanouts 16. Owner equipment manuals
13. Fire stopping at re walls, re-rated oors, 17. Record drawings and/or as-built drawings
and other locations as required
18. Training and commissioning
14. Vent connections: Close enough to trap to
avoid air lock, above ood level, vertical where
required
104 ASPE Plumbing Engineering Design Handbook Volume 1
COMMENTS: _________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
6
INTRODUCTION
Plumbing for
People (or Persons)
with Disabilities
Standard (UFAS) and the U.S. Architectural and 93-112, known as the Rehabilitation Act of 1973, was
Transportation Barriers Compliance Board (ATBCB) passed by the federal government in 1973.
requirements. State and municipal governments also began is-
As part of an ongoing review process, the A117.1 suing their own ordinances regarding architectural
committee was reconvened in 1989 with the intention barriers. These legislative acts were usually modied
of reissuing the standard in 1990. The magnitude of versions of the ANSI A117.1 document. At the present
the changes, both in technical data and in format, time, just about every state has adopted some legisla-
resulted in a delay in publication of the standard tion covering this subject; however, there are major
until December 15, 1992. This standard was the differences from one ordinance to another. Like the
most comprehensive to date and the involvement federal government, the original legislation usually
from disability advocates and interested parties was applied to government-owned or government-nanced
remarkable. The 1992 standard is now referenced structures, but now the requirements generally apply
in several model codes and has resulted in improved to all public accommodations.
accessibility in many regards. The Americans with Disabilities Act (ADA) was
In 1995, the A117.1 committee was called again enacted by the Congress and signed by President
and charged with the task of reviewing the standard George Bush on July 26, 1990. The ADA prohibits dis-
for changes. The makeup of the committee had crimination based on physical or mental disabilities in
grown to include many disability advocacy groups, private places of employment and public accommoda-
model code representatives, and associationsin- tion, in addition to requiring transportation systems
cluding the American Society of Plumbing Engineers and communication systems to facilitate access by the
(ASPE)and design professionals. The committee disabled. The Act is modeled, to a considerable extent,
worked for more than three (3) years, through three on the Rehabilitation Act of 1973, which applies to
(3) public reviews, examining over 1,000 proposed federal grantees and contractors.
changes, during 23 days of meetings, to produce the The ADA is essentially civil rights legislation,
1998 ANSI A117.1-1998 standard. The 1998 stan- but its implementation has a major impact on the
dard has been developed to work in harmony with construction industry. In order to clarify construc-
federal accessibility laws, including the current Fair tion requirements, the Attorney Generals office
Housing Accessibility Guidelines and the proposed commissioned the U.S. Architectural and Trans-
Americans with Disabilities Act Accessibility Guide- portation Barrier Compliance Board (ATBCB) to
lines (ADAAG). prepare architectural guidelines to ensure that the
New provisions for Type B dwelling units are in- construction industry understood what was required
tended to provide technical requirements consistent in order to comply with the Act. The ATBCB, which
with the Fair Housing Accessibility Guidelines of the is represented on the A117.1 committee, used much
U.S. Department of Housing and Urban Develop- of the completed how-to data that was available from
ment. HUD is currently in the process of reviewing A117.1, and where-to data from the ongoing scoping
the 1998 standard to determine equivalency with work being done by the Board for Coordination of
the guidelines. In addition, the A117.1 committee Model Codes (BCMC), its governmental experiences,
worked closely with the ADAAG Review Federal and public comments to produce the guidelines com-
Advisory Committee to harmonize the 1998 edition monly referred to as ADAAG.
with proposed revisions to ADAAG. The U.S. Archi- After incorporating public comments, the nal
tectural and Transportation Barriers Compliance rule was issued on July 26, 1991, in the federal reg-
Board (Access Board) published a notice of proposed ister (28 CFR Part 36) as Nondiscrimination on the
rule making in the Federal Register, November 16, Basis of Disability by Public Accommodations and in
1999. Twenty-ve-hundred comments were received Commercial Facilities. The Act became effective on
for the proposed rule. Until the rule is published in January 26, 1992, and applies to all construction with
nal form and the Federal Department modies its application for permit after January 26, 1992. This
standard to reect the revised guidelines, the current nal rule preempted state and local laws affecting
standard would be in effect. entities subject to the ADA, to the extent that those
laws directly conict with the statutory requirements
LEGISLATION of the ADA. The attorney generals ofce established
In 1969, Public Law 90-480 (known as the Archi- as a procedure for the certication of state and local
tectural Barriers Act of 1968) was signed by President accessibility codes or ordinances that they meet or
Lyndon B. Johnson. The main thrust of this legisla- exceed the requirements of the ADA. It was hoped
tion was that any building constructed, in whole or in that, with such a certied code enforced by local in-
part, with federal funds must be made accessible to, spectors, compliance with ADA would not be decided
and usable by, the physically challenged. Public Law in the courts.
Chapter 6 Plumbing for People (or Persons) with Disabilities 107
In 1994, the ATBCB commissioned a new com- Sight disabilitiesTotal blindness and other
mittee to make recommendations for an improved types of impairment affecting an individuals
document to replace the current Americans with Dis- sight.
abilities Act Accessibility Guidelines (ADAAG). This Hearing disabilitiesTotal deafness and other
committee met for more than two (2) years to review types of impairment affecting an individuals
proposed changes to the document and remove the hearing.
ambiguities that have been a cause of contention to
Coordination disabilitiesThose caused by palsy
designers as well as code-enforcement ofcials. This
due to cerebral, spinal, or peripheral nerve in-
new committee included 22 members representing:
jury.
Advocacy groups (American Council of the Blind;
Disability Rights Education and Defense Fund, Inc; Aging disabilitiesThose brought on by the
Eastern Paralyzed Veterans Association; Maryland natural process of aging, which reduces mobility,
Association of the Deaf; World Institute on Disability), exibility, coordination, and perceptiveness in
code enforcement ofcials [Virginia Building and Code individuals. (Note: To some extent, various na-
Ofcials Association; Texas Department of Licensing tional standardse.g., HUDs Minimum Property
Standardsdifferentiate the elderly from people
and Regulation; Southern Building Code Congress
with disabilities.)
International, Inc. (SBCCI); National Fire Protection
Association (NFPA); National Conference of States on The disability classifications that affect the
Building Codes and Standards; International Confer- plumbing engineer the most, in terms of design, are
ence of Building Ofcials (ICBO); Council of American the non-ambulatory and the semi-ambulatory groups.
Building Ofcials (CABO); Building Ofcials and Adequate plumbing facilities must be provided for
Code Administrators International, Inc. (BOCA)], these individuals. The architect is responsible for
and designers [American Institute of Architects (AIA), analyzing the needs of a person conned to a wheel-
American Society of Interior Designers (ASID)]. The chair and those forced to use walking aids such as
document that came from this committees work was crutches and braces. However, the plumbing designer
presented to the ATBCB on October 10, 1996. Design should become familiar with the characteristics of
professionals must continue to review the ADA in its the wheelchair and various associated types of equip-
entirety, and forthcoming revisions, as well as state ment. At the present time, there are many variations
and local codes for application to their projects. Some in wheelchair design available on the market. The
states require preapproval of accessible plumbing specications in these guidelines are based on adult
xtures. Approval of the xtures is the responsibility dimensions and anthropometrics. An illustration of
of the xture manufacturers, but the specier must a typical wheelchair design is shown in Figure 6-1
specify and approve only those xtures that have (Refer to Table 6-1 for graphic conventions).
received approval. In addition to the dimensions of the wheelchair,
There are still a number of concerns regarding the plumbing engineer must take into consideration
whether the established standards properly address how wheelchairs are employed and how the person
the specic needs of children and the elderly. Children in a wheelchair utilizes plumbing xtures.
cannot necessarily reach xtures set at established The following information on xture require-
heights for people with disabilities. Also, the elderly ments for the use of people with disabilities is based
may have trouble accessing xtures set low to meet on the recommended design criteria contained in the
established height requirements for people with dis- proposed ANSI A117.1-1998. A117.1-2003 is proposed
abilities. to be published May of 2004. For convenient reference
to the ANSI A117.1 text, the corresponding ANSI
DESIGN article numbers have been used (e.g., 601.1 and
Although plumbing is only a small portion of the 602.5). Illustrations, in most cases, are the same
overall effort to create a totally barrier-free environ- as or similar to those in ANSI A117.1. Therefore,
ment, it is one of the most important areas to be dealt A117.1 gure numbers (such as Figure B4.15.2.1
with by engineers. and Figure B4.20.3.1) have been included with the
The following are the various classications of Plumbing Engineering Design Handbook gure
disabilities: numbers.
Non-ambulatory disabilitiesThose that conne Explanatory notes have been added after the
individuals to wheelchairs. recommendations for each xture, where deemed of
value. Where there are differences between A117.1
Semi-ambulatory disabilitiesThose that neces- and ADAAG other than of an editorial nature, it is
sitate individuals to require the aid of braces, also noted.
crutches, walkers, or some other type of device
in order to walk.
108 ASPE Plumbing Engineering Design Handbook Volume 1
Direction of approach.
Maximum.
Minimum.
Centerline.
Note: Dimensions that are not marked minumum or maximum are absolute, unless indicated otherwise in text or captions.
PLUMBING ELEMENTS
AND FACILITIES1
601 General
601.1 Scope Plumbing elements and facilities re-
quired to be accessible by scoping provisions adopted
by the administrative authority shall comply with the
applicable provisions of this chapter.
602 Drinking Fountains and Water Coolers
602.1 General Accessible xed drinking fountains
and water coolers shall comply with 602.
602.2 Clear oor or ground space A clear oor
or ground space complying with 305 shall be pro-
vided.2
602.2.1 Forward approach Where a forward
Figure 6-2 Clear Floor Space approach is provided, the clear oor or ground space
for Wheelchairs shall be centered on the unit and shall include knee
Source: CABO/ANSI A117.1-1992, Reprinted with permission. and toe clearance complying with 306.2
602.2.2 Parallel approach Where a parallel ap-
CLEAR FLOOR OR GROUND proach is provided, the clear oor or ground space
SPACE FOR WHEELCHAIRS shall be centered on the unit.
The minimum clear oor or ground space required to
602.3 Operable parts Operable parts shall comply
accommodate a single, stationary wheelchair and oc-
with 309.2
cupant is 30 inches 48 inches (760 mm 1220 mm).
(See Figure 6-2-B4.2.4.1.) The minimum clear oor or 602.4 Spout height Spout outlets shall be 36
ground space for wheelchairs may be positioned for inches (915 mm) maximum above the oor or ground.
forward or parallel approach to an object (see Figure (See Figure 6-9A-B4.15.2.1A.)
6-3-B4.2.4.2). Clear oor or ground space for wheel- 602.5 Spout location Units with a parallel ap-
chairs may be part of the knee space required under proach shall have the spout 3 inches (89 mm)
some objects. One full, unobstructed side of the clear maximum from the front edge of the unit, including
oor or ground space for a wheelchair shall adjoin bumpers. Units with a forward approach shall have
another wheelchair clear oor space. If a clear oor the spout 15 inches (380 mm) minimum from the ver-
space is located in an alcove or otherwise conned tical support and 5 inches (125 mm) maximum from
on all or part of three sides, additional maneuvering the front edge of the unit, including bumpers.
clearances shall be provided as shown in Figure 6-4
602.6 Water ow The spout shall provide a ow
(B4.2.4.4).
of water 4 inches (100 mm) high minimum to allow
Anthropometrics the insertion of a cup or glass under the ow of water.
Forward reach If the clear oor space only allows The angle of the water stream from spouts within 3
forward approach to an object, the maximum high inches (75 mm) of the front of the unit shall be 30
forward reach allowed shall be 48 inches (1220 mm). degrees maximum. The angle of the water stream
(See Figure 6-5-B4.2.5.1.) The minimum low forward from spouts between 3 inches (75 mm) and 5 inches
reach is 15 inches (380 mm). If the high forward reach (125 mm) from the front of the unit shall be 15 de-
is over an obstruction, reach and clearances shall be grees maximum. The angle of the water stream shall
as shown in Figure 6-6 (B4.2.5.2). be measured horizontally, relative to the front face of
Side reach If the clear oor space allows parallel the unit. (See Figure 6-10-B4.15.2.3.)
approach by a person in a wheelchair, the maximum
602.7 Protruding objects Units shall comply
high side reach allowed shall be 48 inches (1220 mm),
with 307.2
and the low side reach shall be 15 inches (380 mm)
(see Figure 6-7-B4.2.6.1). If the side reach is over Drinking fountain note:
an obstruction, the reach and clearances shall be as The easiest way for someone in a wheelchair to
shown in Figure 6-8 (B4.2.6.2). use a drinking fountain is to approach it from
the side and lean to the side to reach the spout.
The plumbing engineer should therefore spec-
ify a fountain or cooler with a spout located as
110 ASPE Plumbing Engineering Design Handbook Volume 1
Figure 6-7 Unobstructed Side Reach Limit Figure 6-8 Obstructed Side Reach Limit
Source: CABO/ANSI A117.1-1992, Reprinted with Source: CABO/ANSI A117.1-1992, Reprinted with permission.
permission.
(a) Spout Height and Leg Clearance (b) Clear Floor Space
Figure 6-9 Cantilevered Drinking Fountains and Water Coolers
Source: CABO/ANSI A117.1-1992, Reprinted with permission.
Note: Figure 6-9a only: Equipment permitted within dashed lines if mounted below apron.
close to the front edge and as low as possible. back-disabled individuals (ADAAG section 4.1.3,
There are self-contained units available that item no. 10, and appendix A4.15.2). Where only
can be mounted so that spout heights of 33 to 34 one (1) fountain is required by code, it must be
inches (839 to 864 mm) can be obtained, with- an accessible bi-level unit, or two (2) separate
out interfering with required leg clearances. accessible units mounted at different heights
Parallel approach units are more dif- must be provided. Where more than one (1) foun-
cult to use than the cantilevered type and tain is required by code, 50 percent must be in-
should be avoided if possible. If used, the stalled for wheelchair-bound individuals.
spout should be mounted as close to 30 inches 603 Toilet and Bathing Rooms
(762 mm) as the fountain will permit. 603.1 General Accessible toilet and bathing rooms
It is desirable to provide some water coolers or shall comply with 603.
fountains with spout heights of approximately 42 603.2 Clearances
inches (1067 mm) to serve semi-ambulatory users
who can have difculty bending to lower elevations. 603.2.1 Wheelchair turning space A wheelchair
turning space complying with 304 shall be provided
Drinking fountains must be provided not only within the room.2
for wheelchair-bound individuals but also for
1 Text source: CABO/ANSI A117.1-1998
2 See CABO/ANSI A117.1-1998
Chapter 6 Plumbing for People (or Persons) with Disabilities 113
(1220 mm) maximum above the oor or ground. max.), compartment which premises use of grab
Where provided, a fold-down shelf shall be 40 inches bars on either or both sides of the compartment.
(1015 mm) minimum and 48 inches (1220 mm) maxi- ADAAG note:
mum above the oor or ground.
ADAAG has an exception to the height require-
Water closets and toilet compartments note: ment of water closets and grab bars for water
The centerline requirement for water closets has closets located in a toilet room for a single occu-
been adjusted to allow a range of 16 to 18 inches pant, accessed only through a private ofce and
(407 to 457 mm) from the centerline of the xture to not for common or public use. Where six (6) or
the side wall, eliminating the xed 18 inches (457 more compartments are provided in a toilet room,
mm) dimensional requirement. Code enforcement one (1) must be a 60 inch (1525 mm) wheelchair-
ofcials in the eld have successfully argued this accessible compartment, and one (1) must be a
change on the merits of allowing some exibility. 36 inch (915 mm) ambulatory compartment.
The greater or lesser accessibility of a water closet The ush valve handles should not exceed 44
installed 16 inches (407 mm) from the side wall to inches (1118 mm) above the oor. The handles
the centerline of the toilet versus a water closet in- in standard accessible stalls must be at the wide
stalled 18 inches (457 mm) from the side wall has side of the stall (ADAAG section 4.16.5). This
yet to be answered to a majority of either committee. means, depending on how the stall is cong-
The toilet seat height of 17 to 19 inches (432 to 483 ured, the handle must be on either the right or
mm) in public areas is intended to minimize the dif- left side of the ush valve. This does not apply to
ference between the seat and the standard wheelchair tank-type units, although several manufacturers
seat height to aid the transfer process, without elevat- have now come up with a right-hand operator.
ing the toilet seat to the point that stability problems 605 Urinals
are created.
605.1 General Accessible urinals shall comply
The 60 inches (1525 mm) wide wheelchair-ac- with 605.
cessible compartment is preferred and should be
designed. In the design of alterations to existing 605.2 Height Urinals shall be of the stall type or
structures, it may not be possible to create the pre- shall be of the wall-hung type with the rim at 17 inch-
ferred compartment by combining two existing es (430 mm) maximum above the oor or ground.
compartments, or physical conditions may not per- 605.3 Clear oor or ground space A clear oor
mit the full 60 inches (1525 mm) width. In these or ground space complying with 305 positioned for
cases, the authority having jurisdiction may per- forward approach shall be provided.2
mit a narrower compartment. In no case should a
605.4 Flush controls Flush controls shall be hand
width of less than 48 inches (1220 mm) be used.
operated or automatic. Hand-operated ush controls
The needs of a semi-ambulatory user are best shall comply with 309.2
served by a narrower, 36 inches max. (915 mm
Urinal note:
It should be understood that the ref-
erenced urinal is not intended to be
used by a wheelchair occupant for
the normal urination process. It is
intended for the drainage of bladder
bags, a function normally performed
in a water closet compartment, if
available. Where an accessible urinal
is required, it can serve as a childs
urinal. Urinals must be provided with
an elongated rim (ADAAG section
4.18.2). Although ADAAG does not
dene what constitutes an elongated
urinal, the Department of Justice de-
ferred to ANSI, which denes these
xtures as having a lip that protrudes
Figure 6-17 Wheelchair Accessible Toilet Stalls Door Swing In a minimum of 14 in. (356 mm) from
Source: CABO/ANSI A117.1-1992, Reprinted with permission
Chapter 6 Plumbing for People (or Persons) with Disabilities 117
the wall. Flush valve handles should not ex- 607 Bathtubs
ceed 48 inches (1220 mm) above the oor. 607.1 General Accessible bathtubs shall comply
606 Lavatories and Sinks with 607.
606.1 General Accessible lavatories and sinks shall 607.2 Clearance Clearance in front of bathtubs
comply with 606. shall extend the length of the bathtub and shall be
606.2 Clear oor or ground space A clear oor 30 inches (760 mm) wide minimum. A lavatory com-
or ground space complying with 305.3, positioned for plying with 606 shall be permitted at the foot end
forward approach, shall be provided. Knee and toe of the clearance. (See Figure 6-19-B4.21.2.) Where
clearance complying with 306 shall be provided.2 (See a permanent seat is provided at the head end of the
Figure 6-18-B4.20.3.2.) bathtub, the clearance shall extend a minimum of 15
inches (380 mm) beyond the wall at the head end of
EXCEPTIONS: the bathtub.
1. A parallel approach shall be permitted to a kitchen 607.3 Seat A permanent seat at the head end of the
sink in a space where a cook-top or conventional bathtub or a removable in-tub seat shall be provided.
range is not provided. Seats shall comply with 610.
2. The dip of the overow shall not be considered in 607.4 Grab bars Grab bars shall comply with 607.4
determining knee and toe clearances. and 609.
606.3 Height and clearances The front of lavato- 607.4.1 Bathtubs with permanent seats For
ries and sinks shall be 34 inches (865 mm) maximum bathtubs with permanent seats, grab bars complying
above the oor or ground, measured to the higher of with 607.4.1.1 and 607.4.1.2 shall be provided.
the xture rim or counter surface.
607.4.1.1 Back wall Two grab bars shall be provided
606.4 Faucets Faucets shall comply with on the back wall, one complying with 609.4 and the
309.2 Hand-operated, self-closing faucets shall re- other 9 inches (230 mm) above the rim of the bathtub.
main open for 10 seconds minimum. Each grab bar shall be 15 inches (380 mm) maximum
606.5 Bowl depth Sinks shall be 6 inches (165 from the head-end wall and 12 inches (305 mm) maxi-
mm) deep maximum. Multiple-compartment sinks mum from the foot-end wall.
shall have at least one compartment complying with
this requirement.
606.6 Exposed pipes and surfaces Water supply
and drain pipes under lavatories and sinks shall be
insulated or otherwise congured to protect against
contact. (See Figure 6-11-B4.20.3.1.) There shall be
no sharp or abrasive surfaces under lavatories and
sinks.
Lavatories and sinks note:
Conventional slab-type lavatories are available
to meet the dimensional requirements of A117.1,
since the dip of the overow can be ignored.
Built-in lavatories in countertops should be placed
as close as possible to the front edge of the counter- Figure 6-18 Clear Floor Space at
top to minimize the reach to the faucet. Single-lever Lavatories and Sinks
faucets are preferred, but where aesthetics or fear of Source: CABO/ANSI A117.1-1992, Reprinted with
permission
vandalism precludes their use, conventional quar-
ter-turn handles are a good choice. Avoid faucets
that require nger dexterity for grasping or twisting. 607.4.1.2 Foot-end wall A grab bar 24 inches (610
mm) long minimum shall be provided on the foot-end
Both hot and cold water pipes, as well as drain wall at the front edge of the bathtub.
pipes that are in the vicinity of the designated
clear oor space under the xture, must be con- 607.4.2 Bathtubs without permanent seats For
cealed or insulated to protect wheelchair users who bathtubs without permanent seats, grab bars com-
have no functioning sensory nerves. Insulation is plying with 607.4.2.1 through 607.4.2.3 shall be
not required on pipes beyond possible contact. provided.
118 ASPE Plumbing Engineering Design Handbook Volume 1
607.4.2.1 Back wall Two grab bars shall be provided 607.6 Shower unit A shower spray unit shall
on the back wall, one complying with 609.4 and the be provided, with a hose 59 inches (1500 mm) long
other 9 inches (230 mm) above the rim of the bathtub. minimum, that can be used as a xed shower head
Each grab bar shall be 24 inches (610 mm) long mini- and as a hand-held shower. If an adjustable-height
mum and shall be 24 inches (610 mm) maximum from shower head on a vertical bar is used, the bar shall
the head-end wall and 12 inches (305 mm) maximum not obstruct the use of grab bars.
from the foot-end wall. 607.7 Bathtub enclosures Bathtub enclosures
607.4.2.2 Foot-end wall A grab bar 24 inches (610 shall not obstruct controls or transfer from wheel-
mm) long minimum shall be provided on the foot-end chairs onto bathtub seats or into bathtubs. Bathtub
wall at the front edge of the bathtub. enclosures shall not have tracks on the rim of the
607.4.2.3 Head-end wall A grab bar 12 inches (305 bathtub.
mm) long minimum shall be provided on the head-end Bathtub note:
wall at the front edge of the bathtub. A xed seat at the head of the tub adds safety and
607.5 Controls Controls, other than drain stoppers, convenience for transfer purposes, as does the 17
shall be on an end wall. Controls shall be between the to 19 inches (432 to 483 mm) rim height. The rim
bathtub rim and grab bar, and between the open height that is more in line with the tub seat does
side of the bathtub and the midpoint of the width of not require the use of a deeper tub; it is better to
the bathtub. Controls shall comply with 309.4.2 (See use a tub with a deeper apron or use a tile ller.
Figure 6-20-B4.21.4.)
Due to the probable lack of maneuverability of the user, inches (915 mm) wide minimum. (See Figure 6-21-
it is recommended that the plumbing engineer specify B4.22.2.1.)
a temperature and/or pressure-balanced, water-blend- 608.2.2 Standard roll-in type shower compart-
ing valve with temperature-limit stops. ments Roll-in type shower compartments shall
608 Shower Compartments be 30 inches (760 mm) wide minimum by 60 inches
608.1 General Accessible shower compartments (1525 mm) deep minimum, clear inside dimension,
shall comply with 608. measured at the centerpoint of opposing sides and
shall have a minimum 60 inches (1220 mm) wide entry
608.2 Size and clearances on the face of the shower. A 30 inches (760 mm) wide
608.2.1 Transfer-type shower compart- minimum by 60 inches (1525 mm) long minimum
ments Transfer-type shower compartments shall clearance shall be provided adjacent to the open face of
be 36 inches (915 mm) wide by 36 inches (915 mm) the shower compartment. A lavatory complying with
deep inside nished dimension, measured at the 606 shall be permitted at the end of the clear space,
centerpoint of opposing sides, and shall have a mini- opposite the shower-compartment side where shower
mum 36 inches (915 mm) wide entry on the face of controls are positioned. (See Figure 6-22-B4.22.2.2.)
the shower compartment. The clearance in front of 608.2.3 Alternate roll-in type shower compart-
the compartment shall be 48 inches (1220 mm) long ments Alternate roll-in shower compartments shall
minimum measured from the control wall and 36
The shower compartment with inside nish dimen- 609.2 Size Grab bars shall have a circular cross
sions of 36 inches by 36 inches (915 mm by 915 section with a diameter of 1 in. (32 mm) minimum
mm) has been designated a transfer-type compart- and 2 inches (51 mm) maximum, or shall provide
ment to indicate that wheelchair users can trans- equivalent grasp ability complying with 505.7.1.2
fer from their chair to the required seat. These 609.2.1 Noncircular cross sections Grab bars
dimensions will allow a person of average size to with other shapes shall be permitted, provided they
reach and operate the controls without difculty, have a perimeter dimension of 4 inches (100 mm) min-
while providing reasonable knee space for larger imum and 4.8 inches (160 mm) maximum and edges
users. A transfer-type shower is also intended to having an 8 inches (3.2 mm) minimum radius.
serve persons without disabilities so a folding seat
would provide more space for a standing person. 609.3 Spacing The space between the wall and
Temperature may be limited to 105 to 110F (40.5 the grab bar shall be 1 inches (38 mm). The space
to 43C), depending on local code requirements. between the grab bar and objects below and at the
ends shall be 1 inches (38 mm) minimum. The space
609 Grab Bars between the grab bar and projecting objects above
609.1 General Grab bars in accessible toilet or shall be 15 inches (355 mm) minimum. (See Figure
bathing facilities shall comply with 609. 6-24-B4.24.2.1.)
EXCEPTION: The space between the grab bars and is a safety clearance to prevent injuries from arms
shower controls, shower ttings, and other grab bars slipping through the opening. This clearance also
above shall be 1 inches (38 mm) minimum. provides a minimum space for gripping.
609.4 Position of grab bars Grab bars shall be Grab bars that are wall mounted do not affect the
mounted in a horizontal position, 33 inches (840 mm) measurement of required clear oor space where the
minimum and 36 inches (915 mm) maximum above space below the grab bar is clear and does not present
the oor. a knee space encroachment.
610 Seats
610.1 General Seats in accessible bathtubs and
shower compartments shall comply with 610.
610.2 Bathtub seats A removable in-tub seat shall
be 15 inches (380 mm) minimum and 16 inches (405
mm) deep maximum, and shall be capable of secure
placement. A permanent seat shall be 15 inches (380
mm) deep minimum and be positioned at the head
end of the bathtub. The top of the seat shall be 17
inches (430 mm) minimum and 19 inches (485 mm)
maximum above the bathroom oor.
610.3 Shower compartment seats Where a seat
is provided in a roll-in shower compartment, it shall be
a folding type and shall be on the wall adjacent to the
Figure 6-24 Size and Spacing of controls. Seats shall be L-shaped or rectangular. The
Grab Bars
top of the seat shall be 17 inches (430 mm) minimum
Source: CABO/ANSI A117.1-1992, Reprinted
with permission and 19 inches (485 mm) maximum above the bath-
room oor. In a transfer-type shower, the seat shall
extend from the back wall to a point within 3 inches
EXCEPTION: Height of grab bars on the back (75 mm) of the compartment entry. In a roll-in type
wall of a bathtub shall comply with 607.4.1.1 and shower, the seat shall extend from the control wall
607.4.2.1. to a point within 3 inches (75 mm) of the minimum
609.5 Surface hazards Grab bars and any wall or required seat wall width.
other surfaces adjacent to grab bars shall be free of 610.3.1 Rectangular seats The rear edge of a rect-
sharp or abrasive elements. Edges shall have a radius angular seat shall be 2 inches (64 mm) maximum
of 8 inches (3 mm) minimum. from the seat wall, and the front edge 15 inches (380
609.6 Fittings Grab bars shall not rotate within mm) minimum and 16 inches (405 mm) maximum
their ttings. from the seat wall. In a transfer-type shower, the
side edge of a rectangular seat shall be 1 inches
609.7 Installation Grab bars shall be installed in (38 mm) maximum. In a roll-in type shower, the side
any manner that provides a gripping surface at the edge of a rectangular seat shall be 1 inches (38 mm)
locations specied in this standard and that does not maximum from the control wall.
obstruct the clear oor space.
610.3.2 L-shaped seats The rear edge of an L-
609.8 Structural strength Allowable stresses in shaped seat shall be 2 in. (64 mm) maximum from
bending, shear, and tension shall not be exceeded for the seat wall, and the front edge 15 inches (380 mm)
materials used where a vertical or horizontal force of minimum and 16 inches (405 mm) maximum from
250 pounds (113.5 kg) is applied at any point on the the seat wall. The rear edge of the L portion of the
grab bar, fastener mounting device, or supporting seat shall be 1 inches (38 mm) maximum from the
structure. wall and the front edge shall be 14 inches (355 mm)
Grab bars note: minimum and 15 inches. (380 mm) maximum from
Many people with disabilities rely heavily upon grab the wall. The end of the L shall be 22 inches (560
bars to maintain balance and prevent serious falls. mm) minimum and 23 inches (585 mm) maximum
Many people brace their forearms between supports from the main seat wall. (See Figure 6-25-B4.22.3.)
and walls to give them more leverage and stability in 610.4 Structural strength Allowable stresses in
maintaining balance or for lifting. The grab bars clear- bending, shear, and tension shall not be exceeded for
ance of 1 inches (38 mm) required in this standard materials used where a vertical or horizontal force of
Chapter 6 Plumbing for People (or Persons) with Disabilities 123
System Fundamentals). While this reduces the (B) How much hot water is required to provide 80
amount of hot water required it does not decrease gph (0.084 L/s) of 110F (43C) mixed water with
the energy required to heat the water. Many 125F (51.5C) hot water and 75F (23.9C) cold
energy codes and standards for new buildings water?
require the domestic hot water system be set 110 75 = .70 or 70% hot water
at 110F under the impression that this will 125 75
80 gph 0.70 = 56 gph of 125F hot water
automatically reduce energy in direct proportion (0.084 L/s 0.70 = 0.059 L/s of 51.5C hot water)
to the reduced temperature differential (delta
T). It is important to note that setting a water As shown, the reduction in domestic-water tempera-
heater below 120F to avoid blending may allow ture, in itself, does not necessarily result in a reduction
Legionella bacteria to grow inside the domestic in energy input related to the water consumed.
hot water tank. Also, if the building is provided
with a kitchen dishwasher requiring 180F water, 3. Reduce Fixture Flow Rates
a booster heater will need to be sized carefully to The Energy Policy Act (EPACT) of 1992 set
adequately function at the increased delta T. This maximum water usages for specic xtures (e.g.
is due to the reduction of the building domestic 1.6 gallons per ush for water closets). Reduced
water-system temperature. flow rates result in less water needing to be
pumped and heated, smaller pipe sizes, and less
The temperature, after mixing two or more heat loss from piping, consequently saving energy.
volumes (or ows) of water is calculated using Fixture ow rates vary depending upon the supply
the following equation: tting design and water pressure. Manufacturers
Equation 7-1 test results have shown that ows for lavatories
Q1 t1 + Q2 t2 and showers can be quite high, making them
tm =
Q1 + Q2 prime candidates for fixture-flow reduction.
where: Providing automatic ow-control ttings can
tm = Temperature of mixture reduce xture ow rates. On lavatories the type
t1 = Temperature of ow Q1 of faucet and spout usually dictates the location
t2 = Temperature of ow Q2
of these ttings. In showers, the type of head and
Q1 = Cold water, gpm (L/s)
Q2 = Hot water, gpm (L/s) arm determines the tting location. After being
tted with a ow-control device, reduced ow
Example 7-1 rates of one gallon per minute or less are usually
What is the temperature of 45 gpm (2.84 L/s) of 155F seen in lavatories and 3 gallons per minute or
(68.5C) water mixed with 55 gpm (3.47 L/s) of 75F less for showers.
(23.9C) water?
Figure 7-1 provides a way to translate xture
45 155 + 55 75 = 111F ow rate to annual consumption and is useful
45 + 55
in determining the most energy efcient design
in SI units:
ow rate. By varying the percent of hot water at
the xture, annual energy consumption can be
( 2.84 2.84
68.5 + 3.47 23.9 = 44C
+ 3.47 ) predicted.
The ratio (%) of hot water required to be mixed with Example 7-3
cold water to provide a mixed water requirement is
Faucet use at 3.25 gal (12.3 L) of 150F (66C) hot
determined using the following equation:
water per day with a 100% faucet ow rate equates
Equation 7-2 to an annual energy use of 800 103 Btu (844 103
t t kJ) per year. A 67% ow rate reduces energy use to
Ratio HW = tm t 1
2 1 475 103 Btu (507 103 kJ) per year, and a 33% ow
Example 7-2 rate reduces energy use to 225 103 Btu (237.4 103
kJ) per year or a 62% reduction from full faucet ow
(A) How much hot water is required to provide 80 rate.
gph (0.084 L/s) of 110F (43C) mixed water with
Figure 7-1 can be used as a design tool for many
155F (68.5C) hot water and 75F (23.9C) cold
purposes, some of which are to predict energy
water?
consumption, anticipated utility costs, and
110 75 = .44 or 44% hot water
155 75 payback calculations for xture replacement.
80 gph 0.44 = 35 gph of 155F hot water Manufacturers of ow-control devices describe
(0.084 L/s 0.44 = 0.037 L/s of 68.5C hot water) in greater detail their design and installation
requirements. The installation of this water-
Chapter 7 Energy and Resource Conservation in Plumbing Systems 127
Table 7-1 Energy Savings Chart for Steel Hot Water Pipes and Tanks
T Hot Water Tanks,
F (C) Pipe Size, in. (mm) Btu/h/ft2 (kJ/h/m2)
1 1 1 2 2 w/ w/o
(12.7) (19.1) (25.4) (31.8) (38.1) (50.8) (63.5) Insulation Insulation
40 (4.4) 14 (48.44) 17 (58.8) 21 (72.7) 26 (90.0) 29 (100.3) 35 (121.1) 42 (145.3) 6 (68.1) 57 (647.3)
45 (7.2) 16 (55.36) 20 (69.2) 24 (83.0) 30 (103.8) 33 (114.2) 41 (141.9) 48 (166.1) 6 (68.1) 65 (738.2)
50 (10.0) 18 (62.28) 22 (76.1) 27 (93.4) 34 (117.6) 38 (131.5) 47 (162.6) 55 (190.3) 7 (79.5) 73 (829.1)
55 (12.8) 20 (69.20) 25 (86.5) 31 (107.3) 38 (131.5) 42 (145.3) 52 (179.9) 62 (214.5) 7 (79.5) 83 (942.6)
60 (13.6) 23 (79.58) 28 (96.9) 35 (121.1) 42 (145.3) 48 (166.1) 58 (200.7) 69 (238.7) 9 (102.2) 92 (1044.8)
65 (18.3) 25 (86.50) 31 (107.3) 38 (131.5) 47 (162.6) 53 (183.4) 65 (224.9) 77 (266.4) 9 (102.2) 102 (1158.4)
70 (21.1) 28 (96.88) 34 (117.6) 42 (145.3) 52 (179.9) 58 (200.7) 71 (245.7) 84 (290.6) 10 (113.6) 112 (1272.0)
75 (23.9) 30 (103.8) 36 (124.6) 46 (159.2) 56 (193.8) 64 (221.4) 78 (269.9) 91 (314.9) 11 (124.9) 122 (1385.6)
80 (26.7) 33 (114.2) 41 (141.9) 50 (173.0) 61 (211.1) 69 (238.7) 84 (290.6) 99 (342.5) 11 (124.9) 132 (1499.1)
85 (28.4) 36 (124.6) 44 (152.2) 54 (186.8) 67 (231.8) 74 (256.0) 91 (314.9) 107 (370.2) 12 (136.3) 142 (1612.7)
90 (32.2) 38 (131.5) 47 (162.6) 58 (200.7) 72 (249.1) 80 (276.8) 98 (339.1) 116 (401.4) 12 (136.3) 154 (1749.0)
95 (35.0) 42 (145.3) 51 (176.5) 62 (214.5) 77 (266.4) 86 (297.6) 105 (363.3) 124 (429.0) 14 (159.0) 164 (1862.5)
100 (37.8) 45 (155.7) 54 (186.8) 66 (228.4) 82 (283.7) 93 (321.8) 113 (391.0) 133 (460.2) 14 (159.0) 175 (1987.5)
105 (38) 47 (162.6) 58 (200.7) 72 (249.1) 87 (301.0) 98 (339.1) 120 (415.2) 141 (487.9) 15 (170.4) 187 (2123.8)
110 (43) 51 (176.5) 62 (214.5) 75 (259.5) 93 (321.8) 104 (359.8) 128 (442.9) 150 (519) 16 (181.7) 198 (2248.7)
115 (46) 54 (186.8) 65 (224.9) 80 (276.8) 98 (339.1) 110 (380.6) 135 (467.1) 159 (550.1) 16 (181.7) 210 (2385.0)
120 (49) 56 (193.8) 69 (238.7) 85 (294.1) 104 (359.8) 117 (404.8) 143 (494.8) 169 (584.7) 17 (193.1) 222 (2521.3)
Source: San Diego Gas & Electric Co.
Notes:
1. Savings are in Btu/h/linear ft. (kJ/h/linear m), unless otherwise indicated.
2. Figures are based on an assumption of 1 in. (25.4 mm) of insulation.
3. T = to ta where to = Hot water circulating temperature and ta = Air temperature surrounding piping system.
Table 7-2 Energy Savings Chart for Copper Hot Water Pipes
T Pipe Size, in. (mm)
F (C) 1 1 1 2 2 3
(12.7) (19.1) (25.4) (31.8) (38.1) (50.8) (63.5) (76.2)
40 (4.4) 8 (27.68) 12 (41.5) 14 (48.4) 17 (58.8) 20 (69.2) 25 (86.5) 30 (103.8) 35 (121.1)
45 (7.2) 10 (34.6) 13 (45.0) 16 (55.5) 20 (69.2) 23 (79.6) 29 (100.3) 35 (121.1) 40 (138.4)
50 (10.0) 12 (41.5) 15 (51.9) 19 (65.7) 23 (79.6) 26 (90.0) 33 (114.2) 40 (138.4) 46 (159.2)
55 (12.8) 13 (45.0) 17 (58.8) 21 (72.7) 26 (90.0) 30 (103.8) 38 (131.5) 45 (155.7) 52 (179.9)
60 (13.6) 15 (51.9) 20 (69.2) 24 (83.0) 29 (100.3) 34 (117.6) 42 (145.3) 51 (176.5) 58 (200.7)
65 (18.3) 16 (55.4) 21 (72.7) 27 (93.4) 32 (110.7) 37 (128.0) 47 (162.6) 56 (193.8) 65 (224.9)
70 (21.1) 18 (62.3) 24 (83.0) 30 (103.8) 35 (121.1) 41 (141.9) 52 (180.0) 62 (214.5) 71 (245.7)
75 (23.9) 20 (69.2) 26 (90.0) 33 (114.2) 39 (134.9) 44 (152.2) 56 (193.8) 67 (231.8) 76 (263.0)
80 (26.7) 21 (72.7) 28 (96.7) 35 (121.1) 42 (145.3) 49 (169.5) 61 (211.1) 73 (252.6) 85 (294.1)
85 (29.4) 22 (76.1) 31 (107.3) 38 (131.5) 45 (155.7) 53 (183.4) 66 (228.4) 79 (273.3) 92 (318.3)
90 (32.2) 24 (83.0) 33 (114.2) 41 (141.9) 49 (169.5) 57 (197.2) 71 (245.7) 85 (294.1) 99 (342.5)
95 (35.0) 26 (90.0) 36 (124.6) 44 (152.2) 53 (183.4) 61 (211.1) 76 (263.0) 91 (314.9) 106 (366.7)
100 (37.8) 28 (96.7) 38 (131.5) 48 (166.1) 57 (197.2) 65 (224.9) 82 (283.7) 98 (339.1) 113 (391.0)
105 (38) 30 (103.8) 41 (141.9) 51 (176.5) 60 (207.6) 70 (242.2) 87 (301.0) 104 (359.8) 121 (418.7)
110 (43) 32 (110.7) 43 (148.8) 54 (186.8) 65 (224.9) 74 (256.0) 93 (321.8) 111 (384.1) 128 (442.9)
115 (46) 34 (117.6) 46 (159.2) 57 (197.2) 68 (235.3) 78 (269.9) 98 (339.1) 118 (408.3) 136 (470.6)
120 (49) 36 (124.6) 49 (169.5) 61 (211.1) 72 (249.1) 83 (287.2) 104 (359.8) 125 (432.5) 144 (498.2)
Source: San Diego Gas & Electric Co.
Notes:
1. Savings are in Btu/h/linear ft (kJ/h/linear m).
2. Figures are based on an assumption of 1 in. (25.4 mm) of insulation.
3. T = to ta where to = Hot water circulating temperature and ta = Air temperature surrounding piping system.
Equation 7-4 and tenants to benet from lower utility costs.
Motor kW off hours electric rate ($/kWh) Power companies encourage their commercial
= total savings ($) customers to purchase power during off peak
hours in hopes of attening or evening out the
6. Consume Off-Peak Power demand on their generating equipment. Some
One of a plumbing engineers responsibilities is utility companies not only offer lower rates for
to size the domestic water-heating equipment electricity purchased during off- and semi-peak
to meet the needs of the buildings occupants in periods but in many instances have no customer
the most energy efcient manner. While using demand charges. The plumbing engineer can
off-peak power to heat and circulate water does obtain electric-rate schedules from the utility
not change the number of British thermal units serving the site and observe the off-peak periods
(Btu) required, it does allow the buildings owner to program the operation of domestic water-
Chapter 7 Energy and Resource Conservation in Plumbing Systems 129
alternate energy sources should be within 4. Heat pumps and heat reclamation systems
reasonable proximity to the resource. Typical 5. Heat from wastewater
applications include industrial plants with When considering heat recovery, it is important
large volumes of burnable materials such to determine if the hot water demand justies the
as trash, paper, scrap wood, plastics, etc. equipment and maintenance costs, and if the heat
A solid-waste incinerator system typically recovered is sufcient to serve as a heat source.
consists of a waste-disposal plant with a Facilities that typically have the proper blend of
conveyer, loading system, boiler, ash-disposal demand and waste heat are hospitals, military
equipment, heat exchanger, insulated piping, bases, and industrial facilities.
circulating pump, and controls.
A. Air Conditioning and Commercial
C. Geothermal Energy
Refrigeration
Geothermal energy is heat from the earth. In
Systems with air- or water-cooled or
states where this form of energy is believed
evaporative condensers reject heat from air
to be available at reasonable depths, the U.S.
conditioning and refrigeration systems that
Department of Energy (DOE) is supporting
can be reclaimed.
various state energy commissions in their
Within the refrigerant cycle there is a
funding of geothermal assessment programs.
condenser that rejects heat while an evaporator
The temperature of the available liquid or gas
creates a cooling effect. For example, for
(created when water ows through heated,
every 1 Btu/h of cooling effect produced by
permeable rock) and the cost of retrieval
a 40F evaporator, a 105F condensing unit
dictate the viability of geothermal energy.
rejects 1.15 Btu/h of heat. Systems with an
Some geothermal energy uses include steam
air-cooled or evaporative condensor can be
in the generation of electricity, hot water
supplemented with a heat exchanger in the
with a minimum temperature of 150F for
compressors hot gas discharge line to capture
building domestic hot water systems, and
the rejected heat. (Refer to Figure 7-2.)
industrial parks for space and water heating
Systems with water-cooled condensers can
needs. Three prime areas of concern must
be supplemented with a heat exchanger in
be addressed when planning and developing
the hot water return line from the condenser
geothermal energy:
to the cooling tower. (Refer to Figure 7-
1. Competitive Institutional Processes 3.) System efficiency can be improved by
2. Adequate Temperature and Flow Rate providing a storage tank with a tube bundle.
(Refer to Figure 7-4.)
3. Thermal Loads To Make the System
An advantage of the system shown in Figure
Economically Viable
7-4 is that simultaneous use of the domestic
A geothermal energy system typically consists water and refrigeration systems does not
of production and disposal wells, water-to- need to occur for heat recovery. Another
water heat exchangers [usually shell-and-tube advantage of the system shown in Figure 7-
type, two are requiredone for operation 4 is when there is an insufcient amount of
while the other is being cleaned of deposits], heat rejected, a backup water heater can be
insulated piping, a circulating pump, and used to bring the water in the storage tank to
a control system. The plumbing engineer the proper design temperature. The backup
should consult with the state energy ofce heater can operate on fossil fuel, electricity,
(Department of Energy or the Geothermal steam, or may be tted with a tube bundle
Resources Council) for resource information utilizing hot water.
to apply this high-capital, low-operating-cost, B. Steam Condensate
alternate energy source. When steam is used as a source for space
4. Heat Recovery heating, water heating, or process work there
Heat recovery is the capture and reuse of energy is generally steam condensate. The heat
that would normally be lost from a facility. It could content of the condensate can be captured
be in the form of a liquid or a gas. Common waste and reused for heating with the use of a heat
heat sources are: exchanger. Laundries are a prime example of
1. Heat rejected from air conditioning and com- facilities where heat reclaimed from steam
mercial refrigeration processes condensate can be put to use in heat recovery.
2. Heat reclaimed from steam condensate It is essential to select a system with adequate
3. Heat generated by cogeneration plants storage to compensate for uctuations in
132 ASPE Plumbing Engineering Design Handbook Volume 1
reduction in water consumption. There are many for non-potable applications such as landscape
different types of toilets and urinals and each has irrigation, cooling tower make up, toilet ushing,
its own benets, which will be discussed later in and re protection.
this chapter. Graywater is typically collected from showers,
Additional fixtures whose flow rates can be tubs, lavatories, washing machines, and drinking
reduced are showers and faucets. In addition to fountains. It contains a minimal amount of
applying ow-restrictor ttings, as previously contamination and is reused in certain landscape
discussed, metered faucets can be installed which applications such as subsurface irrigation of
provide water for a pre-determined time and lawns, owers, trees, and shrubs, but should
then automatically close. The Americans with not be used for vegetable gardens because of the
Disabilities Act species that these faucets must potential absorption of cleaning and washing
operate for at least 10 seconds. chemicals. Similar to rainwater harvesting,
Electronic sensor controls can be used on graywater is collected, stored, and ltered prior
toilet and urinal ush valves and faucets. They to use. A graywater storage container should be
reduce water consumption and are often used tted with overow protection that is connected
in prisons, military barracks, sporting facilities, to the sanitary sewer system in the event the
and hospitals. Batteries or hard wiring can power amount of water collected is more than the
these controls. Battery controlled valves and amount of water being consumed, a distribution
faucets are typically used for renovation projects pipe becomes clogged, or collected water is not
while new construction is hard wired. used in a timely manner. If graywater is stored
for extended periods of time it often produces an
3. Alternate Sources of Fresh Water offensive smell.
Rainwater harvesting is the collection, storage,
treatment, and use of rainwater. Harvested Water-Management Equipment
water can be used for irrigation, non-potable, As previously stated, toilets and urinals account for
and potable uses. A rainwater harvesting system almost half of a typical buildings water consumption.
typically starts with a catch area that collects The U.S. Environmental Protection Agency (EPA)
rainwater, usually a buildings roof. To ensure has determined that 4.8 billion gallons of water are
potential contaminants and pollutants do not ushed each day. Replacing or retrotting water clos-
enter the systems storage tank, a wash system ets, urinals, showerheads, and faucets with low ow
is installed which diverts the initial portion of the versions can considerably lower a buildings water
rainfall away from the storage tank while cleaning consumption.
the catch area. A screen is usually installed in the 1. Water Closets and Urinals
catch area to keep out debris. Piping routes the Ultra low ow (ULF) water closets consume 1.6
collected rainwater to a storage tank, which can gallons per ush (gpf) and are available in three
be located indoors, outdoors, aboveground, or different classications:
underground. It is important to provide a lid on A. Tank Type
the storage tank to keep light out to discourage B. Flush Valve
algae growth. If the collected water is intended to C. Specialties
be the sole source of water for the building, the
storage tank should be sized based on a 30-year While the problems associated with ULF toilets
rainfall event. Water is typically delivered to the when they first became available have been
building through the use of a domestic water corrected, some low-cost models continue to
booster pump system, and nal water treatment maintain poor performance.
may be needed depending upon the application A. Tank Type
and quality of water collected. Water is drained from this water closet
by gravity and is most commonly used in
4. Reclaimed and Graywater
residential applications. Prior to ULF models
Reclaimed water and graywater collection
these xtures consumed 3.5 gpf. A low-cost
systems can be used to reduce the amount
method of conserving water in these earlier
of domestic water consumed by a building.
models and in todays ULF is using a rell
Wastewater treatment plants provide reclaimed
diverter. When a tank type water closet is
or recycled water to buildings through a second
ushed, water starts to rell the tank as it
municipal water system where two water lines
is emptying. The time elapsed between the
enter a building. One line is used to deliver
open and closed position of the apper, allows
potable water for domestic use and a second to
excess water to ow through the bowl, into
provide treated wastewater that can be used
136 ASPE Plumbing Engineering Design Handbook Volume 1
the bowl, and consequently, the drain. While 2. Showerheads and Faucets
relling the tank, this water is wasted. A The 1992 Energy Policy Act set the maximum
diverter keeps this water in the tank saving ow rates for showerheads and faucets at 2.5
one-half to 1 gallon when installed on older gallons per minute. Prior to the Energy Policy
toilets and a gallon on ULF models. Act, showerhead flow rates were between 3
B. Flush Valve gallons per minute and 7 gallons per minute.
Flush-valve water closets use the buildings Water conserving showerheads incorporate a
water pressure to exert a force when operating. more narrow spray jet and introduce a greater
They typically require 25 to 40 psig to operate volume of air when compared to conventional
and are most commonly used in commercial heads. Additional measures that can be taken
buildings. Older, non-ULF models can be are temporary stop levers that control the shower
retrotted by adjusting the ush valve, but valve to reduce or inhibit water ow when used.
care must be used to not overly constrain This feature would be used while a person is
the valve causing it to malfunction. Early soaping or shampooing him or herself. The use
closure devices also can be used to cause the of ow restrictors in conventional showerheads
ush valve to stop the ow of water sooner is not recommended. They typically restrict the
than normal, limiting the amount of water showerhead too much, providing poor water
discharged. pressure from the head.
(B)
Figure 8-7 Impingement Attack Figure 8-9 (A) Plug-Type Dezincication
(B) Layer-Type Dezincication
Chapter 8 Corrosion 143
current ow due to the potential difference between As an example, considering a pipe-to-soil potential
the anode (metal) and the cathode (structure). A of 0.85 V as protection for a steel pipeline, the driving
corrosion cell or battery is created, and current ows potential of zinc anodes is 0.25 V and for magnesium
from the corroding anode material through the soil is 500 A-h/lb (1795 C/kg). The actual life of anodes
to the cathode or protected structure. Hence the gal- of a given weight at a known current output can be
vanic anode is deliberately caused to waste itself to calculated using the following formulas:
prevent corrosion of the protected structure. Because Equation 8-3
the galvanic anode system relies on the difference
57.08 w
in voltage between two metals, which in most cases LM = i
is limited to 1.0 V or less, the current generated by
the anodes is usually low (approximately 0.1 to 0.5 Equation 8-4
A per anode). Lz = 38.2 w
Galvanic anode systems are usually used for i
structures having small current requirements, such where:
as well-coated, small-diameter pipes; water heaters; LM = Life of magnesium anode (yr)
sewage lift stations; some offshore structures; and Lz = Life of zinc anode (yr)
structures in congested areas where currents must w = Weight of anode, lb (kg)
i = Output of anode (mA)
be kept low to avoid detrimental effects on other
structures. Galvanic anodes may be installed in banks The controlling factor for current output of zinc
at specic locations. They are, however, usually dis- and magnesium anodes is soil resistivity. When soil
tributed around protected structures because of their resistivity is known or determined, then the current
limited current output. output of variously sized anodes for either magnesium
or zinc can be estimated as follows:
of cathodic protection current required. Care must (Phosphate additives to potable water are limited or
be taken to avoid short-circuiting (bypassing) the prohibited in some jurisdictions.)
insulation, or protection can be destroyed. Test sta- In closed-loop cooling systems, and systems in-
tions are wires attached to the underground structure volving heat-exchange surfaces, it may not be possible
(pipeline or tank) to provide electrical contact for the to use lm-forming treatment because of detrimental
purpose of determining protection effectiveness. Test effects on heat transfer. In these cases, inhibitors are
stations are also used to make bonds or connections used; these control corrosion by increasing polariza-
between structures when required to mitigate stray- tion of anodic or cathodic surfaces and are called
current effects. anodic or cathodic inhibitors, respectively. The
Costs of cathodic protection Corrosion of under- anodic or cathodic surfaces are covered, preventing
ground, ferrous metal structures can be economically completion of the corrosion cell by elimination of
controlled by cathodic protection. Cathodic protec- either the anode or cathode.
tion costs are added to the initial investment since When water treatment or inhibitors are used, a
they are a capital expense. To be economically sound, testing program must be established to ensure that
the spending of the funds must yield a fair return over proper additive levels are maintained. In some cases,
the expected life of the facility. continuous monitoring is required. Also, environmen-
To protect a new facility requires an initial in- tal considerations in local areas must be determined
crease of perhaps 10% in capital investment. Payout before additives are used or before any treated water
time is usually 10 to 15 years; thereafter, appreciable is discharged to the sanitary sewer or storm drainage
savings accrue due to this investment, which prevents system.
or reduces the frequency of leaks. Effective corrosion
GLOSSARY
control through the application of cathodic protec-
tion reduces the leak frequency for a structure to the Active The state in which a metal is in the process
minimum with minimum cost. of corroding.
Cathodic protection systems must be prop- Active potential The capability of a metal cor-
erly maintained. Rectier outputs must be checked roding based on a transfer of electrical current.
monthly. Changes or additions to the protected struc-
ture must be considered to see if changes or additions Aeration cell An oxygen concentration cell an
to the cathodic protection system are required. An- electrolytic cell resulting from differences in the
nual inspections by a corrosion engineer are required quantity of dissolved oxygen at two points.
to ensure that all malfunctions are corrected, and Amphoteric corrosion Corrosion usually caused
cathodic protection continues unhampered. by a chemical reaction resulting from a concentration
Inhibitors (Water Treatment) of alkaline products formed by the electrochemical
process. Amphoteric materials are those materials
Plant utility services such as boiler feed water, con-
that are subject to attack from both acidic and alkaline
densate, refrigerants, and cooling water require the
environments. Aluminum and lead, commonly used
addition of inhibitors or water treatment. Boiler feed
in construction, are subject to amphoteric corrosion
water must be treated to maintain proper pH control,
in highly alkaline environments. The use of cathodic
dissolved solid levels, and oxygen content. Condensate
protection in highly alkaline environments, therefore,
requires treatment to control corrosion by oxygen and
intensies the formation of alkaline byproducts.
carbon dioxide. Brine refrigerants and cooling water
in closed-loop circulating systems require proper Anaerobic Free of air or uncombined oxygen.
inhibitors to prevent corrosion. Anion A negatively charged ion of an electrolyte
Water treatment may consist of a simple adjust- that migrates toward the anode under the inuence
ment of water hardness to produce naturally forming of a potential gradient.
carbonate films. This carbonate film, if properly
adjusted, will form to a controlled thickness just suf- Anode Negative in relation to the electrochemical
cient to prevent corrosion by keeping water from process. The electrode at which oxidation or
contacting the metal surface. In cooling water, where corrosion occurs.
hardness control is not practical, inhibitors or lm- Anodic protection An appreciable reduction in
forming compounds may be required. corrosion by making a metal an anode and maintain-
Sodium silicate and sodium hexameta-phosphate ing this highly polarized condition with very little
are examples of lm-forming additives in potable current ow.
water treatment. A tight, thin, continuous lm of
Cathode Positive in relation to the electro-
silica (water glass) or phosphate adheres to the
chemical process. The electrode where reduction (and
metal surface, preventing pipe contact with the water.
practically no corrosion) occurs.
152 ASPE Plumbing Engineering Design Handbook Volume 1
been adopted by the Electrochemical Society and Impingement attack Localized erosion-corrosion
the National Bureau of Standards; it is employed in caused by turbulence or impinging ow at certain
this publication. The opposite convention of G. N. points.
Lewis has been adopted by the American Chemical Inhibitor A substance that, when added in small
Society.) amounts to water, acid, or other liquids, sharply re-
Electronegative potential A potential corres- duces corrosion.
ponding in sign to those of the active or anodic Ion An electrically charged atom or group of atoms
members of the e.m.f. series. Because of the known as radicals.
existing confusion of sign in the literature, it is sug-
gested that anodic potential be used whenever Natural drainage Drainage from an underground
electronegative potential is implied. (See electro- metallic structure to a more negative structure, such
motive force series.) as the negative bus of a trolley substation.
Electropositive potential A potential correspond- Noble potential A potential substantially cathodic
ing in sign to potentials of the noble or cathodic compared to the standard hydrogen potential.
members of the e.m.f. series. It is suggested that Open-circuit potential The measured potential
cathodic potential be used whenever electroposi- of a cell during which no signicant current ows in
tive potential is implied. (See electromotive force the external circuit.
series.)
Overvoltage The difference between the potential
Flash attack A heavily etched, dark surface re- of an electrode at which a reaction is actively taking
sulting from contaminated passivating solutions with place and another electrode at equilibrium for the
high chloride levels. same reaction.
Forced drainage Drainage applied to underground Oxidation Loss of electrons, as when a metal goes
metallic structures by means of an applied e.m.f. or from the metallic state to the corroded state. Thus,
sacricial anode. when a metal reacts with oxygen, sulfur, etc., to form
Galvanic cell A cell consisting of two dissimi- a compound as oxide, sulde, etc., it is oxidized.
lar conductors in contact with an electrolyte, or Oxygen concentration cell A galvanic cell caused
two singular conductors in contact with dissimilar by a difference in oxygen concentration at two
electrolytes. More generally, a galvanic cell points on a metal surface.
converts energy liberated by a spontaneous
chemical reaction directly into electrical energy. Passive The state of a metal when its behavior is
much more noble (resists corrosion) than its
Galvanic corrosion Corrosion that is increased position in the e.m.f. series would predict. This is a
because of the current caused by a galvanic cell surface phenomenon.
(sometimes called couple action).
pH A measure of the acidity or alkalinity of a solu-
Galvanic series A list of metals arranged ac- tion (from 0 to 14). A value of seven (7) is neutral;
cording to their relative corrosion potential in some low numbers (0-6) are acidic, large numbers (8-14)
specic environment; sea water is often used. are alkaline.
General corrosion Corrosion in a uniform Pitting Localized light corrosion resulting in deep
manner. penetration at a small number of points.
Graphitization (graphitic corrosion) Corrosion Polarization The shift in electrode potential
of gray cast iron in which the metallic constituents resulting from the effects of current ow, measured
are converted to corrosion products, leaving the with respect to the zero-ow (reversible) potential,
graphite akes intact. Graphitization is also used in i.e., the counter-e.m.f. caused by the products formed
a metallurgical sense to mean the decomposition of or concentration changes in the electrode.
iron carbide to form iron and graphite.
Protective potential A term sometimes used in
Hydrogen embrittlement Hydrogen embrittlement cathodic protection to dene the minimum potential
causes a weakening of the metal by the entrance of required to suppress corrosion. For steel in sea water,
hydrogen into the metal through, for example, pick- this is claimed to be about 0.85 V as measured against
ling or cathodic polarization. a saturated calomel cell.
Hydrogen overvoltage A higher than expected Remote electrode (remote earth) Remote earth
difference in potential associated with the liberation is any location away from the structure at which
of hydrogen gas. the potential gradient of the structure to earth is
constant. The potential of a structure-to-earth will
change rapidly near the structure and if remote earth
154 ASPE Plumbing Engineering Design Handbook Volume 1
REFERENCES
1. Bosich, Joseph F. 1970. Corrosion prevention for
practicing engineers.
2. Claes and Fitzgerald. 1975-1976. Fundamentals of
underground corrosion control. Plant Engineer-
ing Technical Publishing. Plant Engineering.
New York: McGraw-Hill.
3. Fontana, Mars G., and Norbert D. Greene. 1967.
Corrosion engineering. New York: McGraw-
Hill.
4. Kullen, Howard P. Corrosion. Power. December
1956: 74-106.
5. Laque, F. L., and H. R. Copson. 1965. Corrosion
and resistance of metals and alloys. 2nd ed. New
York: Reinhold Publishing.
6. National Association of Corrosion Engineers.
1971. NACE basic corrosion course. Houston:
National Association of Corrosion Engineers.
7. Peabody, A. W. 1967. Control of pipeline corro-
sion. Houston: National Association of Corrosion
Engineers.
8. Shreir, L. L. 1963. Corrosion control. Vol. 2 of
Corrosion. New York: John Wiley and Sons.
9. Speller, Frank N. 1963. Corrosion causes and
prevention. New York: McGraw-Hill.
10. Uhlig, Herbert H. 1940. Corrosion handbook. New
York: John Wiley and Sons.
9
INTRODUCTION
Seismic Protection
of Plumbing
Equipment
disruption of normal business affairs, or curtailment assistance be obtained from a professional of that dis-
of productionis coming more into focus. cipline. Care should be taken in the design of seismic
The costs of seismic protection of plumbing control systems. Proper design may require assistance
components and equipment range from smallsuch from an engineer experienced in these systems. In
as those to anchor small tanksto a considerable all cases, the current local building code requirements
percentage of installation costssuch as those for for seismic movement should be consulted and used
complete pipe bracing systems. Beyond protection of as minimum standards.
life, the purpose or cost-benet relationship of seismic The detailed analysis and design techniques used
protection must be clearly understood before the ap- for nuclear power plants and other heavy industrial
propriate response to the risk can be made. The design applications, while similar in nature to those discussed
professional responsible for any given element or here, are considered inappropriate for most buildings
system in a building is in the best position to provide and are beyond the scope of this chapter. References
that response. Seldom, however, can rational seismic are given throughout the text for additional study in
protection be supplied solely by a single discipline. specic areas of interest.
Building systems are interdependent in both design
and function, and good seismic protection, like good
CAUSES AND EFFECTS OF
overall building design, is best provided by employing EARTHQUAKES
a cooperative, interdisciplinary approach. Plate Tectonics and Faults
This chapter is intended to provide a basic un- All seismic activity on the earths surface, including
derstanding of the mechanisms of seismic damage earthquakes and volcanoes, are now understood to
and the particular vulnerabilities of plumbing systems be caused by the relative movement of pieces of the
and equipment. It is desirable that the professional earths crust. Ten of the largest pieces, called plates,
sufciently understand the problem in order to select and their prevailing motions, are shown in Figure
the appropriate seismic protection in any situation, 9-3. The edges of these plates make up the worlds
based on a ranking of the damage susceptibility and
primary fault systems, along which 90% of all earth-
a knowledge of the scope of mitigation techniques.
quakes occur. The balance of earthquakes occur on
The seismic-protection techniques currently in
countless additional, smaller faults that lie within
use for buildings are described in general. Although
specic seismic-protection details for some situations plate boundaries. The causes and exact mechanisms
are discussed, it is suggested that structural-design of these intraplate earthquakes, which affect much
(A)
(B)
Figure 9-2 (A) Seismic Zone Map of the United States; (B) Map of Seismic Zones and Effective, Peak-Velocity-Related
Acceleration (Av) for Contiguous 48 States.
Note: Linear interpolation between contours is acceptable.
158 ASPE Plumbing Engineering Design Handbook Volume 1
of the middle and eastern United States, are not well shows such maps, which were used to develop design
understood. criteria zoning for a national seismic code.
The relative movement at plate boundaries is Damage from Earthquakes
often a sliding action, such as occurs along the San
Four separate phenomena created by earthquakes
Andreas Fault along the west coast of North America.
can cause damage:
The plates can also converge, when one plate slides
beneath another, or diverge, when molten rock from 1. Surface fault slip (ground rupture).
below rises to ll the voids that gradually form. Al- 2. Wave action in water created by seismic move-
though overall plate movement is extremely slow, ment (called tsunamis in open bodies of water,
properly measured only in a geologic time frame, the seiches in closed bodies of water).
local relative movement directly at the fault plane 3. Ground shaking.
can occur either gradually (creep) or suddenly, when
tremendous energy is released into the surrounding 4. Ground failure, such as a sudden change to liquid
mass. characteristics in certain sands caused by in-
The most common mechanism used to describe creased pore water pressure called "liquefaction"
and "landslides."
earthquakes is the elastic rebound theory, wherein
a length of fault that is locked together by friction is It is accepted that buildings and their contents are
strained to its capacity by the continuing plate move- not designed to withstand ground rupture caused by
ment, and both sides spring back to their original seismic events. Protection from this is obtained by
positions (See Figure 9-4). Waves in a variety of pat- avoiding potentially dangerous sites. Underground
terns emanate from this fault movement and spread piping can be severely damaged by either fault rup-
in every direction. These waves change throughout ture or ground failure, and frequently pipe lines must
the duration of the earthquake, add to one another, cross areas with these potential problems. Seismic
and result in extremely complicated wave motions and design provisions for underground systems in these
vibrations. At any site away from the fault, the three- cases consist of special provisions for the consider-
dimensional movement of the surface, which is caused able distortion expected in the ground or redundant
by combinations of direct, reected, and refracted systems and valving, such that local damage can be
waves, is known simply as ground shaking. Energy accepted without serious consequences.
content or intensity of the ground shaking decreases
with distance from the causative fault, although be- EARTHQUAKE MEASUREMENT
cause certain structures can be tuned into the motion, AND SEISMIC DESIGN
this is not always apparent. The horizontal, vertical, Ground Shaking and Dynamic Response
and rotational forces on structures are unpredictable The primary thrust of seismic design, as it relates to
in direction, strength, and duration. The structural buildings, is to protect against the effects of ground
load is proportional to the intensity of shaking and shaking. Although recently there has been concern
to the weight of the supported elements. that surface waves may damage structures by pure
By combining knowledge of known fault locations distortion, virtually all design is done assuming the
with historical and instrumented ground motion entire ground surface beneath a structure moves as
records, seismologists can construct maps showing a unit, producing a shaking or random motion whose
zones of varying expected ground motion. Figure 9-2
unidirectional components can be studied mathemati- The characteristically spiked and jagged shape of the
cally and whose effects on structures can be analyzed acceleration time history (accelergram, Figure 9-5)
using structural dynamics and modeling. The move- is universally recognized as being associated with
ment of the ground mass under a building during earthquakes.
an earthquake is measured and recorded using the When any nonrigid structure, such as the pendu-
normal parameters of motion, displacement, velocity, lum or cart and spring of Figure 9-6(A) is subjected
and acceleration. Two orthogonal plan components to a time history of base motion, the movement (D)
and one vertical component are used to completely of the mass (M) can be measured over time, and this
describe the motion. The effect of each orthogonal record of motions becomes the dynamic response (K).
plan component on the structure under design is The dynamic response will be different than the input
considered separately. motion because of the inertial lag of the mass behind
The amplitude of displacement, velocity, and the base and the resultant energy stored by distorting
acceleration at any moment are, of course, related, the connecting structure. The dynamic response to
as each measures the change in the other over time. any input motion, then, will depend on the size of the
Given the record of how one parameter has changed mass and the stiffness of the supporting structure.
over time (time history), the other two can be calcu- The Response Spectrum
lated. However, due to the direct relationship of force
Because of the difculty of measuring all the varia-
to acceleration (F-Ma) and also because acceleration
tions of distortion in a normal structure at each
is easiest to instrumentally measure, acceleration
moment of time, a shorthand measure of maximum
has become the standard measurement parameter.
response is often used. The maximum response of a
3. Joints were loosened or pulled apart in long 2. Suspended piping systems should have consistent
horizontal runs of unbraced cast-iron pipe, and freedom throughout; for example, branch lines
hangers were bent, shifted, or broken. should not be anchored to structural elements if
4. Pipes crossing seismic joints were damaged if the main line is allowed to sway.
provisions were not made for the relative move- 3. If the piping system is allowed to sway, movable
ments between structural units of buildings. joints should be installed at equipment connec-
5. Thermal expansion loops and joints were damaged tions.
when the pipes were not properly guided. 4. Pipes leading to thermal expansion loops or ex-
6. Fire-sprinkler piping was practically undamaged ible pipe connections should be guided to conne
because it was provided with lateral bracing. the degree of pipe movement.
7. Sand lter, water softener, domestic hot water, 5. Whenever possible, pipes should not cross seismic
heating-hot-water expansion and cold-water-stor- joints. Where they must cross seismic joints, ap-
age tanks shifted, toppled, or rolled over when propriate allowance for differential movements
they were not rmly anchored to buildings. must be provided. The crossing should be made
at the lowest oor possible, and all pipe deec-
8. Hundreds of small, gas-red and electric domestic tions and stresses induced by the deections
water heaters fell over. Many of the legs on which should be carefully evaluated. Standards of the
heaters stood collapsed, and vent connectors were National Fire Protection Association (NFPA) for
damaged. earthquake protection to re-sprinkler systems
9. Some plumbing xtures were damaged by falling should be referred to for successful, eld-tested,
debris. installation details that are applicable to any pip-
ing system. The latest revision to FM data sheet
10. Vertical plumbing stacks in tall buildings were 2-8 for sprinkler systems is also valuable as a
practically undamaged. reference guide.
The 1971 San Fernando Earthquake 6. Supports for tanks and heavy equipment should
be designed to withstand earthquake forces and
Damage summary should be anchored to the oor or otherwise se-
1. Unanchored heavy equipment and tanks moved cured.
and damaged the connected piping. 7. Suspended tanks should be strapped to their
2. Heavy equipment installed with vibration isola- hanger systems and provided with lateral brac-
tion mounts moved excessively, often destroyed ing.
the isolators, and damaged the connected pip- 8. Pipe sleeves through walls or oors should be
ing. large enough to allow for the anticipated move-
3. Cast-iron supports for heavy cast-iron boilers ment of the pipes and ducts.
failed. 9. Domestic water heaters should be provided with
4. Pipes failed at threaded connections to screwed legs that can withstand earthquake forces, and
ttings. Some cast-iron ttings were fractured. the legs should be anchored to the oor and/or
strapped to a structurally sound wall.
5. Pipes were damaged when crossing separations
between buildings. 10. Earthquake-sensitive shut-off valves on gas-ser-
vice lines should be provided where maximum
6. Screwed pipe legs under heavy tanks failed, and protection from gas leaks is required.
angle iron legs were deformed.
11. Vibrating and noisy equipment should, if possible,
7. Plumbing xtures were loosened from mounts, be located far from critical occupancies, so that
and enamel was chipped. the equipment can be anchored to the structure,
8. Domestic water heater legs were bent or col- and vibration isolation is not required.
lapsed. Avoid mounting heavy mechanical equipment on
The overall recommendations applicable to plumbing the top or upper oors of tall buildings unless all
equipment from the Alaska report, made primarily as vibration-isolation mounts and supports are care-
a response to observed damage, are worth relating: fully analyzed for earthquake-resistant design.
1. Pipelines should be tied to only one structural When equipment and the attached piping must be
system. Where structural systems change, and isolated from the structure by vibration isolators,
relative deections are anticipated, movable joints constraints should be used.
should be installed in the piping to allow for the
same amount of movement.
Chapter 9 Seismic Protection of Plumbing Equipment 163
(A)
Figure 9-8 Snubbing Devices: Figure 9-9 Isolators with Built-In Seismic Restraint
(A) Three-Dimensional Cylinder Snubber
Chapter 9 Seismic Protection of Plumbing Equipment 165
(B)
Figure 9-8 Snubbing Devices: (B) Three-Directional Angle Snubbers
166 ASPE Plumbing Engineering Design Handbook Volume 1
begins, resilient pads are added to ease the shock load 1. Fuel oil, gas, medical gas, and compressed air
that could be caused by impact. piping 1-inch (25.4-mm) nominal diameter and
Because of the stored energy in isolation springs, larger.
it is more efcient to anchor the assembly, as restraint 2. Piping in boiler rooms, mechanical rooms, and
is built into the isolator rather than being a separate refrigeration mechanical rooms 1-inch (31.8-
unit. In retrot applications, or occasionally due to mm) nominal diameter and larger.
dimensional limitations, separate snubbers are pref-
3. All piping 2-inches (63.5-mm) nominal diameter
erable. Once snubbers are decided upon, those that
and larger.
restrain in three dimensions are preferred because
that minimizes the number required. Although some Conventionally installed piping systems have
unconrmed rubber-in-shear isolators are intended survived earthquakes with minimal damage. Fitting
to resist loads in several directions, there is little failures generally occur at or near equipment connec-
data to indicate adequacy to resist the concurrent tors where equipment is allowed to move, or where a
large amplitude dynamic loading that could occur in main is forced to move and small branches connected
an earthquake. Unless such isolators are considered to the main are clamped to the structural elements. In
for real earthquake loading (as opposed to code re- theory, then, a few well-placed pipe restraints in the
quirements) with a suitable safety factor, additional problem areas could provide adequate seismic protec-
snubbing is recommended. Rubin-in-shear isolators tion. In practice, however, the exact conguration of
with metal housing are more likely to have the over- piping is seldom known to the designer, and even if it
load capacity that may be needed to resist seismic was, the key brace locations are not easy to determine.
loading, but unless they are specically tested and Often, partial restraint in the wrong location is worse
rated for this loading, ultimate capacities should be than no restraint at all. Correct practice is therefore
compared with expected real seismic loads. to provide complete restraint when seismic protection
of piping systems is advisable. This restraint can be
Vibration-isolated, suspended equipment This
applied throughout the system or in local, well-dened
is by far the most difcult type of equipment to re-
areas such as mechanical or service rooms.
strain, particularly if only a small movement can be
Although there are many variables to consider
tolerated. The best method is to place an independent,
when restraining pipe against seismic movement, the
laterally stable frame around the equipment with
techniques to do so are simple and similar to those
proper operating gaps padded with resilient mate-
used for hanging equipment. Fixing pipe directly
rial, similar to a snubber. However, this frame and its
to structural slabs, beams, columns, or walls is, of
support system can be elaborate and awkward. An al-
course, the simplest method. Many codes and guide-
ternate method is to provide a self-contained, laterally
lines consider hangers of less than 12 inches (305 mm)
stable, suspended platform upon which conventional
as being equivalent to direct attachment. For pipes
seismic isolators or snubbers can be mounted.
suspended more than 12 inches (305 mm), diagonal
Smaller equipment bolted or welded directly to
braces to the structure above or horizontal struts to
the structure doesnt need restraints, but the bolts or
an adjacent structure are normally installed at verti-
welds must be designed for seismic loads. However,
cal hanger locations. Vertical suspension hardware is
equipment suspended close to the structure requires
usually incorporated into braces, both for efciency
restraints. Isolators within hangers should always
and because it is readily available.
be installed tight against the supporting structural
Connection to the pipe at transverse braces is ac-
member. When hanger rods are used to lower the
complished by bearing the pipe or insulation on the
unit, cross bracing or diagonal bracing should be
pipe clamp or hanger. Attachment to the pipe at longi-
installed.
tudinal brace points is not as simple. For small loads,
Cable that is installed taut, but allowed to sag
tight-tting clamps (such as riser clamps) dependent
under its own weight will allow vibration isolation to
on friction are often used. For larger loadings, details
function. Additional slack is not required and should
commonly used for anchor points in high-temperature
not be allowed. Use of neoprene grommets or bushings
systems with welded or brazed direct connections to
is not required. The cable sag and cable exibility
the piping may be necessary. Welding should be done
provide adequate cushioning.
by certied welders in accordance with American
Piping Systems Welding Society (AWS) D 1.1 and shall use either the
Normally, piping suspended by hangers less than 12 shielded or submerged arc method.
inches (305 mm) in length, as measured from the Transverse bracing shall be at 40 feet (12.2 m)
top of the pipe to the bottom of the support where maximum spacing, except that fuel oil and gas piping
the hanger is attached, do not require bracing. The shall be at 20 feet (6.1 m) maximum spacing. Longi-
following piping shall be braced: tudinal bracing shall be at 80 feet (24.4 m) maximum
Chapter 9 Seismic Protection of Plumbing Equipment 167
spacing, except that fuel oil and gas piping shall be at oors. Limitations on depth and location also exist
40 feet (12.2) maximum spacing. in the bottom ange of steel or reinforced concrete
The many parameters that must be considered beams and in the bottom chord of joists.
before the exact details and layout of a pipe bracing Many steel oor-deck styles have down utes 1
system can be completed are shown schematically in in. (38.1 mm) or less in width; the strength of
Figure 9-10. These parameters are discussed in more drilled or shot-in anchors installed in these loca-
detail below: tions is questionable.
1. Weight of pipe and contents Since the motion being The structures of buildings that employ intersti-
restrained is a dynamic response, the forces that tial space may have the capacity to brace pipe to
must be resisted in each brace are proportional either the top or the bottom of the space, which
to the tributary weight. greatly increases bracing layout exibility.
2. Location of pipe The strength of structural 4. Piping material The strength and ductility of
members, particularly compression members, is the material will affect brace spacing. The stiff-
sensitive to length, so a pipe that must run far ness will affect dynamic response and therefore
from a structural support may require more or loading.
longer braces. In boiler service rooms, a horizon-
5. Joint type The joint has proven to be the ele-
tal grid of structural beams has sometimes been
ment most likely to be damaged in piping systems;
placed at an intermediate height to facilitate
threaded and bell-and-spigot joints have been
bracing of pipes.
particularly susceptible. The joint type also de-
3. Type of structure The connection of hangers and termines, in conjunction with the pipe material,
braces to the structure is an important factor in the length of the span between braces. Brazed
determining a bracing system, as demonstrated and soldered joints perform acceptably. Most
by the following considerations: Many light roof- no-hub joints, however, have virtually no stiff-
deck systems cannot accept point loads except at ness; effective bracing of such systems is nearly
beam locations; pipe locations and brace layout impossible. Mechanical joints exhibit the most
are thereby severely limited unless costly cross complex behavior, with spring-like flexibility
beams are placed at every brace. Other roof and (when pressurized) within a certain rotation and
oor systems have signicant limitations on the then rigidity. In addition, the behavior of such sys-
magnitude of point loads, which limit brace spac- tems under earthquake conditions, which cause
ing. axial loadings necessary to transmit forces to
It is often unacceptable to have anchors drilled or longitudinal braces, is unknown. As a minimum,
shot into the underneath of prestressed concrete cast iron and glass pipe, and any other pipe joined
with a shield-and-clamp assembly, where the top ing system. A misplaced longitudinal brace can
of the pipe exceeds 12 inches (305 mm) from the become an unwanted anchor and cause severe
supporting structure, shall be braced on each side damage. Thermal forces at anchor points, un-
of a change of direction of 90 degrees or more. less released after the system is operational, are
Riser joints shall be braced or stabilized between additive to tributary seismic forces. Potential
oors. For hubless, pipe-riser joints unsupported interference between seismic and thermal sup-
between oors, additional bracing is required. All port systems is particularly high near pipe bends
pipe vertical risers shall be laterally supported where a transverse brace can become an anchor
with a riser clamp at each oor. for the perpendicular pipe run.
6. Vibration Traditionally, unbraced pipe systems 8. Condensation The need to thermally insulate
seldom cause vibration transmission problems be- high-temperature and chilled water lines from
cause of their inherent exibility. Many engineers hanging hardware makes longitudinal brace
are concerned that completely braced tight attachment difcult. In some congurations of
piping systems could cause unpredictable sound short runs with bends, transverse braces can
and vibration problems. be utilized near elbows to brace the system in
7. Temperature movement Pipe anchors and guides both directions. Friction connections, using wax-
used in high-temperature piping systems must impregnated oak or calcium-silicate sleeves as
be considered and integrated into a seismic brac- insulators, have been used.
Rod
2
1
Diagonal angle
Bolt to angle
8 2
2
6
7
5
3 3
1
4
1 5
Triangle Plate 1-1/4"x1-1/4"x12 Ga. Channel
1/4" Plate Length Varies
1/4"X1-1/4" Flat Bar (Not Included)
2 6
3 7
1/2" All-Thread Rod
(Not Included) 1/4" Dia Mach. Bolt
Length Varies with Clamp Nut
With Nylon Lock Nut 30 Ft # Torque
4 8
Pipe Hanger Phillips Sleeve Anchor
Size and Type Can Vary
(B)
Figure 11b Figure 9-11System
Pipe Bracing Pipe Bracing
- Tension 360 Systems: (B) Tension 360
170 ASPE Plumbing Engineering Design Handbook Volume 1
R
bv
R
bh R
bv
R
bh
Support structure connections
Flexible
connector
Flexible
connector
Longitudinal
channel brace
Hanger rod
Transverse
channel brace
Nut
Flexible connector
Flexible connector
H
L H
t
Hanger
H
L
H
t
P
(C)
Figure 9-11 Pipe Bracing Systems: (C) Superstrut.
Several bracing systems have been developed that The guidelines set forth by SMACNA and PPIC
contain some realistic and safe details governing utilize three pipe-bracing methods:
a wide range of loading conditions and congura-
1. The structural angle.
tions. For example, SMACNA (Sheet Metal and Air
Conditioning Contractors' National Association) and 2. The structural channel.
PPIC (Plumbing and Piping Industry Council) have 3. The aircraft cable method. (See Figure 9-12.)
prepared some guidelines on bracing systems for use
by engineers, architects, contractors, and approving Several manufacturers have developed their
authorities. Some of these details for construction own seismic bracing methods. (See Figures 9-13 and
of seismic restraints are seen in Figures 9-11 and 9-14.)
9-12.
Chapter 9 Seismic Protection of Plumbing Equipment 171
Whatever method is used, one should determine seismic applications is to recognize the possibility of
the adequacy of the supporting structure by properly repeated, large differential movements.
applying acceptable engineering procedures.
Pipe risers seldom pose a problem because they CODES
are normally clamped at each oor and movement due Design Philosophy
to temperature changes are routinely considered. Very The process of the seismic design for buildings has had
large or stiff congurations, which could be affected by a reasonably long time to mature. Beginning in the
interstory drift, or situations where long, free-hanging 1920s, after engineers observed heavy building dam-
horizontal runs could be inadvertently braced by a age from earthquakes, they began to consider lateral
riser, are possible exceptions. The effect of mid-span forces on buildings in this country and Japan. Todays
couplings with less strength or rigidity than the pipe procedures are based on analytical results as well as
itself must also be considered. considerable design experience and observed per-
The techniques for handling the possible dif- formance in earthquakes of varying characteristics.
ferential movement at locations of utility entrances Lateral forces for buildings specied in most codes are
to buildings or at building expansion joints are well much lower than could be calculated from structural
developed because of the similarity to nonseismic dynamics for a variety of reasons, including:
problems of settlement, temperature movement,
and wind drift. Expansion loops or combinations of 1. Observed acceptable performance at low design
mechanically exible joints are normally employed. levels.
For threaded piping, exibility may be provided by 2. Expected ductile action of building systems (abil-
the installation of swing joints. For manufactured ball ity to continue to withstand force and distort after
joints, the length of piping offset should be calculated yielding). Redundancy of resisting elements in
using seismic drift of 0.015 feet per foot (0.0046 meter most systems.
per meter) of height above the base where seismic 3. High damping as distortions increase, which cre-
separation occurs. The primary consideration in ates a self-limiting characteristic on response.
(A)
Figure 9-12 Construction Details of Seismic Protection for Pipes: (A) Transverse Bracing for Pipes
Source: SMACNA 1991. Note: For additional information, refer to SMACNA 1991.
172 ASPE Plumbing Engineering Design Handbook Volume 1
(B)
Figure 9-12 Construction Details of Seismic Protection for Pipes: (B) Longitudinal Bracing for Pipes
Note: Movement due to temperature has been neglected in this example.
Source: SMACNA 1991. Note: For additional information, refer to SMACNA 1991.
Chapter 9 Seismic Protection of Plumbing Equipment 173
(C)
Figure 9-12 Construction Details of Seismic Protection for Pipes: (C) Strut Bracing for Pipes
Source: SMACNA 1991. Note: For additional information, refer to SMACNA 1991.
174 ASPE Plumbing Engineering Design Handbook Volume 1
(D)
Figure 9-12 Construction Details of Seismic Protection for Pipes: (D) Alternate Attachment to Hanger for Pipe Bracing
Source: SMACNA 1991. Note: For additional information, refer to SMACNA 1991.
(E)
Figure 9-12 Construction Details of Seismic Protection for Pipes: (E) Alternate Bracing for Pipes
Source: SMACNA 1991. Note: For additional information, refer to SMACNA 1991.
Chapter 9 Seismic Protection of Plumbing Equipment 175
(F)
Figure 9-12 Construction Details of Seismic Protection for Pipes: (F) Strut Bracing for Pipe Trapeze
Source: SMACNA 1991. Note: For additional information, refer to SMACNA 1991.
(G)
Figure 9-12 Construction Details of Seismic Protection for Pipes: (G) Connections to Steel Beams
Source: SMACNA 1991. Note: For additional information, refer to SMACNA 1991.
176 ASPE Plumbing Engineering Design Handbook Volume 1
(H)
Figure 9-12 Construction Details of Seismic Protection for Pipes: (H) Connections to Open-Web Steel Joists
Source: SMACNA 1991. Note: For additional information, refer to SMACNA 1991.
(I)
Figure 9-12 Construction Details of Seismic Protection for Pipes: (I) Connections to Steel
Source: SMACNA 1991. Note: For additional information, refer to SMACNA 1991.
Chapter 9 Seismic Protection of Plumbing Equipment 177
(J)
Figure 9-12 Construction Details of Seismic Protection for Pipes: (J) Hanger Rod Connections
Source: SMACNA 1991. Note: For additional information, refer to SMACNA 1991.
(K)
Figure 9-12 Construction Details of Seismic Protection for Pipes: (K) Hubless Cast-Iron Pipe
Source: SMACNA 1991. Note: For additional information, refer to SMACNA 1991.
178 ASPE Plumbing Engineering Design Handbook Volume 1
(L)
Figure 9-12 Construction Details of Seismic Protection for Pipes: (L) Riser Bracing for Hubless Pipes
Source: SMACNA 1991. Note: For additional information, refer to SMACNA 1991.
(M)
Figure 9-12 Construction Details of Seismic Protection for Pipes: (M) Connections for Pipes on Trapeze.
Source: SMACNA 1991. Note: For additional information, refer to SMACNA 1991.
Chapter 9 Seismic Protection of Plumbing Equipment 179
Hanger rod
1/2 x 15/16 (12.7 x 23.8 mm) screw
Tranverse with 1/2 clamp
channel brace nut typical
1
Bracing may vary in
1 min.
Clevis hanger slope by 45 above
or below horizontal
Add bolt sleeve
D
L
H H
t t
Hanger rod
1/2 x 15/16 (12.7 x 23.8 mm) screw
Tranverse with 1/2 clamp
channel brace nut typical
Nut
Stud is for 1
longitudinal brace 1 min.
where required
Bracing may vary in
slope by 45 above
H H or below horizontal
t t D
L
Hanger rod
1/2 x 15/16 (12.7 x 23.8 mm) screw
Tranverse
with 1/2 clamp
channel brace
nut typical
1
Nut
1 min.
Transverse Only
(B)
(C)
Longitudinal Only
8 2
7
5
3
1
4
(A)
Figure 9-14 A Seismic Bracing Method: (A) Lateral Sway Bracing
182 ASPE Plumbing Engineering Design Handbook Volume 1
8 2
2
6
7
5
3 3
1
4
(B)
Figure 14b Sway bracing - Lateral and Longitudinal
Figure 9-14 A Seismic Bracing Method: (B) Lateral and Longitudinal Sway Bracing.
Chapter 9 Seismic Protection of Plumbing Equipment 183
4. Less-than-perfect compliance of the foundation 5. Tentative provisions for the development of seismic
to the ground motion. regulations for buildings (ATC-3). (See Applied
5. Economic restraints on building codes. Technology Council 1978.).
The fact that the actual response of a building All of these codes require consideration of a lateral
during an earthquake could be 3 or 4 times that force that must be placed at the center of gravity of
represented by code forces must be understood and the element. The lateral force, or equivalent static
considered in good seismic design. Traditionally, this force, is calculated using some or all of the following
is done by rule of thumb and good judgment to ensure parameters:
that structural yielding is not sudden or does not 1. Zone Similar to Figure 9-2, the zone category
produce a collapsed mechanism. More recently, the affects the lateral force calculated by considering
response of many buildings to real earthquake input the size and frequency of potential earthquakes
is being considered more specically using computer in the region.
analysis. 2. Soils The effect of specic site soils on ground
Design of seismic protection for nonstructural motion.
elements, including plumbing components and equip-
3. Force factor This considers the basic response
ment, has neither the tradition nor a large number
of the element to ground motion and is affected
of in-place tests by actual earthquakes to enable by subparameters, which could include location
much renement of design force capability or design within the building and possible resonance with
technique. Unfortunately, few of the effects listed the structure.
above that mitigate the low force level for structures
apply to plumbing or piping. Equipment and piping 4. Importance A measure of the desirability of
systems are generally simple and have low damping, protection for a specic element.
and their lateral force resisting systems are usu- 5. Element weight All codes require calculation of
ally nonredundant. It is imperative, therefore, when a lateral force that is a percentage of the element
designing seismic protection for these elements, to weight.
recognize whether force levels being utilized are 6. Amplification factor This is defined by the
arbitrarily low for design or realistic predictions natural period, damping ratio, and mass of the
of actual response. Even when predictions of actual equipment and the structure.
response are used, earthquake forces are considered
7. Response factor Determined by driven frequency
sufciently unpredictable when friction is not allowed (equipment motors) and natural frequency.
as a means of anchorage. Often, less-than-full dead
load is used to both simulate vertical accelerations and It is of critical importance that the various build-
to provide a further safety factor against overturning ing codes and their requirements be obtained and
or swinging action. adhered to.
Code Requirements Sprinkler systems: NFPA 13 Because of the
All current building codes require most structures and potential for re immediately after earthquakes,
portions of structures to be designed for a horizontal sprinkler piping has long received special atten-
force based on a certain percentage of its weight. Each tion. The reference standard for installation of
code may vary in the method of determining this sprinkler piping, NFPA 13 (National Fire Protection
percentage, based on factors including the seismic Association 1996), is often cited as containing proto-
zone, the importance of the structure, and the type type seismic bracing for piping systems. In fact, in
of construction. those cases observed, sprinkler piping has performed
It is difcult to consider specic code require- well. The bracing guidelines followed for some time
ments out of context. The code documents themselves in seismically active areas are actually contained in
should be consulted for specic usage. Most codes Appendix A of NFPA 13. However, good earthquake
currently in use, or being developed, can generally be performance by sprinkler piping is also due to other
discussed by considering these four: factors, such as limited pipe size, use of steel pipe,
coherent layouts, and conservative suspension (for
1. Uniform Building Code 1997 (UBC). vertical loads).
2. California administrative code of regulations, Use of NFPA 13 guidelines for pipe bracing is not
parts 2 of 2001 Edition of Title 24 (Title 24, discouraged, but it should not be considered a panacea
CAL). for all piping systems. Other organizations, such as
3. International Building Code 2000 (IBC). Factory Mutual (FM), have developed guidelines for
properties insured by them and in many cases are
4. Seismic design for buildings. Tri-Services Manual.
more restrictive.
(See U.S. Department of Defense 1973.)
184 ASPE Plumbing Engineering Design Handbook Volume 1
In typical pipe braces [Figure 9-16(B)], it is Because of the variety of computer programs
important to note that R, the gravity force in the available and because many have proprietary restric-
hanger rod, is signicantly affected by the addition tions, specic programs are not listed here. Piping
of the brace and is not equal to W, as indicated previ- analysis programs are available at most computer
ously. Dealing with these loads is a huge problem. A service bureaus, many universities, and national
tension rod hanger commonly goes into compression computer program clearinghouses.
in such a situation. Cable restraints do not have this
problem. DESIGN CONSIDERATIONS
COMPUTER ANALYSIS OF PIPING Loads in Structures
SYSTEMS It is always important to identify unusual equipment
Computers programs have been used to analyze pip- and piping loads during the rst stages of project
ing systems for stress for some time. These programs design to assure that the structural system being de-
were initially developed to consider thermal stresses veloped is adequate. Consideration of seismic effects
and anchor point load, but software is now commonly makes this coordination even more important because
available that can consider seismic and settlement seismic forces produce unusual reactions. During an
loading, spring or damping supports, snubbers (simi- earthquake, not only must horizontal forces be taken
lar to equipment snubbers), differing materials, and into the structure, but vertical load effects are inten-
nonrigid couplings. The seismic loading normally can sied due to vertical accelerations and overturning
be gured by using a full-time history, as a response movements. These reactions must be acceptable to
spectrum, or equivalent static forces. The time his- the structure locally (at the point of connection) and
tory has the inherent problem of requiring a search of globally (by the system as a whole).
each time increment for worst-case stresses and brace If the structural system is properly designed
loadings. The computer time and man-hours required for the appropriate weights of equipment and pip-
are seldom justied. In fact, for seismic loading alone, ing, seismic reactions will seldom cause problems
computer analysis is almost never performed because to the overall system. However, local problems are
brace loadings can easily be determined by tributary not uncommon. Most oors are required by code to
length methods, and rule-of-thumb pipe spans (brace withstand a 2000-pound (908 kg) concentrated load,
spacing) are contained in several publications (see so this is a reasonable load to consider acceptable
National Fire Protection Association 1996; Hillman, without special provisions. However, seismic reac-
Biddison, and Loevenguth; and U.S. Dept. of Defense tions to structures can easily exceed this gure; for
1973). Computer analysis may be appropriate, how- example:
ever, when it is necessary to combine seismic loading 1. A longitudinal brace carrying a tributary load
with several of the following considerations: of 80 feet (24.8-m) of 8-inch (203-mm) steel pipe
1. Temperature changes and anchorage. lled with water will generate reactions of
this magnitude.
2. Nonlinear support conditions (springs, snubbers,
etc.). 2. Transverse or longitudinal braces on trapezes
often have larger reactions.
3. Complex geometry.
3. A 4000-pound (1816-kg) tank on legs could also
4. Several loading conditions. yield such a concentrated load. In addition, pos-
5. Piping materials other than steel or copper. sible limitations on attachment methods due to
structure type could reduce the effective maxi-
6. Joints or couplings that are signicantly more mum allowable concentration.
exible or weaker than the pipe itself.
Roof structures have no code-specied concen-
trated load requirement and often are the source of
Chapter 9 Seismic Protection of Plumbing Equipment 187
If not over
24" (610mm)
45
Pipe or L
45
45 45
Pipe or L's
45
45 45
Angle or
equal
2 bolts in each
connection
P P P
1. Eccentricity in e P M=P M =M
connection not e M
r
from M
Same as resisted machine or
R R R
Structure M from structure
r
2. Sidesway or
tipping Rails
Legs Sidesway restrained by bracing or cross beams
3. Isolators with
no restraint Added
snubbers
h
See also item 1.
4. Isolators with
restraint
h Sidesway restrained
See items 1 & 2
5. Location of
connection
to structure (bottom flange
(lateral force) unbraced)
Perpendicular beam
6. Location of
connection
to structure (eccentric)
(vertical force)
7. Type of
connector
(friction only)
Restrainer
8. Brace
conguration Missing Stable
component Eccentricity triangle
9. Typical details
L2 x 2 L3 x 3
(50 x 50mm) (75 x 75mm) Limited
No limiting
conditions
10. Trapeze
Longitudinal
One longitudinal braces
brace provided each end
at center or end
tion 7 also shows a connector in common use, which 2. Combined shear and tension should be considered
is probably acceptable in a nonseismic environment in the design. A conservative approach commonly
but which should be secured in place as shown under used is the following equation:
dynamic conditions. Equation 9-2
Most pipe bracing systems utilize bracing mem- (T/Ta) + (V/Va) < 1
bers in pure tension or compression for stiffness and where:
efciency. This truss-type action is only possible when T = Tension, lbf/in2
bracing congurations make up completed triangles, Ta = Allowable tension, lbf/in2
as shown on the right under condition 8. The brace V = Shear, lbf/in2
conguration on the far left is technically unstable Va = Allowable shear, lbf/in2
and the eccentric condition shown produces moment 3. Edge distances are important because of the
in the vertical support. expansive nature of these anchors. Six (6)
As previously indicated, typical details must be diameters are normally required.
carefully designed and presented to prevent their mis-
use. Condition 9 shows the most common deciency: 4. Review the embedments required for design
values. It is difcult to install an expansion bolt
A lack of limiting conditions.
over -inch (12.7-mm) diameter in a typical oor
Condition 10 shows a situation often seen in the
system of 2-inch (63.5-mm) concrete over steel
eld where interferences may prevent placement of
decking.
longitudinal braces at the ends of a trapeze and either
one is simply left out or two are replaced by one in 5. Bolt sizes over -inch (6.4-mm) diameter have
the middle. Both of these substitutions can cause embedments sufcient to penetrate the reinforc-
an undesirable twist of the trapeze and subsequent ing envelope. Bolts should therefore not be placed
pipe damage. All eld revisions to bracing schemes in columns, the bottom ange of beams, or the
should be checked for adequacy. bottom chord of joists. Bolts in slabs or walls are
less critical, but the possibility of special and
Other potential problems that occur less fre-
critical reinforcing bars being cut should always
quently include incompatibility of piping systems with
be considered. The critical nature of each strand
differential movement of the structure (drift) and
of tendon in prestressed concrete, as well as the
inadvertent self bracing of piping through short, stored energy, generally dictates a complete pro-
stiff service connections or branches that penetrate hibition of these anchors.
the structure. If the possibility of either is apparent,
pipe stresses should be checked or the self-bracing 6. Installation technique has been shown to be ex-
restraint eliminated. tremely important in developing design strength.
A few problems associated with making connec- Field testing of a certain percentage of anchors
should be considered.
tion to a structure were discussed above, in relation to
9-17. When connecting to structural steel, in addition Additional Considerations
to manufactured clip devices, bolting and welding are Seismic anchorage and bracing, like all construction,
also used. Holes for bolting should never be placed in should be thoroughly reviewed in the eld. Consider-
structural steel without the approval of the structural ing the lack of construction tradition, the likelihood
engineer responsible for the design. Field welding of eld changes or interferences, and other potential
should consider the effects of elevated temperatures problems (discussed above), seismic work probably
on loaded structural members. should be more clearly controlled, inspected, and/or
The preferred method of connecting to concrete tested than normal construction.
is through embedments, but this is seldom practical. Another result of the relative newness of seismic
Since the location of required anchorages or braces protection of equipment and piping is the lack of per-
is often not known when concrete is poured, the use formance data for the design and detailing techniques
of drilled-in or shot-in anchors is prevalent for this now being used. Considerable failure data were col-
purpose. Although these anchors are extremely useful lected in Anchorage and San Fernando, but essentially
and practically necessary connecting devices, their no eld data are available to assure that our present
adequacy has many sensitivities and they should be assumptions, although scientically logical and ac-
applied with thorough understanding and caution. curate, will actually provide the desired protection.
The following items should be considered in the design Will rm anchorage of equipment cause damage to the
or installation of drilled or shot-in anchors: internal workings? Will the base cabinet, or frame-
1. Manufacturers often list ultimate (failure) values work (which is now seldom checked), of equipment
in their literature. Normally, factors of safety of be severely damaged by the anchorage? In contrast,
4 or 5 are applied to these values for design. the present requirements for structures are largely
Chapter 9 Seismic Protection of Plumbing Equipment 191
the result of observations of damage to structures in Transverse bracing Bracing that prevents a pipe
actual earthquakes over 75 years. from moving from side to side.
The net result of current standards in seismic pro-
tection can only be positive. The ne-tuning of scope, REFERENCES
force levels, and detailing techniques must wait for 1. American National Standards Institute. Draft. ANSI-
additional, full-scale testing in real earthquakes. ASSI: Building code requirements for minimum design
loads in buildings and other structures. New York.
GLOSSARY 2. Applied Technology Council. 1978. Tentative provisions
for the development of seismic regulation for buildings
Anchor A device, such as an expansion bolt, for (ATC-3). Washington, D.C.: U.S. Department of Com-
connecting pipe-bracing members into the structure merce, National Bureau of Standards.
of a building.
3. Ayres, J. M., and T. Y. Sun. 1973. Non-structural
Attachment See "positive attachment." damage. The San Fernando, California, Earthquake of
February 9, 1971. Washington, D.C.: National Oceanic
Bracing Metal channels, cables, or hanger angles and Atmospheric Administration.
that prevent pipes from breaking away from the 4. Ayres, J. M., T. Y. Sun, and F. R. Brown. 1973. Non-
structure during an earthquake. See also "longitudinal structural damage to buildings. The Great Alaska
bracing" and "transverse bracing." Together, these Earthquake of 1964: Engineering. Washington, D.C.:
resist lateral loads from any direction. National Academy of Sciences.
Dynamic properties of piping The tendency of 5. California, State of. 1988. California Code of Regula-
tions. Division 122 of Title 24, Building Standards.
pipes to change in weight and size because of the
movement and temperature of uids in them. This 6. Hillman, Biddison, and Loevenguth. Guidelines for
seismic restraints of mechanical systems. Los Angeles:
does not refer to movement due to seismic forces.
Sheet Metal Industry Fund.
Essential facilities Buildings that must remain 7. Hodnott, Robert M. Automatic sprinkler systems hand-
safe and usable for emergency purposes after an book. Boston, Ma.: NFPA.
earthquake in order to preserve the health and safety 8. International Conference of Building Ofcials. 1988.
of the general public. Examples include hospitals, Uniform Building Code 1988. Whittier, California:
emergency shelters, and re stations. International Conference of Building Ofcials.
Equipment For the purposes of this chapter, "equip- 9. National Fire Protection Association (NFPA). 1996.
ment" refers to the mechanical devices associated with Standard for the installation of sprinkler systems.
NFPA no. 13. Boston, Ma: NFPA.
pipes that have signicant weight. Examples include
pumps, tanks, and electric motors. 10. Sheet Metal and Air Conditioning Contractors' Na-
tional Association, Inc. (SMACNA). 1991. Seismic
Gas pipe For the purposes of this chapter, "gas pipe" restraint manual guidelines for mechanical systems.
is any pipe that carries fuel gas, fuel oil, medical gas, Chantilly, Va: SMACNA.
vacuum, or compressed air. 11. The Sheet Metal Industry Fund of Los Angeles, Calif.,
and the Plumbing and Piping Industry Council, Inc.
Lateral force A force acting on a pipe in the hori- 1982. Guidelines for seismic restraint of mechanical
zontal plane. This force can be in any direction. systems. Los Angeles, Calif.
Longitudinal bracing Bracing that prevents a 12. U.S. Department of Defense. April 1973. Seismic design
pipe from moving in the direction of its run. for buildings. In Department of Defense Tri-Services
Manual. (TM-5-809-10. NAVFAC P-355, AFM SB-S
Longitudinal force A lateral force that happens Ch. 13) Washington, D.C.: Department of the Army,
to be in the same direction as the pipe. the Navy, and the Air Force.
OSHPD Ofce of Statewide Health Planning and 13. U.S. General Services Administration Public Buildings
Service. Design guidelines. Earthquake Resistance
Development (California).
of Buildings. Vol. 1. Washington, D.C.: Government
Positive attachment A mechanical device designed Printing Ofce.
to resist seismic forces that connects a nonstructural 14. U.S. Veterans Administration. Earthquake resistant
element, such as a pipe, to a structural element, such design requirements handbook (H-08-8). Washington,
as a beam. Bolts and screws are examples of positive D.C.: Veterans Administration Ofce of Construction.
attachments. Glue and friction due to gravity do not
create positive attachments.
Seismic Related to an earthquake. Seismic loads
on a structure are caused by wave movements in the
earth during an earthquake.
192 ASPE Plumbing Engineering Design Handbook Volume 1
10
INTRODUCTION
The plumbing system can be the source of one of the
most intrusive, unwanted noises in high-rise apart-
Acoustics in
Plumbing
Systems
ACOUSTICAL RATINGS OF The noise of the water ushing the closet bowl
PLUMBING FIXTURES AND is a function of the specic ow rate from the tank,
APPLIANCES the proximity of the tank to the closet bowl, and the
method of mounting the tank itself. While sound levels
The acoustical rating tests for xtures are still in as high as 90 dB(A) at 3 feet (0.9 m) are possible in
their infancy and have not yet been internationally
older style ttings with the tank located as much as
standardized. While some countries, most notably
6 feet (1.8 m) above the bowl, modern, close-coupled
Germany, do have useful standards, the United States
tanks, when properly installed (with bowl cover
has yet to formalize any plumbing acoustic tests. The
problem of adequately dening the direct airborne down), may be as low as 55 dB(A).
and structure-borne components of vibration still The noise of the tank relling is a function of its
constitutes a major problem in performing acoustic design, which includes the type of construction of
rating tests. Only the German standard DIN 52218, its envelope, the method of mounting to the wall (or
Laboratory Testing on the Noise Emitted by Valves, closet bowl), the type of tank valve used, the water,
Fittings and Appliances Used in Water Supply Instal- and the time required for the rell cycle. There are
lations (Part 1), has so far addressed this problem. many cases where the noise of the tank relling is far
Also, the International Organization for Standardiza- more annoying than the noise produced by the toilet
tion (ISO) has published standard 3822/1, Laboratory ushing. The noise of toilet tanks relling may be
Tests on Noise Emission by Appliances and Equipment as low as 40 dB(A) at 3 feet (0.9 m) in well-designed
Used in Water Supply Installations, and the American units incorporating quiet valves and silenced, tail-pipe
Society for Testing and Materials (ASTM) has assemblies. In poorly designed installations operating
established a project E-33.08B, Plumbing Noise, to at the maximum ow rate, this noise may be as high
investigate this problem.1 as 95 dB. Flush-valve operation can be as high as 95
The airborne sound radiated by showers, dish- dB, while blowout-type xtures have been recorded
washers, waste-disposal units, washing machines, at as high as 120 dB.
water closets and bathtubs is specied by the xture/ Urinals The noise associated with urinals is a func-
appliance manufacturer. The sound ratings for ttings tion of the wall-mounting method used to install the
are normally expressed in terms of sound power or xture and the ushing action of the urinalwater
A-weighted and octave-band levels measured in a re- discharge into the xture and the ejection of the ma-
verberant toilet room or kitchen-type environment at terials. The ush-valve operation may be as high as
a distance of 3 feet (0.9 m). Because of the differences 95 dB, with blowout units as high as 110 dB.
in the reverberations between one environment and
another, the characteristics of the test environment Bathtubs The noise from bathtubs is usually
should ideally have a reverberation time lying in the caused by the impact of a high-velocity water stream
range of 1 to 2 seconds and be independent of the into a glazed metallic, berglass, or acrylic bathtub.
frequency. While this noise varies during the lling cycle, it may
also be signicant during the drainage cycle.
Valves The sound levels from valves are dependent
In both cases, this noise is a function of the
upon the size of the tting, the mass ow rate, and the
bathtub material and its structural design as well
pressure differential across the tting. Sound levels
from taps and valves at a distance of 3 feet (0.9 m) as its method of installation, particularly the extent
may range between 30 and 50 dB(A) for well-designed of its structural decoupling from the walls and oor
and properly installed ttings, 50 and 70 dB(A) for (in order to reduce the acoustical impact on adjacent
adequately designed and adequately installed ttings, rooms or other apartments). In many European
and 70 and 90 dB(A) for poorly designed and poorly countries, the building regulations specify stringent
installed ttings. Improvements in the performance of decoupling procedures to minimize the structure-
faucets are most notably achieved through the incor- borne noise propagation. Outside these countries,
poration of aerators, which may result in reductions such procedures are relatively unknown and are not
in noise levels of as much as 15 or more dB. generally utilized. The noise of a bathtub lling typi-
cally lies in the range of 60 to 100 dB(A) at 3 feet (0.9
Water closets The noise from water closets can be m), depending on the ow rate. The point of impact
subdivided into: of the water stream with the side of the bathtub is
The noise of the water ushing the closet bowl. generally reduced by using an aerator on the spout.
Good design practice calls for the water spout to be
The noise of the water relling the tank.
installed so that the water stream is not directed to
The noise of a ush-valve operation, including strike the bottom of the bathtub.
water discharge into the xture and the ejection
of materials from the closet bowl. Showers Shower noise is mostly a function of the
oor surface in the shower enclosure and the type of
Copies of the DIN and ISO standards are available from the American National Standards Institute (ANSI), 1430 Broadway, New York,
1
NY 10018.
Chapter 10 Acoustics in Plumbing Systems 195
shower head. The constant-temperature controller is between 65 and 90 dB(A) at 3 feet (0.9 m), and few
only signicant when the water-pressure drop across manufacturers publish the sound-rating data.
it is unusually high or the method of supporting the An indirect discharge of the wastewater into a
pipe from the walls results in the generation of reso- trough or hub drain may be very loud in the room
nant noise. Shower noise typically lies in the range but may have a reduced noise transmission through
of 60 to 90 dB(A) at 3 feet (0.9 m). the piping system.
Dishwashers Dishwasher noise is a function of the GENERAL ACOUSTICAL DESIGN
basic design of the unit, the choice of the mounting
procedures employed, and the extent to which the Water Pipes
installer provides additional thermal and acousti-
Origin and spread of noise The causes of noise
cal insulation. The noise from dishwashers can be
are the surge due to the sudden opening or closing of
minimized by mounting the units on rubber isolation
valves and ow where the cross sections of such valves
devices or by providing layers of berglass or mineral
are greatly restricted. In addition, because of the high
wool insulation on their tops, rear and sides. Signi-
velocity, cavitation and turbulence are also created
cant noise is created by the activation of solenoids and
by the sudden changes in direction. The higher the
solenoid-activated valves that create water hammer
pressure head of the ttings, the louder the noise.
and sound propagation through the piping.
Water hammer arrestors (shock absorbers) may be
The use of exible connections and the incorpo- benecial in eliminating sound noise generated by
ration of surge eliminators to minimize the water these problems.
hammer are highly recommended. Typical noise levels Noises originate when a stream of water strikes
from dishwashers are in the range of 65 to 85 dB(A) the base of the bathtub, sink, or lavatory. In the emp-
at 3 feet (0.9 m) with peaks as high as 105 dB(A) cre- tying operation, gurgling noises often occur because
ated by solenoid operation. of the whirlpool action. These noises are conducted
Waste-disposal units Sink or waste-disposal-unit partly along the pipe and partly by the column of wa-
noise is a function of the design of the unit as well as ter. The pipes induce the walls and ceilings to vibrate
the design of the sink or basin to which it is attached. and radiate sound.
Lightly constructed, stainless-steel sinks or basins
Reducing the noise at its origin Fittings of
will tend to amplify the sound energy. The supporting
satisfactory design with a low noise level should be
cupboards or xtures may also have a similar effect.
employed whenever possible.
The sinks and basins used to support such ttings
should be designed to incorporate an effective damp- Flush tanks, in particular, can be substantially
ening of the bowl through the application of damping quieter than pressure ush valves, especially when
materials or framework. insulated. Low-ush, gravity-ush valve xtures will
The plumbing connection to the waste-disposal operate more quietly than high-velocity (blowout)
units should be exible at the inlet and the discharge. type xtures.
The noise levels produced by these units can vary The largest possible cross sections for the pipes
widely and most manufacturers do not publish the should be used and the water supply pipes in all criti-
noise-rating data. Noise levels can vary between 75 cal areas should be designed for a maximum velocity
and 105 dB(A) at 3 feet (0.9 m), depending on the of 4 ft/s (1.2 m/s).
method of mounting and the extent to which the The emptying noise can be reduced by using waste
protective covers are used. ttings to ensure that the air is simultaneously and
uninterruptedly sucked out of the stream of water
Washing machines Washing-machine noise is and carried away with it.
a function of the design of the unit and, to a lesser The pressure in the pipes inside of the building
extent, the method of mounting or type of plumbing can be reduced to the extent that the operating condi-
connections used. The airborne noise levels can be tions allow closed-circuit pressure.
somewhat reduced through the application of damp-
ening material on the inside surfaces of the enclosing Reducing the spread of noise The designer must
panels. make a distinction among the pipes laid on a wall,
those in a wall, and those in shafts.
The incorporation of isolation mounts does not
normally reduce the direct airborne sound but may In the case of pipes installed on a wall or in pipe
drastically reduce the structure-borne component shafts, structure-borne, sound-damping packing (e.g.,
audible in adjacent apartments or rooms and per- cork, felt, proled strips of rubber, or other elastic
ceptible vibration in the oor during spin cycle. The materials) should be inserted between the fastenings
noise levels produced by washing machines range and the pipe. The packing should not be compressed
by excessive tightening of the pipe clips. Instead of
196 ASPE Plumbing Engineering Design Handbook Volume 1
packing for structure-borne sound control, vibration 1. Apparatus and machines in which the noise is
isolation mounts should be used. predominantly transmitted as structure-borne
Pipes in the wall should be wrapped with sound- sound (e.g., motors, pumps, pressure-increasing
damping materials (e.g., felt, bituminized felt, or installations, ventilation machinery, drives for
viscoelastic damping materials) without leaving any elevators, gearing, and heavy switch gear) must
gaps. The same effect may be achieved by having pipes be sound insulated/vibration isolated from the
elasticity mounted in a rm outer casing. building.
Several pipes running in the same direction in 2. In order to reduce the structure-borne sound
shafts can be fastened to a single common rack. This transmission from the heating installations into
rack should not have any structural, noise-conducting occupied rooms,a concrete oating oor should be
connections with the walls. Common racks should be added in the rooms where the solid fuel is stored
fastened to the wall with rubber/metal connections and where there is heating equipment. The boil-
interposed. ers must be supported on vibration isolators and
When pipes pass through ceilings or walls, they be separated from other components and from the
should be taken through sound-control sleeves of oating oor. The pipes can be supported by col-
brous damping materials and resilient sealant. This lector blocks on the oating oor. Rigid fastening
approach must not adversely affect the airborne sound to ceilings, oors, or walls should be avoided.
control (for instance, through joints), in particular 3. Ceilings over rooms where there is heating equip-
in the case of party ceilings and walls of separate ment should be provided with a oating barrier
tenants. In the case of ceilings and walls that have consisting of plaster or gypsum board in order to
to be re resistant, this approach must be complied increase the airborne soundproong.
with when deciding on the re-rated sleeves that will 4. In the case of refuse-disposal installations, the
generally be sealed with a re-rated silicone foam. inside shaft should be constructed in such a way
In the case of apparatus and equipment, such as that the building is insulated against structure-
washing machines, spin dryers, bathtubs, and wash borne sounds. Whenever possible, low-noise
sinks that generate noise or in which noise occurs materials should be used. Metal sheeting should
during lling and emptying, resilient sound-damping be provided with a resilient impact-absorbing
materials should be used at the places where they coating on the inside and/or covering. The roof
touch or are attached to the structure. In the case of of the shaft should be made of sound-absorbent
bathtubs, a solid joint between the bathtub outlet and material.
the waste pipe should be avoided. Rubber pads under 5. Refuse bins should stand on a oating concrete
the bathtub supports are recommended. slab and be enclosed by walls and ceilings com-
Bear in mind, in the case of water pipes and ap- plying with the requirements for party walls and
paratus in or on walls that border occupied spaces, ceilings of apartments. If deector plates are
that the permissible loudness levels are not exceeded. provided, these devices must be xed in a exible
In such cases, conventional water-closet ush valves manner and with structure-borne sound insula-
should be avoided and quiet-acting siphon jet actions tion.
should be used.
Pumps
Occupied Domestic Spaces
Sources of noise The following items are some of
Keeping within the maximum allowable loudness
the major sources of noise from pumps in plumbing
levels in occupied rooms requires that steps be taken
systems:
during the planning and construction stages of the
building. The term occupied domestic spaces gen- 1. Unbalanced motors.
erally covers hotels, motels, dormitories, and other
2. Pulsation of the air mass ow from electric fans.
locations where, in addition to domestic appliances,
(This is a major source of noise in 2-pole, fan-
the elevators, incinerators, ventilation equipment,
cooled, electric motors. The noise from the fan
switch gear, boilers, and refuse-disposal installations
is usually so dominant that all other sources of
can cause unacceptable noise levels in habitable ar-
noise in the electric motor can be neglected.)
eas, particularly sleeping quarters. As early as the
planning stage, the various points requiring consid- 3. Pulsation of the magnetic eld in the electric
eration must be taken into account by the plumbing motor.
designer. 4. Motor/gear/pump journal and thrust bearings.
Because of the multiplicity of inuences involved,
5. Contacting of the components in parallel-shaft
no simple or standard rules can be given for keeping
and epicyclic gears.
within the permissible loudness levels. For some
groups of installations, the following criteria apply: 6. Imbalance of the pump impellers.
Chapter 10 Acoustics in Plumbing Systems 197
7. Pulsation in the pumps. (Hydrodynamic noise 6. Pump impeller blades. The clearance between
generation is inherent in all types of pumps; the the tip of the impeller and cut-water should be
fundamental frequency of noise, when the pump increased (a maximum of 85% impeller diameter
runs at the design point, is governed by the to volute diameter is recommended).
number of blades and their interaction with the 7. Impeller and guide-vane tips. Should be dressed
volute cut-water or diffuser guide vane ring. The in order to reduce the thickness and intensity of
intensity of the noise generated and the relative the trailing wakes.
strength of the various harmonics produced are
determined by the velocity prole shape leav- 8. Out of balance. Should be balanced to fine
ing the impeller passages, vortex wakes shed by limits. Impeller, motor, blades, and rotor should
vanes, and the impulsive effect as they pass under be balanced at all rpms to eliminateor mini-
the volute cut-water. The impulse wave form, mizevibrations.
although very complex, can be resolved into a fun- 9. Cavitation. The suction characteristics of the
damental equal to the speed times the number of installation/system should be improved. (Ideally,
blades and a series of harmonics. Manufacturing the pump should always be under positive head
errors, which produce angle or pitch variations at the pump suction.)
between the blades, are instrumental in gener-
ating a less-prominent series of harmonics with Plant noise The resulting noise output of the plant,
fundamental frequency equal to the speed with as installed on the site, is dependent upon all of the
the amplitude and/or the frequency modulation above factors coupled with the induced resonance of
of the blade-passing frequency. At off-design op- the adjacent parts (such as pipes, bedplates, fabricated
eration, unsteady ow conditions can arise due stools, tanks, and panels). These factors form part of
to ow separation and rotating stall effects.) the nal environment of the pump and are discussed
under the section Noise and Vibration Control,
8. Cavitation. (Air is entrained in the solution, which
which follows. The effects are best investigated by
can damage the pump; impellers constructed
determining the natural frequency of these parts, by
with open-grain material, such as cast iron, may
separate excitation, or by operating the pump through
disintegrate because of the implosive effect of
its service-speed range. The natural frequency of
cavitation.)
the part can be modied by a simple trial-and-error
Possible modications Obviously, if the overall stiffening or damping.
noise level of the pumping plant is considered to be Other effects are also likely to appear for the
too high to comply with the accepted specications, rst time on the site. One of them is the interaction
identifying and reducing the noise output from the of the pump with the intake sump. Testing a model
components and equipment in the plumbing system of the sump intake before installation can prevent
contributing the most noise will yield the most dra- air-entraining vortices, eddies, and distorted ow
matic results. distributions, which cause a mismatch at the impeller
Some possible modications the plumbing en- leading edges. Vortex formations generated entirely
gineer should consider in order to reduce the noise below the water level can be particularly troublesome
output from the system are as follows: in actual practice, since these formations are caused
1. Gearbox. A silencing enclosure or cladding by water spinning at high velocities, which causes
should be provided. submerged cavitating vapor cores to be generated and
drawn into the sump intake. These vortices cannot be
2. Motor fan. A silencer should be provided at
the air inlet and outlet or, if possible, the design observed on the site; however, they can be prevented
should be modied. at the outset by testing the sump model with observa-
tion windows tted below the surface level.
3. Motor rotor. The number of slots should be Associated venturi-meters, valves, and pipes, in
changed or, if possible, its design should be modi- the nal installation, contribute to raising the general
ed. noise level of the station. Water at high velocities
4. Pump and pump bearings. Sleeve types should be passing through partially closed valves, particularly
employed. in high-pressure systems, can produce severe cavita-
5. Pump operation. The pump should be operated tion noise, which is generated by the rapid collapse of
near design ow conditions in order to achieve the vapor bubbles against the walls of the valve and
the correct system matching. (Modifying the downstream pipe. Sound-pressure levels of 110 dB
characteristics of the system or altering the di- have been recorded.
ameter of the impeller, resulting in operation at These high sound-pressure levels can be greatly
lower speeds, will make the pump operate more reduced by using multistage pressure breakdown
quietly.) systems and by paying special attention to the valves
198 ASPE Plumbing Engineering Design Handbook Volume 1
port design. Thick-walled pipe and external acoustic If the ow velocity changes abruptly (e.g., by the
installation are only effective for localized noise sudden closing of a tap or valve), the pressure increase
reduction; they do not reduce the noise in the uid can be determined by using the following equation:
stream but shroud it where treatment is used. Much Equation 10-3
of the noise is still carried downstream and, at times,
upstream as well, depending on the system. Poor Pr = WaV
144g
pipe design, involving many sharp bends and sudden where
expansions and contractions, can induce considerable Pr = Pressure rise, lb/ft2 s
turbulence and noise. W = Specic weight of liquid, lb/ft3
Estimating the noise level of a pump Small, a = Velocity of pressure wave, ft/s2
motor-driven pump sets, which are commonly em- V = Change in ow velocity, ft/s
g = Acceleration due to gravity, ft/s2
ployed in plumbing systems, can be conveniently
tested in an anechoic chamber with accurate results. The pressure generated by water hammer may
However, the most important sources of sounds in cause straight pipe lengths to vibrate. If the pipes are
large pumping stations are usually associated with in close contact with the walls and not xed at suf-
custom-built units. ciently rigid short intervals, they may strike against
Pump noise levels are measured by the near-eld the walls with a succession of blows.
technique 3 feet (0.9 m) from the unit in order to If such ttings (solenoid valves, foot-action valves,
minimize the sound transmissions from pipe coupled spring-loaded taps, and check valves) could be elimi-
to the pump. The sound-pressure level, at 3 feet (0.9 nated, then the incidence of water hammer could be
m) from the pump, can be estimated by using the greatly reduced. However, as these ttings are inte-
following equation (presented in the International gral parts of a plumbing installation, the designer
System of Units, or SI units, which is the best means must allow for this condition. The following guidelines
for available test data): are recommended to the plumbing engineer:
Equation 10-1 Maintain a water velocity in the range of 4 ft/s
Pump sound-pressure level = 163.9 + (1.2 m/s) at the appliance.
8.5 log (rpm specic (volume ow rate head)
speed impeller diam. impeller width)
Secure the piping so that it does not come into
contact with the building structure.
where
Pump sound-pressure level = dB(A) Use rubber isolators.
Volume ow rate = L/s The use of air vessels (chambers) will reduce
Head = stages/m the effects of water hammer. A vessel with a exible
Specic speed = m/s membrane to separate the air chamber from the
Width and diameter of impeller = mm
water (water hammer arrestor or shock absorber) is
Where the noise characteristics of a particular recommended to prevent loss of air.
pump are already known, the change of the noise Design Procedures
level with the pump speed can readily be determined
by using the following equation: To provide a plumbing system that conforms to spe-
cic acoustic standards, the designer requires the
Equation 10-2 following information:
dB = 50 log ( N1
N2 ) 1. The maximum noise levels allowable in each
habitable room.
where
N1 and N2 = Pump speeds 2. Location of equipment with respect to adjacent
Flow Velocity and Water Hammer spaces.
In simple terms, the magnitude of the pressure 3. The data on the acoustic performance of the build-
increase due to water hammer is a function of the ing materials and the method of construction.
velocity of the pressure wave and the rate of exchange 4. The acoustic ratings of the plumbing appliances
of the ow velocity. The velocity of the pressure wave and xtures, piping, and valves.
(which is the same as the velocity of sound in the
5. The acoustic performance of the noise-isolation
water contained in the pipe) depends on the physical
devices that can be incorporated in the plumbing
properties of the water and of the pipe material. For
installation (i.e., vibration mountings and rubber
all commercially available copper pipes, the velocity
spacers).
of the wave propagation has a value in the range of
3000 to 4000 ft/s (915 to 1220 m/s). 6. The data on the effects of the background noises
to screen out the effects of the plumbing noises.
Chapter 10 Acoustics in Plumbing Systems 199
7. Supervision of the plumbing installation in order often can communicate with the surroundings only by
to ensure adherence to the acoustic details. setting the enclosure into vibration. These vibrations
Specific acoustic performance guarantees for may radiate sound directly or may be transmitted
plumbing installations should be avoided where through the supporting structure, to be converted to
sufcient research has not been carried out. On any airborne sound elsewhere.
critical projects, the retention of an acoustical con- Vibration isolators, such as resilient mounts and
sultant may be essential. In the end, the nal results resilient pipe hangers, are commonly used to reduce
are as much dependent on the quality of the work- structure-borne vibrations. Theoretically, in order
manship and supervision as they are on the design to design an adequate isolation system, the engineer
details. Many well-designed projects fail to achieve must realize how much vibratory force is generated
the required performance because of inadequate by the equipment and the maximum permissible force
supervision, which is necessary in order to pinpoint transmission to the building. Since these design pa-
and correct substandard details. rameters cannot readily be obtained, some practical
guidelines have been formulated to provide effective
Noise and Vibration Control isolation at a reasonable cost. These are generally
All noise-control problems can be reduced to three adequate for all but the most critical or special ap-
basic elements: source, path, and receiver. plications (such as very light or exible structures
Noise-control problems frequently involve con- or equipment installed above adjoining very quiet
sideration of several sources of noise, several paths spaces).
for the transmission of noise, and several different To ensure that the desired noise isolation is
receivers. The relationship among these elements de- achieved, a detailed vibration-control specication
nes the seriousness of the problem. In order to solve and its stringent enforcement are required. With
a noise problem, the source strength can be reduced, increased public awareness of noise, government
the path can be made less effective in transmitting agencies such as the General Services Administra-
sound, or the receiver can be made more tolerant tion (GSA Guide Specication Number 4-1515-71,
of disturbance. However, most practical solutions Public Building Service) and Federal Housing Ad-
involve a trade-off, so concentration on only a single ministration (FHA A Guide to Airborne, Impact and
aspect of the problem may result in over-design or an Structure-Borne Noise Control in Multifamily Dwell-
unsatisfactory solution. ings) have established recommended guidelines on
For sources that not only produce noise and vi- noise and vibration control.
bration problems but also have the potential to lead However, it is not enough merely to have noise-
to damage or decrease the useful channel space for control specications. Adequate detailing techniques
liquids, it is desirable to reduce the source strength. are most essential for communications between the
Cavitation is a typical example of this kind of prob- design engineers and the contractors. For most situ-
lem. The solution to this problem hinges on the pump ations, acoustical details are well developed and are
suction (i.e., net positive suction head, NPSH). One available for most applications. From a practical point
may consider placing the pump at a lower elevation, of view, most plumbing xtures cannot be effectively
if practical, or one may improve the suction piping isolated, although they can be installed to minimize
and raise or pressurize the supply tank. In recent vibration.
years, efcient suction-assisting devices (such as When pipes are connected to vibrating equipment
booster pumps) have become commonly used where installed on vibration isolators, sufcient exibility
low NPSH must be handled at low cost. Several must be built into the piping systems to match the
manufacturers supply add-on or built-in inducers for equipment vibration isolators. In addition, adequate
end-suction pumps. exibility is required in order to protect the equip-
For noise and vibration sources that do not in- ment from any strains imposed by misalignment and
uence systems operating conditions or reliability, by thermal movement of the piping. Piping exibility
control of noise transmission (i.e., the path) from can be achieved by the inherent resilience of the pipe
the source to the noise-sensitive area may be the in simple bend-and-loop congurations (if there is suf-
most economical solution. Noise may be transmitted cient length) or by the use of exible pipe connectors,
through structure-borne, airborne, and uid-borne which also attenuate the transmission of noise and
paths. Structure-borne noise travels in the form of vibration along the piping system. However, their use
high-frequency structural vibrations; airborne noise as vibration-isolation devices should be considered
travels in the form of sound waves; and uid-borne very carefully for the following reasons:
noise travels in the form of pressure uctuations. The
They are the weakest component in the piping
structure-borne path usually plays an important role
system. (Without proper specication of the mate-
because the noise source within the pump, or piping ,
200 ASPE Plumbing Engineering Design Handbook Volume 1
rial, installation, and maintenance, they may fail Good matching between machine characteristics and
and cause severe water damage.) system requirements is essential for performance,
In many instances, sound energy may ank the as well as for noise control. For example, in a sys-
exible pipe connectors so that pipe-wall noise is tem operating over a narrow load range, a pump of
exited downstream of the resilient break. Indeed, single-volume design (selected for near-peak efciency
the various restraints added by the manufactur- operation) is acceptable because the unbalanced
ers to reduce the possibility of failure make the radial load on the impeller is the least at optimum
exible pipe connectors almost as rigid as the pipe delivery.
itself. Adequate criteria should be established for equip-
ment vibration to ensure that there are no excessive
Studies have found that exible pipe connectors
forces that must be isolated or will adversely affect the
are most effective in the case of cavitation. Flexible
performance or the life of the equipment. There are
pipe connectors have also been found to be effective
many ways to develop equipment-vibration criteria. A
in the attenuation of the tonal components at the
simple but satisfactory approach would be to use the
impeller passage frequency of a pump.
criteria that have been developed on the basis of the
Equipment design Quiet operation of pumps experience of persons and rms involved with vibra-
begins with proper design. Although todays state- tion testing of mechanical equipment in the building
of-the-art design and development of pumps and construction industry.
plumbing xtures has a long heritage, noise is still
Pressure Most model plumbing codes have estab-
seldom considered by the manufacturer. This is per-
lished the rate of ow desirable for many common
haps because of the designers lack of awareness and
types of xtures as well as the average pressure
experience, but even knowledgeable designers yield
necessary to provide this rate of ow. Although the
to economic pressures for cost reduction.
pressure varies with the design of the xture, a pres-
It is obvious that the primary purpose of a pump
sure of 5 to 8 psi (34.5 to 55.2 kPa) at the entrance
or plumbing xture is to move liquids and to perform
to the xture is generally the minimum required for
the necessary plumbing functions. These consider-
good service at lavatory faucets and tank-type water
ations must come rst. However, noise and vibration
closets. A pressure of 15 psi (103.4 kPa) may be ample
controls should be integrated in the design and may
for most of the manufacturers requirements. Some
then be expected to lead to improved performance
xtures, especially wall-hung water closets, require
with little or no cost penalty. Quite often, the cost of
a pressure up to 25 psi (172.4 kPa).
modication is negligible. The key to effective noise
Water pressure in many mains is typically 50 to 80
control is a complete understanding of the noise-gen-
psi (334.7 to 551.6 k Pa). As the water ows through
erating mechanisms.
a pipe, the pressure continually decreases along the
By simply changing the cut-water clearance of
pipe, due to the loss of energy from friction and the
a pump, a major reduction in the blade-passage-fre-
difference in elevation between the water main and
quency noise is achieved. Similarly, water faucets can
the xture.
easily be designed for quiet operation. For a particular
From a noise-control point of view, it is desir-
value of pressure drop, a valve can be designed to
able to keep the xture inlet water pressure as low
minimize cavitation and its resulting noise within
as possible. This condition usually can be achieved
the water-pressure design range.
by installing pressure-regulating devices in order to
Some water-closet manufacturers indicate that,
balance the pressure gradient in the water system.
like dishwashers and food-waste disposers, economy
Many cities experience large pressure uctuations in
models are noisier than more expensive ones. Nev-
the hydraulic gradient of their water systems due to
ertheless, quietness in water closets is a marketable
demand changes (such as after working hours). The
attribute. One of the problems with ush-valve-op-
inlet water pressure must be kept higher than the
erated water closets is the high initial noise impulse
required minimum pressure to ensure good service.
that is associated with the opening of the ush valve.
The alternative, if it were practical, would be to have
However, if the valve discharges against a properly
continuous adjustments of the systems inlet pressure
selected resistance, the noise impulse can be substan-
as the demand changes. The system pressure also has
tially reduced. There is no doubt that a cost-saving,
a great effect on the occurrence of cavitation. The
quiet xture could be achieved with more research.
plumbing system must be operated at a pressure level
SYSTEM DESIGN high enough to prevent cavitation.
Equipment selection To select a quiet unit, the Speed Changes in the operating conditions of the
engineer must have an understanding of the noise pump have a signicant effect upon the level of pres-
characteristics of plumbing xtures and appliances. sure uctuations, particularly for plumbing systems
Chapter 10 Acoustics in Plumbing Systems 201
It keeps the external, impervious cover separated systems are discussed in this section. However, most
from the surface. plumbing noise problems are not caused directly by
It attenuates sound (particularly, at high frequen- the noise radiated to the air from these sources. Usu-
cies). ally, the plumbing system transmits the sounds so that
the mechanical vibration follows its support system to
It reduces the amplitude at the resonant fre- the surface and is eventually radiated as noise.
quency dened by the mass of the cover and the
A complete discussion of vibration-isolation
stiffness of the layer of porous material.
theory is beyond the scope of this chapter. Only the
The typical noise reduction from a pipe wrapping methods of vibration control that are readily applied
is in the range of 0 to 5 dB at low frequency and 15 and broadly useful in practical problems are consid-
to 25 dB at high frequency. ered here. This chapter does not address the various,
System layout A system that is undersized (or specic, vibration-control techniques that are useful
that contains a section of undersized piping) will usu- only in the hands of a specialist or that require de-
ally generate excessive noise. It is good engineering tailed measurements and analyses.
practice to use simple-design pipe layout (i.e., long Selection criteria A vibration-isolating device
straight runs with a minimum of elbows and tees ) should be selected using the following criteria:
and long radius elbows and connectors. The straight
1. It must be soft enough to provide the desired
run can be estimated as being 12 times the diameter isolation effect and have a stiffness that is less
of the pipe. Piping layout near pumps and valves is than the local stiffness of each of the items it
also of great importance. Figure 10-5 illustrates some connects.
examples of suction-piping installations.
2. It must provide a natural frequency that is consid-
Vibration isolation The sources most commonly erably lower than the lowest excitation frequency
responsible for the generation of noise in plumbing of concern.
3. It must be capable of carrying the loads imposed common vibration-isolation devices are illustrated
on it. in Figures 10-6 and 10-7. Additionally, refer to Table
4. It must be able to withstand the environment to 10-1 for the recommended static deection for pump
which it will be exposed. vibration-isolation devices.
Steel springs Steel springs are available for almost
Vibration-control devices In plumbing systems, any desired deection. These devices are generally
vibration-control devices generally consist of steel used as vibration isolators that must carry heavy loads
springs, air springs, rubber isolators, pads or slabs where more isolation performance is desired than rub-
of brous (or other resilient) materials, isolation ber or glass ber provides or where the environmental
hangers, exible pipe connectors, concrete bases, or conditions make other materials unsuitable. They are
any combination of these items. Some of the most generally available for deection only up through 4
GLOSSARY
Acoustics The study of airborne sound and struc-
tural vibration propagation over the frequency range
2 to 20 kHz.
Decibel The unit used to qualify the level of sound
(or loudness) relative to an arbitrary reference point
[zero is equal to 20 Pa (20 x 10-6 pascals)]. These units
are also employed to quantify sound power. This unit
is the smallest increment of change in sound intensity
that a normal human being can detect, while a 10-
decibel change of increasing or decreasing sound is
commonly regarded as a subjective doubling or halv-
ing of loudness, respectively. Abbreviated dB.
Decibel (A) scale A frequency-modied sound level
in which low-frequency and high-frequency sounds
are attenuated in a similar manner to that in which
the human ear responds to wide-range sounds. It is
the most common unit used for sound measurement
to relate sound intensity to normalized subjective
loudness. Abbreviated dB(A).
Hertz The unit of frequency internationally ac-
Figure 10-9 Suggested Mounting of Piping and cepted to be equivalent to cycles per second of sound. 1
Plumbing Fixture
Hertz is equal to 1 cycle/second. Abbreviated Hz.
1. All piping in the equipment room. Net positive suction head (NPSH) Actual uid
energy available or required at the inlet of a pump.
2. All piping outside of the equipment room, within
50 feet (15.2 m) of the connected pump. Noise criteria (NC) curves Employed to assess
loudness or annoyance on an octave band basis.
3. All piping over 2 inches in diameter (nominal
These noise criteria (NC) curves have been partially
size) and any piping suspended below or near a
superseded by the preferred noise criteria (PNC)
noise-sensitive area.
curves.
4. The rst three (3) supports provide the same
deection as the pump vibration isolators. They Octave A doubling of the frequency. Also used as the
most common frequency division for the specication
Chapter 10 Acoustics in Plumbing Systems 207
worth and its cost. For a facilities construction project, projects life-cycle. In this regard, it is important that
best value is a nished project that will consistently the concept of a team be immediately integrated
perform its required basic function and has the low- into all aspects and phases of the project. For it is this
est total cost. Therefore, construction of a facility team that needs to ultimately be responsible for the
can yield maximum value when value engineering is nished project and its nal total cost.
incorporated into the project. This is accomplished by As with any project, there are three major com-
providing and developing alternatives that produce ponents that comprise the cost cycle: Material costs,
the desired results and maintain the quality and reli- labor costs, and administrative and operation cost
ability of the project utilizing the most efcient and (which is typically described as overhead). It is up
effective mix of resources at the least cost. to the team to constantly monitor and evaluate all
It would seem that implementing value engineer- aspects of the project, including any changes and mod-
ing would be fairly simple; all you need to do is control ications that may affect the quality, life-expectancy
and/or reduce costs. First, however, we need to have or life-cycle, maintenance cycles, and reliability of
some perspective about where, how and why value each aspect of the project; from development through
engineering will be applied. For the plumbing engi- engineering, design, and construction. Interestingly,
neer and designer, the most typical application is the although labor is a major component for each area
creation of a building. In this regard, there are at least of a buildings creation, it is not often subject to any
three major aspects of costs that will be of concern in-depth analysis in value engineering. Instead, the
to the overall development/engineering/construction main effort of value engineering is directed at the cost
team: The development costs, the engineering and and value of things the cost of the elements of
design costs, and the construction costs. Within these construction, the functionality of each element, and
three areas all related costs associated with the cre- the materials and products being utilized.
ation of a building will be lumped, such as property The Intent of Value Engineering
acquisition, inspections, licenses and permits, build-
In 1965, the U.S. Department of Defense conduct-
out, nishing, etc.
ed a study to evaluate cost-saving opportunities that
In the end, there is one person or organization
could accrue from the use of value engineering. The
concerned with the total picture in the creation of
study examined a number of projects and analyzed
a buildingthe owner or developer. And, as noted
415 project changes that were considered successful
earlier, value engineering can be introduced at any
value changes. The result of the study was that
point in the construction or life-cycle of the project.
only a limited number of factors could achieve over 95
Therefore, for maximum efciency and to assure
percent of cost savings. These factors were: Excessive
maximum value, value engineering needs to be inte-
cost, additional design effort, advances in technology,
grated from the beginning and continue throughout a
and the questioning of specications.
Percent Total
Reason for Change Savings Achieved Change Denitions
Advances in technology 23 Incorporation of new materials, components, techniques or
processes not available a the time of the previous design effort.
Additional design effort 15 Application of additional skills, ideas and information available
but not utilized during previous design effort.
Change in users needs 12 Users modication or redenition of mission, function or
application of item.
Feedback from test/use 4 Design modications based on user tests or eld experience
suggesting that specied parameters governing previous design
were unrealistic or exaggerated.
Questioning specications 18 Users specications were examined, questioned, determined to
be inappropriate, out-of-date or over specied.
Design deciencies 4 Prior design proved inadequate in use (e.g., was characterized
by inadequate performance, excessive failure rates or technical
deciency.
Excessive cost 22 Prior design proved technically adequate, but subsequent cost
analysis revealed excessive cost.
Other 2
Source: Directorate of Value Engineering, Ofce of the Assistant Director of Defense as taken from Value Engineering Theory & Practice in
Industry, Thomas R. King, 2000, Lawrence D. Miles Foundation, Washington, DC.
Figure 11-1 Qualitative Results From the Implementation of Value Engineering
Chapter 11 Basics of Value Engineering 213
The study (see Figure 11-1) revealed: no single system, etc. Or, alternately stated, worth is the least
factor was ever dominant in the implementation of cost to provide the function, product, or service. Still
value engineering. It was rare for the implementa- confused? Its no wonder. The concept of value and
tion of the change the result of a bad design; trying worth are amorphous; they are not easily measured or
to second-guess a design looking for deciencies dened. A number of basic questions were developed
provided little value, because the majority of designs as part of the concept of value engineering. To help
perform as expected. What was discovered is that determine value and worth, it is important to
many designs did not always provide maximum value note that these questions relate to the general nature
due to excessive costs, over specifying and the lack of of value engineering, and are relevant for all types
value for the project. of engineering, from construction to manufacturing.
What is Value? They have been modied below to be more construc-
tion specic.)
Value means different things to different people.
Thus, there is no one perfect denition of value. For 1. Are the products, systems, and materials neces-
purposes of value engineering, value does not simply sary for the functionality of the project, and do
equate to cost reduction. There are all kinds of they contribute value to the project?
values economic, moral, social, political, etc. In 2. Are the costs of the products, systems, or materi-
terms of value engineering, it is the economic value als in proportion to their usefulness within the
that most conforms to what is being measured or project?
evaluated. Value, then, is: 3. Do the designed or specied products, systems,
The lowest cost to provide the necessary and or materials need all the designated features?
required products, functions, or services at the 4. Are there other products, systems, or materials
chosen time to its needed place with the requisite available that will accomplish the intended use
quality. or purpose and provide better performance?
For engineering purposes, value can be best de- 5. Are the exact products, systems, or materials
ned by the following formula: available for less?
Value = Worth 6. Are there other products, systems, or materials
Cost
In this formula, when value is equal to or greater available that will accomplish the intended use
than 1 (V=1), it is understood that there is equality or purpose at a lower cost?
of value. As an example, consider the specication of 7. Are there other products, systems or materials
a vacuum pump. The pump is vital to the function of available that will accomplish the intended use
the design. If the pump costs $1,000 and it is indeed and purpose with an equal performance?
worth $1,000, then there is equality of value (good 8. Is there another dependable supplier that can
value). If the pump is only worth $800 and cost provide the products, systems, or materials for
$1,000, then there is imperfect value (poor value). If less?
the pump is worth $1,200 and cost $1,000, then there
9. Does the total cost of the products, systems, or
is increased value (outstanding value).
materials include all materials, reasonable labor,
Which then brings up the whole concept of cost and overhead?
and worth. Cost seems pretty straight forward. Its
what you pay for the product or service. But, what 10. Are the products, systems, or materials the proper
is worth? For value engineering purposes, worth ones considering the quantity available or manu-
is the concept of the value of a function, product,
Job Plan Phases
Noted Practitioners Name SAVE*
Miles Fowler King Parker Mudge International
Information Preparation Information Information General Information
Analysis Information Function Analysis Function Information Function Analysis
Creativity Analysis Creative Creative Function Creative
Judgement Creativity Evaluation Judicial Creation Evaluation
Development Synthesis Implementation Development Evaluation Development
Development Presentation Investigation Presentation
Presentation Implementation Recommendation
Follow-up Follow-up
factured, or the quantity that is needed and will The value engineers job is compounded by having to
be used? collect information from many individuals and disci-
plines. For this reason, it is best to integrate value
ELEMENTS OF VALUE engineering throughout each phase of the project:
ENGINEERING Conception, design, engineering, bidding, construc-
In the world and vernacular of value engineering, tion, commissioning, and occupancy.
a value engineering analysis incorporates a VEJP For the plumbing design portion of a facility, the
(Value Engineering Job Plan). Because this analysis value engineer must follow the engineers thinking
is in itself an engineering project, the job plan is di- and collect and assemble the same information used
vided into phases. The number of phases can vary by the engineer (see gure 11-3). This means detailing
(see Figure 11-2). It all depends on what expert you every product and design element.
have learned from, what books youve read and what
direct experience you have had in conducting value ABC Project Plumbing Design
engineering projects.
Project Description Documents
It doesnt really matter how many phases there Original Client Directions/Specications
are in a VEJP. What is vital is that the engineer Architectural Drawings
be comfortable with all the phases of his/her plan, Engineering Drawings
understand the various techniques for each phases Detail Drawings
evaluation and analysis, and that the plan provide Materials List
Details of Materials Examined/Considered
a systematic and consistent approach for imple- Material Line Information
mentation of the project. This introduction to value Product List
engineering integrates the six general phases as listed Details of Products Examined/Considered
by Society of American Value Engineers (SAVE) with Product Line Information
the ve phases from Lawrence E. Mills (considered the Vendor Information
father of value engineering) and incorporates the Figure 11-3 Information Gathering
various techniques of implementation within each.
Phase One: Information There are many variations of VE worksheets, but
This phase addresses three questions: What is it? typically they include the basic information form that
What does it do? and What does it cost. In practice describes the project and related data such as in Figure
this phase describes the project and collects the nec- 11-4A. Additional information forms such as Figure
essary information, both critical components for the 11-4B, allow each detail of the project or design.
remainder of the value engineering project. Actually, The next phase of the information collection pro-
gathering information is pretty simple and straight- cess is to understand the background and purpose of
forward. The really hard part is making sure the the complete project and each of its elements. This
information gathered is factual, accurate, unbiased, requires developing the right questions or checklist of
untainted by opinion, and contains no assumptions. items that need to be collected, understood, and used
As every plumbing engineer knows, the hardest for the remainder of the engineering process. Figure
part of the project is collecting accurate and factual 11-5 is a sample of such a checklist.
information. A project can only be engineered and As the VE collects all this information, he/she
designed according to the quality of information needs to keep a detailed record of information sources
used. Likewise, value engineering is only as good and types of actions needed or taken. This record
and accurate as the quality and accuracy of the data provides the forensic trail that will backup the nal
and information collected and used throughout the conclusions. It is a way to track each stage of the
process. information collection process and provides a refer-
The information phase of value engineering is ence record and a source record for the analysis and
the heart of the overall process. It is also undoubt- recommendations. A sample of a source record form
edly the hardest to explain and understand as the is shown in Figure 11-6.
collection of the data that will be vital to a successful With all the information and data that has been
value engineered result is often colored by layers of collected, the engineer must still make a qualitative
subjectiveness, biases and lack of objectivity. determination of its value. The following can help
The key to successful information gathering is make that determination of questions:
being prepared. The value engineer, like the plumb- 1. Does the information/data support the deni-
ing engineer, depends on organization and structure tion/specications/requirements of the project?
and design standards. The value engineer collects 2. Does the information/data seem to be factual and
the key information in a standardized format. The valid for the project/detail being analyzed?
use of forms or checklists is helpful in this endeavor.
Chapter 11 Basics of Value Engineering 215
Name of Project:
Detail Name:
Description:
Detail Location:
Description:
Drawing Number:
Pertinent Information:
Name of Project:
Project Location:
Address:
City: State: Zip:
Lot Number: Lot Description:
Owners:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Developers:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Architects:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Engineers:
Structural:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Electrical:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Plumbing:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
HVAC:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Communications:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Other:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Name of Project:
Project Location:
Address:
City: State: Zip:
Lot Number: Lot Description:
Owners:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Developers:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Architects:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Engineers:
Structural:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Electrical:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Plumbing:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
HVAC:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Communications:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Other:
Address:
City: State: Zip:
Telephone: Fax: E-mail:
Project Details
1. Detailed Specificatons established by user/owner:
3. Project Considerations:
A. Environmental Conditions (before, during, after):
C. Desired/Required
a. Reliability:
b. Serviceability:
c. Maintainability:
c. Operability:
4. Prior Experiences/Concerns
A. History of projects:
B. Operation of projects:
C. Maintenance of projects:
5. Anticipated Market
A. Requirements:
B. Expected Percentage of Total Market:
C. Market Expected to Serve:
6. Anticipated Life
A. Of Original Built Project:
B. Total Life With Rehab:
7. Project Competitors:
12. Are There Any Special Processes or Uses for the Project:
Detail/Product/Material Specification
Detail/Product/Material Description:
3. Detail/Product/Material Considerations:
A. Environmental Conditions (before, during, after):
C. Desired/Required
a. Reliability:
b. Serviceability:
c. Maintainability:
d. Operability:
e. Special Features:
7. Detail/Product/Material Competitors:
9. For the Detail/Product/Material What Are Desired (consider weight, dimentsions, tolerances, shock and
vibration, facility environment, operating environment, life, performance, appearance):
A. Physical Requirements:
B. Performance Requirements:
C. Workmanship Requirements:
13. Are There Any Special Processes or Uses for the Detail/Product/Material:
3. Is all the information/data current and up-to- The are two primary elements of establishing the cost
date? of a design/product/material: the material cost and
4. Does the information/data form an integrated the labor cost. It is important to note at this juncture
whole? Does each item support the other items? that a cost is not the same as the acquisition price.
Cost determination becomes complicated by economic
5. Are there any conicts within the information/ forces applied throughout the project life-cycle. There
data collected?
are project costs, development costs, product/assem-
6. Does the information/data conform to the expecta- bly/material costs, labor costs, overhead costs and, of
tions of the investigator? course, a markup for prot.
7. Is there information/data that is suspect? Does All the costs associated with a project need to be
some of the information/data seem to be inaccu- determined. Furthermore, they need to be segregated
rate or nonrepresentative of the project/detail? into actual and estimated, and a record must be kept
of the original source for the information/data.
8. Is there additional information/data that needs
to be collected? What is Cost? Value engineering is big on the term
9. Do the relationships/associations between the in- cost. However, as noted earlier, cost can mean dif-
formation/data sets require further exploration? ferent things to different people and for different
reasons. The rst important law is that, in most
10. Is there any reason to suspect that any of the instances, cost and price are not synonymous. Con-
information/data is biased, not objective? sider cost to be the valuation of labor, time, and other
11. If the information/data causes any concern or cre- resources used to achieve the end result. A price is
ates a restrain to the analysis can, it be veried a xed sum for a given item or service that results in
by more than one source? the transfer of ownership of the product or service.
Determine/Collect Costs: Collection of the costs The difference between cost and price is often noth-
related to the project/detail/material being analyzed ing more than perception (i.e., whether you are the
is the next step in the information/data collection buyer or the seller). So, for example, the cost of the
phase. Cost determination can quickly become com- product for the seller is included in the price to the
plex and overwhelming. Sufce to say, the smaller the buyer. On the other hand, the price to the buyer may
design element of a project such as a stand-alone be the cost and additional value will be added to
product, like a pump or water heater that is being determine a new and different price.
analyzedthe easier it will be to come to grips with In value engineering, the primary element is cost!
a cost determination. The total value engineering of Of course, to complicate matters there are product
a facility will involve determining costs for all aspects and producer costs and total cost to a user. For most
of the development, engineering, design, construction, facility projects, both of these cost structures are go-
and commissiong of the project. ing to be part of the analysis.
For the value engineer, these costs are a measure- There are three costs involved with any proj-
ment tool for the other information/data that has been ect/design/material: The major or prime costs, the
collected and a determinant of the economic impact overhead costs, and the cost of goods. The best way
of the item under consideration (and thus a measure to describe all this is with a simple diagram (see
for the level of effort that should be applied.) Figure 11-7).
{ }
Profit
Selling Costs
}
General and Administrative Costs
Final Purchase/
Selling Price Field Service and Miscellaneous Costs
Indirect Labor
Indirect Material Cost
}Overhead Costs
Acquisition
Costs
Cost of Goods
Purchased/
Installed
Direct Labor
}
Direct Material Cost
Major/Prime Costs
In the facility business there may be myriad structure. Likewise, there are one-time costs for all of
levels of purchasersfrom the owner to the developer these providers. Figure 11-9 offers an example of the
to the architect to the engineer/designer to the con- differing cost elements that will not only comprise the
tractor. Therefore, the cost structure actually becomes cost of a total project but also be considered at each
a pyramid of costs and prices with different users stage of the project process.
along each link in the project chain. Figure 11-8 gives With all the costs collected and detailed, the analy-
a generalization of the cost makeup for each user at sis can proceed. The next step is to relate all of the
{
the different stages of the facility project process. costs to each other, dene relationships, and establish
which of the costs are related to specications for the
project/design and which are imposed requirements.
Maintenance Costs
Costs associated with specications are those imposed
by the owner/developer/user of the facility. These costs
Operating Costs can be connected to the land, construction limitations,
Total Installation Costs
Cost of Shipping/Receiving/Storage
or user-dened needs.
Cost
Base Acquisition Costs Required costs are those that different vendors,
project managers, and contractors impose on the
project due to his/her experience and knowledge.
Price/First Cost
They are the expert costs that form the basis for
the creation of the facility.
Figure 11-8 Generalized Total Cost to Each User It is the value engineers job to discover and under-
stand all these different potential costs. Then, as part
A wide variety of costs go into each element and of his/her analysis, the engineer must differentiate be-
aspect of a facility. These costs are divided into ongo- tween costs that are real based on specications,
ing costs and one-time costs. Ongoing costs are those available information, and conditionsand those that
that will occur throughout the life of the project. The are imaginary (skewed by bias, attitudes, habits,
owner has one set of ongoing costs, while each prod- lack of information, old technology, lack of ideas and
uct/service/material provider has its own ongoing cost creativity, and temporary conditions).
Value engineering has come about because users available for a project and focusing on those that will
will inevitably overestimate their needs and have provide the largest economic benet and result in the
unrealistic expectations. This will be compounded highest levels of return for the expended effort.
by those involved in a facility project who often Phase Two: Analysis/Function Analysis
over-engineer and over-design at the beginning of a
The questions What does it do? and What is it sup-
project due to the unrealistic expectations and over-
posed to do? continue to be addressed in this phase
estimates of the owner/user. It is the value engineer
and concisely sum up this concept. In this phase the
who must bring expectations, estimates, and reality
engineer needs to identify the functions of the project.
into focus.
The Analysis/Function phase is often considered the
The Pareto Principle: Vilfredo Pareto devel-
heart of value engineering because it is in this phase
oped an economic theory regarding the distribution
that the engineer has a methodology to reestablish
of wealth. This principle has found its way into many
the original project/element needs into simply work-
disciplines of engineering, and especially value engi-
able expressions.
neering, where the principle is better known as the
For example, value engineering, the accepted
80/20 Rule. In its original form, Pareto stated that
denitions for Function are:
80 percent of all wealth is held by just 20 percent of
all people. This 80/20 principle has been applied to That which makes a product work or sell; that
everything from manufacturing to construction to which satises the needs or requirements of
engineering principles. In this chapters context, it the user.
states that 80 percent of a facilitys costs will be as- If it were only that simple. The difculty in this
sociated with just 20 percent of its components. phase is the translation and giving of substance to
Is it true? The principle is stated as the theory of the words used for project/element specications and
the Law of Inverse Proportions and is actually a con- requirements. An engineering discipline has taken
cept. It is very useful when examining the resources these words, brought them to life, and provided a vi-
sual interpretation. The value engineer must now also lower cost, it may be that the nonquantiable part
examine those same words and provide a structured of the requirements is an overriding consideration.
evaluation and analysis to them which results in (E.g, color; while a basic white porcelain bowl may
a functional analysis and/or denitions. be less expensive, the use of a special color porcelain
bowl may be an important and overriding appear-
RULES OF FUNCTION ANALYSIS ance/selling requirement.)
There are three generally accepted rules for con- Rule 3: All functional denitions can also be
ducting functional analysis or creating functional divided, into one of two descriptive uses: Basic or
denitions. secondary. A basic function is one that describes the
Rule 1: The expression of all functions must be primary purpose for a product, system, or material.
accomplished using two words; one must be an active Secondary functions are all other functions of the
verb, the other a descriptive or measurable noun. product, system, or material that do not directly
Figure 11-10 offers a sample listing of verbs and accomplish the primary purpose but support the
nouns typically used in value engineering functional primary purpose or are the result of a specic engi-
denitions. neering or design approach. In functional analysis,
Rule 1 is based on the adage that less is more. the secondary functions are the ones that can be
The concept is if you cannot provide a denition of a combined, modied, or eliminated.
function in two words, either you do not have enough This rule further enhances the ability to assign
information about the project/element, or the item a relative importance to the function. For a majority
has not yet been dened in its simplest form. By be- of projects/products/materials, there is only one basic
ing limited to two words, you will be able to describe function to be derived. In those rare cases when more
the simplest element of the project in a manner that than one basic function is stated, usually it is just
reduces the potential for mis-communication or mis- a restatement of the original basic function. When
understanding. there are secondary functions, they tend to fall into
Rule 2: All functional denitions can be divided two categories: Specic and dependent.
into one of two levels of importance: Work or ap- Specic functionality requires a specic action to
pearance (or selling). Work functions are expressed be accomplished. Dependent functionality are those
in action verbs and descriptive or measurable nouns functions that require some prior action before it can
that establish a quantitative statement for the item. be performed. Secondary functions can exist because
Appearance or Sell functions are expressed in passive they are part of the specications or requirements,
verbs and in general or nonmeasurable nouns that or because they are inherent to the engineering or
describe a qualitative statement for the item. design approach used.
Rule 2 provides meaning to the descriptive terms Function Denitions
or rule 1. The denitions here are designed to amplify
With all the rules in place and understood, the value
the meanings of the function under consideration. If
engineer begins the function analysis. Figure 11-11
the function cannot be described with action or active
shows a sample of the type of form that helps in this
verb, the functionality of the element is questionable.
phase. The form is straightforward, and, given all
If there is no action, then nothing is being accom-
the denitions and explanations supplied, should be
plished and, thus, there is no end result or usefulness
self-evident. The most important part of this phase is
to the function.
to dene the function or the element under analysis
By using measurable nouns, the evaluating en-
and create its functional denitions.
gineer will establish a cost-to-function relationship.
Example 3 in Figure 11-11 is considered one of the
These nouns provide a quantitative measure to the
quintessential examples in value engineering analysis
function, and, therefore, provide a measurable level
for explaining the use of two-word denitions. The
of usefulness for the function.
pencil is an everyday object that requires a successive
Why, then, have appearance or sell factors, if they
and seemingly unnecessary number of items to dene
do not provide any quantiable or measurable attri-
it and all of its elements. However, this remains the
bute? First, having appearance or sell factors involved
crux of the value engineering denition phase. Ex-
in the function that can be separated out, will help in
ample 4 in Figure 11 provides an example that could
the assignment of some proportionate amount of the
well be used to evaluate a product used in plumbing
elements cost. Second, by identifying these function
engineering. However, as should be obvious, in both
descriptors, the engineer will be providing a further
these examples, the emphasis of the value engineering
description of the specications and requirements
would be in the manufacture of the item and is not
of the function. This will help the owner in the nal
related to its role in a construction project.
decision process regarding the function. While the
Only a portion of the form in Figure 11-11 is lled
value engineer may well nd an equal element at
out at this early stage of the analysis process. At a
226 ASPE Plumbing Engineering Design Handbook Volume 1
Detail/Product/Material Specification:
Function:
Description (e.g., part number):
Label
FUNCTIONS* Function
Cost per V= vital
Item AP Function E = Essential Notes/
Qty Descrp. VERB NOUN B S W SL (Estimate) N = Nice to Have Comments
Note: B Basic
S Secondary
W Work
AP/SL Appearance/Sell
Example 3: Pencil
Pencil
Make Marks
Remove Marks X X
1 Eraser
Secure Eraser X
1 Band
Improve Appearance X
Support Lead X
Tansmit Force X
1 Body
Accomodate Grip
Display Info
Protect Wood
Improve Appearance X
1 Paint
Make Marks X
1 Lead
Figure 11-11 Function Analysis/Denition Form (Continued)
HOW? WHY?
One Time Ongoing
Function Function
Project
WHEN? Objectives
Independent Dependent/
Dependent Sequential
Project Function
Function
(Supporting) Function
Specifications
Figure 11-12
Independent
Critical PPath
ath (Minor) Function
Chapter 11 Basics of Value Engineering
(Output) Function Function (Input)
Function Function Function
Critical PPath
ath (Major)
Concurrent of Support
Synonymous Function
Function
Sequential
Activity Function
WHEN
Independent
Function
WHEN
WHEN
Activity
WHEN
Independent
Function
WHEN
Lower Order
Higher Order
WHY Function HOW
Function Function
WHEN
Activity
3. Lower Order Function: Functions to the right secondary value and exist to meet the perfor-
of another function on the critical path are a mance requirements specied in the objectives
lower order functions. This is not to imply a and specications.
relative importance or ranking to these functions. 7. Dependent/Sequential Functions: To exist,
Rather, the lower functions are those necessary functions to the right of the Basic Function are
to successfully perform the basic or higher order dependent on the functions to their left and re-
function. quire one to be completed before they enter as a
4. Basic Function: The function under study. The performance requirement.
basic function cannot change. 8. Independent Functions: These functions are
5. Objectives and Specifications: These are the above or below the critical path line and are neces-
parameters and requirements that must be sary to satisfy the WHEN question in relationship
achieved for the function to perform as needed in to the main or basic function.
its operational place in the project. Objectives and 9. Independent (supporting) Functions: These func-
specications are not themselves functions; they tions do not depend on another function as does
inuence the selection of lower order functions. a dependent/sequential function. However, they
6. Critical Path Functions: Any function that is on are still considered secondary functions to the
the HOW or WHY logic path is a critical path basic function and the major critical path.
function. If the function is on the WHY path it 10. Function: The end event or purpose of the prod-
is considered a major critical path. Otherwise, uct/system/material under analysis. It must rst
like the independent supporting functions or the be expressed in a verbnoun form.
dependent functions, it becomes a minor critical
path item. Supporting functions tend to be of
Chapter 11 Basics of Value Engineering 231
11. Activity: The method selected to perform a have existed somewhere else at some other time. Cre-
function. ativity is also the mother of innovation, and both are
For engineers familiar with systems-type dia- important elements of the value engineering process.
graming, it would appear that the FAST diagram is If creativity is something new, then innovation is
backwards. As an example, consider the position of a creative or imaginative use or application of the
the WHY part of the function. For systems analysis, concept. Innovation is adaptive of creativity.
it is on the left. But for FAST the HOW function is in Creativity is conceptualizing a pipe structure;
the left position and dominates the analysis. In this basically a hollowed or formed material that can be
position, all the functions/activities to the right are connected, bent, twisted, buried, hung or laid at or
dependent on the basic function or moving toward vertical. The innovation is to use the creative idea to
the WHY of the function. carry liquids or gases from point A to point B.
Figure 11-13 diagrams the how, why, and when Creativity is divergent thinking. It is overcoming
relationship, relates it to the FAST diagram, and perceptions, preconceived notions, emotional blocks,
shows a simple how functional relationship. cultural divides, and habits. To be successful it is im-
perative to avoid the path of least resistance: Follow
Purpose of the Model the past. After all if it worked before it must still
As it turns out, in the team environment the FAST be a workable solution today. No sense reinventing
model, while a means to an end, is not the vital part the wheel.
of this process. The vital part is the dialogue and dis-
cussions between the team members as the model is
Creative Thinking Personied
formulated and built. It is the process of identication Positive creative thinking can be described by the
functions, questions, justications, relationships invention of the cotton gin. Eli Whitney was trying
that is the key to the structure of the function to nd a way to remove seed from raw cotton. One
analysis and provides the team with a methodology afternoon, on a walk, he noticed a cat trying to catch
to produce a desired result. In fact, once the model is a chicken through a wire fence. The cats claw would
created its only purpose remains as an explanatory, stick through the fence whenever a chicken came
rationale, and communication to the decision makers close, but all that came through the fence on the cats
and other engineering disciplines. claw was feathers. This was the observation that pro-
It would seem to be intuitive that the next step vided the creative incentive. Whitney conceived the
should be evaluation and cost determination. But in concept of pulling the cotton (feathers) though a comb
value engineering the next phase is creativy. (fence). It was a subtle difference to all the thinking
that went before. Instead of trying to remove seeds
Creativity from the cotton by pulling on the seeds, Whitneys
The creative process evaluates the project with an solution was to pull the cotton away from the seeds.
emphasis on, What else will do the job? The creative Inexibility: An illustration of just the oppo-
part of the value engineering process is best summed site inexible thinking is of an innovation made to
by the trite expression, start with a clean sheet of an invention that to this day remains a world-wide
paper. Again, this phase requires a team approach standard despite its outmoded purpose. It is the com-
to engineering disciplines. In the creativity phase the puter keyboard congured in the QWERTY style. This
team needs to unstructure itself and separate itself style was an innovation of Christopher Sholes who,
from all of the previous phases. The team needs to invented the typewriter. Because of the mechanics
leave the drawings, information, forms, and models of the typewriter, and that gravity was the engine
behind and nd a fresh environment in which to to move the keys back into position, Sholes found
reassemble. In this creativity environment the only that fast typists would quickly create key jambs as
information permitted are the two-word, verb-noun they stroked faster than the keys could clear each
functions that describe a single product/system/mate- other and return to rest. Through persistence and
rial being analyzed. experimentation, he developed a keyboard layout
It is up to the team to now develop creative ideas. that separated the most often used letter keys and
Creativity is not an exact science; but it is teachable thereby SLOWED down the typing process. Today,
and thus learnable. The creative phase is to be the that same slow down mentality continues with the
act of putting together unconnected or seemingly un- modern computer keyboard. This despite the Dvorak
related factors or ideas to create a single new idea. and American Standard system of keyboard layout
Creativity is the art of bringing something new into that produces a faster result. Ingrained habit is hard
existence. It is an original concept not an imitation of to overcome.
something else. The important element of creativity Roadblocks to Creativity: Creativity takes
is perception: If the creative thought or idea is new work. Hard work. Of course, as an alternative to
to us, it is a creative act regardless of whether it may providing the creativity phase in value engineering,
232 ASPE Plumbing Engineering Design Handbook Volume 1
the engineer can fall back on, and use one of the top Equilateral Triangles
ten reasons for why value engineering should not be
used at this time:
1. It isnt in the budget.
2 We dont have the time.
3. Lets form a committee.
4. Has anyone else tried it on this type of project?
5. Why change it? Its always worked perfectly be-
fore?
6. We tried that before.
7. The developers will never buy into it.
8. Youre years ahead of your time.
9. Lets shelve it for the time being. Arrange the sticks to make four equilateral tri-
10. Its against company policy. angles. All of the ends of each stick must touch each
(Adapted form Value Management, General Services Administration, other. (And, as engineers, we all know that an equilat-
Washington, DC.) eral triangle has three sides of the same length.)
Divergent Thinking See the end of this chapter for the solution.
Finding Solutions: In this phase the team is
Creativity in value engineering is best described as
not trying to nd solutions, only ideas. To help this
speculation and brainstorming. An all too often over-
process the leader has some help; a simple paper
used and trite phrase, Thinking Outside the Box
and pencil and of course, a form can be created
is an attempt to describe divergent thinking.
from this idea (see Figure 11-14). The brainstorm-
Outside the Box: What is outside the box think-
ing or speculative process consists of two techniques:
ing? One much used example is the Nine Dots:
Nine Dots unassisted creativity and assisted creativity.
With unassisted creativity, one team member
takes the creativity worksheet and is assigned one
two-word denition for one of the functions. The
individual lists every possible idea he/she has regard-
ing that function, such as create seal. Once the
individual has put down whatever ideas he/she has,
the worksheet is moved on to another team member
who then adds his/her own ideas. The sheet is passed
to each team member in turn.
The second step, assisted creativity, is nothing
more than a group exercise where each participant
hitchhikes on each others ideas in order to create
yet another new idea. To get started the team splits
into 3 parts: one group has the worksheet for one of
First draw nine dots in the form of a square on a the two-word function denitions, one group has a set
piece of paper as shown. of idea generators or checklists to help the think-
Next, without lifting you pencil from the pa- ing, and the third group has reference sources such
per, draw four straight connected lines that will go as a dictionary and thesaurus. As one sub-team reads
through all nine dots. You may not backtrack on a line the list, the second could nd new words and ideas
and each line must go through each dot only once. using the alphabet concept (take a word and think of
See the end of this chapter for the solution. another word with a different starting letter of the
Another often used example is the six sticks. You alphabet) and the dictionary, while the third worked
are given six sticks (use toothpicks, straightened the checklists continually questioning all the thought
paperclips or matchsticks) of equal length as shown processes. Two sample checklists are shown in Figure
below. 11-15A and Figure 11-15B.
There are a couple of important elements to using
this process. The rst is that the strong individuals
habit of being judgmental must be abated. To do this,
the group should decide beforehand how to indicate
Chapter 11 Basics of Value Engineering 233
1. 31. 61.
2. 32. 62.
3. 33. 63.
4. 34. 64.
5. 35. 65.
6. 36. 66.
7. 37. 67.
8. 38. 68.
9. 39. 69.
10. 40. 70.
11. 41. 71.
12. 42. 72.
13. 43. 73.
14. 44. 74.
15. 45. 75.
16. 46. 76.
17. 47. 77.
18. 48. 78.
19. 49. 79.
20. 50. 80.
21. 51. 81.
22. 52. 82.
23. 53. 83.
24. 54. 84.
25. 55. 85.
26. 56. 86.
27. 57. 87.
28. 58. 88.
29. 59. 89.
30. 60. 90.
How much of this is the result of custom, tradition, or opinions? Can cause and effect be reversed?
Why does it have this shape? Is one possibly the other?
How would I design it if I had to build it in my home workshop? Should it be put on the other end or in the middle?
What if this were turned inside out? Reversed? Upside down? Should it slide instead of rotate?
What if this were larger? Higher? Wider? Thicker? Lower? Longer? Demonstrate or describe it by what it isnt.
What else can it be made to do? Suppose this were left out? Has a search been made of the patent literature? Trade journals?
How can it be done piecemeal? Could a vendor supply this for less?
How can it appeal to the senses? How could this be made easier to use?
How about extra value? Can it be made safer?
Can this be multiplied? How could this be changed for quicker assembly?
What if this were blown up? What other materials would do this job?
What if this were carried to extremes? What is similar to this but costs less? Why?
How can this be made more compact? What if it were made lighter or faster?
Would this be better symmetrical or asymmetrical? What motion or power is wasted?
In what form could this be-liquid, powder, paste, or solid? Rod, tube, Could the package be used for something afterwards?
triangle, cube, or sphere? If all specications could be forgotten, how else could the basic
Can motion be added to it? function be accomplished?
Will it be better standing still? Could these be made to meet specications?
What other layout might be better? How do competitors solve problems similar to this?
1. Can the dimensions be 4. Can the time element Uniformity 9. Can the state or
changed? be changed? 7. Can the form be condition be changed?
Border Alternated changed? Abraded
Converge Anticipated Accidents avoided Coagulated
Deeper Chronologized Conformation Colder
Delineate Faster Curved Disposable
Encircle Longer Damage avoided Drier
Intervene Perpetuated Delays avoided Effervesced
Invert (reverse) Recurrence Harder Elasticized
Larger Renewed Irregular Harden
Longer Shorter Notched Heavier
Make slanted or parallel Slower Regular Hotter
More shallow Synchronized Rougher Incorporated
Place horizontally 5. Can the cause or Smoother Insulated
Shorter effect be changed? Something added Lighter automatic electric blanket
Smaller Altered Softer Liqueed
Stand vertically Counteracted Straight Lubricated
Stratify Destroyed Symmetrical Open or closed
Thicker Energized Theft avoided Parted
Thinner Inuenced Preformed
Use crosswise 8. Can the motion be Pulverized
Louder changed?
2. Can the quantity be Softer Resistant
Admitted Soften
changed? Strengthened Animated
Add something Stimulated Solidied
Agitated Vaporized
Combine with something 6. Can there be a change Attracted
Complete Wetter
in character? Barred
Fractionate Add color Deviated 10. Can the use be
Join something Altered Directed adapted to a new
Less Change color Lifted market?
More Cheaper Lowered Children
3. Can the order be Interchanged Oscillated Elderly
changed? More expensive Repelled Foreigners
Arrangement Resilient Rotated Men
Assembly or disassembly Reversed Slowed Physically Challenged
Beginning Stabilized Speeded Women
Focus Stronger Stilled
Precedence Substituted
Weaker
Figure 11-15B Creativity Checklist
Chapter 11 Basics of Value Engineering 235
someone is being judgmental and thus can modify the It is important, however, that no idea be discarded
behavior (e.g., slapping the table with a palm). out-of-hand, for whatever reason. All ideas have some
The two sub-teams switch roles from time-to-time merit, which is not always immediately obvious.
until they reach the point of stagnation and agree that To get started, the team should use a worksheet
they are nished. The team will by now have created to list the advantages and disadvantages of each func-
a unique creative list of new and old ideas for tion or idea that is an offshoot of a function. Figure
each function under study. After the creative process, 11-17A shows a sample of such a worksheet. The
it becomes time for the evaluation phase. A possible essence of this step is to be sure that no good ideas
result of this team effort for the two-word denition are overlooked, and that no efforts are misdirected.
create-seal is shown in Figure 11-16. As the functions and ideas are rened, combined,
Evaluation and evaluated, it is important to be evaluating the
time required to develop alternatives versus any
The evaluation phase is a continuation of the creativ-
potential gain. The gain is, of course, improvements
ity phase. It deals with a combination of appraisal,
in quality, maintainability, and reliability, as well as
judgement, and selection to the qualitative and quan-
cost advantages. Similarly, any immediately perceived
titative criteria and ideas developed for each function.
disadvantages may, with a little thought and creativ-
In this phase, we go from divergent thinking to
ity, be turned into advantages. Figure 11-17B shows
convergent thinking. Where, divergent thinking is
the information included.
problem identication and fact nding, convergent
At this stage, the form is fairly self-explanatory:
thinking is a mixing of appraisal, evaluation, judge-
In the rst column is a simplied and short state-
ment, selection, development, and implementation.
ment of an idea from the functional development; in
It is this phase that will create the nal develop-
the second and third columns, every advantage and
ment of workable and meritorious alternatives. The
disadvantage, no matter how large, how important,
introduction of appraisal, evaluation, and judgement
or how small or insignicant is identied.
will eliminate or reduce unnecessary costs and create
If all this sounds a bit simplistic, it is. But, at the
a preferred recommendation or course of action.
same time, it is an important step. Although we make
Yet also in this phase it is all too easy to impart
evaluations, simple and complex on a daily basis, we
a cost-reduction spiral that does not result in value
often do so intuitively. With this structured method-
engineering, but simple cost reductions for budgetary
ology, the evaluation process will be seen to be more
reasons. It is in this phase that it is all too easy to
complex and exacting than simple intuition.
degrade the product/system/material by reducing its
This worksheet is carried through the Develop-
quality, reliability, or maintainability.
ment/Investigation Phase. In practice, this worksheet
Finally, in this phase ideas developed in the
will be analyzed and evaluated twice rst in the
function and creativity phases will be rened and
evaluation phase by the value engineering team,
combined and evaluated by comparison. All of the
and then in the Development/Investigation Phase,
costs of each function or idea will be established, and
when similar forms will be used with other team
the team will continue to develop function alterna-
components.
tives. To do this will require a couple of new forms, an
evaluation technique, and continuing the completion Cost Analysis and Evaluation
of the functional denition and analysis form. This step is also integrated into the development and
In Concert With investigation phase. In this initial evaluation step, a
new worksheet is used to rst draw a sketch of the
Although this Evaluation Phase is shown as distinct
function item being evaluated and then prepare a
from the Develpment/Investigation Phase, in reality
basic cost basis. Figure 11-18A shows the basic work-
in many cases, the two phases often overlap and there
sheets, and Figure 11-18B shows the same sheets with
is really only one. It is up to the value engineering
the information included.
team to decide how many phases will be needed and
In the sketch step, all that is needed is a freehand
what will be done when.
drawing that incorporates the essential items. With
Rening, Combining, Evaluating by the parameters clearly dened and set there will be
Comparison fewer tangential discussions and considerations.
Idea generation is a dynamic process that doesnt Using the simple concept of the wall box, in this
ever really stop. The creative thought process is an phase the requirement may be for an off-shelf-unit
ongoing series of judgements and evaluations. In the supplied out of a catalogue. It will be in the next phase,
evaluation phase ideas that seem unusable may well the Development/Investigation, when the team is
be combined with other ideas to create a better solu- expanded and a second review and evaluation made
tion. Some ideas will stand out as preferred solutions, that advantages/disadvantages and cost savings can
while others may be found to be lacking information. be integrated with each other.
236 ASPE Plumbing Engineering Design Handbook Volume 1
IDEA FROM
FUNCTIONAL DEVELOPMENT ADVANTAGES DISADVANTAGES
Plan(s)/Action(s) on Idea(s)
Wall Box; Confine and Secure Material
5. Requires access to
latch key or opening
mechanism
6. Additional Cost to
Install
Piano Hinge
Piping Entrance/Exit
Knock out plugs
Lock Mechanism
Do or Overlap Lip
CUMULATIVE
ESTIMATED ESTIMATED
FUNCTION CREATIVE IDEA(S) & DEVELOPMENT COST COST
Total
Cost Summary
Material & Material Burden $
Direct Labor $
Direct Labor Burden $
Total $
Figure 11-18B Functional Idea Development and Estimated Cost Worksheet Blank
242 ASPE Plumbing Engineering Design Handbook Volume 1
CUMULATIVE
ESTIMATED ESTIMATED
FUNCTION CREATIVE IDEA(S) & DEVELOPMENT COST COST
Total $12.75
Cost Summary
Material & Material Burden $
Direct Labor $
Direct Labor Burden $
Total $
Figure 11-18B Functional Idea Development and Estimated Cost Worksheet Example
Chapter 11 Basics of Value Engineering 243
In this evaluation phase, everything from quan- With the evaluation and analysis complete, Fig-
tity purchases to custom designed and manufactured ure 11-20B shows that the functions in importance
items should be taken into account. The value engi- as follows:
neering team is: Establishing the rst benchmarks Prevent Loss 15
of the functional and cost analysis; examining any
Protect Inside 10
secondary functions that should or can be considered;
and ensuring that all of the project parameters have Conne Material 9
been met. The team must answer many questions: Protect Material 9
Are all the specications and requirements met? Are Establish Privacy 5
all the two-word function denitions accounted for?
Enhance Appearance 1
Are all functions and needs being met? Is there dupli-
cation of effort or denitions that can be eliminated Store Material 0
and, thus, reduce costs? From this analysis, the value engineering team would
Incorporating the Functional Denitions declare the Prevent Loss function to be the basic
In the information phase, the Functional Denitions function. The nal weighted list shows the relative
Worksheet was initialized. The evaluation phase importance of each of the functions to each other and
provides the information necessary to complete the to the project.
nal four sections of the worksheet: the Work versus With this information, the Function Denition
Appearance evaluation, the estimated cost, the im- and Analysis Worksheet can now be completed as
portance valuation of each element, and any notes or shown in Figure 11-21. Note that the basic and sec-
comments. The rst step is to evaluate and compare ondary functions have now been redened based on
the functional relationships and create a numerical the evaluation, and it can now be determined which
weighting of the functions. This numerical weighting of the elements are vital, essential, or would just be
will provide a basis for determining value or levels of nice to have.
importance of the functions, as well as the magnitude This analysis would continue to examine each
of importance. To create a numerical evaluation, a of the system functions in relationship to the others
Functional Evaluation Worksheet will be utilized as and would, in turn, create a weighted evaluation of
shown in Figure 11-19. each of the separate products/systems/materials for
To start, use the function denition and analysis the overall project being examined.
worksheet for detail/product/material. Continuing The Pencil: Another Look
the Wall Box example, the worksheet identied eight An alternative evaluation and analysis could also
functions for the wall box and listed them in order in be constructed by establishing idea criteria using
the Functional Evaluation WorksheetPart 1. This a qualitative approach. In this method, each of the
simply provides a list order for the items with appro- items of the function can be evaluated in the reverse
priate alphabetic identication. See Figure 11-20A. of the function definitions and uses perscriptive
Comparison of Functions: The value engi- connotations for expressing value. In this instance,
neering team must know and compare each function the listing order might look like Figure 11-22A, the
with every other function. Starting with the function evaluation worksheet part 2 like Figure 11-22B,
delineated as A or Conne Material, it is compared and the completed Evaluation worksheet part 1 like
to function B, Store Material. Conne Materials is Figure 11-22C.
determined to be more important than Store Materi- This alternate analysis can be conducted by the
als, and is thus accorded a listing of A in the A line value engineering team or can wait until the next
under the B listing in the Functional Evaluation phase, Development/Investigation, and be conducted
Worksheet Part 2. with an expanded value engineering team.
At the same time that the relative importance is
being determined, the magnitude of the importance DEVELOPMENT/ INVESTIGATION
must also be established. The numerical weights Consultation and Evaluation
provided in Part 2 are then used to establish this
The evaluation phase is continued here in the Devel-
importance difference. As seen, the Conne Materials
opment/Investigation phases as the value engineering
is rated to be of major importance when compared to
team brings in other team members to provide addi-
Store Materials.
tional creativity and energy to the process. All of the
Each of the remaining functions are evaluated
functional development worksheets are prepared for
and analyzed in a similar manner in relationship
review by the advanced team. In Figure 11-23, the
to all of the functions below it, as shown in Figure
Idea Evaluation Worksheet is recreated with only
11-20B.
the ideas of the function development lled in. As
244 ASPE Plumbing Engineering Design Handbook Volume 1
Detail/Product/Material Specification:
Function:
Description (e.g., part number):
Evaluation Summary
List
Order Functions Weight
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Detail/Product/Material Specification:
Function:
Description (e.g., part number):
Numerical Evaluation:
Weight Factors
1 = Nice to Have Minor Importance
2 = Essential Medium Importance
3 = Vital Major Importance
A B C D E F G H I J K L M N O P Q R S T U
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
Evaluation Summary
List
Order Functions Weight
A Confine Material
B Store Material
C Protect Inside
D Protect Material
E Prevent Loss
F Enhance Appearance
G Establish Privacy
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Numerical Evaluation:
Weight Factors
1 = Nice to Have Minor Importance
2 = Essential Medium Importance
3 = Vital Major Importance
A B C D E F G H I J K L M N O P Q R S T U
A A-3 C-1 C-3 E-2 A-3 A-3
F G-3
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
Evaluation Summary
List
Order Functions Weight
A Confine Material 9
B Store Material 0
C Protect Inside 10
D Protect Material 9
E Prevent Loss 15
F Enhance Appearance 1
G Establish Privacy 5
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Detail/Product/Material Specification:
Function:
Description (e.g., part number):
Label
FUNCTIONS* Function
Cost per V= vital
Item AP Function E = Essential Notes/
Qty Descrp. VERB NOUN B S W SL (Estimate) N = Nice to Have Comments
Confine Material X X E
Wall Store Material X X N
1 Protect Inside X X E
Box
Protect Material X X E See Confine Mate-
Prevent Loss X X 12.75 V rial Above
Enhance Appearance X X N
Establish Privacy X X N
Note: B Basic
S Secondary
W Work
AP/SL Appearance/Sell
Evaluation Summary
List
Order Functions Weight
A Elimnate Paint
B Reduce length of lead
C Remove eraser
D Stain wood in lieu of paint
E Make body out of plastic
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Numerical Evaluation:
Weight Factors
1 = Nice to Have Minor Importance
2 = Essential Medium Importance
3 = Vital Major Importance
A B C D E F G H I J K L M N O P Q R S T U
A B-2 A-1 D-1 A-1
C D-1 C-1
D D-2
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
Evaluation Summary
List
Order Functions Weight
A Elimnate Paint 2
B Reduce length of lead 9
C Remove eraser 1
D Stain wo od in lieu of paint 5
E Make body out of plastic 0
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Provide 2 by 2 10 gauge
polished aluminum wall box to
confine and secure on/off regu-
lator valve for hot water for
each fixture in each bathroom
before, a Sketch is provided, as is the ideas develop- Finally, a Risk Guide is used to make the nal
ment sheet. determination as to each idea. Figure 11-25 denes
Once again, the team sets down rules to follow a sample Risk Guide.
similar to those that went before. In this phase addi- In this approach, the Risk 1 level can be imple-
tional team members might include the manufacturer, mented or accepted without much concern. All the
contractor, and owner representative. This phase other categories will require further investigation.
can provide an intense critique of the function/idea Cost Analysis, More
under discussion. It is this value-added group that
One of the major elements of value engineering is the
reestablished advantages and disadvantages, with the
nal cost analysis that is done for the recommenda-
initial value engineering team providing input based
tions and alternatives. Cost considerations are an
on their initial worksheet.
important element of the value engineering process.
Second Creativity, Evaluation, Cost Up to this point, the process has relied on creative
Anaylsis techniques, brainstorming, functional analysis, and
In this phase, the larger team will again do creativity comparitive analysis. The concentration has been on
and evaluation. As seen in Figure 11-24A and 11-24B, the technical side of the equation.
the sketch can be signicantly modied, and a new, The result for value analysis must also incor-
secondary approach to the idea development phase porate the cost analysis side of value engineering.
can result in a different evaluation that could result Interestingly, in many value engineering projects, a
in signicant cost savings. comparative-cost analysis is not often conducted. A
As seen in Figure 11-24, in this development/in- cost analys will look at life-cycle costing, break-even
vestigative phase the emphasis was on alternatives to analysis, and comparitive-cost analysis. For purposes
a catalogue box and a new brainstorming session of this basic overview, the details and in-depth review
with different expertises and viewpoints. of the various cost-analysis methodologies are not
Final Alternatives included.
With additional idea evaluation and cost estimates Are We There Yet?
worksheets and possible sketches, the expanded value The evaluation phase was intended to provide vis-
engineering team is ready to redevelop the idea. The ibility to all ideas and ush out any constraints while
team would again establish advantages and disadvan- offering alternative solutions. This phase, while
tages using Figure 11-23 worksheet. At this stage, all seeming to repeat some of the evaluation phase, is
of the engineering diciplines, contractors, and even the nal organization and analysis phase. It is in
the owners would help in the nal development and this phase that the value engineering team prepares
investigation to determine the best outcome. their nal recommendations prior to presentation to
With a workable and best-cost idea developed, the the owners/clients.
nal step is to use construction supplies and industry The value engineering process reviewed here
standards to conrm the ability to meet the nal has used, depended and recommended the use of
engineering and design. standardized worksheets. One major disadvange to
The Gut Feel Index this approach is the attempt to nd a standardized
The Gut Feel Index is what engineers have developed process that is all encompassing for all situations and
from the original Delphia method of evaluation. The projects. Alas, that is not the case. So why then have
Delphia method attempts to achieve a consensus of worksheets?
opinion within a group using questionnaires regard- The primary purpose is use as a tool, to help pro-
ing future events and technical expertise. vide structure to the process and offer a presentation
The Gut Feel Index is similar, but uses the in- format. All of the worksheets help form a picture of
tuitive qualication of each developed idea using the value engineering process and provide illustrative
the technical expertise of the individuals. Each team detail for support of the nal recommendations. It is
member scores each idea on a scale of 1 to 10 based important that the end result show that there was
on its technical merits and the economic expectations. depth to the engineering and analysis; that what is
Low technical requirements, low costs, and low risks proposed is not just a suggestion or best guess but
get the highest mark. is based on engineering discipline.
High rankings by any individual are further ex- Perhaps the best nal step for the value engin-
plained to the other goup members so all understand ering team is to have yet one more checklist; this
the rationale behind the rankings. The average of the one of questions that support the value engineering
scores are then computed. process.
Chapter 11 Basics of Value Engineering 255
Wall Box
Standard Wall Box:
ABC Manufacturer
Model Number 123456-A
Size 2 X 2
Piano Hinge
Spot Weld Plastic One-piece Hinge Plastic Composition
CUMULATIVE
ESTIMATED ESTIMATED
FUNCTION CREATIVE IDEA(S) & DEVELOPMENT COST COST
Custom Box
$.75 $6.35
Drill Mounting Holes on Site
Total$6.35 $7.45
Cost Summary
Material & Material Burden $
Direct Labor $
Direct Labor Burden $
Total $
1. Does the proposed solution or alternative satisfy repudiation, or rejection of another engineers work.
all of the original requirements and specica- People react in different ways, but in the engineering/
tions? design profession a couple of things can be counted
2. Are there any issues or idea that remain unre- on occuring.
solved prior to nal recommendations? First, because it is human nature, change, no
matter how slight or how right, will be resisted. Over-
3. Are all reliability requirements and specications
coming resistance will require patience and proof.
met by the alternative?
This requires that the value engineering team have
4. Are all of the recommendations and alternatives all their worksheets for all aspects and phases of the
compatible with all other systems, processes and process available for critical review.
materials? Second, all recommendations and alternatives
5. Do the recommendations or alternatives create must be based on the same technical basis as the
any health or safety concerns? original specication. Not everyone will require ex-
6. Do the recommendations and alternatives meet quisite detail to be convinced while, others will never
the operational and maintainability requirements be satised with whatever is provided.
of the project/system? To prevail, the value engineering team need only
present two items: the facts and the truth. The pre-
7. Are the recommendations or alternatives able to sentation of the facts must be accomplished in the
be implemented within the guidelines of codes
same deliberate manner that was followed throughout
and regulations, and offer no additional delays or
the value engineering process. Prepared with the
costs over the original engineering and design?
worksheets and a written analysis, the presentation
8. Do the recommendations and alternatives support will be able to account for every requirement and spec-
the owners/clients requirements, specications, ication, and be able to trace the path of the analysis
and goals? from beginning to end with a clear understanding of
Everything is now in place and ready for the nal the nal recommendations/alternatives.
step the presentation of the results. The worksheets used throughout the value en-
ginering process will prove invaluable. They paint a
Recommendation/Presentation
picture for all to see and will provide a concise and
The presentation and recommendation phase is the
complete visual explanation of the end result, along
culmination of all the previous phases. Will the value-
with compelling and unrefutable conclusion.
engineering-team reccommendations and alternatives
be accepted or rejected? Present Costs
In the end, it all boils down to salesmanship. The whole exercise for value engineering is to provide
The recommendations and alternatives, no matter cost savings on the total project. It is the presenta-
how they are couched, will be seen as an attack, tion of exacting support details that will result in a
258 ASPE Plumbing Engineering Design Handbook Volume 1
successful and fully accepted modication. Because percent of the product/project/system will produce 80
value engineering is a team approach and depends percent of the savings. It is for this 20 percent that a
on a Team Recommendation, an agreed-to consuen- value engineering analysis is of value.
sus result is the one most sought after by everyone Unfortunately, most so-called value engineer-
involved. ing it is simly the misappropriation of a term that
Present Recommendation connotes structured and scientic analysis to the
evaluation of a product/system/material. In reality, it
The nal step is to present a team recommendation.
is nothing more than simple cost cutting or cost reduc-
A recommendation worksheet is shown in Figure
tions for the sake of savings alone. This process is not
11-26. This worksheet will be a summary of all the
value engineering, no matter what you may wish to
support worksheets and will spell out the ndings
call it. It is more appropriate to use the proper term
and recommendations.
for what all too often passes for value engineering
Making the Presentation cost reductions. Or, if a analytical name needs to
The nal presentation should be both a written report be used, Cost Fitting is appropriate.
of ndings and a verbal description. Both need to be
Cost Fitting
clear and concise, and the presentation condent and
Cost tting is where engineers, designers, and the like
positive. The basic strategies for successful presenta-
are often left out of the process and the designs and
tions are:
mechanicals are turned over to a value engineer,
1. Expain the Whys: Provide the facts, detail the often nothing more than a contractor seeking the
modication/changes, and describe and acknowl- bid for the project. The budget is the budget, as
edge any risks. developers and owners like to say.
2, List the Benets: Its important to concentrate In this iteration of cost tting, the Pseudo Value
on the benets that will accrue because of the Engineer (PVE) will offer replacement products or
value engineering process. However, be sure not designs that can be installed for less money or To
to exaggerate or oversell the results. meet the budgetary needs of the project. There is no
3. Make it a Participatory Presentation: Be sure concern in cost tting for the quality of the engineer-
to involve the audience in the discussion and ing or design. One problem with cost tting is that
presentation. Incorporate audience suggestions. there is always an alternative to anyones choice of a
Involvement is ownership. product or design element. The PVE, knowing this,
can offer cost savings over the design engineers
4. Answer Questions Before They Are Asked: Be
ready for the negativity that will be present by original work. All too often, the cost savings result in
some individuals. increased prots for the PVE as he/she garners the
business with an on-budget bidonly to use inferior
5. Be Prepared: Avoid surprises by being prepared, or less-desirable products/systems/materials with
and dont let emotions interfere with the presen- greater markups for the supplier.
tation.
Level the Playing Field
6. Acknowledge Difculties or Unknowns: Dont
One option open to engineers is to have included in
gloss over an obvious problem or a void in the
their contracts a series of clauses that would provide
presentation. Acknowledge the unknown and
provide an interpretation or at least some alter- or require true value engineering to be performed
native response. on their designs. The role of the engineer is not to
inhibit good value engineering of a project. As already
7. Repeat, Repeat, Repeat: Repetition is the road shown, value engineering is a discipline that, when
to understanding. However, in repeating, be sure properly applied, will result in cost savings without
you are prepared with alternative road directions any sacrice in quality of design. The following ex-
and maps. Repeating the same words over and
ample in Figure 11-27 is not intended to be exact
over will not make the material understood any
legal language or offered as a instant contract addi-
easier to be embraced.
tion. Rather, it is provided as a concept for insuring
Is It Value Engineering? that proper value engineering is implemented on the
In the construction industry, the emphasis is con- engineers design and mechanicals.
stantly on the cost side of the equation. All too often The Dja Vu of the Science of Value
the quality of the engineering and design are at- Engineering
tacked under the rubric of value engineering. As Does the science of value engineering seem very
should be clear by this point, true value engineer- familiar? It should, because it contains many of the
ing can be an expensive undertaking. It is why value same elements followed in plumbing engineering and
engineering invokes the Pareto principle: Only 20 design. As you read about value engineering, you
Chapter 11 Basics of Value Engineering 259
1. INTENT AND OBJECTIVES-This clause applies to any cost reduction proposal (hereafter referred to as a Value
Engineering Change Proposal or VECP) initiated and developed by the Contractor for the purpose of changing any
requirement of this contract. This clause does not, however, apply to any such proposal unless it is identied by
the Contractor, at the time of its submission to the Owner, as a proposal submitted pursuant to this clause.
1.1 VECPs contemplated are those that would result in net savings to the Owner by providing either: (1) a decrease in
the cost of performance of this contract, or; (2) a reduction in the cost of ownership (hereafter referred to as col-
lateral costs) of the work provided by this contract, regardless of acquisition costs. VECPs must result in savings
without impairing any required functions and characteristics such as service life, reliability, economy of operation,
ease of maintenance, standardized features, esthetics, re protection features, and safety features presently required
by this contract. However, nothing herein precludes the submittal of VECPs where the Contractor considers that
the required functions and characteristics could be combined, reduced, or eliminated as being nonessential or
excessive for the function served by the work involved.
2. SUBCONTRACTOR INCLUSIONThe Contractor shall include the provisions of this clause, with the pre-determined
sharing arrangements contained herein, in all subcontracts in excess of $25,000, and any other sub-contracts which,
in the judgment of the Contractor, is of such nature as to offer reasonable likelihood of value engineering cost
reductions. At the option of the rst-tier Subcontractor, this clause may be included in lower tier subcontracts. The
Contractor shall encourage submission of VECPs from Sub-contractors; however, it is not mandatory that VECPs
be submitted, nor is it mandatory that the Contractor accept and/or transmit to the Owner VECPs proposed by his
Subcontractors.
3. DATA REQUIREMENTSAs a minimum, the following information shall be submitted by the Contractor with each
VECP:
3.1 A description of the difference between the existing contract requirement and the proposed change, and the
comparative advantages and disadvantages of each; including justication where function or characteristic of a
work item is being reduced;
3.2 Separate detailed cost estimates for both the existing contract requirement and the proposed change, and an
estimate of the change in contract price, including consideration of the costs of development and implementation
of the VECP and the sharing arrangement set forth in this clause;
3.3 An estimate of the effects the VECP would have on collateral costs to the Owner, including an estimate of the
sharing that the Contractor requests be paid by the Owner upon approval of the VECP;
3.4 Architectural, engineering, or other analysis in sufcient detail to identify and describe each requirement of the
contract, which must be changed if the VECP is accepted, with recommendation as to how to accomplish each
such change and its effect on unchanged work.
should have been aware that this discipline is very products and materials available on the market and
much like that of plumbing engineering and design. therefore, by inference, the most expensive products
In fact, the elements described could just as easily and materials. The perception is of the engineering
be transported to, and applied to a plumbing design artist over-engineering a project. The engineer is
project. The elements techniques of value engineering suspect of using materials and products that have a
are similar to most other engineering disciplines, and longer life-cycle cost than may actually be necessary in
almost exactly the same as used by many other disci- order to provide an extra measure of safety, longevity,
plines. Well then, if the plumbing engineer is already and quality of design.
doing all this, why does it need to be done again? It is this quality of design that is perceived by
For the projects owner, developer, or manager those nancing the project to result in a more costly
it becomes an issue of perception. Each of the en- enterprise than is necessary, while still providing the
gineering and design disciplines used throughout safety and longevity desired. Enter the discipline of
the creation of a facilitys project are always open value engineering. This engineering step at each stage
to suspect and suspicion. Engineers and designers of a project is perceived to be nothing more than an
are often seen not just as engineers doing their oversight function protecting the economic interests
necessary and important work, but as engineering of the owner and insuring quality of design at the best
artists. The engineering artist is suspect as creating possible cost. It is not intended to be cost reductions
an enduring engineering work of art under the guise simply for the sake of cost reduction.
of quality of design. A forever lasting engineered What the engineer often sees as being the end
product that may well include redundancies will most result of value engineering, and why many object to
likely include the most up-to-date and state-of-the-art its use, is the misconception that lower costs equate
Chapter 11 Basics of Value Engineering 261
directly with reduced quality. The plumbing engi- Solution to Equilateral Triangle
neer, like all other engineers and designers, needs to The solution calls for thinking off the two-dimensional
remain exible and open to the integration of other surface of a table and into three dimensions. The so-
disciplines ideas and concepts. Value engineering is lution shown is as viewed from above. Its a Pyramid
not a methodology designed to undermine the engi- shape. The base is, of course, one of the equilateral
neering, design, or specications of a project. Nor is it triangles.
intended to outsmart or out-think the engineers.
Value engineering is not intended or designed to re-
duce quality, safety, professionalism or creativity. It is
an analysis to identify and stop waste, thus lowering
costs while maintaining quality.
Value engineering, when performed properly, will
not affect performance and will not result in trade-
offs to reliability, quality, or maintainability. And this
may well be the crux of the conundrum inherent in
the discipline. Value engineering is only as good as the
process followed, the experience of the engineers, and
like any project, subject to various obvious and hidden
agendas by numerous parties involved. Moreover, it is
not unheard of for many value engineered changes
to be nothing more than an owner-mandated cost
reduction disguised under the rubric of value engi- REFERENCES
neered. Which is not much different than having a
1. Dell=Isola, Alphonse J. Value Engineering in the
carefully engineered and specied product substituted
Construction Industry. New York: Construction
by a contractor as something deemed equal, often
Publishing Company, 1974
for nothing more than increased prot potential and
no real savings for the owner. Despite the negative 2. Dell=Isola, PE, Alphonse. Value Engineering:
connotation often is improperly designated with the Practical Applications. Kingston, MA: R. S. Means
value engineering label, the concept needs to be looked Company, 1997.
at as an adjunct to a projects engineering, and each 3. Fallon, Carlos. Value Analysis, Second Revised
other engineering discipline needs to embrace the con- Edition. Southport, NC: Miles Value Foundation,
cept and use it effectively within his/her discipline. 1986.
4. Kaufman, Jerry J. Value Engineering for the
Practitioner, 3rd Edition. Raleigh, NC: North
Solution to Nine Dots Carolina State University, 1990.
5. King, Thomas R. Value Engineering, Theory &
& & & Practice in Industry. Washington, DC: Lawrence
D. Miles Value Foundation, 2000.
6. Mudge, CVS, Arthur E. Value Engineering, A
Systematic Approach. Pittsburgh, PA: J. Pohl
Associaties, 1996.
& & &
7. Miles, Lawrence D. Techniques of Value Analysis
and Engineering, 3rd Edition. Washington, DC:
Lawrence D. Miles Foundation, 1989.
8. Park, Richard. Value Engineering, A Plan for In-
& & & vention. Boca Raton, Fl: CRC Press LLC, 1999.
consumed. The exact amount of reduction in water of a solar water-heating system may be an option for
usage varies depending on the type of building and some buildings. However, if there is a high demand
occupancy, but can be a signicant amount upwards and you require a quick recovery on the water heat-
of 75 percent over conventional faucets. ing system, then a solar water-heating system may
Waterless urinals have been developed to use not be advisable. The use of photovoltaic receptors
a biodegradable, immiscible uid that is less dense to generate electricity to heat water can also be a vi-
than normal liquid waste and allows the waste to able option if your situation only requires a limited
pass through a special trap and then to the drainage amount of hot water.
system. These products do not connect to the building The use of small electric or natural gas-red
water supply and do not use water. There is quite a instantaneous water heaters, which only use energy
bit of controversy about the use of these products and when the water is owing, is very much a viable op-
their potential for increased maintenance costs. Some tion--especially when the xture is remotely located
areas have provisions in the plumbing code that would from the rest of the building, or the hot water demand
prohibit the use of these xtures and require special is only needed for a short period of time. Understand-
permissions or variances in order for the xtures to ing how the building uses hot water and accurately
be used. Care should be taken by the designer to fully determining the demand of the building are prerequi-
understand the advantages and disadvantages and sites to providing a water heater that is not oversized,
discuss these items with the building owner prior to and, therefore, an energy-wasting device.
using this type of xture. Reducing the amount of standby heat loss from
Composting water closet systems use little or no the water heater or storage tank is all part of saving
water, are not connected to a conventional plumbing energy. Not storing quantities of hot water and using
system, and convert wastes into compost by means an instantaneous water heater may provide a great
of an aerobic decomposition process carried out by solutionif you have the right circumstances. How-
micro and macro organisms. Another type of xture ever, other types of facilities may need to have a large
that does not use water is an incinerating water quantity of water stored for use during high-demand
closet, which utilizes a combustion chamber in order periods. It is important to have conversations with
to incinerate wastes. Use of these units is typically the client and understand the constraints the design
limited to remote locations or locations where water will need to conform to.
availability is limited. Again, the limitations of code Opportunities for the application of different
should be investigated prior to using these units. water heating technologies are endless. Depending
Dual-ush water closets are available with con- on the type of building you are designing, there may
trols to provide a reduced volume of water when a be multiple solutions for providing hot water to the
full ush is not required. These xtures are becoming building xtures.
more common in the United States. Several manu- Hot-water recirculation systems conforming to
facturers currently have units available. ASHRAE 90.1 should also be provided. These systems
require that the piping system be insulated with a
ADDITIONAL LEED POINTS minimum insulation thickness and the circulating
ENERGY SAVERS pump be controlled by a temperature-sensing device
Another area where LEED points are available is or a time clock. This standard should be consulted
energy efciency and energy-use reduction. There prior to the design of a recirculation system. Another
are many ways energy consumption can be reduced consideration to limit the energy lost in a hot-water
in a plumbing system. While the most common ways recirculation system is the routing of the supply and
to conserve energy have to do with heating, ventilat- return piping. Using the shortest route for the dis-
ing, and air-conditioning systems in a building, there tribution system will provide a more-efcient piping
are still ways to conserve energy in the plumbing system, thereby saving energy from the heat loss of
system. the system. These systems should also be balanced to
Using high-efciency water heaters to heat do- provide uniform heat loss throughout the system and
mestic water is one of the rst steps in saving energy limit the temperature drop in the system.
in a plumbing system. Using solar water heating In certain building types and installations, con-
systems or photovoltaic technology and generating sideration may be given to using a central-chilled
electricity to heat water can also be an option in drinking-water system for energy conservation. The
some cases; capture an alternative energy source amount of energy consumed by electric water coolers
and reduce the amount of other types of energy used. spaced throughout a facility may actually be greater
Many of the alternatives for heating water will de- than the amount of energy consumed by a central
pend on the type of building being designed and the chiller with a looped piping system to the drinking
quantity of hot water your system requires. The use fountains and the recirculation pumpkeeping the
266 ASPE Plumbing Engineering Design Handbook Volume 1
water in the system moving and cool. As with a hot- sustainableeven to the point of not using lead and
water recirculation system, a chilled drinking-water oakum for joining cast-iron hub and spigot piping.
system should also have the piping insulated to pre- Not many areas still use this method of joining pip-
vent heat gain and also prevent condensation on the ing, but there are some areas where lead and oakum
piping system. Of course, using drinking fountains are still prevalent today.
instead of electric water coolers would also save en-
ergy, piping, and insulation costs associated with the GREEN ROOFS
system. The building owner should be consulted prior One portion of some sustainable designs is the use
to providing a non-chilled drinking-water solution for of green roofs or roofs that have a thin layer of
their building. soil, which contains vegetation and helps provide
The possibilities are numerous for energy con- additional insulation and a thermal break for the
servation, and taking the time to stop and review the building occupants. There are several types of these
building being designed can provide some interesting systems available, each with its own specic criteria
ways to save energy. The use of a waste-heat-recovery and method of installation. Common to many of the
system to preheat the inlet water to domestic water different types of green roofs is the requirement to
heaters can to limit the amount of energy used to heat be able to provide some type of irrigation water for
the domestic water. If a building system is connected the plants.
to a central steam system where the condensate is not Typically, the preferred solution in sustainable
returned, using the heat remaining in the condensate design would be to use some type of water other than
is advisable. It is common to provide heat-recovery the potable water supply to the building. Many of the
systems on large laundry and car-wash facilities, but potential solutions for how much water will be needed
common to apply them to other types of buildings. for the irrigation systems, as well as the type of irri-
Recovering the heat from dishwashers, glass gation system to be used, should be veried with the
washers, showers, and other devices that use hot architect or landscape designer. It is recommended
water has not been utilized on a wide basis. One tech- the plantings used in this type of situation be more
nology that allows heat recovery from these types of drought resistant than conventional types of plants.
uses is the gravity-lm heat exchanger. This device This assists with the premise to save as much water
utilizes a vertical counter-ow heat exchanger that as possible. Whether rainwater or clear water wastes
extracts heat from waste water and uses it to preheat from the building is collected to water the plants,
the cold water to the water heater. The heat exchanger there are several options available. The use of other
consists of a copper drainage pipe with small-diam- types of water, not drinking water, will assist in the
eter copper piping coiled around the drainage piping reduction of water use for the building.
over a given length. The heat is transferred from the It is common for the irrigation system of a green-
drainage piping to smaller coils on the outside of the roof installation to be a drip-type irrigation system.
piping. The unit is installed in the vertical position Other types of systems exist to limit the amount of
so waste water in a vertical stack ows down the run-off water into the roof-drainage system. The de-
entire perimeter of the waste piping with a center signer of the landscape portion of the green roong
core of air in the middle. This type of conguration system should be consulted on the type of irrigation
would not be as efcient installed in the horizontal system to be provided. The type of irrigation system
position, as water in the drainage piping would only used may depend on the type of vegetation planted
be in contact with the coiled piping over half of the on the roof, and whether or not water must be in a
piping system perimeter. specic area for a predetermined length of time, or if
another type of system is recommended.
INNOVATIVE IDEAS The roof-drainage system used in a green roof
When thinking about sustainable design and portions setting is designed as a conventional roof drainage
of the plumbing system that could be modied to system would be. The plumbing code should be con-
provide a more ecological solution to the installation sulted regarding the amount of rainwater anticipated
of plumbing systems, there are several things that and the requirements of storm durations. Pipe sizing
could be investigated. for the storm-drainage system remains the same as
Considering the use of mechanical joints or press it would for a conventional system. If a secondary
joints with o-ring gaskets to limit the use of ux drainage system is required for a conventional roof,
and solder and reduce the potential negative health and the green roof being designed contains the same
effects of the byproducts of making soldered joints attributes, (such as parapets) then a secondary drain-
could be shown to be sustainable. While the use of age system with overow drains or scuppers would
lead pipe has declined to almost nothing, the retrot also be required on the green roof. Green roofs are
of any system containing lead would be considered designed in many shapes and sizes, and each will be
Chapter 12 Green Design for Plumbing Systems 267
different depending on the designer and the area with Rainwater-collection systems are becoming more
which they are working. prevalent for use in irrigation systems. These collec-
To help keep soil and other plants away from the tion systems require the storage of the rainwater,
roof drains, usually a small area around the drain is usually in underground storage tanks that can be
separated from the remainder of the green roof. Care quite large. The amount of storage depends on the re-
should be taken when designing these systems to quirement for irrigation water, as well as the amount
keep debris and other portions of the plantings from of rainwater anticipated. Some amount of water treat-
getting into the roof-drainage system and potentially ment and ltration should be anticipated to keep the
creating a problem. Additional screening of the roof- sprinkler heads from fouling and becoming clogged
drain strainers may be necessary. with debris, but not to the same extent as the water
used to ush water closets and urinals.
GREY WATER SYSTEMS If rainwater collection is being considered, the
One of the technologies becoming more prevalent in designer needs to investigate its potential impacts.
the design of sustainable plumbing systems is the use Certain areas of the country prohibit the collection
of grey water systems. The systems reuse previously of rainwater because the rainwater serves other
used water for another. Typically, grey water systems areas of the country as their primary water supply.
are used to ush water closets and urinals and should Thus, rainwater collection in one area could create
not come into any human contact. The collection of a signicant shortfall in another water supply if the
rainwater for use in this type of system is also gain- rainwater is not allowed to ow downstream.
ing acceptance and can reduce the amount of potable
water used for things other than drinking.
Typically these systems gather water from vari-
ous uses (allowing the water to be classied as grey
water) and bring that water back to a central loca-
tion. Once the water is gathered into a tank, it can
then be sent back to the system to be used again.
The water must be ltered prior to distribution to
water closets and urinals to remove substances from
the water that may cause the ush valves or other
components to fail. For example, small particles of
sand or other matter can clog the diaphragms of ush
valves so they run continuously. Distribution pumps
are required to pressurize the system and allow it to
function properly.
Grey water systems are commonly found in laun-
dry facilities, car washes, and other such facilities.
Treatment of the waste water from these systems is
usually required before the water can be used again.
Various manufacturers of these systems are avail-
able and should be consulted regarding the specic
requirements of their systems.
Another potential resource for grey water usage
is condensate gathered from high-efciency condens-
ing-type water heaters, and boilers, and from fan-coil
units, air-handling units, etc. That water can be
used to provide makeup water to the boiler or chiller
makeup water systems. Condensate gathered from
high-efciency water heaters and boilers should be
tested and potentially treated to reduce corrosive
properties that may restrict it from being reused for
another purpose. The condensate gathered from cool-
ing coils or fan-coil units is generally water relatively
free of impurities and can also reduce the amount of
chemical treatment of the makeup water required for
the other systems.
268 ASPE Plumbing Engineering Design Handbook Volume 1
Index
dened, 2004 V1: 17 aerobic wastewater treatment plants, 1999 V2: 232233
xtures, 2003 V4: 2 AFF (above-nished oor), 2004 V1: 14
pipe characteristics, 2003 V4: 5960 AFFF foam concentrates, 2000 V3: 21
piping, 1999 V2: 14, 15, 68, 2000 V3: 48 after-coolers
plastic underdrains, 2000 V3: 131 air compressors, 2000 V3: 202203
weirs, 2000 V3: 146 air dryers and, 2000 V3: 207
activated alumina air dryers, 2000 V3: 204 medical air compressors, 2000 V3: 66
activated alumina water treatment, 1999 V2: 318 after-lters, 2000 V3: 203
activated carbon ltration (absorphan) AGA (American Gas Association)
in gray-water systems, 1999 V2: 27, 28 appliance venting standards, 1999 V2: 178
in gray-water treatment, 1999 V2: 29 dened, 2004 V1: 17
illustrated, 1999 V2: 301 gas-train vent standards, 1999 V2: 177
overview, 1999 V2: 300 relief valve standards, 1999 V2: 166
pure-water systems, 1999 V2: 323 water heating standards, 1999 V2: 170
small water systems, 1999 V2: 318 age of water mains, 2000 V3: 8
well water, 1999 V2: 244, 245 age-related disabilities, 2004 V1: 107
Activated Carbon Process for Treatment of Wastewater aggregation in soil structure, 1999 V2: 218
Containing Hexavalent Chromium (EPA 600/2-79- aggressiveness index, 1999 V2: 292
130), 2000 V3: 96 aging disabilities, 2004 V1: 107
activated sludge systems, 2000 V3: 95 aging water mains, 2000 V3: 8
active, dened, 2004 V1: 151 agitators in kill tanks, 1999 V2: 344
active potential, dened, 2004 V1: 151 agreement documents, 2004 V1: 62
active sludge, 2004 V1: 17 agreement states, 1999 V2: 340
active verbs in function analysis, 2004 V1: 224, 225 agricultural drain tile, 1999 V2: 221
activities in FAST approach, 2004 V1: 231 AHJ. See authorities having jurisdiction
actual cfh (acfh), 1999 V2: 180 ahp, AHP (air horsepower), 2004 V1: 14
actual cubic feet per minute. See acfm (actual cubic feet AHU (air-handling units), 2004 V1: 14
per minute) AI (aggressiveness index), 1999 V2: 292
actual ow rates, 2000 V3: 5, 217 AIA (American Institute of Architects). See American
actual liters per minute (aL/min), 2000 V3: 69, 200 Institute of Architects
actual pressure. See static pressure (SP) air
actuator-control valves, 2000 V3: 119 free, 2004 V1: 17, 2000 V3: 199, 200201
ACU (air-conditioning units), 2004 V1: 14 oil-free, 2000 V3: 83
ADA. See Americans with Disabilities Act in pipes, 1999 V2: 2
ADAAG (Americans with Disabilities Act Accessibility properties, 2000 V3: 199
Guidelines), 2004 V1: 105, 106 standard, 2004 V1: 1718
ADAAG Review Federal Advisory Committee, 2004 V1: water vapor in, 2000 V3: 200201
123 air, compressed. See compressed air (A, X#, X#A)
adapter ttings, 2004 V1: 17 air, free, 2004 V1: 17, 2000 V3: 199, 200201
addenda in contract documents, 2004 V1: 6263 air, oil-free, 2000 V3: 83
addresses of organizations and associations, 2004 V1: air, standard, 2004 V1: 17
5859 air-admittance valves, 2004 V1: 43, 1999 V2: 64
adiabatic processes, 2000 V3: 200 air binding, 2000 V3: 178, 180
adjustment section in specications, 2004 V1: 71, 92 air-bleed vacuum controls, 1999 V2: 268269
administrative and operation costs in value engineering. air breaks, 2004 V1: 17. See also air gaps
See overhead air chambers (AC)
administrative authorities, 2004 V1: 17 dened, 2004 V1: 17
admiralty brass, 2004 V1: 144 self-priming pumps, 2000 V3: 142
adp, ADP (apparatus dew points), 2004 V1: 14 symbols for, 2004 V1: 10
adsorption, 2000 V3: 204 water hammer arresters, 2004 V1: 198, 201, 1999 V2:
adult-sized wheelchairs, dimensions, 2004 V1: 108. See 132, 143
also wheelchairs air circuits in instrumentation, 2000 V3: 199
advanced oxidation water treatment, 1999 V2: 318 air compressors
aerated lagoons, 2000 V3: 95 accessories, 2000 V3: 202203
aerating fountain nozzles, 2000 V3: 108, 119120 compressed air systems, 2000 V3: 201202
aeration, 2004 V1: 17 dry-pipe systems, 2000 V3: 12
aeration cells, 2004 V1: 151 medical systems, 2000 V3: 65
aerators pulsation, 2000 V3: 205
aeration treatment, 1999 V2: 292294, 318 selection factors, 2000 V3: 213
lavatories and sinks, 2000 V3: 33 sizing, 2000 V3: 210213
sovent aerators, 1999 V2: 19, 46, 5456, 60, 62 types of, 2000 V3: 201202
aerobic, dened, 2004 V1: 17 vacuum pumps, 1999 V2: 259
272 ASPE Plumbing Engineering Design Handbook Volume 1
AIR COND (air conditioning). See air-conditioning area alarms, 2000 V3: 72
systems master alarms, 2000 V3: 72
Air-Conditioning and Refrigeration Institute (ARI), 2004 testing, 2000 V3: 81
V1: 4647, 58 on vacuum systems, 1999 V2: 259, 262
air-conditioning cooling towers. See cooling-tower water on water tanks, 1999 V2: 151
air-conditioning engineers, 2000 V3: 2728 overll prevention, 2000 V3: 158, 167
air-conditioning systems (AIR COND) pressurized fuel delivery systems, 2000 V3: 162
xture-unit values, 1999 V2: 9 Alaska Earthquake, 2004 V1: 161162
pipes, 2003 V4: 36 Albern, W.F., 1999 V2: 277
symbols, 2004 V1: 14 alcohol-resistant AFFF foam concentrates, 2000 V3: 21
waste heat usage, 2004 V1: 131 algae, 1999 V2: 282, 289, 2000 V3: 148
water demand, 1999 V2: 243 algaecides, 2000 V3: 150
air-conditioning units (ACU), 2004 V1: 14 alkalinity
air-consuming devices, 2000 V3: 206 alkaline solutions in corrosion rates, 2004 V1: 145
air-cooled after-coolers, 2000 V3: 203 boiler feed water, 1999 V2: 314
air densities, calculating, 2004 V1: 5 dealkalizing treatment, 1999 V2: 295
air dryers measuring, 1999 V2: 282283, 2000 V3: 123
compressed air systems, 2000 V3: 203204 pH and, 1999 V2: 285, 329, 2000 V3: 91
deliquescent dryers, 2000 V3: 207 predicting scale and corrosion, 1999 V2: 290
desiccant dryers, 2000 V3: 207 swimming pool water, 2000 V3: 147
medical air compressors, 2000 V3: 66 water saturation, 1999 V2: 293
refrigerated air dryers, 2000 V3: 207 allowable leakage in compressed air systems, 2000 V3: 209
selection, 2000 V3: 204 allowable radiation levels, 1999 V2: 339
air ducts, 2000 V3: 23 allowable vacuum system pressure loss, 1999 V2: 263
air ow rates, 2004 V1: 14 alloy pipes, 2004 V1: 18
air gaps. See also air breaks; effective openings alloys, 2004 V1: 18
as cross-connection control devices, 1999 V2: 144, 145, alpha ray radiation, 1999 V2: 337
148 alt, ALT (altitude), 2004 V1: 14
dened, 2004 V1: 17 alteration (altrn, ALTRN), 2004 V1: 14
air-gate valves, 1999 V2: 268 alternate bracing attachments for pipes, 2004 V1: 174
air-handling units (AHU), 2004 V1: 14, 267 alternating current (ac, AC), 2004 V1: 14
air horsepower (ahp, AHP), 2004 V1: 14 alternative collection and treatment of waste water, 1999
air intakes, 2000 V3: 211 V2: 232
air locks, 2004 V1: 201 alternative energy solutions, 2004 V1: 263267
air pressure, 1999 V2: 255256, 2000 V3: 12 alternative energy sources, 2004 V1: 130131
air receivers, 2000 V3: 205206 alternative sketches in value engineering, 2004 V1: 254,
air-separation chambers, 1999 V2: 56 255
air springs, 2004 V1: 203, 210 alternative treatment of waste water, 1999 V2: 226227
air temperatures Alternatives for Small Wastewater Treatment Systems:
pool heating and, 2000 V3: 121 Cost-effectiveness Analysis, 1999 V2: 238
swimming pools and, 2000 V3: 129 Alternatives for Small Wastewater Treatment Systems:
air tests On-site Disposal/Seepage Treatment and Disposal,
in cold-water systems, 1999 V2: 154 1999 V2: 238
dened, 2004 V1: 18 Alternatives for Small Wastewater Treatment Systems:
air velocity in vacuum cleaning systems, 1999 V2: 270 Pressure Sewers/Vacuum Sewers, 1999 V2: 238
air vessels (chambers), 2004 V1: 198 alternators
aircraft cable bracing method, 2004 V1: 171 medical air compressors, 2000 V3: 67
aircraft fuel, 1999 V2: 13 vacuum systems, 2000 V3: 70
airport runways, piping underneath, 1999 V2: 250 altitude (alt, ALT), 2004 V1: 14. See also elevation
aL/min (actual liters per minute), 2000 V3: 69, 200 altitude valves, 1999 V2: 249
ALARA (as low as reasonably achievable), 1999 V2: 341 altrn, ALTRN (alteration), 2004 V1: 14
alarm check valves, 2004 V1: 13, 18, 2000 V3: 9 alum, 1999 V2: 294, 2000 V3: 147, 150
alarm lines on sprinklers, 2000 V3: 9 aluminates, 2000 V3: 147
alarm relays, 2000 V3: 24 aluminosilicates, 2000 V3: 204
alarms aluminum, 2004 V1: 139, 144, 1999 V2: 281, 2000 V3: 20,
aboveground tank leakage, 2000 V3: 168 145
dened, 2004 V1: 18, 2000 V3: 83 aluminum 1100, 2004 V1: 141
on bulk oxygen supply, 2000 V3: 62 aluminum 2017 and 2024, 2004 V1: 141
on corrosive-waste systems, 2000 V3: 40 aluminum check valves, 1999 V2: 177
on hazardous waste systems, 2000 V3: 90 aluminum hydroxide, 1999 V2: 281, 2000 V3: 149150
on kill tanks, 1999 V2: 345 aluminum piping, 1999 V2: 68, 176, 196, 2000 V3: 47, 210
on medical gas systems aluminum silicates, 1999 V2: 301302, 2000 V3: 134
Index 273
aluminum sulfate, 1999 V2: 294, 2000 V3: 149150 Renery Piping, 2000 V3: 95
Amateur Athletic Union (AAU), 2000 V3: 151 ANSI/NFPA Standard no. 54: National Fuel Gas
amb, AMB (ambient), 2004 V1: 14 Code, 2000 V3: 248, 254
ambient (amb, AMB), 2004 V1: 14 ANSI/NSPI-1: Standard for Public Swimming
ambient temperature, 2004 V1: 18 Pools, 2000 V3: 125, 151
ambulatory accessible stalls, 2004 V1: 114 ANSI/NSPI-5: Standard for Residential, In-ground
American Chemical Society, 2004 V1: 153 Swimming Pools, 2000 V3: 151
American Concrete Institute, 1999 V2: 102, 114 ANSI Z358.1, 2003 V4: 18
American Consulting Engineers Council (ACEC), 2004 V1: ANSI ZE 86.1: Commodity Specication for Air,
62 2000 V3: 65, 86
American Gas Association (AGA) ASME/ANSI B16.22 Wrought Copper and Copper
appliance venting standards, 1999 V2: 178 Alloy Solder-Joint Pressure Fittings, 2003
dened, 2004 V1: 17 V4: 37
gas-train vent standards, 1999 V2: 177 ASME/ANSI B16.23 Cast Copper Alloy Solder-Joint
relief valve standards, 1999 V2: 166 Drainage Fittings, 2003 V4: 45
water heating standards, 1999 V2: 170 ASME/ANSI B16.26 Cast Copper Alloy Fittings for
American Institute of Architects (AIA) Flared Copper Tube, 2003 V4: 37
General Conditions of the Contract for Construction, ASME/ANSI B16.29 Wrought Copper and Wrought
2004 V1: 62 Copper Alloy Solder-Joint Drainage
Masterspec, 2004 V1: 71 Fittings, 2003 V4: 45
medical-gas guidelines, 2000 V3: 50 B16.15 Cast Bronze Threaded Fittings, 2003 V4: 27
specications format, 2004 V1: 63 B16.24 Cast Copper Alloy Pipe Flanges and
American National Standards Institute (ANSI) Flanged Fittings, 2003 V4: 27
abbreviation for, 2004 V1: 14, 18 B36.1 standard, 2003 V4: 48
address, 2004 V1: 58, 2000 V3: 97 standard air denition, 2000 V3: 200
consensus process, 2004 V1: 41 water quality standards, 1999 V2: 319
gas piping standards, 1999 V2: 194 American Petroleum Institute
list of standards, 2004 V1: 46 address, 2000 V3: 97, 173
publications, 2004 V1: 41 emergency vent standards, 2000 V3: 167
ANSI A112.6.1, 2003 V4: 6 publications
ANSI A112.18.3, 2003 V4: 14 AOIRP 1004: Bottom Loading and Vapor Recovery
ANSI A112.19.6, 2003 V4: 5, 9 for MC-306 Tank Motor Vehicles, 2000 V3:
ANSI A117.1-1980, 2004 V1: 105 173
ANSI A117.1-1986, 2004 V1: 105 API Bulletin no. 1611: Service Station Tankage
ANSI A117.1-1998, 2004 V1: 105, 106, 109123, Guide, 2000 V3: 173
2003 V4: 2, 14 API Bulletin no. 1615: Installation of Underground
ANSI/ASME B16.15 Cast Bronze Threaded Gasoline Tanks and Piping at Service
Fittings, 2003 V4: 34 Stations, 2000 V3: 173
ANSI/ASME B16.24 Cast Copper Alloy Pipe API Specication 12D: Large Welded Petroleum
Flanges and Flanged Fittings, 2003 V4: 34 Tanks, 2000 V3: 95
ANSI-ASSI: Building Code Requirements for API Specication 12F: Small Welded Petroleum
Minimum Design Loads in Buildings and Tanks, 2000 V3: 95
Other Structures, 2004 V1: 191 API Standard 250: Steel Tanks for Oil Storage,
ANSI/AWWA C104/A21.4 Cement Mortar Lining, 2000 V3: 95
2003 V4: 32 removal of globules standards, 1999 V2: 348
ANSI/AWWA C105/A21.5 Polyethylene Encasement, separators, 2000 V3: 93
2003 V4: 32 American Public Health Service, 1999 V2: 287
ANSI/AWWA C110/A21.10 Fitting, 2003 V4: 32 American Society for Testing and Materials (ASTM)
ANSI/AWWA C111/A21.11 Rubber-Gasket Joints, abbreviation for, 2004 V1: 18
2003 V4: 32 address, 2004 V1: 58
ANSI/AWWA C115/A21.15 Flanged Pipe, 2003 V4: ASTM B819 tubing, 2000 V3: 77
32 consensus process, 2004 V1: 41
ANSI/AWWA C116/A21.16 Fusion-Bonded Epoxy electronics-grade water standards, 1999 V2: 320
Coating, 2003 V4: 32 high-purity water standards, 1999 V2: 317
ANSI/AWWA C150/A21.50 Thickness Design, 2003 list of standards, 2004 V1: 41, 4952
V4: 32 membrane lters, 1999 V2: 289
ANSI/AWWA C151/A21.51 Manufacturing, 2003 publications
V4: 32 A-53 standard, 2003 V4: 48
ANSI/AWWA C153/A21.53 Compact Fittings, 2003 A-74 standard, 2003 V4: 28
V4: 32 A-106 standard, 2003 V4: 48
ANSI/AWWA C600 Installation, 2003 V4: 32 A-135 standard, 2003 V4: 48
ANSI B3.13: Chemical Plant and Petroleum A-716 Culvert Pipe, 2003 V4: 32
274 ASPE Plumbing Engineering Design Handbook Volume 1
A-746 Gravity Sewer Pipe, 2003 V4: 32 D-2466 standard, 2003 V4: 62
A-888 standard, 2003 V4: 28 D-2467 standard, 2003 V4: 62
ASME/ANSI B16.23 Cast Copper Alloy Solder-Joint D-2609 standard, 2003 V4: 61
Drainage Fittings, 2003 V4: 45 D-2662 standard, 2003 V4: 58
ASTM D2863: Method for Measuring the Minimum D-2665 standard, 2003 V4: 62
Oxygen Concentration to Support Candle- D-2666 standard, 2003 V4: 58
like Combustion of Plastics, 2000 V3: 85 D-2672 standard, 2003 V4: 62
B-16.9 standard, 2003 V4: 48 D-2737 standard, 2003 V4: 61
B-16.11 standard, 2003 V4: 48 D-3139 standard, 2003 V4: 62
B-16.28 standard, 2003 V4: 48 E-33.08b Plumbing Noise, 2004 V1: 194
B-16.50 Wrought Copper Braze Fittings, 2003 V4: F-477 standard, 2003 V4: 62
45 F-876 standard, 2003 V4: 61
B-29 standard, 2003 V4: 49 F-877 standard, 2003 V4: 61
B-42 Standard Specication for Seamless Copper F-1281 standard, 2003 V4: 62
Pipe, Standard Sizes, 2003 V4: 34 F-1282 standard, 2003 V4: 62
B-43 Standard Specication for Seamless Red reagent-grade water standards, 1999 V2: 279, 319
Brass Standard Sizes, 2003 V4: 27 American Society of Civil Engineers (ASCE)
B-88 Specication for Seamless Copper Water Tube, contract publications, 2004 V1: 62
2003 V4: 35 sewer publications, 1999 V2: 95, 114
B-306 Specication for Copper Drainage Tube American Society of Heating, Refrigerating and Air-
(DWV), 2003 V4: 35 Conditioning Engineers, Inc. (ASHRAE)
B-306 Standard Specication for Copper Drainage address, 2004 V1: 58
Tube (DWV), 2003 V4: 45 dened, 2004 V1: 18
B-813 Standard Specication for Liquid and Paste hot-water recirculation systems, 2004 V1: 265
Fluxes for Soldering Applications of Copper list of standards, 2004 V1: 47
and Copper Alloy Tube, 2003 V4: 37 publications
B-819 Specication for Seamless Copper Tube for Handbook of Fundamentals, 2004 V1: 2, 5, 6, 40,
Medical Gas Systems, 2003 V4: 35 2000 V3: 197
B-819 Standard Specication for Seamless Copper Handbooks, 1999 V2: 214
Tube for Medical Gas Systems, 2003 V4: 45 water heating codes and standards, 1999 V2: 170
B-828 Standard Practice for Making Capillary American Society of Mechanical Engineers (ASME)
Joints by Soldering of Copper and Copper address, 2004 V1: 58, 2000 V3: 97
Alloy Tube and Fittings, 2003 V4: 37 air receivers, 2000 V3: 205
C-4 standard, 2003 V4: 49 dened, 2004 V1: 18
C-12 standard, 2003 V4: 49 red and unred pressure vessel standards, 1999 V2:
C-14 Standard Specication for Concrete Sewer, 170
Storm Drain, and Culvert Pipe for Non- list of standards, 2004 V1: 4748
reinforced Concrete, 2003 V4: 32 publications
C-76 Standard Specication for Reinforced ANSI/ASME A112.6.1, 2003 V4: 6
Concrete Culverts, Storm Drain, and Sewer ANSI/ASME A112.18.1, 2003 V4: 14
Pipe, 2003 V4: 32 ANSI/ASME A112.19.6, 2003 V4: 5, 9
C-296 standard, 2003 V4: 26 ANSI/ASME B16.15 Cast Bronze Threaded
C-301 standard, 2003 V4: 49 Fittings, 2003 V4: 34
C-425 standard, 2003 V4: 49 ANSI/ASME B16.24 Cast Copper Alloy Pipe
C-428 standard, 2003 V4: 26 Flanges and Flanged Fittings, 2003 V4: 34
C-443 Standard Specication for Joints for ASME A17.1 Safety Code for Elevators and
Circular Concrete Sewer and Culvert Pipe, Escalators, 2000 V3: 25
Using Rubber Gaskets, 2003 V4: 32 ASME/ANSI B16.22 Wrought Copper and Copper
C-599-77 standard, 2003 V4: 48 Alloy Solder-Joint Pressure Fittings, 2003
C-655 Standard Specication for Reinforced V4: 37
Concrete D-Load Culvert Storm Drain and ASME/ANSI B16.24 Cast Copper Alloy Pipe
Sewer Pipe for Reinforced Concrete Pipe, Flanges and Flanged Fittings, 2003 V4: 37
2003 V4: 32 ASME/ANSI B16.26 Cast Copper Alloy Fittings for
C-700 standard, 2003 V4: 49 Flared Copper Tube, 2003 V4: 37
C-828 standard, 2003 V4: 49 ASME/ANSI B16.29 Wrought Copper and Wrought
C-896 standard, 2003 V4: 49 Copper Alloy Solder-Joint Drainage
D-1148 standard, 2003 V4: 61 Fittings, 2003 V4: 45
D-1784 standard, 2003 V4: 62 ASME Boiler and Pressure Vessel Code, 2000 V3: 95
D-1785 standard, 2003 V4: 62 B16.15 Cast Bronze Threaded Fittings, 2003 V4: 27
D-2239 standard, 2003 V4: 61 Fuel-Gas Piping, 1999 V2: 214
D-2241 standard, 2003 V4: 62 relief valve standards, 1999 V2: 166
D-2464 standard, 2003 V4: 62 American Society of Plumbing Engineers (ASPE)
Index 275
ASPE Solar Energy System Design Handbook, 2004 overview, 2004 V1: 105
V1: 130 Amin, P., 1999 V2: 325
dened, 2004 V1: 18 ammonia, 1999 V2: 282, 294
Domestic Water Heating Design Manual, 2000 V3: 45 amp, AMP, AMPS (ampere). See amperes
medical gas station guidelines, 2000 V3: 50, 5152 ampacity, 2000 V3: 83
publications, 1999 V2: 65 amperes (A, amp, AMP, AMPS)
American Society of Plumbing Engineers Research ampere-hours, 2004 V1: 139
Foundation (ASPERF), 2004 V1: 18 amperes per meter, 2004 V1: 33
American Society of Safety Engineers (ASSE), 2004 V1: 18 measurement conversions, 2004 V1: 33
American Society of Sanitary Engineering (ASSE), 2004 symbols for, 2004 V1: 14
V1: 18 amphoteric corrosion, dened, 2004 V1: 151
address, 2004 V1: 58 amphoteric materials, 2004 V1: 145
ASSE 1002, 2003 V4: 8 amusement parks, numbers of xtures for, 2003 V4: 19
ASSE 6000 Professional Qualications Standard for anaerobic bacteria in septic tanks, 1999 V2: 227
Medical Gas Systems Installers, Inspectors, anaerobic wastewater treatment, 2000 V3: 95
Veriers, Maintenance Personnel and anaerobic, dened, 2004 V1: 18, 151
Instructors, 2003 V4: 45 Analysis phase of value engineering, 2004 V1: 213,
list of standards, 2004 V1: 4849 224. See also Function Analysis phase in value
American standard pipe threads, 2004 V1: 18 engineering
American Standards Association. See American National analytical grade water, 1999 V2: 317
Standards Institute (ANSI) anchoring equipment
American Water Works Association (AWWA) anchorage forces in earthquakes, 2004 V1: 186
address, 2004 V1: 58 anchors, dened, 2004 V1: 191
dened, 2004 V1: 18 re-protection equipment, 2000 V3: 23
list of standards, 2004 V1: 52 illustrations of potential problems, 2004 V1: 189
publications seismic protection, 2004 V1: 163
ANSI/AWWA C104/A21.4 Cement Mortar Lining, anchoring pipes, 1999 V2: 18, 85
2003 V4: 32 anchors, dened, 2004 V1: 18, 12004 V1: 191
ANSI/AWWA C105/A21.5 Polyethylene Encasement, anechoic chambers, 2004 V1: 198
2003 V4: 32 anesthesia workrooms
ANSI/AWWA C110/A21.10 Fitting, 2003 V4: 32 xtures, 2000 V3: 36
ANSI/AWWA C111/A21.11 Rubber-Gasket Joints, health-care facilities, 2000 V3: 32
2003 V4: 32 medical air, 2000 V3: 53
ANSI/AWWA C115/A21.15 Flanged Pipe, 2003 V4: medical gas stations, 2000 V3: 51
32 anesthetic gas management, 2000 V3: 7071
ANSI/AWWA C116/A21.16 Fusion-Bonded Epoxy anesthetics, 2000 V3: 83
Coating, 2003 V4: 32 anesthetizing locations, 2000 V3: 83
ANSI/AWWA C150/A21.50 Thickness Design, 2003 ANG (angle). See angles (ANG)
V4: 32 ANGI (angles of incidence), 2004 V1: 14
ANSI/AWWA C151/A21.51 Manufacturing, 2003 angle grates in school shower rooms, 1999 V2: 11
V4: 32 angle snubbers, 2004 V1: 165
ANSI/AWWA C153/A21.53 Compact Fittings, 2003 angle stops, 2004 V1: 18
V4: 32 angle valves (AV), 2004 V1: 9, 18
ANSI/AWWA C600 Installation, 2003 V4: 32 angles (ANG)
AWWA Cross Connection Control Manual, 1999 V2: measurements, 2004 V1: 33
155 symbols, 2004 V1: 14
AWWA Standard for Disinfecting Water Mains, angles of bend, 2004 V1: 18
1999 V2: 155 angles of incidence (ANGI), 2004 V1: 14
AWWA Standard for Disinfection of Water Storage angular acceleration measurements, 2004 V1: 33
Facilities, 1999 V2: 155 angular velocity measurements, 2004 V1: 33
C-400 standard, 2003 V4: 26 animal research centers, 1999 V2: 147, 344, 2000 V3: 51
C651 Disinfecting, 2003 V4: 32 animal shelters, 1999 V2: 16
American Welding Society (AWS), 2004 V1: 52, 58, 167 animal treatment rooms, 2000 V3: 45
American wire gage (AWG), 2004 V1: 14 anions
Americans with Disabilities Act Accessibility Guidelines anion resins, 1999 V2: 284, 305
(ADAAG), 2004 V1: 106 dened, 2004 V1: 151, 1999 V2: 280
Americans with Disabilities Act (ADA) in electromotive force series, 2004 V1: 144
ADAAG Review Federal Advisory Committee, 2004 V1: in ion exchange, 1999 V2: 300, 301, 302
123 in pH values, 1999 V2: 329
faucet ow rates, 2004 V1: 135 annealed temper (soft), 2003 V4: 37
xture standards, 2003 V4: 2 annual costs. See costs and economic concerns
history, 2004 V1: 106 annular chambers in dry-pipe systems, 2000 V3: 11
276 ASPE Plumbing Engineering Design Handbook Volume 1
annular spaces in wells, 1999 V2: 240, 243 measurements, 2004 V1: 33
anodes non-SI units, 2004 V1: 34
anode expected life, 2004 V1: 148 symbols, 2004 V1: 14
anodic protection, 2004 V1: 151152 area alarms, 2000 V3: 49, 72, 81
dened, 2004 V1: 139, 151 area drains, 2004 V1: 18
galvanic series of metals, 2004 V1: 141 areas of sprinkler operation, 2000 V3: 16
sacricial anodes, 2004 V1: 147 areaways, 1999 V2: 67, 69
anodic inhibitors, 2004 V1: 151 arenas, numbers of xtures for, 2003 V4: 19
anodic potential (electronegative potential), 2004 V1: 153 ARI (Air Conditioning and Refrigeration Institute), 2004
anodic protection, dened, 2004 V1: 151152 V1: 4647, 58
ANSI. See American National Standards Institute (ANSI) arm baths, 2000 V3: 32, 35, 38
anthracite coal lters, 1999 V2: 244, 300, 2000 V3: 132, Army Corps of Engineers, 2004 V1: 63
134 arresters for water hammer. See water hammer arresters
anthropometrics for wheelchairs, 2004 V1: 109 arterial vents, 2004 V1: 18, 1999 V2: 52
anti-cross-connection precautions, 1999 V2: 32 articulated-ceiling medical gas systems, 2000 V3: 59
anti-siphon ballcocks, 2003 V4: 8 as low as reasonably achievable (ALARA), 1999 V2: 341
anti-vortex drains, 2000 V3: 117 ASA A117.1-1961, 2004 V1: 105
anti-vortex grating, 2000 V3: 110 asbestos cement piping, 1999 V2: 122, 2000 V3: 245
apartment buildings asbestos concrete piping, 2003 V4: 26
reghting demand ow rates, 2000 V3: 232 ASCE. See American Society of Civil Engineers (ASCE)
numbers of xtures for, 2003 V4: 20, 21 ASHRAE. See American Society of Heating, Refrigerating
apparatus dew points (adp, ADP), 2004 V1: 14 and Air-Conditioning Engineers, Inc. (ASHRAE)
appearance functions ASI (architects supplemental instructions), 2004 V1: 63
dened, 2004 V1: 225 ASME. See American Society of Mechanical Engineers
in value engineering, 2004 V1: 243 (ASME)
appliances. See also xtures ASPE. See American Society of Plumbing Engineers
acoustic ratings, 2004 V1: 194195, 198 (ASPE)
appliance connectors, 1999 V2: 176 ASPERF (American Society of Plumbing Engineers
codes and standards, 2004 V1: 4344 Research Foundation), 2004 V1: 18
dened, 1999 V2: 213 aspirating nozzles on foam extinguishers, 2000 V3: 21
draft hoods on appliances, 1999 V2: 178, 213 aspirators, 2004 V1: 18, 2000 V3: 38
gas regulators, 2000 V3: 251 ASSE. See American Society of Safety Engineers (ASSE);
gravity vents for gas appliances, 1999 V2: 178 American Society of Sanitary Engineering (ASSE)
natural gas, 1999 V2: 175, 177178 assembly costs, 2004 V1: 222
oxygen depletion and gas appliances, 1999 V2: 178 assembly halls
Applied Technology Council (ATC), 2004 V1: 183, 191 numbers of xtures for, 2003 V4: 19, 21
approaches to toilet compartments, 2004 V1: 114 single-occupant toilet rooms, 2003 V4: 23
approvals assisted creativity, 2004 V1: 232
for radioactive materials systems, 1999 V2: 340 assisted living facilities, numbers of xtures for, 2003 V4:
for special-waste drainage systems, 1999 V2: 328 20
approved, dened, 2004 V1: 18 Association for the Advancement of Medical
approved testing agencies, 2004 V1: 18 Instrumentation (AAMI), 1999 V2: 279, 317, 319
approximate (approx., APPROX) ASTM. See American Society for Testing and Materials
approximate values, 2004 V1: 32 (ASTM)
dened, 2004 V1: 14 ASTM A53 piping, 2000 V3: 254
appurtenances, in plumbing cost estimation, 2004 V1: 93, ASTM A106 piping, 2000 V3: 254
97 ASTs (aboveground storage tanks). See aboveground tank
aquastats, 2004 V1: 10, 2000 V3: 112, 125 systems
Aqueous Film-Forming Foam (AFFF), 2000 V3: 21 ATBCB (U.S. Architectural and Transportation Barriers
aquifers Compliance Board), 2004 V1: 106, 107
dened, 1999 V2: 240 ATC-3 (Tentative Provisions for the Development of
potentiometric surfaces, 1999 V2: 241 Seismic Regulations for Buildings), 2004 V1: 183,
in private water systems, 1999 V2: 239 191
unconsolidated aquifers, 1999 V2: 241 Atienze, J., 1999 V2: 34
arabic numerals, 2004 V1: 32 atm, ATM (atmospheres). See atmospheres
arcades, numbers of xtures for, 2003 V4: 19 atmospheres (atm, ATM)
Architect-engineers Turf Sprinkler Manual, 2000 V3: 105 converting to SI units, 2004 V1: 39
architects supplemental instructions (ASI), 2004 V1: 63 symbols, 2004 V1: 14
Architectural Barriers Act (90-480), 2004 V1: 106 vacuum units, 1999 V2: 254
area (A) atmospheric pressure in vacuum, 1999 V2: 254
calculating, 2004 V1: 35 atmospheric regulators, 2000 V3: 251
conversion factors, 2004 V1: 35 atmospheric tanks
Index 277
dened, 2000 V3: 153 automatic trap primers, 1999 V2: 10, 14
foam, 2000 V3: 21 automotive trafc, 1999 V2: 11, 223
venting, 2000 V3: 157158 autopsy rooms
atmospheric vacuum breakers (AVB) xtures, 2000 V3: 35, 38
cross-connection control, 1999 V2: 144 health-care facilities, 2000 V3: 32
dened, 2004 V1: 18 medical gas stations, 2000 V3: 51, 58
faucets, 2003 V4: 14 medical vacuum, 2000 V3: 54
hazard levels and, 1999 V2: 145 non-potable water, 2000 V3: 45
irrigation sprinklers, 2000 V3: 103, 104 AV (acid vents), 2004 V1: 8, 17
spillage, 1999 V2: 148 AV (angle valves), 2004 V1: 9, 18
atmospheric vaporizers, 2000 V3: 61 availability. See demand
atmospheric vents (steam or hot vapor) (ATV), 2004 V1: 9 available vacuum, safety factors and, 1999 V2: 276
attachments, 2004 V1: 191 AVB. See atmospheric vacuum breakers (AVB)
atto prex, 2004 V1: 34 average (avg, AVG), dened, 2004 V1: 14
ATV (atmospheric vents), 2004 V1: 9 average pressure drops in water systems, 1999 V2: 125,
Auciello, Eugene P., 1999 V2: 114 126, 127
auditoriums, numbers of xtures for, 2003 V4: 19, 21 avg, AVG (average), 2004 V1: 14
authorities having jurisdiction AW (acid wastes), 2004 V1: 8, 17, 2000 V3: 42
dened, 2004 V1: 17, 18, 2000 V3: 83 AWG (American wire gage), 2004 V1: 14
re hazard evaluations, 2000 V3: 2 AWS. See American Welding Society (AWS)
re-protection system design, 2000 V3: 1 AWWA. See American Water Works Association (AWWA)
gaseous re-suppression systems, 2000 V3: 22 Ayres, J.M., 2004 V1: 191
manholes, 2000 V3: 234 az, AZ (azimuth). See azimuth (az, AZ)
medical gas stations, 2000 V3: 56 azimuth (az, AZ)
public sewer availability, 2000 V3: 234 solar (SAZ), 2004 V1: 14
swimming pools, 2000 V3: 127 symbols for, 2004 V1: 14
automatic air vents (AAV), 2004 V1: 10 wall (WAZ), 2004 V1: 14
automatic alternators, 2000 V3: 70
automatic drain valves, 2000 V3: 103
automatic drains in vacuum systems, 2000 V3: 70
B
B-16.9 standard, 2003 V4: 48
automatic ll lines makeup-water systems, 2000 V3: 124 B-16.11 standard, 2003 V4: 48
automatic re-detection devices, 2000 V3: 13 B-16.15 Cast Bronze Threaded Fittings, 2003 V4: 27
automatic re-protection systems, 2000 V3: 118 B-16.24 Cast Copper Alloy Pipe Flanges and Flanged
history and objectives, 2000 V3: 12 Fittings, 2003 V4: 27
pipes and hangers, 2000 V3: 15 B-16.28 standard, 2003 V4: 48
automatic ushometer valves, 2003 V4: 8 B-29 standard, 2003 V4: 49
automatic heat-up, 2000 V3: 191, 195, 196 B-36.1 standard, 2003 V4: 48
automatic overll prevention, 2000 V3: 167 B-43 Standard Specication for Seamless Red Brass
automatic overrides for irrigation controllers, 2000 V3: Standard Sizes, 2003 V4: 27
104 b/m (bills of material), 2004 V1: 14
automatic skimmers, 2000 V3: 146 back pressure tests, 2003 V4: 5
Automatic Sprinkler and Standpipe Systems, 2000 V3: 29 back pressures in pipes, 1999 V2: 2, 4, 35, 2000 V3: 251
automatic sprinkler systems back-siphonage, 2004 V1: 18, 1999 V2: 144, 145, 2000 V3:
combined dry-pipe and pre-action, 2000 V3: 15 103. See also backow
design density, 2000 V3: 15 back-spud water closets, 2003 V4: 3
effectiveness statistics, 2000 V3: 2 back-to-back water closets, 2003 V4: 67
elevator shafts, 2000 V3: 25 back venting, 1999 V2: 43, 47
re hazard evaluation, 2000 V3: 23 backlling
re pumps for, 2000 V3: 25 around septic tanks, 1999 V2: 228
gaseous re-suppression systems and, 2000 V3: 22 around subsurface drainage pipes, 1999 V2: 102
history, 2000 V3: 12 around water system pipes, 1999 V2: 250
hydraulic design, 2000 V3: 1518 backll dened, 2004 V1: 18
materials, 2000 V3: 12 building sewers and, 1999 V2: 15
numbers of sprinklers in operation, 2000 V3: 16 fountain piping systems, 2000 V3: 116
pipes and hangers, 2000 V3: 12, 15 labor productivity rates, 2004 V1: 96
pre-action systems, 2000 V3: 13 in plumbing cost estimation, 2004 V1: 93
system design, 2000 V3: 218 storage tanks, 2000 V3: 155, 172
types, 2004 V1: 29, 2000 V3: 815 backow. See also back-siphonage
water supplies, 2000 V3: 38 backow connections, dened, 2004 V1: 18
Automatic Sprinkler Systems Handbook, 2004 V1: 191 dened, 2004 V1: 18
automatic storage water heaters, 1999 V2: 160 backow preventers
automatic tank gauging, 2000 V3: 159160 codes, 2004 V1: 42
278 ASPE Plumbing Engineering Design Handbook Volume 1
cold-water pressure losses and, 1999 V2: 125 Baltimore Dept. of Public Works, 1999 V2: 34
cold-water systems, 1999 V2: 144149 banned practices in asbestos concrete piping, 2003 V4: 26
cross-connection control devices, 1999 V2: 144145 banquet halls, numbers of xtures for, 2003 V4: 19
dened, 2004 V1: 18 bare pipe, 2004 V1:150, 2004 V1: 150
domestic water supply, 2000 V3: 221224 barium, 1999 V2: 281
faucets, 2003 V4: 1314 baro, BARO (barometric), 2004 V1: 14
re-protection connections, 2000 V3: 225, 226 baro pr, BARO PR (barometric pressure). See barometric
xtures in health-care facilities, 2000 V3: 33 pressure
hazard assessment, 1999 V2: 145 barometers (baro, BARO)
installation, 1999 V2: 148149 symbols for, 2004 V1: 14
isolating premises, 1999 V2: 145147 vacuums and, 1999 V2: 254
makeup water in fountains, 2000 V3: 124 barometric (baro, BARO), dened, 2004 V1: 14
pressure loss, 2000 V3: 224 barometric loops, 1999 V2: 144
reduced pressure zones, 2000 V3: 223 barometric pressure (baro pr, BARO PR, BP), 2000 V3:
roof drains, 1999 V2: 84 200
thermal expansion compensation and, 1999 V2: 167 altitude adjustments, 1999 V2: 257
vacuum breakers, 1999 V2: 144, 149, 2000 V3: 33, 45 barometric, dened, 2004 V1: 14
background levels of radiation, 1999 V2: 339 barometric pressure, dened, 2004 V1: 15
backing rings, 2004 V1: 18 in vacuums, 1999 V2: 254, 275
backup, dened, 2004 V1: 18 barrels
backup demineralizers, 2000 V3: 46 converting to SI units, 2004 V1: 39
backup storm-drainage systems, 1999 V2: 70, 79 dimensions, 2003 V4: 2931
backwash from pool ltration, 2000 V3: 112, 113, 137 barrier free, 2004 V1: 18. See also people with disabilities
backwash from water softeners, 1999 V2: 244, 307 barriers
backwash pits, 2000 V3: 137, 140, 143 around tanks, 2000 V3: 169
backwashing in sound insulation, 2004 V1: 193
diatomaceous earth lters, 2000 V3: 139 bars, converting to SI units, 2004 V1: 39
lters, 1999 V2: 300 bars, numbers of xtures for, 2003 V4: 19
in regeneration cycle, 1999 V2: 304305 base acquisition costs, 2004 V1: 223
sand lters, 2000 V3: 132 base materials
vacuum diatomaceous earth ltration, 2000 V3: 135 base dened, 2004 V1: 18
backwater valves, 2004 V1: 19, 43, 1999 V2: 12, 13 compounds in water, 1999 V2: 280
bacteria pH control, 2000 V3: 9192
biological fouling, 1999 V2: 289, 316317 base units, 2004 V1: 33
chemical control, 1999 V2: 311313 basic functions in value engineering, 2004 V1: 225, 227,
demineralizer systems, 2000 V3: 46 230
distilled water and, 2000 V3: 46 basic material standards, 2004 V1: 66
in drinking water, 1999 V2: 244 Basic Plumbing Code (BOCA), 2000 V3: 154
in feed water, 1999 V2: 282 basket strainers
in lters, 1999 V2: 300 fountain pumps, 2000 V3: 116
in hot water, 2000 V3: 45 head loss and, 2000 V3: 115
in septic tanks, 1999 V2: 227 maintenance, 2000 V3: 110
in swimming pools, 2000 V3: 148 materials, 2000 V3: 146
in water-heating systems, 1999 V2: 169 pre-manufactured skimmers, 2000 V3: 137
in wells, 1999 V2: 243 pumps, 2000 V3: 115
bafe systems, 2000 V3: 46 swimming pool pumps, 2000 V3: 140
bafeplates, 2004 V1: 18 bathhouses, 1999 V2: 235, 2000 V3: 129, 130
bafes in septic tanks, 1999 V2: 228 bathing rooms, 2004 V1: 112113
bag-lter gross ltration, 1999 V2: 300 bathroom groups, 1999 V2: 43, 62, 63, 2000 V3: 217
Bahamas, gray-water systems in, 1999 V2: 33 bathtub ll valves, 2003 V4: 16
bailers, 2000 V3: 162 bathtubs
balancing pumps, 2004 V1: 197 accessibility design, 2004 V1: 117119
balancing valves (BLV), 2004 V1: 9, 2000 V3: 115 acoustic ratings of, 2004 V1: 194
balcony drains, 1999 V2: 69 bathtub enclosures, 2004 V1: 118119
ball-and-globe valves, 2000 V3: 118 estimated water ows from, 1999 V2: 25
ball check valves, 2004 V1: 18 xture-unit loads, 1999 V2: 3
ball joints, bracing and, 2004 V1: 171 grab bars, 2004 V1: 116, 117
ball removal tests, 2003 V4: 5 gray-water systems and, 2004 V1: 135, 1999 V2: 22
ball valves (BV), 2004 V1: 9, 18, 1999 V2: 332, 2000 V3: 72 health-care facilities, 2000 V3: 32
Ballanco, Julius, 1999 V2: 114 infant bathtubs, 2000 V3: 34
ballast pads, 2000 V3: 172 minimum numbers of, 2003 V4: 1822
ballcocks, 2003 V4: 8 overows, 2003 V4: 16
Index 279
blow-off in air compressors, 2000 V3: 205 in health-care facilities, 2000 V3: 44
blowdown low-pressure re pumps, 2000 V3: 25
boiler blowdown, 1999 V2: 314, 315 noise control, 2004 V1: 199
cooling towers, 1999 V2: 316 booster water heaters, 2004 V1: 126, 129, 1999 V2: 160
removing sludge, 1999 V2: 289 boosting water pressure, 1999 V2: 149152
steam traps, 2000 V3: 195 borate, 1999 V2: 282
blowout xtures, acoustic design and, 2004 V1: 195 bore holes for wells, 1999 V2: 240
blowout urinals, 2003 V4: 89, 9 bored wells, 1999 V2: 241
blowout water closets, 2003 V4: 3 borings
blue dyes in gray water, 1999 V2: 22, 33 subsurface site drainage, 1999 V2: 100
blue water in pools, 2000 V3: 148 wells, 1999 V2: 240
BLV (balancing valves), 2004 V1: 9, 2000 V3: 115 borosilicate glass piping, 1999 V2: 14, 15, 122, 2000 V3: 40,
Board for Coordination of Model Codes (BCMC), 2004 V1: 2003 V4: 47
106 Bosich, Joseph F., 2004 V1: 154
boarding houses, numbers of xtures for, 2003 V4: 20 bottled gas, 1999 V2: 174
bobbin-wound berglass lters, 2000 V3: 131 bottled water, 2003 V4: 14
BOCA. See Building Ofcials and Code Administrators Bottom Loading and Vapor Recovery for MC-306 Tank
International, Inc. (BOCA) Motor Vehicles (AOIRP 1004), 2000 V3: 173
BOD (biological oxygen demand), 2000 V3: 21, 93 Bourdon gauges, 1999 V2: 260
body sprays, 2003 V4: 16 bowl depth of sinks, 2004 V1: 117
Boegly, W.J., 1999 V2: 238 Boyle, W.C., 1999 V2: 34
Boiler and Pressure Vessel Code, 2000 V3: 95 BP (barometric pressure). See barometric pressure
boiler blow-off tanks, 2004 V1: 18 bp, BP (boiling points). See boiling points (bp, BP)
boiler blow-offs, 2004 V1: 18 braces (walking aids), 2004 V1: 107
boiler feed lines, 2003 V4: 34 bracing
boiler room earthquake protection, 2004 V1: 166 aircraft cable method, 2004 V1: 171
Boiler Water Treatment, 1999 V2: 325 alternate attachments for pipes, 2004 V1: 174
boilers avoiding potential earthquake problems, 2004 V1: 189
cast-iron supports for, 2004 V1: 162 dened, 2004 V1: 191
codes and standards, 2004 V1: 42 hanger rod connections, 2004 V1: 177
condensation, 2004 V1: 267 hanger rods, 2004 V1: 166
earthquake protection, 2004 V1: 163 hubless cast-iron pipe, 2004 V1: 177
feed lines, 2003 V4: 34 lateral sway bracing, 2004 V1: 181182
feed pumps, 2000 V3: 188189 longitudinal and transverse bracing, 2004 V1: 180
feed receivers, 2000 V3: 188 longitudinal-only bracing, 2004 V1: 172, 180
feed water corrosion inhibitors, 2004 V1: 151 open-web steel joists, 2004 V1: 176
feed water treatments, 1999 V2: 314315 pipes on trapeze and, 2004 V1: 175, 178
gas train arrangements, 2000 V3: 251 piping systems for seismic protection, 2004 V1: 166
natural gas systems and, 1999 V2: 174 182
scaling, 1999 V2: 289 riser bracing for hubless pipes, 2004 V1: 178
sediment buckets in drains, 1999 V2: 12 self bracing, 2004 V1: 190
short cycling, 2000 V3: 180 spacing of, 2004 V1: 184
steam heating systems, 2000 V3: 178 steel beam connections, 2004 V1: 175
swimming pool heaters, 2000 V3: 138 structural angle bracing, 2004 V1: 171
boiling points (bp, BP) structural channel bracing, 2004 V1: 171
dened, 1999 V2: 213 strut bracing, 2004 V1: 173, 175
liquid fuels, 2000 V3: 153 superstrut, 2004 V1: 170
liquid oxygen, 2000 V3: 61 sway bracing, 2004 V1: 179, 180, 181182, 185186,
symbols for, 2004 V1: 14 187
bollards, 2000 V3: 169, 172 Tension 360 bracing, 2004 V1: 169
bolting problems in seismic protection, 2004 V1: 190 transverse bracing, 2004 V1: 171, 179
bolts for water closets, 2003 V4: 6 truss-type actions, 2004 V1: 190
BOM (bills of material), 2004 V1: 14 typical earthquake bracing, 2004 V1: 168
bonded joints, 2004 V1:150 brainstorming in creativity, 2004 V1: 232
bonds and certicates, 2004 V1: 62 brake horsepower (bhp, BHP)
bonnets, 2004 V1: 18 re pumps, 2000 V3: 25
booster-pump systems pumps, 2004 V1: 6
connections, 2000 V3: 225 symbols for, 2004 V1: 14
constant pressure and, 1999 V2: 152 branch-bottom connections, 2004 V1: 11
constant use and, 1999 V2: 121 branch intervals, 2004 V1: 18, 1999 V2: 64
domestic water service, 2000 V3: 216 branch lines, 2000 V3: 85
re-protection systems, 2000 V3: 8 branch sewers (submain sewers), 2004 V1: 30
Index 281
branch tees, 2004 V1: 18 Btu, BTU (British Thermal units). See British Thermal
branch-top connections, 2004 V1: 11 units
branch vents, 2004 V1: 18 Btu/h (British thermal units per hour), 2004 V1: 18, 2000
branches, dened, 2004 V1: 18 V3: 122
brand names in specications, 2004 V1: 66, 67 Btu (J) (re loads), 2000 V3: 3
brass bubble aerators, 1999 V2: 293
dezincication, 2004 V1: 141 bubbler irrigation heads, 2000 V3: 103
in electromotive force series, 2004 V1: 144 bubbles, 1999 V2: 38, 2000 V3: 21. See also detergents;
in galvanic series, 2004 V1: 141 soaps; suds
brass (copper alloy) pipe, 1999 V2: 14, 2003 V4: 27 bufng nishes on grates, 1999 V2: 11
brass ttings, 1999 V2: 196 building code list of agencies, 2004 V1: 42
brass oor drains, 1999 V2: 15, 16 Building Code Requirements for Minimum Design Loads
brass pipes, 1999 V2: 68, 122, 176, 196, 2000 V3: 116 in Buildings and Other Structures, 2004 V1: 191
brass pool lighting, 2000 V3: 145 building drains
brazed joints combined, 2004 V1: 19
earthquake protection and, 2004 V1: 167 cross-sections of, 1999 V2: 2
inspection, 2000 V3: 80 dened, 2004 V1: 19, 1999 V2: 64
medical gas tubing, 2000 V3: 77, 2003 V4: 45 ow in, 1999 V2: 2
brazing alloys on gas piping, 1999 V2: 196 inspection checklist, 2004 V1: 102103
brazing ends, 2004 V1: 18 installation, 1999 V2: 15
Brazing Joints for Copper and Copper Alloy Pressure pneumatic pressure in, 1999 V2: 2
Fittings, 2003 V4: 45 sanitary. See sanitary drainage systems
break points (chlorination), 2000 V3: 149 sovent system connections, 1999 V2: 6061
breakdown chlorination, 2000 V3: 149 storm. See storm-drainage systems
breathing apparatus building inspectors, 2000 V3: 2
chlorine gas, 2000 V3: 148 Building Ofcials and Code Administrators International,
diatomaceous earth and, 2000 V3: 134 Inc. (BOCA), 1999 V2: 114, 2000 V3: 154
for emergencies, 1999 V2: 332, 333 BOCA Basic Plumbing Code, 1999 V2: 114, 2000 V3:
brick dome covers on seepage pits, 1999 V2: 225 154
brines building sewers (house drains), 2004 V1: 19, 1999 V2: 15
hydrostatic monitoring systems, 2000 V3: 160 building sites. See site utilities; sites
refrigerants, 2004 V1: 151 building storm-sewer pipe codes, 2004 V1: 42
in water softening, 1999 V2: 307 building subdrains, 2004 V1: 19
British thermal units (Btu, BTU) Building Systems Design, 1999 V2: 277
British thermal units per hour (Btu/h), 2004 V1: 18, building traps, 2004 V1: 19
2000 V3: 122 buildings
Btu (J) (re loads), 2000 V3: 3 acceptable plumbing noise levels, 2004 V1: 193
calculating hot water savings, 2004 V1: 127 building material acoustic insulation, 2004 V1: 193
converting to SI units, 2004 V1: 39 construction and re hazards, 2000 V3: 2
dened, 2004 V1: 18, 136, 1999 V2: 213 dened, 2004 V1: 18
natural gas services, 2000 V3: 249 essential facilities, 2004 V1: 191
symbols for, 2004 V1: 14 expansion, 2000 V3: 49
bromine, 2000 V3: 123, 149 isolating premises with backow hazards, 1999 V2:
bromtriuoro-methane CBrF3 (halon 1301), 2004 V1: 25 145147
bronze ltration tanks, 2000 V3: 131 minimum numbers of xtures, 2003 V4: 1822
Bronze Fittings for Brazed Joints, 2003 V4: 27, 34 standard re tests, 2000 V3: 3
bronze oor drains, 1999 V2: 15 storm-drainage systems. See storm-drainage systems
bronze-mounted, dened, 2004 V1: 18 subdrains, 2004 V1: 19
bronze pumps, 2000 V3: 115, 145 traps, 2004 V1: 19
bronze sediment buckets, 1999 V2: 14 type of structure and earthquake protection, 2004 V1:
bronze trim, 2004 V1: 18 167
bronze valves, 2000 V3: 145 utilities. See site utilities
bronze, in electromotive force series, 2004 V1: 141 built-in continuous pool gutters, 2000 V3: 137
Brown & Sharpe wire gage (B&S), 2004 V1: 14 built-in showers, 2003 V4: 15
Brown, F.R., 2004 V1: 191 bulk media tests, 2003 V4: 6
Brown, J., 1999 V2: 325 bulk oxygen systems, 2000 V3: 59, 6162, 63
brown water, 2000 V3: 147 bulkhead ttings, 2000 V3: 163
Brownstein, E., 1999 V2: 65 bull head tees, 2004 V1: 20
brushes for swimming pool cleaning, 2000 V3: 146 bumpers, 2000 V3: 228, 229
Bryan, John L., 2000 V3: 29 Buna-N (nitrile butadiene), 2000 V3: 169
B&S (Brown & Sharpe wire gage), 2004 V1: 14 Bunsen burners, 1999 V2: 176
buried piping. See underground piping
282 ASPE Plumbing Engineering Design Handbook Volume 1
burners, dened, 1999 V2: 213 calcium silicates, 1999 V2: 283
burning methane, 2004 V1: 130131 calcium sulfate, 1999 V2: 281
burning rates of plastic pipe, 2003 V4: 5960 calculations. See equations
burst pressure, 2004 V1: 20 calendars for irrigation controllers, 2000 V3: 104
Burton, Franklin L., 2000 V3: 125 California Administrative Code of Regulations, 2004 V1:
bushels, converting to SI units, 2004 V1: 39 183
bushings, 2004 V1: 20 California Code of Regulations, 2004 V1: 191
businesses, numbers of xtures for, 2003 V4: 19 California Plumbing Code, 1999 V2: 34
butane, 1999 V2: 194, 213. See also fuel-gas piping systems calories
butt caps on re hydrants, 2000 V3: 4 caloric values of natural gas, 1999 V2: 173, 212, 214
butt-welded standard weight pipe, 2003 V4: 48 converting to SI units, 2004 V1: 39
butt welding caloric values in re loads, 2000 V3: 23
butt-weld end connections, 2004 V1: 23 Camerons Hydraulic Data, 2000 V3: 221
butt weld joints, 2004 V1: 20 camps, septic tank systems for, 1999 V2: 231232
butt weld pipes, 2004 V1: 20 CAN/CSA-B137.1 standard, 2003 V4: 61
radioactive drainage systems, 1999 V2: 341 CAN/CSA-B137.2 standard, 2003 V4: 62
buttery valves (BFV), 2004 V1: 9, 20, 2000 V3: 118 CAN/CSA-B137.3 standard, 2003 V4: 62
BV (ball valves), 2004 V1: 9, 18, 1999 V2: 332 CAN/CSA-B137.9 standard, 2003 V4: 62
bypass systems for pools, 2000 V3: 122, 144 CAN/CSA-B137.10 standard, 2003 V4: 62
bypass valves, 2004 V1: 20, 2003 V4: 18 can pumps, 2004 V1: 24
bypasses, 2004 V1: 20 CAN3-B137.8 standard, 2003 V4: 58
Canadian Standards Association (CSA)
C address, 2004 V1: 58, 2000 V3: 86
consensus process, 2004 V1: 41
C, C (celsius), 2004 V1: 14, 34
c (centi) prex, 2004 V1: 34 list of standards, 2004 V1: 5354
C (conductance), 2004 V1: 14, 33 medical compressed air standards, 2000 V3: 67
C (coulombs), 2004 V1: 33, 139 publications
c (curies), 1999 V2: 339 CAN/CSA-B137.1 standard, 2003 V4: 61
C (specic heat). See specic heat CAN/CSA-B137.2 standard, 2003 V4: 62
c to c, C TO C (center to center), 2004 V1: 14 CAN/CSA-B137.3 standard, 2003 V4: 62
C-4 standard, 2003 V4: 49 CAN/CSA-B137.9 standard, 2003 V4: 62
C-12 standard, 2003 V4: 49 CAN/CSA-B137.10 standard, 2003 V4: 62
C-296 standard, 2003 V4: 26 CAN3-B137.8 standard, 2003 V4: 58
C-301 standard, 2003 V4: 49 CSA Z-305.1: Non-ammable Medical Gas Piping
C-400 standard, 2003 V4: 26 Systems, 2000 V3: 86
C-425 standard, 2003 V4: 49 water closet standards, 2003 V4: 6
C-428 standard, 2003 V4: 26 candelas (cd), 2004 V1: 33
C-599-77 standard, 2003 V4: 48 candelas per meter squared (cd/m2), 2004 V1: 33
C-700 standard, 2003 V4: 49 cantilevered drinking fountains, 2004 V1: 112
C-828 standard, 2003 V4: 49 CAP (College of American Pathologists), 1999 V2: 279,
C-896 standard, 2003 V4: 49 317, 319
C/m3 (coulombs per cubic meter), 2004 V1: 33 capacitance
CAAA (Clean Air Act Amendments), 2000 V3: 154 measurements, 2004 V1: 33
cables, earthquake protection and, 2004 V1: 166 tank gauging, 2000 V3: 160
CABO (Council of American Building Ofcials), 2004 V1: capacity (ow). See ow rates
123 capacity of swimming pools, 2000 V3: 127128
cadmium, 2004 V1: 141 capillaries, 2004 V1: 20
calcication in lters, 2000 V3: 132, 150 caps on ends of pipes, 2004 V1: 11
calcium capture-type vacuum pumps, 1999 V2: 259
dened, 1999 V2: 283 car trafc, 1999 V2: 11, 223
scale formation and corrosion, 1999 V2: 290 car washes
in water, 1999 V2: 244, 281 gray-water use, 2004 V1: 267
calcium 45, 1999 V2: 340 heat recovery systems, 2004 V1: 266
calcium bicarbonate, 1999 V2: 281 car-washing facilities, 1999 V2: 147
calcium carbonate (lime), 1999 V2: 281, 283, 285, 291, carbohydrazide, 1999 V2: 315
2000 V3: 147 carbon
calcium chloride, 1999 V2: 283 adsorption of oil spills, 1999 V2: 347
calcium hydroxide, 1999 V2: 283 corrosion, 2004 V1: 139, 145
calcium hypochlorite, 1999 V2: 245, 2000 V3: 148149, total organic carbon, 1999 V2: 288
149, 150151 in water, 1999 V2: 281
calcium phosphate, 1999 V2: 283 carbon 14, 1999 V2: 340
Calcium Saturation Index (CSI), 2000 V3: 123 carbon dioxide (CO2)
Index 283
color coding, 2000 V3: 56 liqueed petroleum gas, 1999 V2: 196
decarbonation, 1999 V2: 295 Manning formula and, 2000 V3: 245
extinguishing systems, 2000 V3: 2021 natural gas, 2000 V3: 254
medical gas system tests, 2000 V3: 83 radioactive materials systems and, 1999 V2: 341
portable re extinguishers, 2000 V3: 27 roughness, 1999 V2: 122
in steam systems, 2000 V3: 190 sanitary drainage systems, 1999 V2: 14
symbols for, 2004 V1: 9 storm-drainage systems, 1999 V2: 8992
in water, 1999 V2: 281, 284, 294 tree roots and, 1999 V2: 223
Carbon Dioxide Extinguishing Systems (NFPA 12), 2000 underground piping, 1999 V2: 68
V3: 20, 29 cast-iron soil pipe
carbon ltration (absorphan). See activated carbon dimensions of hubs, spigots and barrels, 2003 V4:
ltration (absorphan) 2931
carbon monoxide, 2000 V3: 83 telescoping and laying lengths, 2003 V4: 28
carbon steel, 2004 V1: 144, 2000 V3: 91, 92, 116, 210 types, 2003 V4: 2731
carbon steel casings, 1999 V2: 179 Cast-iron Soil Pipe and Fittings Engineering Manual,
carbonate lms, 2004 V1: 151 1999 V2: 114
carbonates, 1999 V2: 281, 282, 283, 290, 2000 V3: 147 Cast Iron Soil Pipe Institute (CISPI), 2004 V1: 20, 53, 58,
carbonic acid, 1999 V2: 281 1999 V2: 114
carpets, vacuum calculations for, 1999 V2: 269 CISPI 301 standard, 2003 V4: 28
cartridge ltration, 1999 V2: 300, 305306, 312, 323, 2000 CISPI 310 standard, 2003 V4: 28
V3: 112, 113 cast-iron tank legs, 2004 V1: 163
Cartwright, Peter, 1999 V2: 325 catch basins, 2000 V3: 157
cascade waterfall aerators, 1999 V2: 293 piping size, 1999 V2: 69
casings in site storm systems, 1999 V2: 98
driven wells, 1999 V2: 241 Category II, III, or IV vent systems, 2004 V1: 43
gas boosters, 1999 V2: 179 cathodes
jetted wells, 1999 V2: 241 dened, 2004 V1: 139, 152
well casings, 1999 V2: 240 galvanic series of metals, 2004 V1: 141
Cassidy, Victor M., 2004 V1: 137 cathodic corrosion, 2004 V1: 152
cast-aluminum oor drains, 1999 V2: 15 cathodic inhibitors, 2004 V1: 151
cast bronze solder-joint ttings, 2003 V4: 38 cathodic potential (electropositive potential), 2004 V1: 153
cast bronze threaded ttings, 2003 V4: 27 cathodic protection
Cast Bronze Threaded Fittings, 2003 V4: 27, 34 criteria, 2004 V1: 150151
Cast Copper Alloy Fittings for Flared Copper Tube, 2003 dened, 2004 V1: 20, 152
V4: 37 introduction, 2004 V1: 139
Cast Copper Alloy Pipe Flanges and Flanged Fittings, liquid fuel tanks, 2000 V3: 155
2003 V4: 27, 34, 37 methods, 2004 V1: 147151
Cast Copper Alloy Solder-Joint Drainage Fittings, 2003 sand ltration tanks, 2000 V3: 131
V4: 45 cathodic, dened, 2004 V1: 152
cast-lled acrylic xtures, 2003 V4: 2 cations
cast-lled berglass xtures, 2003 V4: 2 cation resins, 1999 V2: 284, 305
cast glands, 2000 V3: 229 dened, 2004 V1: 152, 1999 V2: 280
cast-in-place anchor bolts, 2004 V1: 163 in ion exchange, 1999 V2: 300, 301, 302
cast iron in pH values, 1999 V2: 329
in electromotive series, 2004 V1: 144 caulking
fountain pumps, 2000 V3: 115 caulked joints on oor drains, 1999 V2: 16
in galvanic series, 2004 V1: 141 dened, 2004 V1: 20
graphitization, 2004 V1: 141 causes and effects
radiators, 2000 V3: 179, 180 in creativity checklist, 2004 V1: 234
swimming pool main drains, 2000 V3: 143 of earthquakes, 2004 V1: 156158
cast-iron boiler supports, 2004 V1: 162 caustic embrittlement, 2004 V1: 152
cast-iron ttings, 1999 V2: 196 caustic soda, 1999 V2: 333, 337, 2000 V3: 93
cast-iron xtures caustic waste from regeneration cycle, 1999 V2: 304
enameled, 2003 V4: 12 cavitation
in health-care facilities, 2000 V3: 33 anti-vortex drains, 2000 V3: 117
standards, 2003 V4: 2 cavitation corrosion, 2004 V1: 152
cast-iron oor drains, 1999 V2: 16, 17 dened, 2004 V1: 20, 152
cast-iron piping exible pipe connectors and, 2004 V1: 200
blocking, 1999 V2: 250 fountain pumps, 2000 V3: 108
bracing, 2004 V1: 177 modications to pump plants, 2004 V1: 197
corrosion and, 2004 V1: 150 pressure levels and, 2004 V1: 200
laboratories, 2000 V3: 40 reducing noise source strength, 2004 V1: 199
284 ASPE Plumbing Engineering Design Handbook Volume 1
health-care facility medical gas and vacuum systems, chlorimine, 1999 V2: 300
2000 V3: 4950 chlorinated polyethylene sheet shower pans, 2003 V4: 15
idea development and estimated cost forms, 2004 V1: chlorinated polyvinyl-chloride (CPVC)
241242 dened, 2004 V1: 21
idea evaluation worksheet, 2004 V1: 243, 253 industrial waste usage, 2000 V3: 93
project information checklists, 2004 V1: 215220 pipe characteristics, 2000 V3: 48, 2003 V4: 5960
project information sources checklists, 2004 V1: 221 pipes, 1999 V2: 284, 2003 V4: 62
recommendations worksheets, 2004 V1: 258, 259 VOCs and, 1999 V2: 284
storage tanks, 2000 V3: 173 chlorination
storm-drainage calculations, 1999 V2: 109113 disinfecting water systems, 1999 V2: 252
using in presentations, 2004 V1: 257 domestic water systems, 1999 V2: 154
value engineering checklists, 2004 V1: 214 drinking water, 1999 V2: 245
chemical cleaning connections, 2000 V3: 47 gray water, 1999 V2: 27, 28, 29
chemical feed pumps for pools, 2000 V3: 148, 150151 wells, 1999 V2: 243
chemical ltration, 2000 V3: 112 chlorine
Chemical Plant and Petroleum Renery Piping (ANSI as disinfectant in pools, 2000 V3: 123
B3.13), 2000 V3: 95 bleaches, 1999 V2: 230
chemical plants, 1999 V2: 147, 2000 V3:87 breakdown chlorination, 2000 V3: 149
chemical pretreatment of oils, 2000 V3: 93 chlorine-resistant grates, 1999 V2: 15
chemical regeneration in demineralizers, 2000 V3: 46 cyanide and, 2000 V3: 93
chemical-resistance testing, 2003 V4: 2 gas, 2000 V3: 146, 148
chemical spill emergency xtures, 2003 V4: 17 microbial control, 1999 V2: 311
chemical-waste drains pure water systems, 1999 V2: 323
glass pipe, 2003 V4: 47 reecting pools and fountains, 2000 V3: 108
plastic pipes, 2003 V4: 58 removing, 1999 V2: 300
chemical-waste systems residuals, 2000 V3: 146, 147, 148
codes and standards, 1999 V2: 345 reverse osmosis and, 2000 V3: 47
dened, 2004 V1: 20 small drinking water systems, 1999 V2: 318
design considerations, 1999 V2: 346 superchlorination, 2000 V3: 149
pipe and joint selection, 1999 V2: 345346 swimming pool heaters and, 2000 V3: 138
chemically-stabilized emulsions, 1999 V2: 347 swimming pool water chemistry, 2000 V3: 146
chemicals in water chemistry, 1999 V2: 281, 284
analysis of swimming pool water, 2000 V3: 131 chlorouorocarbons (CFCs), 2000 V3: 22
chemical characteristics of drinking water, 1999 V2: chloroform, 2000 V3: 70
316, 318 chrome-plated brass, 2000 V3: 145
chemical control of microbes in water, 1999 V2: 311 chromium III, 2000 V3: 93
chemical treatment of oil spills, 1999 V2: 347, 348 chromium-iron, 2004 V1: 141
emulsions, 2000 V3: 93 chromium VI, 2000 V3: 93
feed pumps for pools, 2000 V3: 148, 150151 Church, James, 1999 V2: 114
ltration, 2000 V3: 112 churches, numbers of xtures for, 2003 V4: 19, 22
laboratory vacuum systems, 1999 V2: 262 Ciba-Geigy Pipe Systems, Inc., 2000 V3: 97
material safety data sheets, 2000 V3: 90 cigarette burn testing, 2003 V4: 2
in septic tanks, 1999 V2: 230231 CIN (cubic inches), 2004 V1: 14
in special-waste efuent, 1999 V2: 328 cinders as backll, 1999 V2: 222
chemistry of water. See water chemistry circles, calculating area, 2004 V1: 5
children, xtures and circuit venting, 2004 V1: 20, 1999 V2: 4344, 64
xture heights, 2004 V1: 107 circuits (ckt, CKT), 2004 V1: 14, 20
water closets, 2003 V4: 45 circular lavatories, 2003 V4: 11
water coolers, 2003 V4: 14 circulating pumps in pools, 2000 V3: 139
chilled drinking water recirculating (DWR), 2004 V1: 8 circulating water systems
chilled drinking water supply (DWS), 2004 V1: 8, 265, in geothermal energy systems, 2004 V1: 131
2000 V3: 34 hot water systems, 1999 V2: 165
chilled water returns (CWR), 2004 V1: 8 standby losses in, 2004 V1: 127
chilled water supply (CWS), 2004 V1: 8 circulation loops, 2000 V3: 47
chimneys CISPI (Cast Iron Soil Pipe Institute)
codes, 2004 V1: 43 abbreviation, 2004 V1: 20
dened, 1999 V2: 213 address, 2004 V1: 58
heights, 1999 V2: 178 Cast Iron Soil Pipe and Fittings Engineering Manual,
china xtures, 2003 V4: 12 1999 V2: 114
chips in acid-neutralization tanks, 2000 V3: 40, 41 CISPI 301 standard, 2003 V4: 28
chloramines, 2000 V3: 149 CISPI 310 standard, 2003 V4: 28
chlorides, 2004 V1: 147, 1999 V2: 281, 283, 302 publications, 2004 V1: 53
286 ASPE Plumbing Engineering Design Handbook Volume 1
coated steel lters, 2000 V3: 131 inadequate water pressure, 1999 V2: 149152
corrosion protection, 2004 V1: 147 introduction, 1999 V2: 115
natural gas piping, 1999 V2: 176 pipe codes, 2004 V1: 45
passivation, 2004 V1: 146147 pipe sizing, 1999 V2: 121131, 133142, 136
septic tanks, 1999 V2: 228 potable water systems, 2000 V3: 45
sprinkler head ratings, 2000 V3: 17 references, 1999 V2: 155
storage tanks, 2000 V3: 172 residential systems, 1999 V2: 115116
storm piping, 1999 V2: 68 testing, cleaning, and disinfection, 1999 V2: 154155
coaxial truck delivery hoses, 2000 V3: 157 water hammer, 1999 V2: 131132
coaxial vapor recovery, 2000 V3: 163, 167 water line sizing, 1999 V2: 116131
cocks, 2004 V1: 20 coliform group of bacteria, 2004 V1: 21
Code of Federal Regulations (CFR), 1999 V2: 317, 2000 coliform organism tests, 1999 V2: 155
V3:88, 2000 V3: 96, 154 coliseums, numbers of xtures for, 2003 V4: 19
codes and standards collection legs in condensate drainage, 2000 V3: 191, 195
chemical-waste systems, 1999 V2: 345 collective bargaining agreements, cost estimates and, 2004
citing, 2004 V1: 67 V1: 98
codes, dened, 2004 V1: 20 collectors (dug wells), 1999 V2: 240
concrete pipe, 2003 V4: 32 College of American Pathologists (CAP), 1999 V2: 279,
domestic water supply, 2000 V3: 216 317, 319
ductile iron pipe, 2003 V4: 32 Collentro, W.V., 1999 V2: 325
re protection, 2000 V3: 1, 225 colloidal particles, removing, 1999 V2: 294, 2000 V3: 93
xtures, 2003 V4: 2 colloidal silica, 1999 V2: 283
gasoline and diesel-oil systems, 2000 V3: 154 colony forming units (cfus), 1999 V2: 282
gray-water systems, 1999 V2: 22 color
health-care facilities, 2000 V3: 3134 of drinking water, 1999 V2: 316
hot-water systems, 1999 V2: 170 of feed water, 1999 V2: 282, 287
industrial wastewater treatment, 2000 V3:8790 of gray water, 1999 V2: 29, 33
infectious and biological waste systems, 1999 V2: medical gas codes, 2000 V3: 54, 56
343344 of pool lights, 2000 V3: 121
medical gas systems, 2000 V3: 83 of soils, 1999 V2: 218219
natural gas services, 2000 V3: 248 of swimming pool water, 2000 V3: 147
NFPA standards, 2000 V3: 1 color codes
plumbing materials and equipment, 2004 V1: 4157 copper drainage tube, 2003 V4: 45
plumbing standards for people with disabilities, 2004 copper pipes, 2003 V4: 3536
V1: 105106 medical gas tube, 2003 V4: 45
reference-based standards, 2004 V1: 66 seamless copper water tube, 2003 V4: 37
searching, 2000 V3: 215 column radiators, 2000 V3: 181
seismic protection, 2004 V1: 171184 columns in ion exchange systems, 1999 V2: 302
special-waste drainage systems, 1999 V2: 327328 combination building water supplies, 2000 V3: 225226
storm sewers, 2000 V3: 240 combination dry-pipe and pre-action systems, 2004 V1: 29,
swimming pools, 2000 V3: 127 2000 V3: 15
vacuum-cleaning systems, 1999 V2: 266 combination xtures, dened, 2004 V1: 21
vacuum systems, 1999 V2: 262 combination storm-drainage and sanitary sewers, 1999 V2:
water analysis, treatment and purication, 1999 V2: 12, 67, 93, 2000 V3: 247
279, 317 combination temperature and pressure relief valves, 1999
water heaters, 2004 V1: 129 V2: 166
coefcients (coeff., COEF), 2004 V1: 14 combination thermostatic and pressure balancing valves,
coefcients of expansion, 2004 V1: 20 2003 V4: 15, 16
coefcients of hydrant discharge, 2000 V3: 4, 5 combination vacuum-cleaning systems, 1999 V2: 266
coefcients of permeability (K factor), 1999 V2: 100101, combination waste and vent systems, 2004 V1: 21, 1999
104105, 242 V2: 4546, 64
coefcients of transmissibility (Q factor), 1999 V2: 101 combined building drains, 2004 V1: 20
102 combined residuals, 2000 V3: 146
coefcients of valve ow (C Cv, Cv, CV), 2004 V1: 14 combustibles
coffee sinks, 1999 V2: 25. See also sinks and wash basins dened, 2000 V3: 83, 153
cogeneration systems, waste heat usage, 2004 V1: 134 re loads, 2000 V3: 23
coherent unit systems, 2004 V1: 32 metal res, 2000 V3: 20
coils (COIL), 2004 V1: 14 combustion efciency, 2004 V1: 21
cold water (CW), 2004 V1: 8 combustion exhaust from natural gas, 1999 V2: 177
cold-water systems combustion products, 2000 V3: 83
backow prevention, 1999 V2: 144149 Commercial Energy Conservation Manual, 2004 V1: 137
excess water pressure, 1999 V2: 152154 commercial facilities
288 ASPE Plumbing Engineering Design Handbook Volume 1
commercial/industrial gas service, 2000 V3: 249 air receivers, 2000 V3: 205206
estimating sewage quantities, 1999 V2: 234 compressors, 2000 V3: 201202, 210213
reghting demand ow rates, 2000 V3: 232 condensate removal, 2000 V3: 213
gray-water systems, 1999 V2: 25 conditioning, 2000 V3: 207
grease interceptors, 1999 V2: 13 contaminants, 2000 V3: 201
natural gas appliance demand, 1999 V2: 175 denitions, 2000 V3: 199200
oil interceptors in drains, 1999 V2: 1213 earthquake bracing for piping, 2004 V1: 167
radioactive waste drainage and vents, 1999 V2: 337 measurement units, 2000 V3: 200
commercial kitchen sinks, 2003 V4: 12, 13 overview, 2000 V3: 199
commercial laundries. See laundry systems and washers piping system design, 2000 V3: 206213
Commercial Standards (CS), 2004 V1: 21 air-consuming devices, 2000 V3: 206207
Commercial Water Use Research Project, 1999 V2: 34 air dryers, 2000 V3: 207
commissioning section in specications, 2004 V1: 71, 92 design sequence, 2000 V3: 206
Commodity Specication for Air (CGA G-7.1/ANSI ZE duty cycles, 2000 V3: 207
86.1), 2000 V3: 65, 83, 86 lters, 2000 V3: 207
Commodity Specication for Nitrogen (CGA G-10.1), 2000 future expansion, 2000 V3: 210
V3: 86 leakage, 2000 V3: 209
commodity tube, 2003 V4: 35 materials, 2000 V3: 210
common vents (dual vents), 2004 V1: 21, 1999 V2: 41, 64 sizing piping, 2000 V3: 74, 78, 210
community bathhouses, 1999 V2: 235 use factors, 2000 V3: 209
Compact Fittings, 2003 V4: 32 pressure drops, 2000 V3: 212
compacted ll, building sewers and, 1999 V2: 15 references, 2000 V3: 214
companion anges, 2004 V1: 21 regulation methods, 2000 V3: 205
comparative cost analysis, 2004 V1: 254 starting unloaders, 2000 V3: 205
comparing functions in value engineering, 2004 V1: 243 tools and equipment, 2000 V3: 208
compartments in septic tanks, 1999 V2: 229 water vapor in air, 2000 V3: 200201
competition swimming pools, 2000 V3: 128, 129, 139 compressed gas. See natural gas systems
components section in specications, 2004 V1: 91 Compressed Gas Association, Inc. (CGA), 2000 V3: 56
composite tanks, 2000 V3: 156 address, 2004 V1: 58, 2000 V3: 86
composting toilets, 2004 V1: 136, 265 list of standards, 2004 V1: 53
compound gauges, 2000 V3: 144 publications
compound water meters, 1999 V2: 115, 116, 117 CGA C-9: Standard for Color-marking of
compounds in water, 1999 V2: 281 Compressed Gas Cylinders Intended for
Comprehensive Environmental Response Compensation Medical Use, 2000 V3: 86
and Liability Act (CERCLA), 2000 V3:88, 2000 V3: CGA G-7.0: Compressed Air for Human
8990, 96 Respiration, 2000 V3: 86
compressed air (A, X#, X#A). See also compressed air CGA G-7.1/ANSI ZE 86.1: Commodity Specication
systems for Air, 2000 V3: 83, 86
compared to free air, 2000 V3: 199 CGA G-8.1: Standard for the Installation of Nitrous
dened, 2004 V1: 18 Oxide Systems at Consumer Sites, 2000 V3:
laboratory or medical compressed air, 2004 V1: 8, 2000 86
V3: 3739, 6568, 75, 8283 CGA G-10.1: Commodity Specication for Nitrogen,
overview, 2000 V3: 199 2000 V3: 86
piping, 1999 V2: 177 CGA P-2: Characteristics and Safe Handling of
supplies to water tanks, 1999 V2: 247 Medical Gases, 2000 V3: 86
symbols for, 2004 V1: 8 CGA P-9: Inert Gases: Argon, Nitrogen and Helium,
tools and equipment, 2000 V3: 208 2000 V3: 81, 82, 86
uses, 2000 V3: 199 CGA V-5: Diameter-Index Safety System, 2000 V3:
water vapor in air, 2000 V3: 200201 83, 86
Compressed Air and Gas Data, 1999 V2: 214 Compressed Air and Gas Handbook, 2000 V3: 214
Compressed Air and Gas Handbook, 2000 V3: 214 standard air denition, 2000 V3: 200
Compressed Air Data, 2000 V3: 214 compression couplings
Compressed Air Design for Industrial Plants, 2000 V3: clay pipe, 2003 V4: 49
214 glass pipe, 2003 V4: 48
Compressed Air for Human Respiration (CGA G-7.0), 2000 compression ttings
V3: 86 cast iron, 2003 V4: 27, 28
Compressed Air Fundamentals, 2000 V3: 214 dened, 2004 V1: 24
Compressed Air Handbook, 2000 V3: 214 compression joints, 2004 V1: 21
Compressed Air Magazine, 2000 V3: 214 compressive strength of plastic pipe, 2003 V4: 5960
compressed air systems compressors (cprsr, CMPR)
accessories, 2000 V3: 202203 dened, 2004 V1: 21
air dryers, 2000 V3: 203204, 207 earthquake protection, 2004 V1: 164
Index 289
air-conditioning system water, 1999 V2: 243 in plumbing cost estimation, 2004 V1: 94
design techniques, 2004 V1: 134135 continuing education, 2004 V1: 72
domestic water supply, 2000 V3: 43 continuous acid-waste treatment systems, 1999 V2: 338
green design, 2004 V1: 263267 continuous deionization (CDI), 1999 V2: 306307
institutional wastewater systems, 1999 V2: 232 continuous duty pumps, 2000 V3: 26
introduction, 2004 V1: 124 continuous ow. See steady ow
large sewage systems and, 1999 V2: 231 continuous ow pool gutters, 2000 V3: 142
urinals, 2003 V4: 89 continuous vents, dened, 2004 V1: 21, 1999 V2: 64
water closet xtures, 2003 V4: 3 continuous waste, 2004 V1: 21
constant-speed pumps, 1999 V2: 152 continuous wastewater treatment, 2000 V3: 95
constantly-used xtures, 1999 V2: 121 continuous welding technique, 2003 V4: 48
Constructed Science Research Foundation Spectext, 2004 contract documents. See construction contract documents
V1: 71 contraction of pipes
construction change directives, 2004 V1: 63 calculating, 2004 V1: 3
construction contract documents (CD) pool temperature and, 2000 V3: 145
contract documents dened, 2004 V1: 61 protecting against, 1999 V2: 18
dened, 2004 V1: 61 Control of Pipeline Corrosion, 2004 V1: 154
overview, 2004 V1: 61 control panels
project manuals, 2004 V1: 6263 clean gas systems, 2000 V3: 24
value engineering clauses in, 2004 V1: 258, 260 re alarm, 2004 V1: 12
construction costs in value engineering, 2004 V1: 212 fountains, 2000 V3: 120121
Construction Specications Canada (CSC) Uniformat, control systems in geothermal energy systems, 2004 V1:
2004 V1: 64 131
Construction Specications Institute (CSI) control valves
classes, 2004 V1: 72 medical gas systems, 2000 V3: 7172
Constructed Science Research Foundation, 2004 V1: 71 swimming pools, 2000 V3: 139
general conditions documents, 2004 V1: 62 controlled-ow storm-drainage systems, 1999 V2: 88,
Manual of Practice, 2004 V1: 61 9394
MasterFormat, 2004 V1: 64 controlled-substance spills, 1999 V2: 277
MasterFormat 2004, 2004 V1: 6465, 7788 controllers
MasterFormat Level Four (1995), 2004 V1: 76 dened, 2004 V1: 21
MasterFormat Level One (1995), 2004 V1: 73 for irrigation systems, 2000 V3: 104
MasterFormat Level Three (1995), 2004 V1: 76 controls
MasterFormat Level Two (1995), 2004 V1: 7375 in accessible shower compartments, 2004 V1: 120
section shell outline, 2004 V1: 8892 in bathtubs, 2004 V1: 118
Sectionformat, 2004 V1: 65 dened, 2004 V1: 21
Uniformat, 2004 V1: 64, 73 on gas boosters, 1999 V2: 182
web site, 2004 V1: 65 on water heaters, 1999 V2: 160
Consultation phase in value engineering, 2004 V1: 243, vacuum systems, 1999 V2: 260, 268, 2000 V3: 70
254 convection, 2000 V3: 121
consumption. See demand convention halls, numbers of xtures for, 2003 V4: 21
contact corrosion, dened, 2004 V1: 152 convergent thinking in evaluation, 2004 V1: 235
contact factors (CF), 2004 V1: 14 converging seismic plates, 2004 V1: 158
contact sheets, 2000 V3: 215 conversion factors and converting
contact time for microbial control, 1999 V2: 311 Fahrenheit and Centigrade, 2004 V1: 38
Containment Control in Biotechnology Environments, 1999 feet of head to pounds per square inch, 2004 V1: 2
V2: 350 fuel gas, 1999 V2: 212
containment oors or dikes, 2000 V3: 90 IP and metric units, 2000 V3: 29
containment of biological wastes, 1999 V2: 343 IP and SI, 2004 V1: 3940, 1999 V2: 256
containment pipes and gas piping, 1999 V2: 176 measurements, 2004 V1: 32
containment sumps, 2000 V3: 156, 163, 167 meters of head to pressure in kilopascals, 2004 V1: 2
contamination issues vacuum acfm and scfm, 1999 V2: 256, 257
backow prevention, 1999 V2: 144149 vacuum pressures, 1999 V2: 254
bored wells, 1999 V2: 241 water impurity measurements, 1999 V2: 285
compressed air, 2000 V3: 201 cooling compressors, 2000 V3: 201
contaminant classication, 2000 V3: 222 cooling equipment, green building and, 2004 V1: 264
contaminators, dened, 2004 V1: 21 cooling re areas, 2000 V3: 20
dug wells, 1999 V2: 240 cooling loads (clg load, CLG LOAD, CLOAD), 2004 V1: 14
gray-water irrigation systems and, 1999 V2: 26 cooling-tower water
well protection, 1999 V2: 243 constant use and, 1999 V2: 121
contingency corrosion inhibitors, 2004 V1: 151
plans for industrial wastes, 2000 V3: 89 exclusion from gray-water systems, 1999 V2: 21
Index 291
Legionella pneumophila, 1999 V2: 169 control of, 2004 V1: 145151, 1999 V2: 18, 244
reducing makeup water, 2004 V1: 264 cooling towers, 1999 V2: 316
use of gray water in, 1999 V2: 21 corrosion cells, 2004 V1: 139, 140, 148
waste heat usage, 2004 V1: 131 corrosion mitigation, 2004 V1: 152
water demand, 1999 V2: 243 corrosion potential, 2004 V1: 152
water treatments, 1999 V2: 315316 corrosion-resistant materials, 2004 V1: 146, 1999 V2:
coordination disabilities, 2004 V1: 107 15
coordination with other designers, 1999 V2: 79, 81, 84 corrosion-resistant sprinklers, 2004 V1: 29
COP (coefcient of performance), 2004 V1: 136 corrosive wastes, 1999 V2: 14
copper deaeration and, 1999 V2: 294
corrosion, 2004 V1: 139 dened, 2004 V1: 139, 152
in electromotive series, 2004 V1: 144 electromotive force series, 2004 V1: 144
in galvanic series, 2004 V1: 141 factors in rate of, 2004 V1: 144145
pool lighting, 2000 V3: 145 fatigue and fatigue limits, 2004 V1: 152
swimming pool main drains, 2000 V3: 143 glossary, 2004 V1: 151154
copper alloy piping, 1999 V2: 14, 2003 V4: 27 hot-water relief valves, 1999 V2: 166
copper-copper sulte half-cells, 2004 V1: 144 inhibitors, 2004 V1: 151
Copper Development Association (CDA), 2004 V1: 20, 1999 introduction, 2004 V1: 139
V2: 65 natural gas piping, 1999 V2: 176
copper drainage tube, 2003 V4: 45, 46 passivation, 2004 V1: 146147
copper joints, 1999 V2: 222 plastic water pipes, 1999 V2: 252
copper-nickel alloys, 2004 V1: 141 predicting water deposits and corrosion, 1999 V2:
copper-phosphorous-silver brazing (BCuP), 2003 V4: 45 290292
copper-phosphorus brazing, 2003 V4: 45 prevention, 2004 V1: 152
copper piping protection, 2000 V3: 165
aboveground piping, 1999 V2: 14, 68 references, 2004 V1: 154
commodity tube, 2003 V4: 35 sacricial anodes, 2004 V1: 148
compressed air systems, 2000 V3: 210 steam systems, 2000 V3: 190
conserving energy, 2004 V1: 128 storage tanks, 2000 V3: 91, 155, 165
copper K piping, 1999 V2: 262 swimming pool heaters, 2000 V3: 146
copper L piping, 1999 V2: 262 total organic carbon and, 1999 V2: 288
fountains, 2000 V3: 116 types of, 2004 V1: 141
fuel-gas piping, 1999 V2: 196 water mains, 2000 V3: 8
gas piping, 1999 V2: 176 Corrosion, 2004 V1: 154
pure-water system, 2000 V3: 47 Corrosion and Resistance of Metals and Alloys, 2004 V1:
radioactive waste systems, 1999 V2: 341 154
roughness, 1999 V2: 122 Corrosion Causes and Prevention, 2004 V1: 154
sizing, 1999 V2: 133 Corrosion Control, 2004 V1: 154
sprinkler systems, 2000 V3: 12, 17 Corrosion Engineering, 2004 V1: 154
swimming pools, 2000 V3: 145 corrosion fatigue, 2004 V1: 152
types, 2003 V4: 3436 Corrosion Handbook, 2004 V1: 154
copper rings over joints, 1999 V2: 223 Corrosion in Swimming Pools and General Guide to
copper salts, 2000 V3: 145, 148 Materials Selection (NSPI 18), 2000 V3: 145
Copper Sovent Single-stack Plumbing System Handbook corrosion mitigation, 2004 V1: 152
Supplement, 1999 V2: 65 corrosion potential, 2004 V1: 152
copper sulfate, 1999 V2: 223 corrosion prevention, 2004 V1: 152
copper-sulfate electrodes, 2004 V1:150 Corrosion Prevention for Practicing Engineers, 2004 V1:
copper tube size (CTS), 2003 V4: 59, 61 154
copper water tube, 2003 V4: 3444 corrosion-resistant materials, 2004 V1: 146, 1999 V2: 15
Copson, H.R., 2004 V1: 154 Corrosion Resistant Materials Handbook, 2000 V3: 97
corona-discharge generators, 1999 V2: 312 corrosion-resistant sprinklers, 2004 V1: 29
corporation cocks, 2004 V1: 21 corrosive wastes, 1999 V2: 14, 2000 V3: 40, 2003 V4: 27
correction factors, 2004 V1: 14 corrugated steel piping, 1999 V2: 122, 2000 V3: 245
correctional centers, numbers of xtures for, 2003 V4: 20 cosmic radiation, 1999 V2: 339
corroded end of galvanic series, 2004 V1: 141 Cost Analysis phase in value engineering, 2004 V1: 235,
corrosion 241243, 254
backow preventers and, 1999 V2: 149 costs and economic concerns
boilers, 1999 V2: 314 administrative and operation costs, 2004 V1: 212
calcium carbonate and, 1999 V2: 291 collecting data on, 2004 V1: 222225
cathodic protection, 2004 V1: 147151 construction costs, 2004 V1: 212
causes, 1999 V2: 289290 cost tting, dened, 2004 V1: 258
coatings, 2004 V1: 147
292 ASPE Plumbing Engineering Design Handbook Volume 1
cost information in value engineering, 2004 V1: 222 counter-mounted lavatories, 2003 V4: 11
225 counter sinks, 2000 V3: 32
cost of goods, 2004 V1: 222 counterclockwise (ccw, CCW), 2004 V1: 14
cost-to-function relationship, 2004 V1: 225 counterow piping designs, 2000 V3: 178, 183
dened, 2004 V1: 213, 222225 counterzoning, 2000 V3: 24
development costs, 2004 V1: 212 couple action. See galvanic corrosion
economic values, 2004 V1: 213214 couples, dened, 2004 V1: 152
engineering and design costs, 2004 V1: 212 couplings
estimating costs, 2004 V1: 9398 asbestos concrete piping, 2003 V4: 26
idea development and estimated cost forms, 2004 V1: cast iron hubless pipes, 2003 V4: 28
241242 dened, 2004 V1: 21
labor costs, 2004 V1: 212 glass pipe, 2003 V4: 47
life-cycle costs, 2004 V1: 137 nonrigid couplings, 2004 V1: 186
material costs, 2004 V1: 212 course vacuum, 1999 V2: 253
overhead, 2004 V1: 212 covers on seepage pits, 1999 V2: 225
Pareto principle, 2004 V1: 224 cp, cp, CP (sp ht at constant pressure), 2004 V1: 16
relationships, 2004 V1: 223 CPD (Certied Plumbing Designer), 2004 V1: 72
specic applications cprsr (compressors). See compressors
air dryers, 2000 V3: 207 CPVC (chlorinated polyvinyl chloride). See chlorinated
cathodic protection costs, 2004 V1:150, 2004 V1:151 polyvinyl-chloride (CPVC)
controlled-ow systems, 1999 V2: 88, 93 cracking, dened, 2004 V1: 152
corrosion resistant materials, 2004 V1: 146 Craytor, J., 1999 V2: 34
driven wells, 1999 V2: 241 creativity
fuel product dispensing systems, 2000 V3: 164 assisted and unassisted, 2004 V1: 232
galvanic cathodic protection costs, 2004 V1: 150 creativity worksheets, 2004 V1: 233234, 236
gas booster location, 1999 V2: 180 rst phase in value engineering, 2004 V1: 213, 231235
gray-water system costs, 1999 V2: 2932 questions for, 2004 V1: 234
hot-water systems, 1999 V2: 157 second phase in value engineering, 2004 V1: 254
ion-exchange cartridges, 1999 V2: 306, 323 creep, pipe supports and, 1999 V2: 14
ion-exchange resins, 1999 V2: 302, 305 crevice-attack corrosion
laboratory acid-waste drainage, 1999 V2: 334 crud traps in radioactive-waste piping, 1999 V2: 341,
pool ltration systems, 2000 V3: 135 343
reduced-size venting, 1999 V2: 50 dened, 2004 V1: 141, 152, 1999 V2: 290
sanitary drainage systems, 1999 V2: 1 reducing, 2004 V1: 146
seismic protection costs, 2004 V1: 156, 183 crimping tools, 2003 V4: 37
single septic tank installations, 1999 V2: 231 CRIP (critical pressure), 2004 V1: 15
sovent single-stack plumbing systems, 1999 V2: 54 critical care areas, 2000 V3: 32, 57
sovent system ttings, 1999 V2: 62 critical ows, dened, 2004 V1: 2
special-waste drainage systems, 1999 V2: 328 critical level, dened, 2004 V1: 21
subsurface site drainage, 1999 V2: 100 critical path functions, 2004 V1: 230
swimming pool heaters, 2000 V3: 138, 139 critical pressure, 2004 V1: 15
utility costs, 2004 V1: 128130 cross connections
vacuum system piping, 1999 V2: 262 backow prevention, 1999 V2: 144149
water distillers, 1999 V2: 298 backwash pits, 2000 V3: 137
wet venting, 1999 V2: 49 dened, 2004 V1: 21
in specications, 2004 V1: 69 health-care facilities, 2000 V3: 45
supporting details for, 2004 V1: 257258 medical gas pipe tests, 2000 V3: 80
types of, 2004 V1: 222225 taking precautions against, 1999 V2: 32
value engineering process and, 2004 V1: 211 types of prevention devices, 1999 V2: 144145
vs. prices, 2004 V1: 222 cross-country pipe lines, 2004 V1: 150
cotton gin, creativity and, 2004 V1: 231 cross-ow lter media, 1999 V2: 284, 300
coulombs (C) cross-linked polyethylene/aluminum/cross-linked
corrosion, 2004 V1: 139 polyethylene (PEX-AL-PEX), 2003 V4: 6162
SI units, 2004 V1: 33 cross-linked polyethylene (PEX), 2003 V4: 61
coulombs per cubic meter (C/m3), 2004 V1: 33 cross-sections of ditches, 2000 V3: 247248
Council for National Cooperation in Aquatics, 2000 V3: cross-sections of drains, 1999 V2: 2, 3, 4
151 cross valves, 2004 V1: 21
Council of American Building Ofcials (CABO), 2004 V1: crosses, dened, 2004 V1: 21
123 crossovers, 2004 V1: 21
countdown timer delays, 2000 V3: 24 crown vents, 2004 V1: 21
counter-e.m.f.s, 2004 V1: 153 crowns, 2004 V1: 21
counter-mounted kitchen sinks, 2003 V4: 12 crud traps, 1999 V2: 290, 341, 343
Index 293
dbt, DBT (dry-bulb temperature), 2004 V1: 23 deliquescent dryers, 2000 V3: 207
dbt, DBT (effective temperature), 2004 V1: 14 delivery pressure in natural gas systems, 1999 V2: 183
DC current, 2004 V1: 14, 147, 1999 V2: 306 delivery rooms. See birthing rooms
dc, DC (direct current), 2004 V1: 14, 147, 1999 V2: 306 delivery section in specications, 2004 V1: 70, 8990
DCBP (double-check backow preventers), 2004 V1: 10 Delphia method of evaluation, 2004 V1: 254
DCV (double-check valves), 2000 V3: 223, 224, 226 delta (diff., ), DIFF, D, DELTA), 2004 V1: 14
DCVA (double-check valve assemblies), 1999 V2: 144, 145, delta t (temperature differential), 2004 V1: 136
149 DELTP (pressure drops or differences). See pressure drops
DD (design development phase), 2004 V1: 64 or differences
DE (deionized water), 2004 V1: 8 Deluge Foam-water Sprinkler Systems and Foam-water
DE (diatomaceous earth). See diatomaceous earth Spray Systems (NFPA 16), 2000 V3: 21, 29
deactivation, dened, 2004 V1: 152 deluge systems, 2004 V1: 29, 2000 V3: 1315
dead-end service in pressure-regulated valves, 1999 V2: deluge valves, 2004 V1: 13, 2000 V3: 13, 14
152 demand
dead ends, dened, 2004 V1: 21 cold-water systems, 1999 V2: 121
dead legs in pure water systems, 1999 V2: 324 dened, 1999 V2: 213
dead loads on roof, 1999 V2: 79 drinking water, 1999 V2: 243244, 245
dead-man abort stations, 2000 V3: 24 re demand, 2000 V3: 3
deaerators re hydrant water demand, 2000 V3: 58
boiler feed water, 1999 V2: 314 ow rates, 2000 V3: 230232
deaeration water treatment, 1999 V2: 294295 hot water, 2004 V1: 136, 1999 V2: 157
sovent deaerators hydropneumatic-tank systems, 1999 V2: 150
connections, 1999 V2: 60 medical air systems, 2000 V3: 66
ttings, 1999 V2: 54 medical gas systems, 2000 V3: 49, 50, 53, 59
illustrated, 1999 V2: 56, 61, 62 medical school-laboratory water demand, 2000 V3: 45
operations of, 1999 V2: 46 natural gas, 1999 V2: 175, 177, 2000 V3: 253254
in sovent systems, 1999 V2: 19 sprinkler systems, 2000 V3: 38, 17
dealkalizing treatment, 1999 V2: 295 vacuum systems, 2000 V3: 55, 70
dealloying, dened, 2004 V1: 152 water conservation and paybacks, 2004 V1: 126
debris in pools and fountains, 2000 V3: 108, 110, 138 water heater types and, 1999 V2: 160
decarbonation, 1999 V2: 295 water supply piping and, 1999 V2: 249
dechlorination, 2000 V3: 123 water treatment methods and, 1999 V2: 308
deci prex, 2004 V1: 34 demineralizer systems, 1999 V2: 295, 300, 2000 V3: 4647
decibel (A) scale (dB(A)), 2004 V1: 206 demolition work, in plumbing cost estimation, 2004 V1: 93
decibels (dB, DB) Denoncourt, 1999 V2: 325
dened, 2004 V1: 206 dens, DENS (density). See density
symbols for, 2004 V1: 14 density (dens, DENS, RHO)
deck drains, 1999 V2: 69 measurements, 2004 V1: 33
decomposition potential, 2004 V1: 152 of natural gas, 1999 V2: 180
decontaminating radioactive waste piping, 1999 V2: 341 symbols for, 2004 V1: 14
decorative pools, gray water and, 1999 V2: 22 dental equipment, 2000 V3: 39, 51
deep-bed sand ltration, 1999 V2: 298, 300 department connections, 2004 V1: 12
deep chambers, 1999 V2: 149 departments having jurisdiction, 2004 V1: 22
deep (dp, DP, DPTH). See depth dependent functionality
deep ends of swimming pools, 2000 V3: 128 dened, 2004 V1: 225
deep ll, building sewers and, 1999 V2: 15 in FAST approach, 2004 V1: 230
deep-seal p-traps, 1999 V2: 13, 84 depolarization, dened, 2004 V1: 152
deep-seated res, 2000 V3: 23 depolarizing cathodes, 2004 V1: 145
deep wells, 1999 V2: 240, 245 deposition corrosion, dened, 2004 V1: 152
denitions. See glossaries deposits from feed water, 1999 V2: 289290. See also scale
denitions section in specications, 2004 V1: 69, 88 and scale formation; sediment; slime; sludge
deg., , DEG (degrees), 2004 V1: 14 depth (dp, DP, DPTH)
degasication, 1999 V2: 295 of leaching trenches, 1999 V2: 222
degradation of pure water, 1999 V2: 323 of liquids in septic tanks, 1999 V2: 230
degrees (deg., , DEG), 2004 V1: 14 of media beds in sand lters, 2000 V3: 132
degrees celsius, 2004 V1: 34 of reecting pools, 2000 V3: 107
DEHA (diethylhydroxylamine), 1999 V2: 315 of septic tanks, 1999 V2: 228
deionization, 1999 V2: 300. See also demineralizer systems of soils, 1999 V2: 219
deionized water (DE), 2004 V1: 8 symbols for, 2004 V1: 14
deka prex, 2004 V1: 34 of water pipes, 1999 V2: 251
delay relays, 2000 V3: 24 of wells, 1999 V2: 240
delays in clean gas extinguishing systems, 2000 V3: 24 depth lters, 1999 V2: 308
Index 295
derived units of measurement, 2004 V1: 33 dia., DIA (diameters). See diameters
description in value engineering phases, 2004 V1: 214 diagnostic facilities, 1999 V2: 340
descriptive specications, 2004 V1: 66 dialogue in FAST approach, 2004 V1: 231
desiccant air dryers, 2000 V3: 204, 207 dialysis machines, 2000 V3: 39
design Diameter-Index Safety System (CGA V-5), 2000 V3: 83, 86
for people with disabilities, 2004 V1: 107 diameters (dia., DIA)
reducing corrosion, 2004 V1: 146 dened, 2004 V1: 22
seismic, 2004 V1: 160161, 186188 inside (ID), 2004 V1: 14
value engineering and, 2004 V1: 212 outside (OD), 2004 V1: 14
design areas for sprinkler systems, 2000 V3: 16 symbols for, 2004 V1: 14
design density, 2000 V3: 15 diaper changing stations, 2003 V4: 23
design development phase (DD), 2004 V1: 64 diaphragm gauges, 1999 V2: 260
design ow in gas boosters, 1999 V2: 182 diaphragm pumps, 1999 V2: 259
Design Information for Large Turf Irrigation Systems, diaphragm reciprocating compressors, 2000 V3: 201
2000 V3: 105 diaphragm tanks, 2000 V3: 21
Design of Hoffman Industrial Vacuum Cleaning Systems, diaphragm valves, 2004 V1: 22, 1999 V2: 332
1999 V2: 277 diaphragms
design standards, 2004 V1: 66 dened, 2004 V1: 22
design storms, 2000 V3: 242244 in deluge valves, 2000 V3: 14
desolver tanks, 1999 V2: 307 diatomaceous earth ltration
destruction phase in ozonation, 1999 V2: 313 advantages and disadvantages, 1999 V2: 318
destructive forces in pipes. See water hammer compared to sand ltration, 2000 V3: 135137
details in projects, checklists, 2004 V1: 220 maintenance, 2000 V3: 112
detector-check water meters, 1999 V2: 116 materials for lter tanks, 2000 V3: 131
detectors, smoke, 2004 V1: 22 overview, 2000 V3: 134135
detention centers, numbers of xtures for, 2003 V4: 20 pressure and vacuum lters, 2000 V3: 132, 141
detention systems for storm water, 1999 V2: 105107, 107 swimming pool usage, 2000 V3: 130, 131
detention times for treated water, 1999 V2: 294 types of, 2000 V3: 139
detergents die-cast metals, 2000 V3: 33
factors in trap seal loss, 1999 V2: 36 dielectric ttings, 2004 V1: 22
high-expansion foam, 2000 V3: 21 dielectric insulation, 2004 V1: 146, 2004 V1:151
in septic tanks, 1999 V2: 230 dielectric isolation, 2000 V3: 116
venting for, 1999 V2: 3637, 39 dielectric unions, 2000 V3: 156
developed length, 2004 V1: 22 diesel drivers, 2000 V3: 25
developers diesel engines, 2000 V3: 26
perception of engineering, 2004 V1: 260 diesel fuel, 1999 V2: 13
value engineering and, 2004 V1: 212 diesel-oil systems
development costs aboveground tank systems, 2000 V3: 165169
dened, 2004 V1: 222 connections and access, 2000 V3: 166
in value engineering, 2004 V1: 212 construction, 2000 V3: 165
Development phase in value engineering corrosion protection, 2000 V3: 165
activities, 2004 V1: 235, 243, 254 lling and spills, 2000 V3: 166167
idea development and estimated cost forms, 2004 V1: leak prevention and monitoring, 2000 V3:167168
241242 materials, 2000 V3: 165
in process, 2004 V1: 213 overll prevention, 2000 V3:167
sketches, 2004 V1: 254, 255 product dispensing systems, 2000 V3:168
Development Presentation phase in value engineering, tank protection, 2000 V3:169
2004 V1: 213 vapor recovery, 2000 V3:168
deviations in measurements, 2004 V1: 32 venting, 2000 V3:167
dew-point temperature (dpt, DPT), 2004 V1: 14 codes and standards, 2000 V3: 154
dew points components, 2000 V3: 155
dened, 2004 V1: 22, 2000 V3: 201 denitions and classications, 2000 V3: 153154
lowering, 2000 V3: 204 designing
medical gas system tests, 2000 V3: 83 installation considerations, 2000 V3:172173
monitors, 2000 V3: 66 piping materials, 2000 V3:169
refrigerated air dryers, 2000 V3: 207 piping sizing, 2000 V3:169170
dezincication of brass, 2004 V1: 141 submersible pump sizing, 2000 V3:170
DFRAD (diffuse radiation), 2004 V1: 14 testing, 2000 V3:170172
dfu (drainage xture units), 2004 V1: 24, 1999 V2: 64 overview, 2000 V3: 153
DHEC (Department of Health and Environmental references, 2000 V3:173
Control), 1999 V2: 170 resources, 2000 V3:173
DI (deionization), 1999 V2: 300 underground tank systems, 2000 V3: 155165
296 ASPE Plumbing Engineering Design Handbook Volume 1
leak detection and system monitoring, 2000 V3: discharge coefcients, 2004 V1: 5
158163 discharge curves, 2000 V3: 220
product dispensing systems, 2000 V3: 163165 discharge permits, 2000 V3: 88
storage tanks, 2000 V3: 155158 discharge piping for vacuum cleaning systems, 1999 V2:
vapor recovery systems, 2000 V3: 163 274
dietary services in health-care facilities, 2000 V3: 32 discharge times in re suppression, 2000 V3: 23
diethylhydroxylamine, 1999 V2: 315 discharge-type check valves, 1999 V2: 179
diff., DIFF (difference or delta), 2004 V1: 14 disconnect switches for pumps, 2000 V3: 120
difference (diff., (, DIFF, D, DELTA), 2004 V1: 14 discontinuous regulation in air compressors, 2000 V3: 205
differential aeration cells, 2004 V1: 152 discs, dened, 2004 V1: 22
differential environmental conditions, corrosion by, 2004 discussions in FAST approach, 2004 V1: 231
V1: 141 dished ends on tanks, 2000 V3: 156
differential movement in earthquakes, 2004 V1: 161 dishwashers
differential pressure acoustic ratings of, 2004 V1: 195
in sand ltration, 2000 V3: 113 dened, 2004 V1: 22
in sizing steam traps, 2000 V3: 193 xture-unit loads, 1999 V2: 3
differential regulators, 2000 V3: 251 health-care facilities, 2000 V3: 36
differentials, dened, 2004 V1: 22 heat recovery systems, 2004 V1: 266
difculties in value engineering presentations, 2004 V1: water xture unit values, 2000 V3: 217
258 water temperatures, 2000 V3: 45
diffuse radiation (DFRAD), 2004 V1: 14 disinfecting
diffuser plates, 2000 V3: 120 codes for, 2004 V1: 43
diffusion aerators, 1999 V2: 293, 318 cold-water systems, 1999 V2: 154155
diffusion wells, 1999 V2: 105 decontaminating infectious wastes, 1999 V2: 344345
digestion, 2004 V1: 22 disinfectant residuals, 2000 V3: 122
digits, 2004 V1: 32 drinking water, 1999 V2: 245
dikes feed water, 1999 V2: 289, 311313
for aboveground storage tanks, 2000 V3: 165, 167 gray water, 1999 V2: 23, 27
for hazardous waste areas, 2000 V3: 90 reecting pools and fountains, 2000 V3: 123
for leaching trenches, 1999 V2: 223 septic tanks, 1999 V2: 230
dilution air, dened, 1999 V2: 213 small drinking water systems, 1999 V2: 318
dilution, pollution and, 2000 V3:87 swimming pools
dimensions algaecides, 2000 V3: 150
in creativity checklist, 2004 V1: 234 aluminum sulfate, 2000 V3: 149150
dened, 2004 V1: 32 breakdown chlorination, 2000 V3: 149
wheelchairs, 2004 V1: 108 calcium hypochlorite, 2000 V3: 148149
DIN 52218, 2004 V1: 194 chemical feeding equipment, 2000 V3: 150151
dir radn, DIR RADN (direct radiation), 2004 V1: 14 chlorine gas, 2000 V3: 148
DIRAD (direct radiation), 2004 V1: 14 cleaning lters, 2000 V3: 150
direct-acting gas regulators, 2000 V3: 250 cyanurates, 2000 V3: 149
direct-count epiuorescent microscopy, 1999 V2: 282 sodium hypochlorite, 2000 V3: 149
direct current (dc, DC) sulfuric acid, 2000 V3: 150
cathodic protection, 2004 V1: 147 superchlorination, 2000 V3: 149
in deionization, 1999 V2: 306 water systems, 1999 V2: 252
symbols for, 2004 V1: 14 Disinfecting, 2003 V4: 32
direct-ll ports, 2000 V3: 156 Disinfection of Escherichia Coli by Using Water
direct-ltration package plants, 1999 V2: 318 Dissociation Effect on Ion Exchange Membranes,
direct-red gas water heaters, 2004 V1: 130, 2000 V3: 138, 1999 V2: 325
146 disintegrations per second (dps), 1999 V2: 338, 339
direct-operated pressure-regulated valves, 1999 V2: 153 disk lters, 1999 V2: 308
direct pump water supplies, 2000 V3: 8 dispenser pans, 2000 V3: 165
direct radiation (dir radn, DIR RADN, DIRAD), 2004 V1: dispensers
14 aboveground tanks, 2000 V3: 168
directly-heated, automatic storage water heaters, 1999 V2: fuel product dispensers, 2000 V3: 164165
160 high-rate dispensers, 2000 V3: 169
dirt cans for vacuum systems, 1999 V2: 268 multiple dispenser ow rates, 2000 V3: 170
dirt in feed water, 1999 V2: 289 dispersed oil, 1999 V2: 347
dirty lters, 2000 V3: 115 displacement
dirty gas, 2000 V3: 250 dened, 2004 V1: 22
disabled individuals. See people with disabilities in earthquakes, 2004 V1: 159
disc water meters, 1999 V2: 116 swimming pools, 2000 V3: 143
discharge characteristic xture curves, 1999 V2: 3 water meters, 1999 V2: 117
Index 297
edge distances, problems in seismic protection, 2004 V1: electric permeability measurements, 2004 V1: 33
190 electric permitivity measurements, 2004 V1: 33
edr, EDR (equivalent direct radiation), 2004 V1: 14, 39, electric resistance, 2004 V1: 33
2000 V3: 178, 180 electric-resistance welding (ERW), 2003 V4: 48
educating public on gray-water systems, 1999 V2: 33 electric resistivity measurements, 2004 V1: 33
educational facilities. See schools electric vaporizers, 2000 V3: 61
eff, EFF (efciency). See efciency electric water heaters, 1999 V2: 158159, 2000 V3: 121
effect water in fountains, 2000 V3: 124 electrical components in gas boosters, 1999 V2: 179
effective openings, 2004 V1: 23 electrical connections for pool heaters, 2000 V3: 138
effective temperature (ET*, ET), 2004 V1: 14 electrical engineers, 2000 V3: 2728
effectiveness (EFT), 2004 V1: 14 electrical equipment
effects in multi-effect distillation, 1999 V2: 298 res, 2000 V3: 21
effects of earthquakes, 2004 V1: 156158 installation of pipe and, 2003 V4: 25
efciency (eff, EFF) electrical makeup water method, 2000 V3: 124
n (FEFF), 2004 V1: 14 electrical phases, 2004 V1: 15
surface (SEFF), 2004 V1: 14 electricity
symbols for, 2004 V1: 14 conversion factors, 2004 V1: 35
thermal, 2004 V1: 136 measurements, 2004 V1: 33
efuent off-peak power savings, 2004 V1: 128129
asbestos concrete piping, 2003 V4: 26 electrochemical equivalents in corrosion, 2004 V1: 139
chemicals in special-waste efuent, 1999 V2: 328 Electrochemical Society, 2004 V1: 153
dened, 2004 V1: 23 electrodeionization, 1999 V2: 306307
estimating sewage quantities, 1999 V2: 233238 electrodes, dened, 2004 V1: 152
layers of in septic tanks, 1999 V2: 227 electrolysis, 2004 V1: 23. See also galvanic action
samples of radioactive waste efuent, 1999 V2: 342 electrolytes
special-waste drainage systems, 1999 V2: 327 dened, 2004 V1: 139, 152, 1999 V2: 280
temperature of special-waste efuent, 1999 V2: 328 specic resistance, 1999 V2: 285287
treatment of sewage efuent, 1999 V2: 227228 electromagnetic radiation, 1999 V2: 338
Efuent Guideline program, 2000 V3: 8889 electrometric compression liners, 2003 V4: 48
EFT (effectiveness), 2004 V1: 14 electromotive force (emf, EMF)
Egozy, 1999 V2: 325 counter-e.m.f.s, 2004 V1: 153
EJ (expansion joints). See expansion joints electromotive force series, 2004 V1: 144
EJCDC (Engineers Joint Contract Documents measurements, 2004 V1: 33
Committee), 2004 V1: 63 symbols for, 2004 V1: 14
ejector pumps and pits, 2000 V3: 236 electromotive force series, 2004 V1: 144, 152
ejectors electron microscopes, 2000 V3: 38, 39, 45, 51
xture-unit values, 1999 V2: 9 electronegative potential, 2004 V1: 153
in sanitary drainage systems, 1999 V2: 9 electronic grade water, 2003 V4: 58
EL (elevation). See elevation electronic product level gauges, 2000 V3: 168
elastic limits, 2004 V1: 23 electronic tank gauging, 2000 V3: 160
elastic rebound theory, 2004 V1: 158 electronics-grade water, 1999 V2: 317, 320
elastic vibration in pipes, 2004 V1: 6 electroplating wastewater treatment, 2000 V3: 94
elasticity of plastic pipes, 2003 V4: 60 electropositive potential, 2004 V1: 153
elastomeric seals or gaskets electroregeneration, 1999 V2: 307
radiation and, 1999 V2: 341 elements in water, 1999 V2: 281
reinforced concrete pipe, 2003 V4: 32 elev., ELEV (elevation). See elevation
swimming pools, 2000 V3: 144 elevated water storage tanks, 1999 V2: 247
water closets, 2003 V4: 6 elevated water supplies, 2000 V3: 8
elbows elevation (elev., EL, ELEV)
ells, 2004 V1: 23 adjustments for vacuum, 1999 V2: 257, 275
risers up or down, 2004 V1: 10 air compressors and, 2000 V3: 66
elderly altitude (alt, ALT), 2004 V1: 14
aging disabilities, 2004 V1: 107 altitude valves, 1999 V2: 249
xtures and, 2004 V1: 107 compressed air and, 2000 V3: 199, 211
electric capacitance measurements, 2004 V1: 33 medical vacuum systems and, 2000 V3: 69
electric charge density measurements, 2004 V1: 33 pressure losses and, 2000 V3: 224
electric re pumps, 2000 V3: 26 in sprinkler hydraulic calculations, 2000 V3: 17
electric hot-water heaters, 2004 V1: 129130 symbols for, 2004 V1: 14
electric inductance, 2004 V1: 33 elevator shafts
electric instantaneous water heaters, 2004 V1: 265 medical gas piping and, 2000 V3: 73
electric irrigation valves, 2000 V3: 103 protection systems, 2000 V3: 25
electric-operated, solenoid valve trap primers, 1999 V2: 14 ellipses, calculating area, 2004 V1: 4
Index 301
evaporative coolers. See cooling-tower water water pipes and, 1999 V2: 251252
evaporators (evap, EVAP), 2004 V1: 14, 2000 V3: 46 expansion bends, 1999 V2: 18
evapotranspiration expansion joints (EJ)
dened, 2004 V1: 23 dened, 2004 V1: 23
in irrigation, 2000 V3: 105 plastic water pipes, 1999 V2: 251
sewage treatment, 1999 V2: 227 roofs, 1999 V2: 79, 85, 87
exa prex, 2004 V1: 34 symbols for, 2004 V1: 10
exact conversions, 2004 V1: 32 thermal expansion and, 1999 V2: 18
exam/treatment rooms expansion loops
xtures, 2000 V3: 35 bracing and, 2004 V1: 171
health-care facilities, 2000 V3: 32 dened, 2004 V1: 23
medical gas stations, 2000 V3: 51 protecting against thermal expansion, 1999 V2: 18
medical vacuum, 2000 V3: 54 expert costs, 2004 V1: 223
examination section in specications, 2004 V1: 71, 91 explosions
excavation explosion-proof (XP) construction, 1999 V2: 179
labor productivity rates, 2004 V1: 9597 explosion-relief devices for vacuums, 1999 V2: 268
plumbing cost estimation, 2004 V1: 93 re-protection systems, 2000 V3: 22
excess air, dened, 1999 V2: 213 hot-water heaters, 1999 V2: 157
excess pressure pumps, 2004 V1: 24 nitric acid, 1999 V2: 333
excess water pressure, 1999 V2: 152154 exposed ends of piping, 2003 V4: 25
excessive costs, value engineering and, 2004 V1: 212 exposures, re hazards and, 2000 V3: 2
exchange capacity of resins, 1999 V2: 302 extended-coverage sidewall sprinklers, 2004 V1: 29
exchangers in distillers, 1999 V2: 298 exterior piping for storm drainage, 1999 V2: 98
Execution section in specications, 2004 V1: 69, 9192 extinguishing systems, 2004 V1: 12
exhaust extra-hazard occupancies
lters on vacuum systems, 1999 V2: 262 dened, 2004 V1: 29
natural gas combustion waste, 1999 V2: 177 deluge systems, 2000 V3: 13
pressure loss in vacuum systems, 1999 V2: 274 reghting hose streams, 2000 V3: 230
vacuum exhaust pipe sizing, 1999 V2: 263 portable re extinguishers, 2000 V3: 27, 28
vacuum system piping, 1999 V2: 259, 274, 2000 V3: 70 extra-heavy cast-iron soil pipe (XH), 2003 V4: 27, 2930
vacuum system stacks, 2000 V3: 70 extra-heavy piping, 2004 V1: 23
exhausted cartridges in ion exchange, 1999 V2: 305306 extra materials section in specications, 2004 V1: 70, 90
exhausters (dry-pipe systems), 2000 V3: 11 extra-strength vitried clay piping, 1999 V2: 68
exhausters (vacuum) extra-strong steel pipe, 2003 V4: 48
air-bleed controls, 1999 V2: 268269 extra-strong weight brass pipe (Schedule 40), 2003 V4: 27
dened, 1999 V2: 266269, 268 extractors in laundry facilities, 2000 V3: 36
locating, 1999 V2: 270 extruded steel piping, 2003 V4: 48
sizing, 1999 V2: 272, 274275 eyeball inlet ttings, 2000 V3: 137
exhibition halls, numbers of xtures for, 2003 V4: 19 eyewashes for emergencies, 1999 V2: 332, 2000 V3: 37,
existing work, 2004 V1: 23 2003 V4: 1718
exp, EXP (expansion). See expansion
expanded air in vacuums, 1999 V2: 256
expansion (exp, EXP, XPAN)
F
F, F (Fahrenheit), 2004 V1: 14, 38
buildings, 2000 V3: 49 F (farads), 2004 V1: 33
calculating pipe expansion, 2004 V1: 3 f (femto) prex, 2004 V1: 34
enlargement of water systems, 1999 V2: 249 F (re-protection water supply). See re-protection
foam extinguishing agents, 2000 V3: 21 systems
future expansion of compressed air systems, 2000 V3: f to f, F TO F (face to face), 2004 V1: 14, 23
210 f & t (ow and thermostatic traps), 2000 V3: 182, 194
glass pipe, 2003 V4: 48 F-477 standard, 2003 V4: 62
HDPE pipe, 2003 V4: 61 F-876 standard, 2003 V4: 61
hot-water systems and, 1999 V2: 167168 F-877 standard, 2003 V4: 61
linear expansion in PVC pipe, 2003 V4: 62 F-1281 standard, 2003 V4: 62
plastic pipe, 2003 V4: 60 F-1282 standard, 2003 V4: 62
plastic pipe thermal expansion, 1999 V2: 251 F/m (farads per meter), 2004 V1: 33
protecting against pipe expansion, 1999 V2: 18 fa, FA (face area), 2004 V1: 14
roof drains and, 1999 V2: 85, 87 fabrication section in specications, 2004 V1: 91
sanitary drainage systems, 1999 V2: 18 face area (fa, FA), 2004 V1: 14
storage tanks and piping, 2000 V3: 172 face-entry ttings on sovent systems, 1999 V2: 62
swimming pool piping, 2000 V3: 145 face piping, 2000 V3: 115
symbols for, 2004 V1: 14 face to face (f to f, F TO F)
thermal expansion tanks, 1999 V2: 167 face-to-face dimensions, dened, 2004 V1: 23
304 ASPE Plumbing Engineering Design Handbook Volume 1
berglass septic tanks, 1999 V2: 228 subsurface drainage, 1999 V2: 102, 103104
eld checklists, 2004 V1: 102103 swimming pools, 2000 V3: 131137
eld orders, 2004 V1: 63 backwash, 2000 V3: 137
eld quality control section in specications, 2004 V1: 71, backwash pits, 2000 V3: 137, 140
9192 diatomaceous earth, 2000 V3: 134135
ll lter tanks, 2000 V3: 131
ll layers, 1999 V2: 104 gutters and, 2000 V3: 137
leaching trenches, 1999 V2: 223 housing, 2000 V3: 129
sewers, 1999 V2: 15 hydraulic design, 2000 V3: 140
subsurface drainage pipes, 1999 V2: 102, 103 inlet ttings, 2000 V3: 137
types of, around building sewers, 1999 V2: 15 main drains, 2000 V3: 137
water pipes, 1999 V2: 250 media types, 2000 V3: 131137
ll hoses, 2000 V3: 157 return inlets, 2000 V3: 110111
ll lines for pools, 2000 V3: 116 role, 2000 V3: 131
ll ports, 2000 V3: 166 selecting components, 2000 V3: 139140
ll spouts in pools, 2000 V3: 145 skimmers, 2000 V3: 137
lling surge tanks, 2000 V3: 137
aboveground tank systems, 2000 V3: 166167 types of lters, 2000 V3: 130
swimming pools, 2000 V3: 144 utility water, 1999 V2: 314
underground liquid fuel tanks, 2000 V3: 156157 vacuum systems, 1999 V2: 268
lm coefcients water quality and, 1999 V2: 244
inside (FI, HI), 2004 V1: 14 water systems, 1999 V2: 125
outside (FO, HO), 2004 V1: 14 water treatment, 1999 V2: 299, 300
lm-processing areas, 2000 V3: 39, 45 n efciency (FEFF), 2004 V1: 14
lms FINA (Federation Internationale de Natation Amateur),
carbonate, 2004 V1: 151 2000 V3: 127, 151
lm formation in rate of corrosion, 2004 V1: 145 nal checklists, 2004 V1: 103
sodium hexametaphosphate, 2004 V1: 151 ne sands
sodium silicate, 2004 V1: 151 ll above subsurface drainage pipes, 1999 V2: 103
lter alum, 1999 V2: 294 gray-water irrigation systems and, 1999 V2: 26, 27
lter cakes, 2000 V3: 134 irrigating, 2000 V3: 100
lter coats, 2000 V3: 134 ne vacuum, 1999 V2: 254
lter intakes, 2000 V3: 66 nish coats, 2004 V1: 147
lter pumps, 2000 V3: 115116, 120 nish inspection, 2004 V1: 103
lter tanks, 2000 V3: 131 Finnemore, E. John, 1999 V2: 19
lters and ltration re areas, 2000 V3: 16
air compressors, 2000 V3: 203 re departments, 2000 V3: 2, 216
cleaning lters, 2000 V3: 150 re hydrants. See hydrants
compressed air systems, 2000 V3: 207 re loads, 2000 V3: 23
dened, 2004 V1: 23 re marshals, 2000 V3: 2, 216
lter bags on vacuum systems, 1999 V2: 268 Fire Protection Handbook, 2000 V3: 8, 29
lter elements or media, 2004 V1: 23, 2000 V3: 134 re-protection systems. See also sprinkler systems (re
135 protection)
ltration water systems, 2000 V3: 47 alarms
fountains electric gongs, 2000 V3: 11
design criteria, 2000 V3: 112113 re alarm control panels, 2004 V1: 12, 2000 V3: 24
lter pumps, 2000 V3: 115116 re alarm systems, 2004 V1: 2324
piping, 2000 V3: 111112, 119 automatic systems, 2000 V3: 118
turnover time, 2000 V3: 110 codes and standards, 2004 V1: 4243
fuel dispensers, 2000 V3: 165 dened, 1999 V2: 18
gas line lters, 2000 V3: 250 detection, 2000 V3: 13, 19
granular lters, 2000 V3: 132134 extinguishers, 2004 V1: 12, 13, 2000 V3: 27
gray water, 2004 V1: 267, 1999 V2: 22, 23, 27, 28, 29 re department connections, 2004 V1: 24, 2000 V3: 11
infectious waste systems, 1999 V2: 345 re-department connections, 2004 V1: 12
iron-removal lters, 2000 V3: 147 re extinguishers, 2000 V3: 27
membrane ltration and separation, 1999 V2: 308311 re hazards
microorganisms, 1999 V2: 312 dened, 2004 V1: 24
oil spills, 1999 V2: 347, 348 evaluation, 2000 V3: 23
pure water systems, 1999 V2: 322323 re loads and resistance ratings, 2000 V3: 23
sand lters, 2000 V3: 149150 ammable or volatile liquids, 1999 V2: 13, 347349
slurry feeding, 2000 V3: 134135 oxygen storage areas, 2000 V3: 63
small drinking water systems, 1999 V2: 318 re lines
306 ASPE Plumbing Engineering Design Handbook Volume 1
conversion to gpm, 1999 V2: 120, 124, 126, 2000 V3: foam systems, 2000 V3: 21
218, 234 liquid fuel system codes, 2000 V3: 154
demand weight of xtures, 1999 V2: 123 liquid fuel system denitions, 2000 V3: 153
drainage xture units (dfu), 2004 V1: 24, 1999 V2: 64 tank construction, 2000 V3: 165
drainage vents and, 1999 V2: 4041 ammable gases, 2000 V3: 83
xture units (fu) dened, 1999 V2: 64 ammable or volatile liquids, 1999 V2: 13, 347349, 2000
maximum for vertical stacks, 1999 V2: 4, 5 V3: 153
pipe sizing and, 1999 V2: 133142, 136 anged end connections, 2004 V1: 23
reduced-size venting and, 1999 V2: 50 Flanged Pipe, 2003 V4: 32
sanitary drainage system loads, 1999 V2: 3 anges
slope of drains, 1999 V2: 7, 9 bonnets, 2004 V1: 25
sovent systems, 1999 V2: 5759, 63 dened, 2004 V1: 25
steady ow in horizontal drains, 1999 V2: 9 ttings, 2004 V1: 25
supply xture units (sfu), 2004 V1: 24 ange ends, 2004 V1: 25
water hammer and, 1999 V2: 144 ange faces, 2004 V1: 25
xtures and xture outlets. See also specic types of anged ttings, 2003 V4: 38
xtures (water closets, showers, etc.) problems in seismic protection, 2004 V1: 190
accessibility standards, 2003 V4: 2 ap valves, 2004 V1: 25
batteries of xtures, 2004 V1: 18, 1999 V2: 64 are nuts, frost proof, 1999 V2: 196
building requirement tables, 2003 V4: 1823 ared ttings, 2003 V4: 34
codes and standards, 2004 V1: 4344 ash attacks, 2004 V1: 146, 153
cold-water system demand, 1999 V2: 121 ash res, 2000 V3: 16
dened, 2004 V1: 27, 2003 V4: 1 ash points
demand weight of, 1999 V2: 123 dened, 2004 V1: 25, 2000 V3: 83, 153
domestic water supply and, 2000 V3: 216 foam extinguishing systems and, 2000 V3: 21
ttings, 2003 V4: 1 liquid fuels, 2000 V3: 153
xture traps and vents, 1999 V2: 40 ash tanks, 2000 V3: 195, 196
ow and pressure requirements, 1999 V2: 129 ash tubes for liqueed petroleum gas, 1999 V2: 197
governing xtures, 1999 V2: 125, 129 ashing condensate, 2000 V3: 197
health-care facilities, 2000 V3: 3139 ashing anges, 1999 V2: 17
general requirements, 2000 V3: 33 ashing ow, 2000 V3: 196197
kitchens and laundries, 2000 V3: 36 ashing L anges, 1999 V2: 17
laboratory rooms, 2000 V3: 3739 ashing rings, 1999 V2: 12, 17, 80
selection, 2000 V3: 3134 at-area leaching trenches, 1999 V2: 223224
special equipment, 2000 V3: 39 at roof drains, 1999 V2: 80
specic areas, 2000 V3: 3336 at-spray irrigation sprinklers, 2000 V3: 103
unique xtures, 2000 V3: 37, 38 exible connectors (FC)
inspection, 2004 V1: 103 acoustics and, 2004 V1: 200
installation productivity rates, 2004 V1: 97 illustrated, 2004 V1: 204, 210
laboratory acid-waste drainage systems, 1999 V2: 334 symbols for, 2004 V1: 10
materials, 2003 V4: 12 vibration control devices, 2004 V1: 203, 205
minimum numbers of, 2003 V4: 1822 exible gas hoses, 1999 V2: 196
per-xture cost estimation, 2004 V1: 97 exible hose connections, 2003 V4: 14
plumbing cost estimation, 2004 V1: 93 exible plastic piping, 2000 V3: 169
plumbing xtures, dened, 2004 V1: 24 exural strength of plastic pipe, 2003 V4: 60
reduced water usage, 2004 V1: 126127 oat switches, 2000 V3: 188
reducing ow rates, 2004 V1: 134135 oat-type level controls, 1999 V2: 249
resilient-mounting design, 2004 V1: 206, 207 oat valves, 2004 V1: 25, 2000 V3: 124, 144
resiliently mounted plumbing xtures, 2004 V1: 207 oatation devices for oil spills, 1999 V2: 348
sizing vents, 1999 V2: 50 oatation of oil in spills, 1999 V2: 347
standards, 2003 V4: 2 oatation vibration isolation, 2004 V1: 164
supply-water trap primers, 1999 V2: 14 oating ball devices in tanks, 2000 V3: 158
types of, 2003 V4: 1 oating oors, soundproong, 2004 V1: 196
vibration of, 2004 V1: 205 oc, 1999 V2: 294
wastewater trap primers, 1999 V2: 14 occulation, 1999 V2: 294, 2000 V3: 150
water xture unit values, 2000 V3: 217 ood level rims, 2004 V1: 25
water-saving xtures, 2004 V1: 126 ooded, dened, 2004 V1: 25
ame arresters, 2000 V3: 158 ooding factors
Flammable and Combustible Liquids Code (NFPA 30), clean agent gas re suppression, 2000 V3: 23
2000 V3: 29, 95, 173 rainfall, 2000 V3: 244
automatic re-protection systems, 2000 V3: 2 underground storage tanks and, 2000 V3: 155
dike construction, 2000 V3: 167 oor cleanouts (FCO), 2004 V1: 11
308 ASPE Plumbing Engineering Design Handbook Volume 1
formazin turbidity unit, 1999 V2: 287 free chlorine, 2000 V3: 149
forms. See checklists and forms free-oating oils, 2000 V3: 93
formula rooms, 2000 V3: 32 free oil, 1999 V2: 347
formulas. See equations free residuals, 2000 V3: 146
forward approaches and reaches free vibration, 2004 V1: 160
approaches for wheelchairs, 2004 V1: 110 freeboard in ditches, 2000 V3: 248
drinking fountains and water coolers, 2004 V1: 109 freestanding lights for fountains, 2000 V3: 121
reach for wheelchairs, 2004 V1: 109, 111 freestanding siamese re-department connections, 2004
FOS (fuel oil supply), 2004 V1: 8 V1: 12
fouling of water, 1999 V2: 289, 316 freestanding sprinkler heads in irrigation, 2000 V3: 102
Foundation for Cross-Connection Control and Hydraulic freezing points (fp, FP), 2004 V1: 14, 2003 V4: 61
Research, 2000 V3: 224 freezing, preventing in cleanouts, 1999 V2: 9
foundations of buildings, 1999 V2: 103, 231 freezing temperatures
foundations of pumps, 1999 V2: 243, 245 backow preventers and, 1999 V2: 149
fountains buried water pipes and, 1999 V2: 251
controls, 2000 V3: 120121 dry-pipe sprinkler systems and, 2000 V3: 9, 11
discharge devices, 2000 V3: 119120 fountains and, 2000 V3: 121122
ltration systems, 2000 V3: 112113 frost lines, 2000 V3: 226
gray water in, 1999 V2: 22 gas piping and, 1999 V2: 196
lighting, 2000 V3: 121 ice and oxygen storage, 2000 V3: 61
makeup-water systems, 2000 V3: 124125 ice inside water storage tanks, 1999 V2: 247
overow and drainage, 2000 V3: 125 irrigation system valves and, 2000 V3: 103
overview, 2000 V3: 107 leaching trenches and, 1999 V2: 222
piping and valves, 2000 V3: 116119 reduced-size venting and, 1999 V2: 50
pool design, 2000 V3: 107111 swimming pool maintenance and, 2000 V3: 131
displays and ow rates, 2000 V3: 108110 testing of cold-water systems, 1999 V2: 154
general considerations, 2000 V3: 107108 water meters and, 1999 V2: 115
inlets, outlets, and devices, 2000 V3: 110111 well heads and, 1999 V2: 243
multilevel pools, 2000 V3: 108 french drains, 2004 V1: 25
pumps, 2000 V3: 113116 French, John L., 1999 V2: 38
display pumps, 2000 V3: 113115 frequencies (Hz, HZ)
lter pumps, 2000 V3: 115116 measurements, 2004 V1: 33
references, 2000 V3: 125126 symbols for, 2004 V1: 15
systems and components, 2000 V3: 111112 frequency of ion regeneration cycles, 1999 V2: 305
display system, 2000 V3: 111 fresh-air inlets, 2004 V1: 25
illustrated, 2000 V3: 114 friction clamps, 2000 V3: 229
lighting systems, 2000 V3: 112 friction connectors, 2004 V1: 189
make-up water system, 2000 V3: 112 friction factors, 2004 V1: 14
overow and drainage, 2000 V3: 112 friction head, calculating, 2004 V1: 6
piping systems, 2000 V3: 111112 friction losses in ow
water-heating system, 2000 V3: 112 calculating friction head loss, 2004 V1: 2
water-treatment system, 2000 V3: 112 compressed air, 2000 V3: 78, 210, 211
valves, 2000 V3: 118119 counterow piping designs, 2000 V3: 178
water-heating equipment, 2000 V3: 121122 fountain display pumps, 2000 V3: 115
water-treatment systems, 2000 V3: 122124 fuel dispensers, 2000 V3: 170
FOV (fuel oil vents), 2004 V1: 8 Hazen-Williams formula, 2004 V1: 2, 1999 V2: 116,
fp, FP (freezing points), 2004 V1: 14 118, 119, 121
fpm, FPM (feet per minute), 2004 V1: 14, 2000 V3: 29 liquid fuel piping, 2000 V3:170
fps, FPS (feet per second), 2004 V1: 14 medical air, 2000 V3: 68, 74, 78
FR (Federal Register), 2000 V3:88 medical gas piping, 2000 V3: 73
fracture rooms, 2000 V3: 32, 36 medical vacuum systems, 2000 V3: 74, 79
framing drawings for facilities, 2000 V3: 31 natural gas systems, 1999 V2: 183, 2000 V3: 253
Frankel, Michael, 1999 V2: 114, 277, 325, 350, 2000 V3: nitrogen systems, 2000 V3: 74, 77
173, 214 nitrous oxide, 2000 V3: 74, 76
Franzini, Joseph B., 1999 V2: 19 oxygen, 2000 V3: 74, 76
fraternities and sororities, numbers of xtures for, 2003 pipe pressure and, 1999 V2: 122132
V4: 20 pressure and, 1999 V2: 125, 130
Frederick, Ralph H., 1999 V2: 114 sizing of branches, 1999 V2: 127
free air standpipe systems, 2000 V3: 19
dened, 2004 V1: 18, 2000 V3: 200 steam pipes, 2000 V3: 187
properties, 2000 V3: 199 submersible fuel pumps, 2000 V3: 170
water vapor in, 2000 V3: 200201 swimming pool gutters and, 2000 V3: 142
Index 311
galvanic corrosion, 2004 V1: 141, 153, 1999 V2: 290 gas vents (GV), 2004 V1: 8, 1999 V2: 213
galvanic series of metals high-pressure (HG), 2004 V1: 8
dened, 2004 V1: 153 line lters, 2000 V3: 250
dielectric insulation and, 2004 V1: 146 low-pressure (G), 2004 V1: 8
listing, 2004 V1: 141 medium-pressure (MG), 2004 V1: 8
galvanized coatings for corrosion prevention, 2004 V1: 147 plastic pipes, 2003 V4: 58
galvanized-iron joints, 1999 V2: 222 services at laboratory outlets, 2000 V3: 3739
galvanized-iron piping, 1999 V2: 14, 136 Spitzglass formula, 2004 V1: 7
galvanized pipe ttings, 2003 V4: 48 gas stations, 2000 V3: 166, 2003 V4: 20
galvanized-steel lters, 2000 V3: 131 gas stripping, 1999 V2: 288
galvanized-steel piping gas-transfer vacuum pumps, 1999 V2: 259
aboveground piping, 1999 V2: 14, 68 gaseous chlorine, 2000 V3: 123
fountains and, 2000 V3: 116 gaseous re-suppression systems, 2000 V3: 2225
fuel product dispensing and, 2000 V3: 169 gases. See also fuel-gas piping systems; liqueed petroleum
liqueed petroleum gas, 1999 V2: 196 gas; natural gas systems
vacuum systems, 1999 V2: 262 as uids, 2000 V3: 199
galvanizing, dened, 2004 V1: 25 contamination in compressed air, 2000 V3: 201
galvomag alloy, 2004 V1: 144 dissolved gases in water, 1999 V2: 284
gamma ray radiation, 1999 V2: 337, 338, 339 forcing upward through terminal stack, 1999 V2: 36
garbage disposers. See food waste grinders hazardous, 1999 V2: 332
garnet in lters, 1999 V2: 300 nitrous fumes, 1999 V2: 333
gas. See gases; medical-gas systems; natural gas systems; preventing concentration with vents, 1999 V2: 35
specic types of gases sulfuric acid, 1999 V2: 333
Gas and Vacuum Systems, 2003 V4: 45 volatile organic compounds, 1999 V2: 284
gas boosters gaskets
design considerations, 1999 V2: 180182 re-protection water supply, 2000 V3: 228229
gas laws, 1999 V2: 179 fuel piping, 2000 V3: 169
glossary, 1999 V2: 182183 special-waste systems, 1999 V2: 328
heat exchanger loop systems, 1999 V2: 181, 182 gasoline, 1999 V2: 13, 2000 V3: 154, 168
high-rise buildings, 1999 V2: 180 gasoline blends, 2000 V3: 154, 168
materials and components, 1999 V2: 179 gasoline systems
overview, 1999 V2: 178183 aboveground tank systems, 2000 V3: 165169
simplex and dual gas booster systems, 1999 V2: 181 connections and access, 2000 V3: 166
sizing, 1999 V2: 182183 construction, 2000 V3: 165
gas chlorinators corrosion protection, 2000 V3: 165
disinfecting swimming pools, 2000 V3: 148 lling and spills, 2000 V3: 166167
iron removal, 2000 V3: 147 leak prevention and monitoring, 2000 V3:167168
gas-red water heaters materials, 2000 V3: 165
conserving energy, 2004 V1: 129 overll prevention, 2000 V3:167
dened, 2004 V1: 129130 product dispensing systems, 2000 V3:168
fountains, 2000 V3: 121 tank protection, 2000 V3:169
instantaneous heaters, 2004 V1: 265 vapor recovery, 2000 V3:168
net efciency of, 2004 V1: 130 venting, 2000 V3:167
swimming pools, 2000 V3: 138 codes and standards, 2000 V3: 154
gas ow rates, 2004 V1: 14, 1999 V2: 173 components, 2000 V3: 155
gas laws, 1999 V2: 179 denitions and classications, 2000 V3: 153154
gas logs, dened, 1999 V2: 213 designing
gas piping codes, 2004 V1: 42 installation considerations, 2000 V3:172173
gas piping systems. See also fuel-gas piping systems; piping materials, 2000 V3:169
gasoline systems; liqueed petroleum gas; natural piping sizing, 2000 V3:169170
gas systems submersible pump sizing, 2000 V3:170
bracing, 2004 V1: 167 testing, 2000 V3:170172
dened, 2004 V1: 191 overview, 2000 V3: 153
gas cocks, 2004 V1: 9 references, 2000 V3:173
gas line earthquake-sensitive valves, 2004 V1: 162 resources, 2000 V3:173
gas main inspection checklist, 2004 V1: 103 underground tank systems, 2000 V3: 155165
gas pressure regulators, 1999 V2: 214, 2000 V3: 250 leak detection and system monitoring, 2000 V3:
252 158163
gas stops (gas cocks), 2004 V1: 9 product dispensing systems, 2000 V3: 163165
gas-train vents, 1999 V2: 177, 213 storage tanks, 2000 V3: 155158
gas trains, 1999 V2: 213, 2000 V3: 251 vapor recovery systems, 2000 V3: 163
gas turrets, 1999 V2: 177 gate valves (GV), 2004 V1: 9, 1999 V2: 332
Index 313
gauge pressure, 2000 V3: 200 gas boosters, 1999 V2: 182183
gauge taps, 2000 V3: 115 health-care facilities, 2000 V3: 8386
gauges (ga, GA, GAGE). See also gages (ga, GA, GAGE) industrial wastewater, 2000 V3: 88
fuel product level gauging, 2000 V3: 167, 168 measurement units, 2004 V1: 32
gauge pressure, 1999 V2: 253, 254 plumbing terminology, 2004 V1: 1731
hazardous materials, 2000 V3: 90 pressure-regulating valves, 1999 V2: 152
medical gas systems, 2000 V3: 72 references for, 2004 V1: 40
symbols for, 2004 V1: 15 seismic protection, 2004 V1: 191
vacuum systems, 1999 V2: 260 vents and venting, 1999 V2: 64
gear journals, 2004 V1: 196 glove boxes, 1999 V2: 342, 343
gear pumps, 1999 V2: 247 GLSP (good large-scale production), 1999 V2: 343
gearbox silencing enclosures, 2004 V1: 197 glues, 1999 V2: 284
gears, acoustic problems, 2004 V1: 196 GLV (globe valves), 2004 V1: 9
Geiger-Mueller counters, 1999 V2: 339 gold, 2004 V1: 141
gel-coated plastic xtures, 2003 V4: 2 Gold-level LEED certication, 2004 V1: 263
general conditions in contract documents, 2004 V1: 62 golf clubs, 1999 V2: 237
General Conditions of the Contract for Construction, 2004 good engineering practice, 1999 V2: 329
V1: 62 good large-scale production (GLSP), 1999 V2: 343
General Conference of Weights and Measures (CGPM), good value, dened, 2004 V1: 213
2004 V1: 32 goods, costs of, 2004 V1: 222
general corrosion, 2004 V1: 153, 1999 V2: 289290 gooseneck spouts, 2003 V4: 14
General Electric Company, 2004 V1: 211 Gorry, M., 1999 V2: 325
general laboratory-grade water, 1999 V2: 317 governing xtures, 1999 V2: 125, 129
General phase in value engineering, 2004 V1: 213 government furnished, contractor installed (GFCI), 2004
General section in specications, 2004 V1: 68 V1: 71
General Services Administration (GSA), 2004 V1: 263 gpd, GPD (gallons per day), 2004 V1: 15
General Storage (NFPA 231), 2000 V3: 2, 29 gpg (grains per gallon), 1999 V2: 285
generalized total costs, 2004 V1: 223 gph, GPH (gallons per hour), 2004 V1: 15
generally-accepted standards, dened, 2004 V1: 25 gph, standard (std gph, SGPH), 2004 V1: 15
Geogehegan, R.F., 1999 V2: 350 gpm (gallons per minute)
geography converting to xture units, 1999 V2: 120, 124, 126,
cost estimates and, 2004 V1: 98 2000 V3: 218, 234
in plumbing cost estimation, 2004 V1: 94 converting to metric units, 2000 V3: 29
geological stability of sites, 1999 V2: 26 fountains, 2000 V3: 115
geothermal energy, 2004 V1: 131 orice size and, 2000 V3: 7
geothermal heat pumps, 1999 V2: 243 wells, 1999 V2: 240
Get Your Process Water to Come Clean, 1999 V2: 325 gr, GR (grains). See grains
GFCI (government furnished, contractor installed), 2004 grab bars
V1: 71 ambulatory accessible toilet compartments, 2004 V1:
giga prex, 2004 V1: 34 115
glass borosilicate piping, 1999 V2: 14, 15, 122 bathtub accessibility, 2004 V1: 117
glass-bulb sprinklers, 2000 V3: 9 clearance, 2004 V1: 122
glass-lined pipes, 2000 V3: 48 health care facilities, 2000 V3: 34
glass piping shower stalls, 2004 V1: 121122
characteristics, 2003 V4: 4548 standards for, 2004 V1: 114122
expansion, 2003 V4: 48 water closet and toilet accessibility, 2004 V1: 114
ttings, 2003 V4: 48, 4950 grades
special wastes, 1999 V2: 334, 341 dened, 2004 V1: 25
glass washers maintaining for piping, 2003 V4: 25
demineralized water, 2000 V3: 46 grain size, 2000 V3: 132
health-care facilities, 2000 V3: 32, 36 grains (gr, GR)
heat recovery systems, 2004 V1: 266 converting to SI units, 2004 V1: 39
laboratory rooms, 2000 V3: 37 grains per gallon, 1999 V2: 285
pure water systems for, 2000 V3: 46 symbols for, 2004 V1: 15
glazed xture surfaces, 2003 V4: 1 grandstands, numbers of xtures for, 2003 V4: 19
Glidden, R., 1999 V2: 277 granular lters
globe valves (GLV), 2004 V1: 9 compared to diatomaceous earth ltration, 2000 V3:
glossaries 135137
acoustics in plumbing systems, 2004 V1: 206210 overview, 2000 V3: 132134
conserving energy, 2004 V1: 136137 swimming pool usage, 2000 V3: 131134
corrosion, 2004 V1: 151154 types of, 2000 V3: 139
fuel-gas systems, 1999 V2: 213214
314 ASPE Plumbing Engineering Design Handbook Volume 1
granulated carbon lters, 1999 V2: 318, 323. See also overview, 2004 V1: 267
activated carbon ltration precautions, 1999 V2: 3233
granule tests, 2003 V4: 5 public concerns and acceptance, 1999 V2: 33
graphic annunciators, 2000 V3: 24 reasons for using, 1999 V2: 21
graphic conventions in plumbing drawings, 2004 V1: 108 reclaimed water, 2004 V1: 135
graphite, 2004 V1: 141 references, 1999 V2: 34
graphite anodes, 2004 V1: 150 system description and components, 1999 V2: 2223
graphitic corrosion, 2004 V1: 153 treatment systems, 1999 V2: 2729
graphitization Gray-water Systems, 1999 V2: 34
cast iron, 2004 V1: 141 grease
dened, 2004 V1: 153 exclusion from gray-water systems, 1999 V2: 21
graphs, water supply, 2000 V3: 5, 6 fats in kitchens, 1999 V2: 13, 2000 V3: 36
grate-type inlets in site storm systems, 1999 V2: 98 grease traps, dened, 2004 V1: 25
grates horizontal wet-vented systems and, 1999 V2: 46
anti-vortex grating, 2000 V3: 110 interceptors. See grease interceptors
bufng, 1999 V2: 11 grease interceptors
grate open areas for oor drains, 1999 V2: 10 codes, 2004 V1: 43
materials for, 1999 V2: 14 commercial kitchen sinks and, 1999 V2: 13, 2003 V4:
on swimming pool drains, 2000 V3: 143 12
sanitary drainage systems, 1999 V2: 1012 dened, 2004 V1: 25
gravel lters, 2000 V3: 132 private sewage-disposal systems, 1999 V2: 235
gravels septic tanks and, 1999 V2: 230, 232
ll above subsurface drainage pipes, 1999 V2: 103 grease traps
gray-water irrigation systems and, 1999 V2: 26, 27 codes, 2004 V1: 43
gravimetric measurement of solids, 1999 V2: 287 commercial kitchen sinks and, 2003 V4: 12
gravitational acceleration units, 2004 V1: 1 greatest temperature difference (GTD), 2004 V1: 15
gravitational constants ((g, G), 2004 V1: 1, 15 Green Building Council, 2004 V1: 263
gravity Green Building Rating System (LEED), 2004 V1: 263265
acceleration of water, 1999 V2: 12 green design, 2004 V1: 263267
forces in earthquakes, 2004 V1: 186 green roof designs, 2004 V1: 266267
loads, 2004 V1: 155 green sands, 1999 V2: 302
gravity circulation, 2004 V1: 5 green water in pools, 2000 V3: 148
gravity drainage, 1999 V2: 329, 2000 V3: 140 Greene, Norbert D., 2004 V1: 154
gravity drops, 2000 V3: 156 Greening Federal Facilities, 2004 V1: 134, 137
gravity-lm heat exchangers, 2004 V1: 266 gridded systems, 2000 V3: 8
gravity-ow systems, 2003 V4: 32, 49 grinder pumps
gravity ushes, 2004 V1: 195, 2003 V4: 68 dened, 2004 V1: 25
gravity returns, 2000 V3: 186187, 188 in sewage tanks, 1999 V2: 226
gravity sand ltration, 2000 V3: 132, 134 Grossel, S.F., 1999 V2: 350
gravity separators in oil spills, 1999 V2: 348 ground failure, 2004 V1: 158
Gravity Sewer Pipe, 2003 V4: 32 ground oor space. See clear oor space
gravity sewers, 1999 V2: 226 ground-motion time history, 2004 V1: 160
gravity tank systems ground-mounted water storage tanks, 1999 V2: 247
re-protection connections, 2000 V3: 225, 227 ground ruptures, 2004 V1: 158
re-protection water supply, 2000 V3: 232 ground shaking, 2004 V1: 158159, 161
operation of, 1999 V2: 150152 ground water
suction piping and, 1999 V2: 248 dened, 1999 V2: 282
supply piping, 1999 V2: 249 determining quantities, 1999 V2: 100101
gravity valves, 2000 V3: 118 disposal of, 1999 V2: 105
gravity vents for gas appliances, 1999 V2: 178 feed water for pure water systems, 1999 V2: 321
gravity water lters, 1999 V2: 244 gray-water irrigation systems and, 1999 V2: 26
gray cast-iron pressure pipe, 2003 V4: 32 monitoring, 2000 V3: 162
Gray, G.D., 1999 V2: 34 private water systems, 1999 V2: 239
gray-water systems storage tanks and, 2000 V3: 172
amount of generated gray water, 1999 V2: 23 storm-drainage systems, 1999 V2: 67
benets of water reuse, 2004 V1: 135 swimming pool locations and, 2000 V3: 128
codes and standards, 1999 V2: 22 underground tanks and, 2000 V3: 155
designing for supply and consumption, 1999 V2: 2327 wicking into buildings, 1999 V2: 99
economic analysis of, 1999 V2: 2932 groundspace for wheelchairs. See clear oor space
green uses of gray water, 2004 V1: 264 group washups, 2003 V4: 11
health-care facilities, 2000 V3: 43, 45 grouts in wells, 1999 V2: 243
introduction, 1999 V2: 21 growth rate of res, 2000 V3: 2
Index 315
GSA (General Services Administration), 2004 V1: 263 hard-temper tubing, 1999 V2: 14, 68, 2000 V3: 73
GSA Guide Specication Number 3-1515-71 (Public hardness of water
Building Service), 2004 V1: 199 boiler feed water, 1999 V2: 314
GTD (greatest temperature difference), 2004 V1: 15 degrees of hardness, 1999 V2: 283
guaranty bonds, 2004 V1: 62 ion exchange treatment, 1999 V2: 300
guard posts for hydrants, 2000 V3: 228, 229 pH and alkalinity, 1999 V2: 293
A Guide to Airborne, Impact and Structure-Borne Noise private water systems, 1999 V2: 244
Control in Multifamily Dwellings, 2004 V1: 199 swimming pools and, 2000 V3: 147
guide-vane tips, acoustic modications, 2004 V1: 197 water softener treatments, 1999 V2: 307308
Guidelines for Seismic Restraints of Mechanical Systems, Harris, Nigel, 1999 V2: 277
2004 V1: 191 Hastelloy B, 1999 V2: 333
Gut Feel Index, 2004 V1: 254 Hastelloy C, 2004 V1: 141, 144
gutters (pools) hazardous materials, emergency xtures and, 2003 V4: 17
drains, 2000 V3: 142 hazardous wastes
ltration and, 2000 V3: 137 dened, 2000 V3: 88
skimmers and, 2000 V3: 137 permits, 2000 V3: 89
surge tanks and, 2000 V3: 137 hazards
gutters (roofs), 1999 V2: 81, 86 accidental acid spills, 1999 V2: 332
gutters (street), 1999 V2: 99 asbestos, 2003 V4: 26
GV (gas vents), 2004 V1: 8, 1999 V2: 213 backow prevention, 1999 V2: 145, 146
GV (gate valves), 2004 V1: 9, 1999 V2: 332 chemical material safety data sheets, 2000 V3: 90
gymnasiums, numbers of xtures for, 2003 V4: 19 classes of hazard occupancies, 2004 V1: 29, 2000 V3:
gypsum board, lining with lead, 1999 V2: 340 17
cold-water systems, 1999 V2: 115
H controlled substance spills, 1999 V2: 277
diatomaceous earth lters, 2000 V3: 134
H (enthalpy), 2004 V1: 14
h (hecto) prex, 2004 V1: 34 exposed piping and accessibility, 2004 V1: 117
H (henrys), 2004 V1: 33 re hazards, 2004 V1: 24, 2000 V3: 23
h (hours), 2004 V1: 15, 34 ammable and volatile liquids, 1999 V2: 347349
h (velocity head), 2004 V1: 5 gas appliances, 1999 V2: 178
H-I alloy, 2004 V1: 144 gas boosters, 1999 V2: 179
H/m (henrys per meter), 2004 V1: 33 gases in septic tanks, 1999 V2: 230
ha (hectares), 2004 V1: 34 gray-water systems, 1999 V2: 3233
hair strainers, 2000 V3: 150 hazardous gases, 1999 V2: 332
HALAR piping, 2000 V3: 48 hazardous materials, dened, 2000 V3: 88
half-circle rotary sprinkler heads, 2000 V3: 102 hazardous substances, dened, 2000 V3: 88
half-dome ends on tanks, 2000 V3: 156 hazardous wastes, dened, 2000 V3: 88
half-full conditions (HF), 2004 V1: 1 hot-water systems, 1999 V2: 157, 169170
half lives, dened, 1999 V2: 340 liqueed petroleum gas, 1999 V2: 194, 197
halogenated agents, 2000 V3: 22, 27, 70, 83 plumbing systems and, 2004 V1: 266
halon 1211, 2000 V3: 22 radiation, 1999 V2: 337338
halon 1301, 2004 V1: 25, 2000 V3: 22 radioactive waste-drainage systems, 1999 V2: 341
Halon 1301 Fire Extinguishing Systems (NFPA 12A), 2000 sanitary precautions for wells, 1999 V2: 243
V3: 23, 29 types of acids, 1999 V2: 332334
halon system types, 2004 V1: 2526 vacuum cleaning system issues, 1999 V2: 276
halothane, 2000 V3: 70 Hazen-Williams formula
hammer. See water hammer chart explanation, 1999 V2: 121
hand-held extinguishers, 2000 V3: 19, 20 charts, 1999 V2: 118, 119
hand-held shower heads, 2004 V1: 120 dened, 2004 V1: 2, 1999 V2: 7
hand tools for vacuum cleaning systems, 1999 V2: 269270 friction losses, 1999 V2: 116, 2000 V3: 118
hand trenching, labor productivity rates, 2004 V1: 9597 HB (hose bibbs), 2004 V1: 10, 1999 V2: 121
Handbook for Mechanical Engineers, 2004 V1: 2, 3, 5, 40 HCFCs (hydrochlorouorocarbons), 2000 V3: 22
Handbook of Chlorination, 1999 V2: 155 hd, HD (head). See pressure (PRESS, PRES, P)
Handbook of Corrosion Resistant Pipeline, 2000 V3: 97 HDPE (high density polyethylene), 2000 V3: 252, 254,
Handbook of Fundamentals, 2004 V1: 2, 5, 6, 40 2003 V4: 58, 61
Handbooks (ASHRAE), 1999 V2: 214 head (hd, HD). See pressure (PRESS, PRES, P)
handicapped individuals. See people with disabilities head loss. See pressure drops or differences (PD, DELTP)
handling section in specications, 2004 V1: 70, 8990 head walls on culverts, 1999 V2: 99
hands-free controls on sinks, 2000 V3: 33, 34 header systems, 1999 V2: 127
handwashing lavatories, 2000 V3: 32, 36, 45 headroom around pipes, 2003 V4: 25
hangers. See supports and hangers headwall gas systems, 2000 V3: 5657
hard conversions, 2004 V1: 32 health-care facilities
316 ASPE Plumbing Engineering Design Handbook Volume 1
dened, 2000 V3: 84 heat exchanger loop gas booster systems, 1999 V2:
drainage systems, 2000 V3: 3942 181, 182
acid-waste metering, 2000 V3: 4142 mineral deposits and, 2000 V3: 147
acid-waste solids interceptors, 2000 V3: 41, 43 swimming pools, 2000 V3: 138
acidic-waste neutralization, 2000 V3: 4041 vibration isolation, 2004 V1: 205
discharge to sewers, 2000 V3: 40 waste heat usage, 2004 V1: 131134
sink traps, 2000 V3: 42 heat fusion joints
waste and vent piping, 2000 V3: 42 heat-fused socket joints, 1999 V2: 334
xtures and equipment, 2000 V3: 3139 PEX piping, 2003 V4: 61
general requirements, 2000 V3: 33 special wastes and, 2000 V3: 40
kitchens and laundries, 2000 V3: 36 heat gain (HG, HEATG)
laboratory rooms, 2000 V3: 3739 latent (LHG, HGL), 2004 V1: 15
numbers of xtures for, 2003 V4: 20 sensible (SHG, HGS), 2004 V1: 15, 16
selection process, 2000 V3: 3134 symbols for, 2004 V1: 15
special equipment, 2000 V3: 39 heat loss (HL, HEATL)
for specic areas, 2000 V3: 3336 dened, 2004 V1: 15
unique xtures, 2000 V3: 37, 38 heat loss retardants, 2000 V3: 150
glossary, 2000 V3: 8386 swimming pools, 2000 V3: 144
medical gas and vacuum systems, 2000 V3: 4983 water heater energy savings and, 2004 V1: 265
certication, 2000 V3: 7783 water heater location and, 2004 V1: 129
codes and standards, 2000 V3: 83 heat pumps, waste heat usage, 2004 V1: 134
design checklist, 2000 V3: 4950 heat recovery systems, 2004 V1: 134, 266
dispensing equipment, 2000 V3: 5459 heat-trace systems, 1999 V2: 165166
gas ow rates, 2000 V3: 5054 heat transfer (Q)
gas storage, 2000 V3: 5968 condensate drainage and, 2000 V3: 189
number of stations, 2000 V3: 50 heat transfer coefcients (U, U), 2004 V1: 15
piping, 2000 V3: 7377 symbols for, 2004 V1: 15
system control valves, 2000 V3: 7172 heat-up method of condensate drainage, 2000 V3: 191
vacuum systems, 2000 V3: 54, 6870 heated water. See hot-water systems
warning systems, 2000 V3: 7273 heaters (HTR), 2004 V1: 15. See also water heaters
waste anesthetic gas management, 2000 V3: 7071 HEATG (heat gain). See heat gain
plumbing overview, 2000 V3: 32 heating engineers, 2000 V3: 2728
references, 2000 V3: 86 heating feed water
resources, 2000 V3: 86 for microbial control, 1999 V2: 312
water-supply systems, 2000 V3: 4348 for pure water systems, 1999 V2: 322
non-potable water, 2000 V3: 45 heating hot water return (HHWR), 2004 V1: 9
potable water, 2000 V3: 45 heating hot water supply (HHWS), 2004 V1: 9
pure-water systems, 2000 V3: 4648 heating systems. See HVAC systems
Health-Care Facilities (NFPA 99), 2000 V3: 50, 56, 6667, heating values of natural gas, 1999 V2: 173, 212, 214
68, 77 heating, ventilation, and air-conditioning systems. See
health hazards. See hazards HVAC systems
hearing disabilities, 2004 V1: 107 heating water. See water heaters
heart-and-lung machines, 2000 V3: 39 HEATL (heat loss), 2004 V1: 15
heat (HT) heavy clay loams, 2000 V3: 100
compression, 2000 V3: 204 heavy equipment earthquake recommendations, 2004 V1:
conversion factors, 2004 V1: 36 163
heat detectors, 2000 V3: 25 heavy metals, 2000 V3: 95
latent, 2004 V1: 15, 137 heavy process gas service, 2000 V3: 249
measurements, 2004 V1: 33 hectares, 2004 V1: 34
protecting against, 1999 V2: 19 hecto prex, 2004 V1: 34
sensible, 2004 V1: 16, 137 heel inlets on traps, 1999 V2: 16
symbols for, 2004 V1: 15 heel-proof grates, 1999 V2: 10
water-heater heat recovery, 1999 V2: 158159 heel-proof strainers, 1999 V2: 80
heat-activated air dryers, 2000 V3: 204 height (hgt, HGT, HT)
heat-actuated devices (H.A.D), 2000 V3: 13 of fountains, 2000 V3: 120
heat distortion of plastic pipe, 2003 V4: 60 grab bars for accessibility, 2004 V1: 114
Heat Exchange Institute, 1999 V2: 265 laundry equipment, 2004 V1: 123
heat exchangers and exchange systems sinks, 2004 V1: 117
air dryers, 2000 V3: 204 symbols for, 2004 V1: 15
corrosion inhibitors, 2004 V1: 151 toilet seats, 2004 V1: 114
geothermal energy, 2004 V1: 131 helium, 2000 V3: 56
in green building, 2004 V1: 266 Henriques, F.C., Jr., 1999 V2: 169, 170
Index 317
inside diameters (ID), 2004 V1: 14, 2000 V3: 156 certicates, 2004 V1: 62
inside lm coefcients, 2004 V1: 14 in labor costs, 2004 V1: 94
inspecting. See also cleanouts insurance carriers, 2000 V3: 1, 2, 22, 216
checklists, 2004 V1: 102103 intake silencers on compressors, 2000 V3: 202
drains in sanitary drainage systems, 1999 V2: 9 intake sump acoustic problems, 2004 V1: 197
hazardous waste systems, 2000 V3: 90 integral check valves on gas turrets, 1999 V2: 177
septic tanks, 1999 V2: 229230 intensity-duration-frequency curves, 2000 V3: 242, 243
sewage-disposal systems, 1999 V2: 238 intensity (luminous), 2004 V1: 33
installation intensive-care rooms
anchor bolts, seismic problems, 2004 V1: 190 xtures, 2000 V3: 35
backow preventers, 1999 V2: 148149 health-care facilities, 2000 V3: 32
condensate traps, 2000 V3: 195 medical gas stations, 2000 V3: 51, 58
estimating productivity rates, 2004 V1: 97 interceptors, 2004 V1: 26. See also specic kinds of
grab bars, 2004 V1: 121122 interceptors
installation costs, 2004 V1: 223 interface controls for medical gas systems, 2000 V3: 73
lavatories, 2003 V4: 11 intergranular corrosion, 1999 V2: 290
liquid fuel storage systems, 2000 V3:172173 interlocking, gas boosters and, 1999 V2: 182
medical gas piping, 2000 V3: 73 intermediate chambers in dry-pipe systems, 2000 V3: 11
pressure-regulated valves, 1999 V2: 153154 intermediate coats, 2004 V1: 147
reduced-size venting, 1999 V2: 52 intermediate gas regulators, 2000 V3: 251
section in specications, 2004 V1: 91 intermediate-level sprinklers, 2004 V1: 29
showers, 2003 V4: 16 intermittent ow in roof drainage, 1999 V2: 88
sovent systems, 1999 V2: 62 intermittent heating in pools, 2000 V3: 145
steam traps, 2000 V3: 195 intermittent sand lters, 1999 V2: 232
storage tank checklist, 2000 V3: 173 International Association of Plumbing and Mechanical
urinals, 2003 V4: 910 Ofcials (IAPMO), 2004 V1: 54, 58, 1999 V2: 34,
water closets, 2003 V4: 67 214, 2003 V4: 18
water system pipes, 1999 V2: 250252 International Building Code, 2004 V1: 183
Installation, 2003 V4: 32 International Code Council (ICC), 2004 V1: 55, 59
Installation of Centrifugal Fire Pumps (NFPA 20), 2000 International Conference of Building Ofcials (ICBO),
V3: 25, 29 2004 V1: 191
Installation of Closed-head Foam-water Sprinkler Systems International Organization for Standardization (ISO),
(NFPA 16A), 2000 V3: 21, 29 2004 V1: 194
Installation of Private Fire Mains (FM 3-10), 2000 V3: 225 International Pipe Standard (IPS), 2004 V1: 15
Installation of Private Fire Service Mains and Their International Plumbing Code, 1999 V2: 39, 2003 V4: 18
Appurtenances (NFPA 24), 2000 V3: 29, 225 International Safety Equipment Association (ISEA), 2004
Installation of Sprinkler Systems (NFPA 13), 2000 V3: 2, V1: 59
12, 15, 16, 21, 29, 232 international swimming meets, 2000 V3: 128
Installation of Standpipe and Hose Systems (NFPA 14), International System of Units (SI)
2000 V3: 2, 18, 29 conversion factors, 2004 V1: 3940
Installation of Underground Gasoline Tanks and Piping at converting, 2004 V1: 39, 1999 V2: 256, 2000 V3: 29
Service Stations (API 1615), 2000 V3: 173 equations, 2004 V1: 1
instantaneous water heaters, 1999 V2: 160 listing, 2004 V1: 3240
institutional facilities natural gas piping sizing, 1999 V2: 197
estimating sewage quantities, 1999 V2: 234 non-SI units, 2004 V1: 34
numbers of xtures for, 2003 V4: 20, 21 prexes and symbols, 2004 V1: 34
septic tank systems for, 1999 V2: 231232 pressure and ow rate measurements, 2000 V3: 200
instructions to bidders, 2004 V1: 62 style and use, 2004 V1: 34, 1999 V2: 253
instrument sterilizers, 2000 V3: 36, 38 interrelationships of functions, 2004 V1: 227, 230
instruments, nitrogen-pressure-driven, 2000 V3: 68 interruptible gas services, 2000 V3: 249
insulation interruption of water service, 1999 V2: 239
airborne sound, 2004 V1: 193 interstitial monitoring, 2000 V3: 160161
dielectric insulation, 2004 V1: 146 interstitial spaces in tanks, 2000 V3: 156, 165
energy savings and, 2004 V1: 265 inventory control in storage tanks, 2000 V3: 161162
in geothermal energy systems, 2004 V1: 131 invertebrates, 1999 V2: 282
hot-water systems, 2004 V1: 127, 1999 V2: 166 inverted bucket traps, 2000 V3: 182, 186, 194
noise insulation, 1999 V2: 15 inverted-membrane roofs, 1999 V2: 82
pure water systems, 1999 V2: 324 inverts
roof drainage, 1999 V2: 85 dened, 2004 V1: 26
short-circuiting installations, 2004 V1:151 on septic tanks, 1999 V2: 228
thickness and energy conservation, 2004 V1: 127
insurance
322 ASPE Plumbing Engineering Design Handbook Volume 1
An Investigation of the Adequacy of Performance of water conservation and, 2004 V1: 264
Reduced-size Vents Installed on a Ten-Story Drain, water demand, 1999 V2: 243
Waste and Vent System, 1999 V2: 65 water quality and requirements, 2000 V3: 99
Investigation phase in value engineering, 2004 V1: 213, water supply, 2000 V3: 105
235, 243, 254 ischoric processes, 2000 V3: 199
iodine, 2000 V3: 149 ISEA (International Safety Equipment Association), 2004
iodine 131, 1999 V2: 340 V1: 59
ion-exchange and removal systems, 1999 V2: 300308 island venting, 2000 V3: 42
continuous deionization, 1999 V2: 306 ISO 3822/1 (Laboratory Tests on Noise Emission by
design considerations, 1999 V2: 308 Appliances and Equipment Used in Water Supply
regenerable ion exchange, 1999 V2: 301 Installations), 2004 V1: 194
regeneration cycle, 1999 V2: 302305 ISO (International Organization for Standardization),
resins, 1999 V2: 301 2004 V1: 194
service deionization, 1999 V2: 305 isoascorbic acid, 1999 V2: 315
small drinking water systems, 1999 V2: 318 isobaric processes, 2000 V3: 199
total dissolved solids and, 1999 V2: 288 isolating medical gas zones, 2000 V3: 71
water softening, 1999 V2: 307 isolating premises with backow hazards, 1999 V2: 145
ionized salts (NaCI), 2000 V3: 46 147
ions isolating valves, 1999 V2: 149
dened, 2004 V1: 153 isolation rooms, 2000 V3: 32, 45, 51
in electromotive force series, 2004 V1: 144 isolation valves, 2000 V3: 49, 115
in pH values, 1999 V2: 329 isolation, vibration
IP units, 1999 V2: 197, 253, 256, 2000 V3: 200 dishwasher isolation mounts, 2004 V1: 195
IPS. See International Pipe Standard (IPS); iron pipe size exibility and, 2004 V1: 199
(IPS) isolation hangers, 2004 V1: 203, 204
IPS outlets, 1999 V2: 18 isolation springs, 2004 V1: 166
IRI (Industrial Risk Insurers), 1999 V2: 177 isolators within hangers, 2004 V1: 166
iron in piping systems, 2004 V1: 202206
corrosion, 2004 V1: 139 problems in seismic protection, 2004 V1: 188191, 189,
in electromotive force series, 2004 V1: 144 206
in galvanic series, 2004 V1: 141 types of vibration control devices, 2004 V1: 203206
removing, 1999 V2: 292 washing machine isolation mounts, 2004 V1: 195
sludge and, 1999 V2: 289 isolators, 2000 V3: 213
in soils, 1999 V2: 219 isosceles triangles, calculating area, 2004 V1: 4
in water, 1999 V2: 244, 245, 281, 283 isothermal processes, 2000 V3: 199
iron bacteria, 1999 V2: 282 isotopes, 1999 V2: 337, 340
iron coagulants, 1999 V2: 294 ITT Fluid Handling
iron oxide, 2004 V1: 139, 2000 V3: 147 Training Manual TES 181: Hoffman Steam Heating
iron oxide lms, 2004 V1: 145 Systems Design Manual and Engineering
iron pipe size (IPS), 2004 V1: 15, 2003 V4: 59, 61 Data, 2000 V3: 197
iron piping Training Manual TES 582: High Temperature
corrosion, 2004 V1: 139 Condensate Return, 2000 V3: 197
ductile iron water and sewer pipe, 2003 V4: 3233 Izod impact, 2003 V4: 60
iron-removal lters, 2000 V3: 147
irradiation treatment of water, 1999 V2: 245, 311312,
318, 323, 324
J
J (joules), 2004 V1: 33
Irrigation Association J/K (joules per kelvin), 2004 V1: 33
The ABCs of Lawn Sprinkler Systems, 2000 V3: 105 J/kg K (joules per kg per kelvin), 2004 V1: 33
address, 2000 V3: 105 Jackson, T., 1999 V2: 65
irrigation systems Jackson turbidity units (JTUs), 1999 V2: 287
design information, 2000 V3: 104105 janitors closets, 2000 V3: 32, 2003 V4: 13
gray-water demand, 1999 V2: 2627 Janoschek, R., 1999 V2: 325
gray-water systems and, 1999 V2: 21, 22, 30 Jayawardena, N., 1999 V2: 325
green roof designs, 2004 V1: 266 JCAHO (Joint Commission for the Accreditation of
methods, 2000 V3: 100101 Hospitals Organization), 2000 V3: 33, 50
overview, 2000 V3: 99 jet pumps, 1999 V2: 241
rainwater harvesting, 2004 V1: 135, 267 jetted wells, 1999 V2: 241
references, 2000 V3: 105 job preparation checklists, 2004 V1: 99
resources, 2000 V3: 105 jockey pumps, 2004 V1: 24, 2000 V3: 26
sample information sheet, 2000 V3: 106 Joint Commission for the Accreditation of Hospitals
soil considerations, 2000 V3: 99100 Organization (JCAHO), 2000 V3: 33, 50
system components, 2000 V3: 101104 joint compounds, 1999 V2: 223
Index 323
joints
acid-waste systems, 1999 V2: 334
K
k, K (conductivity), 2004 V1: 14, 16, 33
asbestos concrete piping, 2003 V4: 26 K (dynamic response to ground shaking), 2004 V1: 159,
bonded joints and cathodic protection, 2004 V1:150 161
bronze joints and ttings, 2003 V4: 3738 K (kelvin), 2004 V1: 15, 34
cast-iron soil pipes, 2003 V4: 27 k (kilo) prex, 2004 V1: 34
caulked joints on oor drains, 1999 V2: 16 K factor (coefcient of permeability), 1999 V2: 100101,
chemical-waste systems, 1999 V2: 345346 104105, 242
clay pipe joints, 1999 V2: 223 K factor (sprinkler heads), 2000 V3: 17
copper drainage tubes, 2003 V4: 45, 46 K piping. See Type K copper
copper joints, 1999 V2: 222, 2003 V4: 3738 Kalinske, A.A., 1999 V2: 19
copper rings over joints, 1999 V2: 223 Kaminsky, G., 1999 V2: 350
copper water tube, 2003 V4: 37 KE (kinetic energy), 2004 V1: 2, 5
CPVC piping, 2003 V4: 62 kelvin (K), 2004 V1: 15, 33
cross-linked polyethylene, 2003 V4: 61 kerosene, 1999 V2: 13, 2000 V3: 154
cross-linked polyethylene/aluminum/cross-linked keyboards, inexible thinking and, 2004 V1: 231
polyethylene (PEX-AL-PEX), 2003 V4: 6162 kg (kilograms). See kilograms
ductile iron water and sewer pipe, 2003 V4: 3233 kg/m (kilograms per meter), 2004 V1: 33
earthquake damage to, 2004 V1: 162 kg/m2 (kilograms per meter squared), 2004 V1: 33
earthquake protection and, 2004 V1: 167 kg/m3 (kilograms per meter cubed), 2004 V1: 33
expansion joints, 1999 V2: 18, 79, 85, 87, 251 kg/ms (kilogram-meters per second), 2004 V1: 33
ll and pipe joints, 1999 V2: 15 kg/s (kilograms per second), 2004 V1: 33
for fountains, 2000 V3: 119 kill tanks, 1999 V2: 344345
galvanized iron joints, 1999 V2: 222 kilo prex, 2004 V1: 34
glass pipe, 2003 V4: 4748 kilocalories, converting to SI units, 2004 V1: 39
heat-fused socket joints, 1999 V2: 334 kilograms (kg)
inspection, 2000 V3: 80 dened, 2004 V1: 33
joint compounds, 1999 V2: 223 kilograms per cubic meter, 2004 V1: 33
labor productivity rates, 2004 V1: 96 kilograms per meter, 2004 V1: 33
lead pipe, 2003 V4: 49 kilograms per meter squared, 2004 V1: 33
liqueed petroleum gas and, 1999 V2: 196 kilograms per second, 2004 V1: 33
materials, 2004 V1: 43 kilometers (km)
mechanical clay pipe joints, 1999 V2: 223 converting to SI units, 2004 V1: 39
medical gas tubing, 2000 V3: 77, 2003 V4: 45 kilometers per hour, 2004 V1: 34
mortar joints on septic tanks, 1999 V2: 228 kilopascals (kPa)
natural gas systems, 2000 V3: 254 converting meters of head loss to, 2004 V1: 2
o-ring gaskets, 2004 V1: 266 converting to psi, 2000 V3: 29
plastic joints, 1999 V2: 222 in SI units, 2000 V3: 200
plastic pipes, 2003 V4: 5960 vacuum pump ratings, 1999 V2: 257
pure-water systems, 2000 V3: 47 vacuum work forces, 1999 V2: 254
PVC piping, 2003 V4: 62 kiloponds, converting to SI units, 2004 V1: 39
radioactive waste systems, 1999 V2: 341 kilowatt hours (kWh, KWH), 2004 V1: 15, 34
red brass pipe, 2003 V4: 27 kilowatts (kW, KW), 2004 V1: 15
reinforced concrete pipe, 2003 V4: 32 kinematic viscosity
restrainers, 2000 V3: 228229 converting to SI units, 2004 V1: 39
sanitary, 2000 V3: 48 measurements, 2004 V1: 33
screwed mechanical joints, 1999 V2: 334 water temperature variations, 1999 V2: 121
seamless copper pipe, 2003 V4: 34 Kinematic Viscosity Centistokes, 2000 V3: 154
special-waste drainage systems, 1999 V2: 328 kinetic energy (KE)
steel pipe, 2003 V4: 48 calculating, 2004 V1: 2
tubing, 1999 V2: 196 velocity head and, 2004 V1: 5
welded joints in radioactive waste systems, 1999 V2: kip ft, KIP FT (thousand foot-pounds), 2004 V1: 16
341 kip, KIP (thousand pounds), 2004 V1: 16
Joukowskys formula, 1999 V2: 132 KIPFT (thousand foot-pounds), 2004 V1: 16
joules, 2004 V1: 33 kitchen sinks
joules per kelvin, 2004 V1: 33 faucets, 2003 V4: 13
joules per kg per kelvin, 2004 V1: 33 types, 2003 V4: 1112
journeyman plumbers, 2004 V1: 26 kitchens. See food-processing areas and kitchens
JTUs (Jackson turbidity units), 1999 V2: 287 km/h (kilometers per hour), 2004 V1: 34
judgementalism, 2004 V1: 232235 knee space for wheelchairs, 2004 V1: 109
Judgment phase in value engineering, 2004 V1: 213 knockout panels for swimming pool lters, 2000 V3: 140
juveniles. See children, xtures and knockout pots in vacuum systems, 1999 V2: 260
324 ASPE Plumbing Engineering Design Handbook Volume 1
Konen, Thomas K., 1999 V2: 34, 65 lab animals, 1999 V2: 344
Kowalsky, L., 2000 V3: 125 medical gas stations, 2000 V3: 51
kPa (kilopascals). See kilopascals natural gas piping, 1999 V2: 177
Kullen, Howard P., 2004 V1: 154 plastic pipes, 2003 V4: 58
kW, KW (kilowatts), 2004 V1: 15 pure water systems for, 1999 V2: 317325, 2000 V3: 46
kWh, KWH (kilowatt hours), 2004 V1: 15, 34 radioactive isotopes in, 1999 V2: 337
KYNAR piping, 2000 V3: 48 vacuum systems
codes and standards, 1999 V2: 262
L diversity factor calculations for vacuums, 1999 V2:
263
L (length). See length
L (liters). See liters leakage, 1999 V2: 265, 267
L/min (liters per minute), 2000 V3: 66, 69, 200 piping, 1999 V2: 262
L piping. See Type L copper pump assemblies, 1999 V2: 261
L/s (liters per second), 2000 V3: 7, 200 sizing, 1999 V2: 262266
L-shaped bath seats, 2004 V1: 122 vacuum-pump systems, 2000 V3: 70
LA (laboratory compressed air), 2004 V1: 8 water systems ltration, 1999 V2: 300
labels laboratory compressed air (LA), 2004 V1: 8
labeled, dened, 2004 V1: 26 Laboratory Studies of the Hydraulic Performance of
labeled re pumps, 2000 V3: 25 One-story and Split-level Residential Plumbing
medical gas tubing, 2000 V3: 77, 81 Systems with Reduced-size Vents, 1999 V2: 65
medical gas valves, 2000 V3: 71 Laboratory Testing on the Noise Emitted by Valves,
parts of gray-water systems, 1999 V2: 22, 33 Fittings, and Appliances Used in Water Supply
labor and materials payment bonds, 2004 V1: 62 Installations, 2004 V1: 194
labor costs Laboratory Tests on Noise Emission by Appliances and
dened, 2004 V1: 222 Equipment Used in Water Supply Installations,
factors in, 2004 V1: 94 2004 V1: 194
ongoing and one-time, 2004 V1: 223 laboratory vacuum (LV), 2004 V1: 9
overtime, 2004 V1: 94 ladders
in plumbing cost estimation, 2004 V1: 93 aboveground storage tanks, 2000 V3: 165
productivity rates, 2004 V1: 9597 swimming pools, 2000 V3: 145146
in take-off estimating method, 2004 V1: 94 lagging (pipe wrappings), 2004 V1: 196, 201202, 1999 V2:
in value engineering, 2004 V1: 212 68, 196
labor rooms lagoons, 1999 V2: 232
xtures, 2000 V3: 36 laid mat lters, 2000 V3: 131
health-care facilities, 2000 V3: 32 lakes, 1999 V2: 26, 27
medical gas stations, 2000 V3: 52, 58 LAL test, 1999 V2: 282
laboratories laminar ow devices, 2000 V3: 33
acid-waste drainage systems, 1999 V2: 332, 2000 V3: laminar ow in pipes, 2004 V1: 2
3942 landscaping
acid-waste treatment, 1999 V2: 334337, 2000 V3: irrigation. See irrigation systems
4041 water efcient, 2004 V1: 263264
continuous acid-waste treatment systems, 1999 V2: landslides, 2004 V1: 158
338 lanes in swimming pools, 2000 V3: 128
discharge to sewers, 2000 V3: 40 Langelier saturation index (LSI), 1999 V2: 291292, 2000
health and safety concerns, 1999 V2: 332 V3: 123
large facilities, 1999 V2: 336 Langelier, W.F., 1999 V2: 291
metering, 2000 V3: 4142 Laque, F.L., 2004 V1: 154
piping and joint material, 1999 V2: 334 large buildings
sink traps, 2000 V3: 42 acid-waste systems, 1999 V2: 336
solids interceptors, 2000 V3: 41, 43 enlargement of water systems, 1999 V2: 249
system design considerations, 1999 V2: 334 xture drainage loads, 1999 V2: 3
types of acids, 1999 V2: 332334 large private sewage-disposal systems, 1999 V2:
waste and vent piping, 2000 V3: 42 231232
classroom water demand, 2000 V3: 45 sovent single-stack plumbing systems, 1999 V2: 19
compressed air use factors, 2000 V3: 209 large-drop sprinklers, 2004 V1: 29, 2000 V3: 2
dened, 2000 V3: 84 large-scale biohazard facilities, 1999 V2: 343
xtures and pipe sizing, 1999 V2: 328 Large Welded Petroleum Tanks (API 12D), 2000 V3: 95
gas service outlets, 2000 V3: 3739 lat, LAT (leaving air temperature), 2004 V1: 15
gas systems, 1999 V2: 176177 latent heat (LH, LHEAT), 2004 V1: 15, 137, 2000 V3: 175,
in health-care facilities, 2000 V3: 32, 3739 189
infectious waste systems, 1999 V2: 343 latent heat gain, 2004 V1: 15
isolating, 1999 V2: 147
Index 325
lateral and longitudinal sway bracing, 2004 V1: 181182, leaching wells, 2004 V1: 26. See also dry wells
184186 lead
lateral force corrosion, 2004 V1: 139
calculating for seismic protection, 2004 V1: 183 in electromotive force series, 2004 V1: 144
dened, 2004 V1: 191 in galvanic series, 2004 V1: 141
problems in seismic protection, 2004 V1: 189 joint seals, 2003 V4: 27, 28
lateral lines, 2000 V3: 85 lead-caulked, cast-iron piping, 1999 V2: 223
lateral sewers, 2004 V1: 26 lead-lined concrete blocks, 1999 V2: 340
lateral stability of suspended equipment, 2004 V1: 164 lead-lined lath for plaster, 1999 V2: 340
laterals in leaching elds, 1999 V2: 221 lead piping, 2004 V1: 266, 1999 V2: 14, 68, 122, 2003 V4:
laundry sinks or trays, 2003 V4: 13 4849
laundry systems and washers lead shielding on radioactive drainage systems, 1999 V2:
accessibility, 2004 V1: 123 339340
acoustic ratings of machines, 2004 V1: 195 lead-tin solders, 2004 V1: 141
clothes washer xture-unit loads, 1999 V2: 3 leaders. See downspouts and leaders; vertical stacks
commercial laundries, 1999 V2: 121, 147 Leadership in Energy and Environmental Design (LEED),
gray water use, 2004 V1: 135, 267, 1999 V2: 22, 25 2004 V1: 263265
health-care facilities, 2000 V3: 32, 36 leakage
heat recovery systems, 2004 V1: 266 clean agent gas re suppression, 2000 V3: 23
laundry sinks and clothes washers, 2003 V4: 13 compressed air systems, 2000 V3: 209, 211
laundry tray xture-unit loads, 1999 V2: 3 eliminating, 2004 V1: 134
natural gas and, 1999 V2: 174 leaking oil into water, 1999 V2: 347349
rates of sewage ows, 1999 V2: 237 waste anesthetic gas management, 2000 V3: 71
sound damping materials, 2004 V1: 196 water conservation and, 2004 V1: 124
suds problems, 1999 V2: 37, 39 leakage detection
waste heat usage, 2004 V1: 131134 aboveground tank systems, 2000 V3:167168
water xture unit values, 2000 V3: 217 annuciators, 2000 V3: 167
water temperatures, 2000 V3: 45 chemical wastes, 1999 V2: 345, 346
lavatories. See also sinks and wash basins connectors, 2000 V3: 166
accessibility, 2004 V1: 117 industrial waste, 2000 V3: 90
faucets and overows, 2003 V4: 1011, 13 infectious waste drainage systems, 1999 V2: 344
xture-unit loads, 1999 V2: 3 ion exchange systems, 1999 V2: 308
ow rates, 2003 V4: 10 special-waste drainage systems, 1999 V2: 327
gray-water systems, 2004 V1: 135, 1999 V2: 22 underground liquid fuel storage tanks, 2000 V3:
health-care facilities, 2000 V3: 32, 33, 38 158163
installation requirements, 2003 V4: 11 leakage tests
minimum numbers of, 2003 V4: 1822 cold-water systems, 1999 V2: 154
patient rooms, 2000 V3: 34 liqueed petroleum gas systems, 1999 V2: 197
recovery rooms, 2000 V3: 36 private water systems, 1999 V2: 252
reduced water usage, 2004 V1: 126127 storage tanks, 2000 V3: 172
shapes and sizes, 2003 V4: 1011 vacuum systems, 1999 V2: 265, 267
sovent systems, 1999 V2: 62 least mean temperature difference (LMTD), 2004 V1: 15
standards, 2003 V4: 2 least temperature difference (LTD), 2004 V1: 15
temperatures, 2000 V3: 45 leaving air temperature (lat, LAT), 2004 V1: 15
typical gray-water supply, 1999 V2: 25 leaving water temperature (lwt, LWT), 2004 V1: 15
typical use, 1999 V2: 25 lecture halls, numbers of xtures for, 2003 V4: 19
vents, 1999 V2: 37 LEED (Leadership in Energy and Environmental Design),
Law of Inverse Proportions, 2004 V1: 224 2004 V1: 263265
lawn imperviousness factors, 2000 V3: 243 leg baths, 2000 V3: 32, 35, 38
lawn sprinkler supply (LS), 2004 V1: 8, 1999 V2: 121 leg clearances
layer-type dezincication, 2004 V1: 142 drinking fountains and water coolers, 2004 V1: 112
layers of efuent in septic tanks, 1999 V2: 227 toilet and bathing rooms, 2004 V1: 113
layers of ll, 1999 V2: 15 Legionella pneumophila, 1999 V2: 144, 169
lb, LBS (pounds). See pounds legislation regarding people with disabilities, 2004 V1:
leaching trenches (leach elds) 106107
choosing absorption systems, 1999 V2: 220 legs in piping systems, 2000 V3: 47
construction of, 1999 V2: 222223 legs on tanks
drain elds dened, 2004 V1: 23 cast-iron tank legs, 2004 V1: 163
at areas, 1999 V2: 223224 problems in seismic protection, 2004 V1: 188, 189
introduction, 1999 V2: 221224 Lehr, Valentine A., 1999 V2: 34
serial distribution, 1999 V2: 223224 length (lg, LG, L)
sloping area trenches, 1999 V2: 224 conversion factors, 2004 V1: 36
326 ASPE Plumbing Engineering Design Handbook Volume 1
design considerations in seismic protection, 2004 V1: low-pressure condensate (LPC), 2004 V1: 9
186188 low-pressure re pumps, 2000 V3: 25
earth load on water pipes, 1999 V2: 250 low-pressure gas (G), 2004 V1: 8
horizontal loads of piping, 2004 V1: 184 low-pressure natural gas systems, 1999 V2: 173194, 192,
live loads on roof, 1999 V2: 79 194
load factors, dened, 2004 V1: 26 low-pressure steam (lps, LPS), 2004 V1: 9, 15, 2000 V3:
settlement loads, 2004 V1: 186 175, 182, 187
sway bracing, 2004 V1: 185186 low-pressure tanks, 2000 V3: 153
vertical seismic load, 2004 V1: 184 low-temperature hot water (lthw, LTHW), 2004 V1: 15
vibration control materials, 2004 V1: 203 low-velocity pressure sand lters, 2000 V3: 139
loams, 2000 V3: 100 low-voltage lighting, 2000 V3: 121
local alarms, 2000 V3: 83. See also area alarms low-water cutoffs, 2000 V3: 124
local application systems (carbon dioxide), 2000 V3: 20 low-water pressure, 1999 V2: 149152
local application systems (halon), 2004 V1: 26 lower order functions, 2004 V1: 230
local authorities, 1999 V2: 68, 327 Lowther plate units, 1999 V2: 313
local barometric pressure in vacuums, 1999 V2: 254 LOX (liquid oxygen), 2004 V1: 8
local rainfall rate tables, 1999 V2: 6978 LP-gases at Utility Gas Plants, 1999 V2: 214
localized corrosion, 1999 V2: 289290 LPC (low-pressure condensate), 2004 V1: 9
location of piping, earthquake protection and, 2004 V1: lpg. See liqueed petroleum gas
167 Lpm (liters per minute). See liters
lock-out regulators, 2000 V3: 252 lps, LPS (low-pressure steam), 2004 V1: 9, 15
locker rooms, 2000 V3: 32 LS (lawn sprinkler supply), 2004 V1: 8
Loevenguth, 2004 V1: 191 LSI (Langelier saturation index), 1999 V2: 291292
log, LOG (logarithm to base 10), 2004 V1: 15 LTD (least temperature difference), 2004 V1: 15
logarithms lthw, LTHW (low-temperature hot water), 2004 V1: 15
logarithm to base 10 (log, LOG), 2004 V1: 15 lubricating oil (LO), 2004 V1: 8, 1999 V2: 13
natural (ln, LN), 2004 V1: 15 lubricating oil vents (LOV), 2004 V1: 8
long runs in vacuum cleaning systems, 1999 V2: 274275 lubricators
long-term thermal stability for hot-water systems, 1999 in compressed air pipe sizing, 2000 V3: 210
V2: 166 compressed air systems, 2000 V3: 207
long-turn tee-wyes, 1999 V2: 4 lumens, 2004 V1: 33
longitudinal bracing luminance measurements, 2004 V1: 33
dened, 2004 V1: 191 luminous ux, 2004 V1: 33
longitudinal and transverse bracing, 2004 V1: 180 luminous measurements, 2004 V1: 33
longitudinal brace points, 2004 V1: 168 lump copper sulfate, 1999 V2: 223
longitudinal-only bracing, 2004 V1: 180 lux, 2004 V1: 33
seismic protection, 2004 V1: 172 LV (laboratory vacuum), 2004 V1: 9
sway bracing, 2004 V1: 184186 LWDS (liquid-waste decontamination systems), 1999 V2:
longitudinal forces, 2004 V1: 191 344345
Looking to Treat Wastewater? Try Ozone, 1999 V2: 325 LWT (leaving water temperature), 2004 V1: 15
loop systems lx (lux), 2004 V1: 33
re hydrants, 1999 V2: 249 lye (sodium hydroxide), 2000 V3: 150
re mains, 2000 V3: 8
loop vents, 2004 V1: 31, 1999 V2: 4344, 64, 2000 V3: 42
louvers in air compression, 2000 V3: 212
M
M alkalinity, 1999 V2: 282
LOV (lubricating oil vents), 2004 V1: 8 M (mega) prex, 2004 V1: 34
low backow hazard, 2000 V3: 222 m (meters). See meters (measurements)
low-expansion borosilicate glass, 2003 V4: 47 m (milli) prex, 2004 V1: 34
Low-expansion Foam (NFPA 11), 2000 V3: 21, 29 M piping. See Type M copper
low-expansion foams, 2000 V3: 21 m/s (meters per second), 2004 V1: 33
low-re input in gas boosters, 1999 V2: 182 m/s2 (meters per second squared), 2004 V1: 33
low-ow xtures m2 (meters squared), 2004 V1: 33
green building and, 2004 V1: 264 m2/s (meters squared per second), 2004 V1: 33
low-ow control valves, 2000 V3: 103 m3 (cubic meters), 2004 V1: 33
low-ush toilets and water closets m3/kg (cubic meters per kilogram), 2004 V1: 33
acoustic design, 2004 V1: 195 m3/min (cubic meters per minute), 2000 V3: 200
conserving water in, 1999 V2: 232 m3/s (cubic meters per second), 2004 V1: 33
low-ow water closets, 1999 V2: 19, 232 MA. See medical compressed air
ultra-low-ow water closets, 2004 V1: 134136, 264, Mach numbers (Mach, MACH), 2004 V1: 15
1999 V2: 19 MacHatton, J.G., 1999 V2: 238
low-level water tank alarms, 1999 V2: 151 machine trenching, labor productivity rates, 2004 V1:
low-pressure carbon dioxide systems, 2000 V3: 2021 9597
328 ASPE Plumbing Engineering Design Handbook Volume 1
surgical use, 2000 V3: 57 membrane selection in reverse osmosis, 1999 V2: 310,
symbol, 2004 V1: 8 311
system description, 2000 V3: 65 overview, 1999 V2: 308311
medical-gas systems pure water systems, 1999 V2: 321
certication, 2000 V3: 7783 reverse osmosis, 1999 V2: 308309
codes and standards, 2000 V3: 83 tangential-ow lters, 1999 V2: 300
color coding, 2000 V3: 54, 56 total dissolved solids and, 1999 V2: 288
design checklist, 2000 V3: 4950 membrane ux, 1999 V2: 309
dispensing equipment, 2000 V3: 5459 membrane productivity, 1999 V2: 321
ceiling-mounted, 2000 V3: 5759 Membrane Technologies in the Power Industry, 1999 V2:
nitrogen equipment, 2000 V3: 59 325
patient headwall systems, 2000 V3: 5657 membranes in waterproong, 1999 V2: 17
station terminals, 2000 V3: 5456 memory metal couplings, 2000 V3: 77
types, 2000 V3: 58 mercantile facilities
diversity factors, 2000 V3: 75 numbers of xtures for, 2003 V4: 20
earthquake bracing for, 2004 V1: 166 single-occupant toilet rooms, 2003 V4: 23
gas ow rates, 2000 V3: 5054 mercury (Hg, HG), 2004 V1: 15
gas storage, 2000 V3: 5968 mercury vapor lamps, 1999 V2: 312
medical compressed air, 2000 V3: 6568 Mermel, H., 1999 V2: 350
nitrogen, 2000 V3: 68 Meslar, H.W., 1999 V2: 350
nitrous oxide, 2000 V3: 6465 MET (mean effective temperatures), 2004 V1: 15
oxygen, 2000 V3: 5963 metal-edged weirs, 2000 V3: 109
health-care facilities, 2000 V3: 4983 metal ashing on roof drains, 1999 V2: 79
number of stations, 2000 V3: 50 metal-plating plants, 1999 V2: 147
piping, 2000 V3: 7377 metallic pipes. See also specic metals
installation, 2000 V3: 73 bedding, 2000 V3: 234, 235
materials, 2000 V3: 7477 pure-water systems, 2000 V3: 47
sizing, 2000 V3: 7374 metals. See also specic metals
system control valves, 2000 V3: 7172 corrosion losses, 2004 V1: 139
typical storage layout, 2000 V3: 60 galvanic series table, 2004 V1: 141
warning systems, 2000 V3: 7273 metallic coatings, 2004 V1: 147
waste anesthetic gas management, 2000 V3: 7071 Metcalf, 1999 V2: 238
medical-gas tube, 2000 V3: 77, 81, 2003 V4: 45 meter set assemblies, 1999 V2: 214
medical laboratories. See health-care facilities; laboratories metered faucet requirements, 2004 V1: 264
medical schools. See health-care facilities meters (general devices)
medical vacuum (MV), 2004 V1: 9 acid wastes, 2000 V3: 4142
medical waste systems. See infectious and biological waste fuel dispensers, 2000 V3: 165
systems natural gas, 2000 V3: 249, 250
Medicare taxes, in labor costs, 2004 V1: 94 meters (measurements)
medicine sinks, 2000 V3: 35 converting units, 2000 V3: 29
Medium and High-expansion Foam Systems (NFPA 11A), meters, 2004 V1: 33
2000 V3: 21, 29 meters of head, 2004 V1: 2
medium-backow hazard, 2000 V3: 222 meters per second, 2004 V1: 33
medium-expansion foams, 2000 V3: 21 meters per second squared, 2004 V1: 33
medium-pressure condensate (MPC), 2004 V1: 9 meters squared, 2004 V1: 33
medium-pressure gas (MG), 2004 V1: 8 meters squared per second, 2004 V1: 33
medium-pressure natural gas systems, 1999 V2: 173194 meters (water)
medium-pressure steam (mps, MPS), 2004 V1: 9, 15, 2000 disk-type, 1999 V2: 127
V3: 175 domestic cold water systems, 1999 V2: 115116
medium-temperature hot water (mthw, MTHW), 2004 V1: ow pressure loss tables, 1999 V2: 117
15 irrigation, 2000 V3: 105
medium vacuum, 1999 V2: 254 locations for, 2000 V3: 217
mega prex, 2004 V1: 34 pressure and, 1999 V2: 123
megaohm-cm, 1999 V2: 285 pressure losses, 2000 V3: 224
Mellar, 2000 V3: 97 sizing sewage systems and, 1999 V2: 233
membrane ltration methane. See fuel-gas piping systems
cross-ow lters, 1999 V2: 300, 310311 Method for Measuring the Minimum Oxygen
gray-water systems, 1999 V2: 27 Concentration to Support Candle-like Combustion
in health care facilities, 2000 V3: 47 of Plastics (ASTM D2863), 2000 V3: 85
membrane ux, 1999 V2: 309 Methods of Estimating Loads in Plumbing Systems, 1999
membrane productivity, 1999 V2: 321 V2: 155
methoxyurane, 2000 V3: 70
Index 331
methyl orange alkalinity, 1999 V2: 282 minimum design ow, 1999 V2: 182
Metric Conversion Act, 2004 V1: 32 minimum inlet pressure in gas boosters, 1999 V2: 182
metric tons, 2004 V1: 34 minor backow hazard, 1999 V2: 145, 146, 2000 V3: 222
metric units. See International System of Units minutes, 2004 V1: 34
Meyers, Vance A., 1999 V2: 114 mirrors, 2004 V1: 113
Meyrick, C.E., 1999 V2: 325 misaligned wells, pumps for, 1999 V2: 245
MFETT (MasterFormat expansion task team), 2004 V1: 64 miscellaneous gases, 2000 V3: 84
mfr, MFR (mass ow rates), 2004 V1: 15, 33 mist eliminators, 1999 V2: 295
mg/L (milligrams per liter), 1999 V2: 285 MIUS Technology Evaluation: Collection, Treatment and
MG (medium-pressure gas), 2004 V1: 8 Disposal of Liquid Wastes, 1999 V2: 238
MH (manholes). See manholes mixed-bed deionization (single-step), 1999 V2: 302, 303,
mho (specic conductivity), 1999 V2: 287 304, 305, 2000 V3: 46
micro prex, 2004 V1: 34 mixed media lters, 2000 V3: 132, 133, 139
microbial growth and control. See also bacteria; mixes in specications, 2004 V1: 91
microorganisms; viruses in feed water mixing faucets, 2000 V3: 34
cooling towers, 1999 V2: 316 mixing ows of water
drinking water, 1999 V2: 316317, 318 conserving energy, 2004 V1: 126
feed water, 1999 V2: 321 mixed-water temperatures, 1999 V2: 159160
pure water systems, 1999 V2: 323 mixing stations, 2000 V3: 36
utility water, 1999 V2: 314 moderate backow hazard, 1999 V2: 145, 146, 2000 V3:
water softeners, 1999 V2: 307, 308 222
water treatments, 1999 V2: 311313 Modern Vacuum Practice, 1999 V2: 277
microbiological fouling of water, 1999 V2: 289, 316 modications section in project manual, 2004 V1: 63
microbiological laboratories, 1999 V2: 343. See also modied header systems, 1999 V2: 127
laboratories modular iron piping, 1999 V2: 196
micromhos, 1999 V2: 287 Moffat, R., 1999 V2: 277
microns mole (mol), 2004 V1: 33
converting to SI units, 2004 V1: 39 molecular weights of elements, 1999 V2: 281
vacuum units, 1999 V2: 254 moments of inertia
microorganisms. See also bacteria; microbial growth and conversion factors, 2004 V1: 36
control; viruses in feed water measurements, 2004 V1: 33
infectious waste drainage systems, 1999 V2: 343 momentum measurements, 2004 V1: 33
pure water systems, 1999 V2: 323, 2000 V3: 47 monel, 2004 V1: 141, 144
water analysis of, 1999 V2: 282 monitor-type intermediate gas regulators, 2000 V3: 251
water treatments, 1999 V2: 311313, 318 monitoring
microscopes, electron, 2000 V3: 38, 39, 45, 51 aboveground tank systems, 2000 V3:167168
MIL F-1183 Bronze Fittings for Brazed Joints, 2003 V4: ground water, 2000 V3: 162
27, 34 underground liquid fuel storage tanks, 2000 V3:
miles 158163
converting to SI units, 2004 V1: 39 measuring leakage, 2000 V3: 158163
miles per hour (mph, MPH), 2004 V1: 15 piping leaks, 2000 V3: 162
Millepore lters, 1999 V2: 288289 remote leakage, 2000 V3: 162163
milli prex, 2004 V1: 34 monthly inventory tank tightness testing, 2000 V3: 161
millibars (mbar) 162
converting to SI units, 2004 V1: 39 Montreal Protocol, 2000 V3: 22
vacuum units, 1999 V2: 254 mop basins, 2003 V4: 12
millicuries (mc), 1999 V2: 339 mop sinks, 1999 V2: 25, 2000 V3: 32, 34
milligrams per liter (mg/L), 1999 V2: 285 morgues and mortuaries, 1999 V2: 16, 147
millimeters Moritz, A.R., 1999 V2: 169, 170
converting to inches, 2000 V3: 29 mortar joints on septic tanks, 1999 V2: 228
converting to SI units, 2004 V1: 39 motels
millirems (mrem), 1999 V2: 339 acoustic plumbing design, 2004 V1: 196
Mills, Lawrence E., 2004 V1: 214 numbers of xtures for, 2003 V4: 20
min (minutes), 2004 V1: 34 septic tanks, 1999 V2: 231232
min., MIN (minimum), 2004 V1: 15 vacuum calculations for, 1999 V2: 269
mineral deposits motion
swimming pools, 2000 V3: 131, 147148 in creativity checklist, 2004 V1: 234
well water, 2000 V3: 131 in earthquakes, 2004 V1: 158159
mineral salts, 1999 V2: 288, 290 Motor Fuel Dispensing Facilities and Repair Garages Code
mineral solids, 1999 V2: 289 (NFPA 30A), 2000 V3: 154
mineral wool, 2004 V1: 193 motor lubrication oil, 2000 V3: 154
minimum (min., MIN), 2004 V1: 15 motor-operated lter bag shakers, 1999 V2: 268
332 ASPE Plumbing Engineering Design Handbook Volume 1
NFPA Fire Protection Handbook, 2000 V3: 8, 29 NFPA Standard no. 329: Recommended Practice
NFPA Standard no. 10: Standard for Portable Fire for Handling Releases of Flammable and
Extinguishers, 2000 V3: 27, 29 Combustible Liquids and Gases, 2000 V3:
NFPA Standard no. 11: Low-expansion Foam, 2000 154
V3: 21, 29 NFPA Standard no. 385: Standard for Tank
NFPA Standard no. 11A: Medium and High- Vehicles for Flammable and Combustible
expansion Foam Systems, 2000 V3: 21, 29 Liquids, 2000 V3: 154
NFPA Standard no. 12: Carbon Dioxide NFPA Standard no. 480: Standard for the Storage,
Extinguishing Systems, 2000 V3: 20, 29 Handling and Processing of Magnesium
NFPA Standard no. 12A: Halon 1301 Fire Solids and Powders, 2000 V3: 20
Extinguishing Systems, 2000 V3: 23, 25, 29 NFPA Standard no. 481: Standard for the
NFPA Standard no. 13: Installation of Sprinkler Production, Processing, Handling and
Systems, 2004 V1: 191, 2000 V3: 2, 12, 15, Storage of Titanium, 2000 V3: 20
16, 21, 29, 232 NFPA Standard no. 482: Standard for the
NFPA Standard no. 14: Installation of Standpipe Production, Processing, Handling and
and Hose Systems, 2000 V3: 2, 18, 29 Storage of Zirconium, 2000 V3: 20
NFPA Standard no. 15: Water Spray Fixed Systems NFPA Standard no. 651: Standard for the
for Fire Protection, 2000 V3: 2, 29 Machining and Finishing of Aluminum
NFPA Standard no. 16: Deluge Foam-water and the Production and Handling
Sprinkler Systems and Foam-water Spray Aluminum Products, 2000 V3: 20
Systems, 2000 V3: 21, 29 NFPA Standard no. 2001: Clean Agent
NFPA Standard no. 16A: Installation of Closed- Extinguishing Systems, 2000 V3: 22, 23,
head Foam-water Sprinkler Systems, 2000 25, 29
V3: 21, 29 sprinkler piping, 2004 V1: 183184
NFPA Standard no. 17: Dry Chemical sprinkler system statistics, 2000 V3: 2
Extinguishing Systems, 2000 V3: 20, 29 National Fuel Gas Code (NFPA 54), 1999 V2: 214
NFPA Standard no. 20: Installation of Centrifugal equivalent lengths, 1999 V2: 184
Fire Pumps, 2000 V3: 25, 29 gas pressures, 1999 V2: 183
NFPA Standard no. 24: Installation of Private Fire industrial boiler gas trains, 1999 V2: 177
Service Mains and Their Appurtenances, natural gas system design, 2000 V3: 248
2000 V3: 29, 225 pipe materials, 2000 V3: 254
NFPA Standard no. 30: Flammable and pipe sizing, 1999 V2: 194
Combustible Liquids Code, 2000 V3: 2, 21, National Ground Water Association (NGWA), 1999 V2:
29, 95, 153, 154, 165, 167, 173 252
NFPA Standard no. 30A: Motor Fuel Dispensing National Institutes of Health, 1999 V2: 262, 343
Facilities and Repair Garages Code, 2000 National Insulation Contractors Association (NICA), 2004
V3: 154 V1: 127
NFPA Standard no. 50: Standard for Bulk Oxygen National Oceanic and Atmospheric Administration
Systems at Consumer Sites, 2000 V3: 61, 86 (NOAA), 2000 V3: 242
NFPA Standard no. 54: National Fuel Gas Code, NOAA, National Weather Service 5-60 Minute
2000 V3: 248, 254 Precipitation Frequency for the Eastern and
NFPA Standard no. 59: LP-Gases at Utility Gas Central United States, 1999 V2: 114
Plants, 1999 V2: 214 Technical Paper no. 40, 2000 V3: 243
NFPA Standard no. 65: Standard for the Processing National Plumbing Code, 1999 V2: 65, 114, 155
and Finishing of Aluminum, 2000 V3: 20 National Pollutant Discharge Elimination System
NFPA Standard no. 72: National Fire Alarm Code, (NPDES), 2000 V3:88, 2000 V3: 89
2000 V3: 24, 29 National Sanitation Foundation (NSF)
NFPA Standard no. 99: Standard for Health Care address, 2004 V1: 59
Facilities, 2003 V4: 45 hot-water system requirements, 1999 V2: 170
NFPA Standard no. 99: Standard for Health-care individual wastewater treatment plants, 1999 V2: 232
Facilities, 2000 V3: 50, 56, 6667, 68, 77, 86 list of standards, 2004 V1: 56
NFPA Standard no. 99C: Gas and Vacuum Systems, PVC plastic ratings, 2000 V3: 145
2003 V4: 45 recycled wastewater quality, 1999 V2: 22
NFPA Standard no. 231: General Storage, 2000 V3: Standard 61, 2003 V4: 26
2, 29 swimming pool components, 2000 V3: 131
NFPA Standard no. 231C: Rack Storage of National Sanitation Foundation Testing Laboratory
Materials, 2000 V3: 2, 29 (NSFTL), 2004 V1: 26
NFPA Standard no. 255: Standard Method of National Society of Professional Engineers (NSPE), 2004
Test of Surface Burning Characteristics of V1: 62, 63
Building Materials, 2000 V3: 77 National Spa and Pool Institute (NSPI)
NFPA Standard no. 291: Standard on Flow Testing address, 2000 V3: 151
and Marking of Fire Hydrants, 2000 V3: 3
334 ASPE Plumbing Engineering Design Handbook Volume 1
ANSI/NSPI-1: Standard for Public Swimming Pools, NC (number of circuits), 2004 V1: 15
2000 V3: 125, 151 NCAA (National Collegiate Athletic Association), 2000 V3:
ANSI/NSPI-5: Standard for Residential, In-ground 151
Swimming Pools, 2000 V3: 151 NCCLS (National Committee for Clinical Laboratory
Report no. 18: Corrosion in Swimming Pools and Standards, Inc.), 1999 V2: 279, 317, 319
General Guide to Materials Selection, 2000 V3: NEC (National Electrical Code), 1999 V2: 170
145 negative gauge pressure, 1999 V2: 254
swimming pool codes, 2000 V3: 127 negative pressure. See vacuum
National Standard Plumbing Code, 1999 V2: 37, 65 negativity in value engineering presentations, 2004 V1:
National Technical Information Service (NTIS), 2000 V3: 258
97 NEMA 4 listing, 1999 V2: 179
National Weather Service Hydro 35, 2000 V3: 242 NEMA 4X listing, 1999 V2: 166
natural drainage (corrosion), 2004 V1: 153 NEMA 12 listing, 1999 V2: 179
natural frequency of vibration control materials, 2004 V1: NEMA Class 1, Division 1, Group D listing, 1999 V2: 179
202 neoprene compression gaskets, 2003 V4: 27
natural gas. See fuel-gas piping systems; natural gas neoprene oor and hanger mounts, 2004 V1: 203, 204, 205
systems neoprene gaskets, 2000 V3: 42
natural gas systems, 2000 V3: 248254 neoprene seal plugs in cleanouts, 1999 V2: 9
appliances, 1999 V2: 175, 177178 nephelometric test, 1999 V2: 287
bottled gas, 1999 V2: 174 nephelometric turbidity units (NTUs), 1999 V2: 287
codes and standards, 2000 V3: 248 net positive suction head (NPSH), 2004 V1: 199, 206, 1999
compressed gas res, 2000 V3: 21 V2: 247, 2000 V3: 140
compressed gases dened, 2000 V3: 199 neutralizing acid in waste water
design considerations, 1999 V2: 173176 discharge from laboratories, 2000 V3: 40
gas boosters, 1999 V2: 178183 health-care facility systems, 2000 V3: 40
gas train vents, 1999 V2: 177 laboratories, 2000 V3: 4041
glossary, 1999 V2: 213214 methods of treatment, 1999 V2: 334337
high-rise buildings and, 1999 V2: 180 sizing tanks, 2000 V3: 42
laboratory gas systems, 1999 V2: 176177 solids interceptors, 2000 V3: 41, 43
low and medium pressure systems, 1999 V2: 173194 tank and pipe materials, 2000 V3: 9192
meters, 2000 V3: 250 types of acids, 1999 V2: 332, 333
overview, 2000 V3: 248 neutralizing tanks, 2000 V3: 42
pipe sizing, 1999 V2: 183194, 2000 V3: 252254 neutrons, 1999 V2: 337
preliminary information, 2000 V3: 215216 New York City, ultra-low-ow toilets in, 2004 V1: 134135
pressure drops and sizing, 1999 V2: 192, 193 New York State Department of Environmental
sample gas utility letter, 2000 V3: 249, 258259 Conservation
sizing by NFPA formula, 1999 V2: 186, 187, 188, 189 address, 2000 V3: 97
sizing by Spitzglass formula, 1999 V2: 183, 210211 Technology for the Storage of Hazardous Liquids, 2000
sizing by Weymouth formula, 1999 V2: 183, 190, 191, V3: 96
198209 newton-meters, 2004 V1: 33
system components, 2000 V3: 250252 newtons, 2004 V1: 33
drip pots, 2000 V3: 252 NF nomographs, 1999 V2: 317
gas line lters, 2000 V3: 250 NFPA. See National Fire Protection Association, Inc.
gas meters, 2000 V3: 250 NGWA (National Ground Water Association), 1999 V2:
gas pressure regulators, 2000 V3: 250252 252
natural gas pipes, 2003 V4: 35, 36 ni-resist cast iron, 2004 V1: 144
testing and purging, 2000 V3: 252, 253 ni-resist ions, 2004 V1: 141
types of services, 2000 V3: 249 NICA (National Insulation Contractors Association), 2004
natural gas water heaters. See gas-red water heaters V1: 127
natural logarithms, 2004 V1: 15 niche lights for pools, 2000 V3: 121, 145
natural osmosis, 1999 V2: 308 nickel
natural period of vibration, 2004 V1: 160 corrosion, 2004 V1: 139
Natural Resources Defense Council, 2000 V3: 88 electromotive force series, 2004 V1: 144
natural water, 1999 V2: 280, 320 galvanic series, 2004 V1: 141
naturally-vented multiple tray aerators, 1999 V2: 293 in stainless steel, 2003 V4: 2
naval rolled brass, 2004 V1: 144 nickel-bronze grates, 1999 V2: 15, 16
NBBPVI (National Board of Boiler and Pressure Vessel nightclubs, numbers of xtures for, 2003 V4: 19
Inspectors), 1999 V2: 166 Nine Dots exercise, 2004 V1: 232, 261
NBR (acrylonitrile butadiene rubber), 2000 V3: 169 nippled-up sprinklers, 2004 V1: 13
NBS (National Bureau of Standards). See National Bureau nipples for cast iron radiators, 2000 V3: 179
of Standards nitrates, 1999 V2: 281, 283
NC (noise criteria), 2004 V1: 15, 206 nitric acid, 2004 V1: 146, 1999 V2: 333
Index 335
nitrifying bacteria, 1999 V2: 282 non-circular grab bars, 2004 V1: 121
nitrile butadiene (Buna-N), 2000 V3: 169 non-circulating water systems, 2004 V1: 127
nitrogen (N) non-continuous joints, 2004 V1:150
color coding outlets, 2000 V3: 56 non-depletable energy sources, 2004 V1: 137
control cabinets, 2000 V3: 58 Nondiscrimination on the Basis of Disability by Public
cylinder supplies, 2000 V3: 60 Accommodations and in Commercial Facilities,
dened, 2000 V3: 84 2004 V1: 106
dry nitrogen, 2000 V3: 252 non-electrolytes, 1999 V2: 280
gas blankets in water tanks, 1999 V2: 324 non-ammable medical gas, 2000 V3: 49
high-pressure dispensing equipment, 2000 V3: 59 Non-ammable Medical Gas Piping Systems (CSA
laboratory outlets, 2000 V3: 3739 Z305.1), 2000 V3: 86
medical gas pipe sizing, 2000 V3: 74, 75, 77 non-looped piping systems, 2000 V3: 16
medical gas stations, 2000 V3: 5152 non-measurable nouns in function analysis, 2004 V1: 224
medical gas storage, 2000 V3: 68 non-metallic coatings, 2004 V1: 147
oil-free, 2003 V4: 45 non-oxidizing chemicals in microbial control, 1999 V2: 311
in raw water, 1999 V2: 284 non-oxidizing piping, 1999 V2: 341
surgical use, 2000 V3: 57 non-porous piping, 1999 V2: 341
symbol, 2004 V1: 9 non-porous soils, 2000 V3: 105
testing concentrations, 2000 V3: 82 non-potable cold water (NPCW), 2004 V1: 9
in water chemistry, 1999 V2: 281 non-potable hot water (NPHW), 2004 V1: 9
nitrogen NF, 2000 V3: 65, 84 non-potable hot water return (NPHWR), 2004 V1: 9
nitrous fumes, 1999 V2: 333 non-potable water systems. See gray-water systems
nitrous oxide (N2O) non-pressure asbestos concrete pipe, 2003 V4: 26
color coding outlets, 2000 V3: 56 non-pumping wells, 1999 V2: 241243
cylinder supplies, 2000 V3: 60 non-puncturing membrane ashing, 1999 V2: 17
dened, 2000 V3: 84 non-reactive silica, 1999 V2: 283
medical gas pipe sizing, 2000 V3: 74, 76 non-reinforced concrete pipe, 2003 V4: 32
medical gas storage, 2000 V3: 6465 non-rigid couplings, 2004 V1: 186
surgical use, 2000 V3: 57 non-SI units, 2004 V1: 34
symbol, 2004 V1: 9 non-sprinklered spaces, 2004 V1: 12
testing concentrations, 2000 V3: 82 Non-structural Damage to Buildings, 2004 V1: 191
waste anesthetic gas management, 2000 V3: 70 non-tilting grates, 1999 V2: 11
nL/min (normal liters per minute), 2000 V3: 200 non-vitreous china xtures
nm3/min (normal cubic meters per minute), 2000 V3: 200 dened, 2003 V4: 1
no-ow pressure in pressure-regulated valves, 1999 V2: standards, 2003 V4: 2
152 normal, compared to standard, 2000 V3: 200
no-hub joints, earthquake protection and, 2004 V1: 168 normal cubic meters per minute (nm3/min), 2000 V3: 200
no-hub outlets, 1999 V2: 18 normal liters per minute (nL/min), 2000 V3: 200
no-man zones around building footers, 1999 V2: 103 normally closed (n c, N C), 2004 V1: 15
no., NO (numbers), 2004 V1: 15 normally open (n o, N O), 2004 V1: 15
no observed adverse effect level, 2000 V3: 22 nose pieces in deaerators, 1999 V2: 56
no-slump concrete, 2003 V4: 32 not applicable (na, N/A), 2004 V1: 15
NOAA (National Oceanic and Atmospheric not in contract (n i c, N I C), 2004 V1: 15
Administration) not to scale (NTS), 2004 V1: 15
NOAA, National Weather Service 5-60 Minute nouns in function analysis, 2004 V1: 224, 225, 231
Precipitation Frequency for the Eastern and nourishment stations in health-care facilities, 2000 V3: 32
Central United States, 1999 V2: 114 nozzles
rainfall records, 2000 V3: 242 dened, 2004 V1: 29
Technical Paper no. 40, 2000 V3: 243 dry-chemical systems, 2000 V3: 19
NOAEL (no observed adverse effect level), 2000 V3: 22 fountains, 2000 V3: 108109, 112, 117118, 119120
noble potential, dened, 2004 V1: 153 fuel dispensers, 2000 V3: 165
noise. See acoustics in plumbing systems irrigation sprinklers, 2000 V3: 103
noise criteria (NC), 2004 V1: 15, 206. See also preferred pressure, 2000 V3: 19, 219
noise criteria (PNC) curves pressure ow tables, 2000 V3: 4, 7
nominal diameter (DN), 1999 V2: 253 sprinklers, 2000 V3: 9
nominal pipe size (NPS), 1999 V2: 253, 2003 V4: 61, 62 standpipe systems, 2000 V3: 19
nominal values, 2004 V1: 32 water level in pools and, 2000 V3: 112
nomographs, 1999 V2: 3132 NPCW (non-potable cold water), 2004 V1: 9
non-agreement states, 1999 V2: 340 NPDES (National Pollutant Discharge Elimination
non-ambulatory disabilities, 2004 V1: 107 System), 2000 V3:88, 2000 V3: 89
non-aqueous liquid wastes, 2000 V3:87 NPHW (non-potable hot water), 2004 V1: 9
non-aspirating nozzles, 2000 V3: 21 NPHWR (non-potable hot water return), 2004 V1: 9
336 ASPE Plumbing Engineering Design Handbook Volume 1
open-web steel joists in pipe bracing, 2004 V1: 176 gas boosters, 1999 V2: 179, 183
openings for tool access. See cleanouts gas or vacuum. See stations
operating costs, 2004 V1: 223 pools and fountains, 2000 V3: 110111
operating hot-water temperatures, 1999 V2: 166 pressure in cold-water systems, 1999 V2: 153
operating-pressure steam classication, 2000 V3: 175178 septic tanks, 1999 V2: 228
equipment ratings, 2000 V3: 178 symbols for, 2004 V1: 11
vacuum systems, 2000 V3: 178 velocity of ow from outlets, 2004 V1: 6
vapor systems, 2000 V3: 175178 outpatient-services rooms, 2000 V3: 32, 45
operating rooms outside air (oa, OA), 2004 V1: 15
articulated ceiling medical gas systems, 2000 V3: 59 outside diameters (OD), 2004 V1: 14
xtures, 2000 V3: 3536 outside lm coefcients, 2004 V1: 14
medical gas stations, 2000 V3: 52, 58 outside the box thinking, 2004 V1: 232
medical vacuum, 2000 V3: 54 outstanding value, dened, 2004 V1: 213
water demand, 2000 V3: 45 overall system thermal efciency, 2004 V1: 136
operators of vacuum systems, 1999 V2: 269 overengineering, perception of, 2004 V1: 260
oral surgery equipment, 2000 V3: 39, 52 overestimating needs, 2004 V1: 224
orbital welding process, 1999 V2: 341 overll prevention, 2000 V3: 90, 2000 V3:167, 2000 V3:
orders in creativity checklist, 2004 V1: 234 167
ordinary hazard occupancies overow
dened, 2004 V1: 29 for bathtubs, 2003 V4: 16
reghting hose streams, 2000 V3: 230 for lavatories, 2003 V4: 1011
portable re extinguishers, 2000 V3: 27, 28 for pools and fountains, 2000 V3: 112, 125
ordinary lobe pumps, 1999 V2: 259 storm drains. See secondary storm-drainage systems
organic free water, 1999 V2: 317 overhead
organic materials in water, 2000 V3: 46 costs in value engineering, 2004 V1: 212, 222
organic polyelectrolytes, 1999 V2: 294 in plumbing cost estimation, 2004 V1: 93
organisms in water, 1999 V2: 282, 2000 V3: 146. See also overhead steam return lines, 2000 V3: 196
microorganisms overheating vacuum exhausters, 1999 V2: 268269
orices overland ow rates for sites, 2000 V3: 242, 244, 245
on hydrants, 2000 V3: 7 overland ow times for sites, 1999 V2: 96, 97, 98, 111
on nozzles, 2000 V3: 7 overlap in toilet accessibility, 2004 V1: 114
ornamental sprinklers, 2004 V1: 29 overload protection in fountain pumps, 2000 V3: 120
ORP (oxidation reduction potential), 2000 V3: 122, 123 oversized steam traps, 2000 V3: 196
orthotolidin tests, 1999 V2: 154 overspray areas in irrigation, 2000 V3: 104
oscillating-type monitors, 2000 V3: 21 overtime labor costs, in take-off estimating method, 2004
oscillation in pumps, 2004 V1: 201 V1: 94
OSHA (Occupational Safety and Health Administration), overturning, preventing, 2004 V1: 163, 189
1999 V2: 333 overvoltage, dened, 2004 V1: 153
OSHPD (Ofce of Statewide Health Planning and owner furnished, contractor installed (OFCI), 2004 V1: 71
Development), 2004 V1: 191 owners
osmosis, dened, 1999 V2: 308 perception of engineering, 2004 V1: 260
osmotic pressure, 1999 V2: 308 value engineering and, 2004 V1: 212
Otis, Richard J., 1999 V2: 238 OX (oxygen). See oxygen (O2, OX)
OTO pumps, 1999 V2: 259 oxidation, dened, 2004 V1: 153
Otten, Gerald, 1999 V2: 325 oxidation reduction potential (ORP), 2000 V3: 122, 123
Otto plate units, 1999 V2: 313 oxidized sewage, 2004 V1: 27
ounces (oz, OZ) oxidizing chemicals in microbial control, 1999 V2: 311
converting to SI units, 2004 V1: 40 oxidizing gases, 2000 V3: 84
symbols for, 2004 V1: 15 OXY/ACR pipes, 2003 V4: 36
out-of-sequence work conditions, cost estimates for OXY/MED pipes, 2003 V4: 36
projects and, 2004 V1: 98 OXY, MED piping, 2003 V4: 36
outdoor gas booster installation, 1999 V2: 180 oxygen concentration cells, 2004 V1: 153
outdoor gas hose connectors, 1999 V2: 196 oxygen-delivery equipment, 2000 V3: 85
outdoor swimming pools. See also swimming pools oxygen-enriched atmospheres, 2000 V3: 85
components for, 2000 V3: 139 Oxygen-fuel Gas Systems for Weldings and Cuttings, 1999
considerations, 2000 V3: 129 V2: 214
outfall sewers, 2004 V1: 26 oxygen index, 2000 V3: 85
outlet pressures oxygen (O2, OX)
outlet pressure regulators, 2000 V3: 14, 15 bulk oxygen systems, 2000 V3: 6162, 63
standpipe systems, 2000 V3: 19 color coding outlets, 2000 V3: 56
outlets. See also inlets; stations corrosion process, 2004 V1: 145, 1999 V2: 284
ow rates at outlets, 2004 V1: 3, 5 cylinder-manifold supply systems, 2000 V3: 6263, 64
338 ASPE Plumbing Engineering Design Handbook Volume 1
dened, 2000 V3: 8485 parallel-ow piping designs, 2000 V3: 178, 183
medical gas pipe sizing, 2000 V3: 74, 75, 76 parallel installation of pressure-regulated valves, 1999 V2:
medical gas stations, 2000 V3: 50, 5152 153
medical gas storage, 2000 V3: 5963 parallel-shaft gears, 2004 V1: 196
medical gas systems, 2000 V3: 49 parapet wall scuppers, 1999 V2: 79, 82
medical reserve supply, 2000 V3: 60 Parekh, B.S., 1999 V2: 325
oxygen depletion and gas appliances, 1999 V2: 178 Pareto principle, 2004 V1: 224, 258
oxygen pitting, 2000 V3: 190 Pareto, Vilfredo, 2004 V1: 224
oxygen USP, 2000 V3: 65, 84 parking lot drainage pipes, 2003 V4: 32
oxygenated water, 1999 V2: 245, 2000 V3: 116 Parmalee heads, 2000 V3: 1
reducing with carbon dioxide, 2000 V3: 20 part-circle rotary sprinkler heads, 2000 V3: 102
removing, 1999 V2: 294 partially-sprinklered spaces, 2004 V1: 12
saturation with, 1999 V2: 292294 participation in value engineering presentations, 2004 V1:
surgical use, 2000 V3: 57 258
symbols for, 2004 V1: 8 particle size in sand lters, 2000 V3: 132
testing concentrations, 2000 V3: 82 particulate radiation, 1999 V2: 339
in water, 1999 V2: 281 particulate silica, 1999 V2: 283
oxygen scavengers, 1999 V2: 314, 315 particulates
oxygen toxicity, 2000 V3: 85 contamination in compressed air, 2000 V3: 201
oz, OZ (ounces), 2004 V1: 15, 40 in water, 1999 V2: 282, 287288
ozonation parts per million (ppm, PPM), 2004 V1: 15, 1999 V2: 285,
cooling tower water, 1999 V2: 316 2000 V3: 46
pure water systems, 1999 V2: 323 pascal-seconds, 2004 V1: 33
small drinking water systems, 1999 V2: 318 pascals, 2004 V1: 33
water treatments, 1999 V2: 245, 312313 passenger terminals, numbers of xtures for, 2003 V4: 19
ozone passivation, 2004 V1: 146147
layer, 2000 V3: 22 passive, dened, 2004 V1: 153
in pools and fountains, 2000 V3: 123124 passive verbs in function analysis, 2004 V1: 224
ozone generators, 1999 V2: 313 pathogenic organisms, 1999 V2: 282
paths
P of acoustic problems, 2004 V1: 199
of discharge, 2000 V3: 4
P alkalinity, 1999 V2: 282
P (peta) prex, 2004 V1: 34 patient rooms
p (pico) prex, 2004 V1: 34 bathing areas, 2000 V3: 32
P (pressure). See pressure xtures for, 2000 V3: 34
p-traps health-care facilities, 2000 V3: 32
oor drains with, 2004 V1: 11 medical gas stations, 2000 V3: 52, 58
laboratory sinks, 2000 V3: 42 medical vacuum, 2000 V3: 54
storm drainage systems, 1999 V2: 84 patient head wall stations, 2000 V3: 58
Pa (pascals), 2004 V1: 33 patient vacuum (VAC), 2000 V3: 85
PA (pipe anchors), 2004 V1: 10 paved areas
Pa s (pascal-seconds), 2004 V1: 33 imperviousness factors, 2000 V3: 243
packed-bed, activated-carbon lters, 1999 V2: 300, 301 storm drainage, 1999 V2: 67
packed tower aeration, 1999 V2: 318 PB (polybutylene). See polybutylene (PB)
packerhead method, 2003 V4: 32 PCT (percentages), 2004 V1: 15
packing material PCUs (platinum cobalt units), 1999 V2: 287
in seepage beds, 1999 V2: 224 PD (pressure drops or differences). See pressure drops or
sound damping, 2004 V1: 196 differences
in vacuum deaerators, 1999 V2: 295 PD (pump discharge lines), 2004 V1: 8
padding PDI (Plumbing and Drainage Institute). See Plumbing and
for glass pipe, 2003 V4: 47 Drainage Institute (PDI)
for vibration control, 2004 V1: 203, 204 PDI symbols for water hammer arresters, 1999 V2: 144
pain, thresholds of, 1999 V2: 169 PE-AL-PE (polyethylene/aluminum/polyethylene), 2003
painting cast iron radiators, 2000 V3: 179 V4: 62
paints in septic tanks, 1999 V2: 230 PE (polyethylene). See polyethylene (PE)
Pair, Claude H., 2000 V3: 105 PE (potential energy), 2004 V1: 2, 5
panels, lining with lead, 1999 V2: 340 pea gravel backll, 2000 V3: 172
paper towel clogs, 1999 V2: 11, 231 Peabody, A.W., 2004 V1: 154
parafn, 1999 V2: 13 peak consumption in gas boosters, 1999 V2: 182
paragraph numbering in CSI format, 2004 V1: 65 peak demand
parallel approaches for wheelchairs, 2004 V1: 109, 110 ushometer valves and, 2003 V4: 8
parallel-condensate trapping, 2000 V3: 196 medical air, 2000 V3: 53, 66
Index 339
two-pipe systems, 2000 V3: 180182 plate tectonics, 2004 V1: 156158
Piping Handbook, 1999 V2: 214 platform diving, 2000 V3: 128
Piping Specications and Installation Practices, 2000 V3: platinum, 2004 V1: 141
97 platinum cobalt units (PCUs), 1999 V2: 287
Piping Systems Fundamentals and Application, 1999 V2: Platinum-level LEED certication, 2004 V1: 263
155 platy soils, 1999 V2: 218
piston reciprocating compressors, 2000 V3: 201 plot plans, irrigation systems and, 1999 V2: 26
pit-type re-department connections, 2004 V1: 12 plug-type dezincication, 2004 V1: 142
pitch plug valves (PV), 2004 V1: 9
dened, 2004 V1: 27 plumbing
pitch down or up, 2004 V1: 11 appliances, 2004 V1: 27
radioactive waste systems, 1999 V2: 342 appurtenances, 2004 V1: 27
special-waste drainage systems, 1999 V2: 329 code agencies, 2004 V1: 42
vacuum cleaning systems, 1999 V2: 276 cost estimation, 2004 V1: 9398
pitless adapters, 1999 V2: 243 dened, 2004 V1: 27
pitot pressure, 2000 V3: 5, 7, 220 designs, 2004 V1: 100102
pitot tubes, 2000 V3: 4, 217, 219 ttings. See ttings
pitting, dened, 2004 V1: 153 xtures. See xtures
pitting corrosion, 2004 V1: 141, 1999 V2: 290, 2000 V3: plumbing systems dened, 2004 V1: 27
190 specications. See specications
PIV (post indicator valves), 2000 V3: 228 symbols, 2004 V1: 713
PL (Public Laws). See Public Laws terminology, 2004 V1: 1731
places of worship, numbers of xtures for, 2003 V4: 19, 22 Plumbing and Drainage Institute (PDI)
plain air chamvers, 1999 V2: 132, 143 abbreviation for, 2004 V1: 27
plain-end steel pipe, 2003 V4: 55 address, 2004 V1: 59
plane angles, 2004 V1: 33, 36 list of standards, 2004 V1: 5657
plans. See construction contract documents; plumbing PDI symbols for water hammer arresters, 1999 V2:
drawings 143, 144
plant noise, 2004 V1: 197198 Plumbing and Piping Industry Council (PPIC), 2004 V1:
planting area drains, 1999 V2: 83 170, 191
plantings, types of, 2000 V3: 104 Plumbing Design and Installation Reference Guide, 1999
plaster, lining with lead, 1999 V2: 340 V2: 114
plaster traps, 2000 V3: 36 Plumbing Design Manual, 1999 V2: 114
plastic ltration tanks, 2000 V3: 131 plumbing drawings
plastic xtures abbreviations, 2004 V1: 1416
standards, 2003 V4: 2 checklists, 2004 V1: 100102
types of, 2003 V4: 2 costs analysis phase, 2004 V1: 241
plastic joints, 1999 V2: 222 dened, 2004 V1: 61
plastic piping function evaluation, 2004 V1: 239240
bedding, 2000 V3: 234, 235 functional development, 2004 V1: 254, 255
codes, 2004 V1: 43 graphic conventions, 2004 V1: 108
compressed air systems, 2000 V3: 210 introduction, 2004 V1: 61
corrosion, 1999 V2: 252 in specications, 2004 V1: 69
ttings, 2003 V4: 58 Plumbing Efciency through Gray-water Recycling, 1999
fountain piping, 2000 V3: 116 V2: 34
fuel product dispensing and, 2000 V3: 169 plumbing engineering, 2004 V1: 27, 2000 V3: 2728
gas piping, 1999 V2: 176, 196, 2000 V3: 253, 254 Plumbing-Heating-Cooling ContractorsNational
joints, 2003 V4: 5960 Association (PHCC-NA), 2004 V1: 57, 59, 95, 1999
laboratory wastes, 2000 V3: 42 V2: 65
Manning formula and, 2000 V3: 245 plumbing inspectors, 2004 V1: 27
polyolen piping, 2003 V4: 61 Plumbing Manual, 1999 V2: 155
sanitary drainage systems, 1999 V2: 14 Plumbing Noise, 2004 V1: 194
storm-drainage systems, 1999 V2: 68, 8992 Plumbing Product Efciency Act, 2003 V4: 3, 8, 10, 11
thermal expansion and, 1999 V2: 251 plumbing specications. See specications
types, 2003 V4: 5865 PNC (preferred noise criteria curves), 2004 V1: 206
plastic pumps, 2000 V3: 115 pneumatic pressures, 1999 V2: 23, 40, 2000 V3: 68
plastic swimming pool main drains, 2000 V3: 143 pneumatic tank gauging, 2000 V3: 160
plastic valves, 2000 V3: 145146 pneumatic valves, 2000 V3: 119
plastic-wrapped steel piping, 1999 V2: 196 POC (points of connection), 2004 V1: 11
plastic wraps on toilet seats, 2003 V4: 5 point-of-use lters, 2000 V3: 203, 210
plate and frame modules in reverse osmosis, 1999 V2: 309, point-of-use ultraltration, 1999 V2: 300
310 point-of-use water heating, 2004 V1: 129, 2000 V3: 45
342 ASPE Plumbing Engineering Design Handbook Volume 1
points of connection (POC), 2004 V1: 11 polyvinylidene uoride piping, 1999 V2: 324, 2000 V3: 48
polar solvents, 2000 V3: 21 ponding
polarization on roofs, 1999 V2: 79
dened, 2004 V1: 153 slow-release storm-water systems, 1999 V2: 106
hydrogen lm buildup, 2004 V1: 139 storm water ponds, 1999 V2: 68
polishing deionizers, 1999 V2: 301, 302, 307 ponds, stabilization, 1999 V2: 232
polishing water in pure water systems, 1999 V2: 321 Pool/Spa Operators Handbook, 2000 V3: 125
pollution pools, 2004 V1: 27. See also reecting pools; swimming
contamination in compressed air, 2000 V3: 201 pools
dilution, 2000 V3:87 poor value, dened, 2004 V1: 213
dispersion from gas appliances, 1999 V2: 178 pop-up sprinkler heads, 2000 V3: 101, 102
ltering air pollution, 2000 V3: 66 porcelain enameled steel xtures
priority pollutants, 2000 V3: 88 dened, 2003 V4: 2
sanitary precautions for wells, 1999 V2: 243 standards, 2003 V4: 2
polyamide membranes, 1999 V2: 310, 311 pore size in lter membranes, 1999 V2: 310
polybutylene (PB), 2004 V1: 27, 2003 V4: 5960 porous piping, 1999 V2: 102
polyelectrolytes, 1999 V2: 294 porous soils, 2000 V3: 99100
polyester xtures, 2003 V4: 2 portable re extinguishers, 2004 V1: 13, 2000 V3: 27
polyethylene/aluminum/polyethylene (PE-AL-PE), 2003 portable vacuum systems, 2000 V3: 144
V4: 62 positive attachments, dened, 2004 V1: 191
Polyethylene Encasement, 2003 V4: 32 positive-displacement air compressors, 2000 V3: 65, 201
polyethylene (PE), 2004 V1: 27, 2000 V3: 254, 2003 V4: positive-displacement water meters, 1999 V2: 115
5861 positive pressure, backow and, 1999 V2: 144
polyethylene piping, 1999 V2: 284 post indicator valves (PIV), 2000 V3: 228
polyethylene storage tanks, 1999 V2: 323 pot and pan sinks, 2000 V3: 36
polymer membranes, 1999 V2: 310, 311 potable water. See drinking water; private water systems;
polymeric silica, 1999 V2: 283 wells
polymers, 2004 V1: 27 potash alum, 1999 V2: 294
polyolen piping, 2003 V4: 61 potassium, 1999 V2: 281, 283
polypropylene piping potassium bicarbonate, 1999 V2: 283
laboratories, 1999 V2: 334, 2000 V3: 40 potassium carbonate, 1999 V2: 283, 2000 V3: 207
pipe characteristics, 2003 V4: 5960 potassium chloride, 1999 V2: 283
pure-water systems, 2000 V3: 48 potassium hydroxide, 1999 V2: 230
soil and waste piping, 1999 V2: 14 potassium permanganate, 1999 V2: 245
sulfuric acid and, 2000 V3: 92 potential energy (PE)
USP water, 1999 V2: 324 calculating, 2004 V1: 2
VOCs and, 1999 V2: 284 velocity head and, 2004 V1: 5
polypropylene storage tanks, 1999 V2: 323, 2000 V3: 91 potentiometric surfaces of aquifers, 1999 V2: 241
polysulfone membranes, 1999 V2: 310, 311 POTW (Publicly Owned Treatment Works), 2000 V3: 89
polytropic processes, 2000 V3: 200 POU ltration, 1999 V2: 300
polyvinyl chloride (PVC) pounding forces in water. See water hammer
aboveground piping, 1999 V2: 68 pounds (lb, LBS)
dened, 2004 V1: 28 converting to SI units, 2004 V1: 40
xtures, 2003 V4: 2 pounds per square foot (psf, PSF), 2004 V1: 15
fountain piping, 2000 V3: 116, 119 pounds per square inch (psi, PSI), 2004 V1: 2, 15, 2000
noise, 1999 V2: 15 V3: 29, 180, 200
pipe characteristics, 2003 V4: 5960 pounds per square inch absolute (psia), 2004 V1: 15,
piping, 1999 V2: 284 1999 V2: 254, 2000 V3: 85, 200
pure-water systems, 2000 V3: 48 pounds per square inch gauge (psig), 2004 V1: 15, 1999
sand ltration tanks, 2000 V3: 131 V2: 254, 2000 V3: 68, 85, 200
sanitary drainage, 1999 V2: 14 symbols for, 2004 V1: 15
shower pans, 2003 V4: 15 power
sizing, 1999 V2: 8992 conversion factors, 2004 V1: 36
skimmers, 2000 V3: 146 converting to SI units, 2004 V1: 39
storage tanks and hazardous wastes, 2000 V3: 91 measurements, 2004 V1: 33
sulfuric acid and, 2000 V3: 92 power company off-peak power savings, 2004 V1: 128129
sunlight and, 2000 V3: 116 power control self-regulating index, 1999 V2: 166
swimming pool piping, 2000 V3: 145 power steam, 1999 V2: 298
types of piping, 2003 V4: 62 power usage, economizing on, 2004 V1: 128129
volatile organic compounds, 1999 V2: 284 Powered Industrial Trucks, 1999 V2: 214
weirs, 2000 V3: 146 powered vaporizers, 2000 V3: 61
polyvinyl-uoridine (PVDF), 2004 V1: 28 PP. See polypropylene piping
Index 343
PPIC (Plumbing and Piping Industry Council), 2004 V1: cold-water systems, 1999 V2: 115
170, 191 compressed air, 2000 V3: 200, 203, 207
ppm, PPM (parts per million), 2004 V1: 15, 1999 V2: 285, conversion factors, 2004 V1: 36
2000 V3: 46 critical (CRIP), 2004 V1: 15
Practical Design of a High-purity Water System, 1999 V2: discharge pressure from gas boosters, 1999 V2: 178
325 domestic water supply, 2000 V3: 217221
Practical Plumbing Design Guide, 1999 V2: 114 dynamic (velocity) (vp, VP), 2004 V1: 15
Prandtl-Colebrook equation, 1999 V2: 60 eliminating with vents, 1999 V2: 35
pre-action systems, 2004 V1: 29, 2000 V3: 13, 15, 25 fall-off pressure, 1999 V2: 122
pre-action valves, 2004 V1: 13 re pumps, 2000 V3: 25
pre-bid information, 2004 V1: 62 xture requirements, 1999 V2: 129
pre-cast concrete pipe, 2003 V4: 32 ow and air, 1999 V2: 2
pre-cast manholes, 2000 V3: 234, 237 uctuation warnings, 2000 V3: 72
pre-cast septic tanks, 1999 V2: 228 fountains, 2000 V3: 118
pre-cast water storage tanks, 1999 V2: 247 friction head, 2004 V1: 2, 6
pre-coat cakes in ltration, 2000 V3: 134 friction loss and, 2004 V1: 2, 1999 V2: 130
pre-compressed, glass-ber pads, 2004 V1: 204 gas boosters, 1999 V2: 178183
pre-engineered cathodically protected steel tanks, 2000 V3: heavy ow drains, 1999 V2: 9
155, 156 hot-water system pressures, 1999 V2: 157, 166167
pre-engineered dry-chemical systems, 2000 V3: 19 hydraulic shock, 2004 V1: 6
pre-engineered fountains, 2000 V3: 107 hydrostatic pressure, 1999 V2: 4
pre-fabricated roong drains, 1999 V2: 82 induced siphonage, 1999 V2: 40
pre-fabricated septic tanks, 1999 V2: 228 interstitial tank monitoring, 2000 V3: 161
pre-fabricated shower bases, 2003 V4: 15 low-pressure switches on gas boosters, 1999 V2: 179
pre-fabricated shower enclosures, 2003 V4: 15 measurements, 2004 V1: 33, 1999 V2: 4, 253
pre-fabricated water storage tanks, 1999 V2: 247 natural gas pressure, 1999 V2: 173, 174, 183, 2000 V3:
pre-heating input water, 2004 V1: 266 249, 252253
pre-manufactured skimmers, 2000 V3: 137 nitrogen surgical instruments, 2000 V3: 59
pre-treatment in pure water systems, 1999 V2: 321 nitrous oxide, 2000 V3: 64
pre-treatment ordinances, 2000 V3: 89 nozzle pressure ow tables, 2000 V3: 4
precipitates in water, 1999 V2: 245, 291 plastic piping systems, 2000 V3: 48
precipitation. See rainwater and precipitation pneumatic pressures in sanitary drains, 1999 V2: 23
precision in measurements, 2004 V1: 32 pressure-regulating valves, 1999 V2: 152154
predicting water deposits and corrosion, 1999 V2: 290292 pressure surges, 1999 V2: 35
preferred noise criteria (PNC) curves, 2004 V1: 206 pressure-volume relationships (gas laws), 1999 V2: 179
prelters pressure waves. See water hammer
air compressors, 2000 V3: 203 pump afnity laws, 2004 V1: 6
feed water, 1999 V2: 289 relative discharge curves, 2000 V3: 220
prexes in SI units, 2004 V1: 34 relief valves, 1999 V2: 166167, 167
premium grade PVC piping, 2000 V3: 48 residual pressure, 1999 V2: 123, 131
preparation soil pressures, 2000 V3: 155
checklists, 2004 V1: 99 sprinkler systems, 2000 V3: 3, 17, 18
in plumbing cost estimation, 2004 V1: 93 stack ow capacity and, 1999 V2: 4
section in specications, 2004 V1: 91 static (sp, SP), 2004 V1: 15, 16
in value engineering presentations, 2004 V1: 258 static pressure loss, 1999 V2: 123
Preparation phase in value engineering, 2004 V1: 213 storm-drainage stacks, 1999 V2: 67
preparing for jobs, checklists, 2004 V1: 99 submersible fuel pumps, 2000 V3: 170
PRES (pressure). See pressure suds pressure zones, 1999 V2: 37, 38, 39
Presentation phase in value engineering, 2004 V1: 213, swimming pool pumps, 2000 V3: 140
257258, 259 symbols for, 2004 V1: 15
Presidents Committee on Employment of the tests
Handicapped, 2004 V1: 105 fountain piping systems, 2000 V3: 117
press joints, 2004 V1: 266 medical gas systems, 2000 V3: 80, 82
PRESS (pressure). See pressure storage tanks, 2000 V3: 171
pressure (PRESS, PRES, P). See also pressure drops or vacuum cleaning system requirements, 1999 V2: 270
differences vacuum dened, 1999 V2: 253
acoustic design for water pipes, 2004 V1: 195196 vacuum pressure measurement, 1999 V2: 254256
air-consuming devices, 2000 V3: 206207 vapor (vap pr, VAP PR, VAP), 2004 V1: 15
barometric. See barometric pressure velocity head (h), 2004 V1: 5
blocked storm leaders and, 1999 V2: 86 velocity of water in pipes and, 1999 V2: 122132
bottled gas, 1999 V2: 174 water mains, 2000 V3: 216
carbon dioxide extinguishing systems, 2000 V3: 20 water pressure, 1999 V2: 149152
344 ASPE Plumbing Engineering Design Handbook Volume 1
water supply piping and, 1999 V2: 249 pressure product-dispensing systems, 2000 V3: 163164
water vapor in air and, 2000 V3: 200201 pressure-regulating or reducing valves (PRV)
pressure-assist water closets, 2004 V1: 136 acoustic design and pressure, 2004 V1: 200
pressure-balancing xtures. See pressure-regulating or fountains, 2000 V3: 119, 120
reducing valves (PRV) glossary, 1999 V2: 152154
pressure diatomaceous earth ltration, 2000 V3: 132, 135, health-care water supplies, 2000 V3: 44
139, 141 irrigation systems, 2000 V3: 103
pressure differentials shower valves, 2003 V4: 15
condensate drainage, 2000 V3: 191193 steam systems, 2000 V3: 191, 195
ttings, 2004 V1: 194 symbols for, 2004 V1: 9
pressure-differential-actuated valve trap primers, 1999 tub valves, 2003 V4: 16
V2: 14 types of, 1999 V2: 153154
steam systems, 2000 V3: 191 pressure regulators
pressure drops or differences (PD, DELTP) cold-water systems, 1999 V2: 122
air ltration and, 2000 V3: 207 compressed air systems, 2000 V3: 207
average pressure drops in water systems, 1999 V2: deluge valves, 2000 V3: 14, 15
125, 126, 127 ushometer tanks, 2003 V4: 8
backow preventers and, 2000 V3: 224 gas train vents, 1999 V2: 177
calculating, 2004 V1: 2 natural gas systems, 1999 V2: 174, 214, 2000 V3:
compressed air systems, 2000 V3: 78, 207, 210, 211, 250252
212 outlet pressure protection in gas boosters, 1999 V2:
dened, 1999 V2: 214 183
double-check valves and, 2000 V3: 224 water storage tanks, 1999 V2: 248249
lter pumps, 2000 V3: 115 pressure-relief lines in sovent systems, 1999 V2: 61
re hydrants and, 1999 V2: 249 pressure-relief outlets in deaerators, 1999 V2: 56
ttings, 2000 V3: 221 pressure-relief valves (RV), 2004 V1: 10
fountains, 2000 V3: 118 pressure sand lters, 2000 V3: 112, 113, 132133, 134, 139
friction loss of head, 1999 V2: 118, 119, 121 Pressure Sewer Demonstration at the Borough of
fuel system checklist, 2000 V3: 171 Phoenixville, Pennsylvania, 1999 V2: 238
gas boosters, 1999 V2: 182 pressure sewers, 1999 V2: 226
gas line lters and, 2000 V3: 250 pressure surges, 1999 V2: 35
gas meters and, 1999 V2: 176 pressure swing air dryers, 2000 V3: 207
installing taps, 2000 V3: 221 pressure switches (PS), 2004 V1: 10, 2000 V3: 121
liqueed petroleum gas storage, 1999 V2: 194 pressure tanks, 2000 V3: 153
medical air, 2000 V3: 74 pressure vacuum breakers, 1999 V2: 145, 148
medical gas, 2000 V3: 73 pressure-volume relationships (gas laws), 1999 V2: 179
natural gas systems, 1999 V2: 174, 183, 192, 193 pressure water lters, 1999 V2: 244
piping runs, 2000 V3: 221 pressure waves. See water hammer
sanitary drainage, 1999 V2: 2 pressurized fuel delivery systems, 2000 V3: 162, 170
sizing vacuum piping, 1999 V2: 263 pressurized steam return lines, 2000 V3: 196
sprinkler hydraulic calculations, 2000 V3: 18 pri, PRI (primary), 2004 V1: 15
static pressure loss, 1999 V2: 123 prices, 2004 V1: 222. See also costs and economic concerns
strainers and, 2000 V3: 224 PRIM (primary), 2004 V1: 15
swimming pool pumps, 2000 V3: 140 primary (pri, PRI, PRIM), 2004 V1: 15
symbols for, 2004 V1: 15 primary barriers for infectious wastes, 1999 V2: 343
vacuum cleaning systems, 1999 V2: 272274, 274 primary tanks
vacuum exhauster sizing, 1999 V2: 274 aboveground types, 2000 V3: 165, 167
vacuum pressures, 1999 V2: 258, 263 construction, 2000 V3: 156
valves, 2000 V3: 221 interstitial monitoring, 2000 V3: 160161
water meters, 2000 V3: 224 underground tanks, 2000 V3: 155
pressure-equalizing lines in sovent systems, 1999 V2: 60 prime costs, 2004 V1: 222
pressure gauges primers, 2004 V1: 147
with gauge cocks (PG), 2004 V1: 10 priming in dry-pipe systems, 2000 V3: 12
measurements, 1999 V2: 254 priority pollutants, 2000 V3: 88
swimming pools, 2000 V3: 140, 144 prism-like soils, 1999 V2: 218
pressure loss. See pressure drops prisons, numbers of xtures for, 2003 V4: 20, 22
pressure maintenance (jockey) pumps, 2004 V1: 24 privacy, urinals and, 2003 V4: 9, 10
pressure media lters, 1999 V2: 300 private sewage-disposal systems
pressure piping aerobic wastewater treatment plants, 1999 V2: 232
asbestos concrete, 2003 V4: 26 233
glass pipe, 2003 V4: 45 collection and treatment alternatives, 1999 V2: 226
pressure-powered pumps, 2000 V3: 188 227
Index 345
public facilities, numbers of xtures for, 2003 V4: 21 pump suction, 1999 V2: 249
public hydrants, 2004 V1: 12 secondary containment areas, 2000 V3: 90
Public Law 90-480, 2004 V1: 106 starter controls, 2000 V3: 120
Public Law 93-112, 2004 V1: 106 static deection for vibration, 2004 V1: 205
Public Law 98, 2000 V3: 154 strainers and suction screens, 2000 V3: 116
Public Law 616, 2000 V3: 154 submersible, 1999 V2: 243, 2000 V3:170, 2000 V3: 170
public sewers sulfuric acid and, 1999 V2: 332
availability of, 2000 V3: 234 sump pumps in sanitary drainage systems, 1999 V2: 9
dened, 2004 V1: 27 swimming pools, 2000 V3: 129, 139, 140142, 145146
discharging into, 1999 V2: 328 systems for water supplies, 1999 V2: 245247
neutralizing acid wastes for, 1999 V2: 334337 vacuum pumps, 2000 V3: 189
public storm sewer systems, 1999 V2: 67, 98, 105, 2000 vibration isolation, 2004 V1: 205, 206
V3: 245247 well pumps, 1999 V2: 245247
radioactive waste systems and, 1999 V2: 342 Pumps and Pump Systems, 2004 V1: 40
public swimming pools. See swimming pools Pumps and Pump Systems Handbook, 1999 V2: 152
public use purchasers in cost equation, 2004 V1: 223
dened, 2004 V1: 28 pure tones, 2004 V1: 208
lavatories, 2003 V4: 10 pure-water systems. See also water purication
Publicly Owned Treatment Works (POTW), 2000 V3: 89 dened, 1999 V2: 279
pubs, 2003 V4: 19, 22 health-care facilities, 2000 V3: 43, 4648
puddle anges, 2000 V3: 116 piping materials, 2000 V3: 4748
pull-out spray accessories, 2003 V4: 12, 14 types of pure water, 2000 V3: 46
pulsation purging
air compressors, 2000 V3: 212 medical gas zones, 2000 V3: 72, 80, 8182
electric fans, 2004 V1: 196 natural gas systems, 2000 V3: 252
magnetic eld pulsation, 2004 V1: 196 puried water (PW), 1999 V2: 320, 2003 V4: 47. See also
pump discharge lines (PD), 2004 V1: 8 pure-water systems; water purication
pump heads, 1999 V2: 105 purity
pumped sewage-disposal systems, 1999 V2: 226 compressed air, 2000 V3: 207
pumper connections, 2004 V1: 12 testing medical gas systems, 2000 V3: 82
pumping push-on joints, 2000 V3: 228229
septic tanks, 1999 V2: 227, 230 push-seal gasketed outlets, 1999 V2: 18
wells, 1999 V2: 241243 putrefaction, 2004 V1: 28
pumping head, 1999 V2: 245 Putting Industrial Vacuum to Work, 1999 V2: 277
pumps puzzles
acoustics, 2004 V1: 196197, 196198, 198, 200201 Nine Dots exercise, 2004 V1: 232, 261
automatic shutdown, 2000 V3: 90 Six Sticks exercise, 2004 V1: 232, 261
bases, 1999 V2: 243, 245 PV (plug valves), 2004 V1: 9
bearings, 2004 V1: 197 PVBs (pressure vacuum breakers), 1999 V2: 145, 148
boiler feed pumps, 2000 V3: 188189 PVC. See polyvinyl chloride (PVC)
cavitation, 2000 V3: 112 PVDF (polyvinyl-uoridine), 2004 V1: 28, 1999 V2: 14,
circulating pump efciency, 2004 V1: 265 2000 V3: 48
condensate transfer pumps, 2000 V3: 188 PVE (Pseudo Value Engineers), 2004 V1: 258
design of, 2004 V1: 200 PW (pure water), 1999 V2: 320. See also pure-water
earthquake protection, 2004 V1: 164 systems; water purication
efciency, 2004 V1: 67 pyramids, calculating volume, 2004 V1: 4
ejector pumps, 2000 V3: 236 pyrogens, 1999 V2: 282, 310, 2000 V3: 46
re pumps, 2000 V3: 2526
fountains, 2000 V3: 108, 112, 120, 125
geothermal energy systems, 2004 V1: 131
Q
Q factor (coefcient of transmissibility), 1999 V2: 101102
gravity tank systems, 1999 V2: 150152 Q (heat transfer), 2004 V1: 15
gray water use, 2004 V1: 267 QAIR (air ow rates), 2004 V1: 14
hydropneumatic-tank systems, 1999 V2: 150 QAR (air ow rates), 2004 V1: 14
impellers, 2004 V1: 197 QFL (uid ow rates), 2004 V1: 14
liquid fuel systems, 2000 V3:170 QGA, QGAS (gas ow rates), 2004 V1: 14, 1999 V2: 173
liquid-waste decontamination systems, 1999 V2: 344 qt, QT (quarts), 2004 V1: 15, 40
matching water storage to pump ow, 1999 V2: 248 quads, converting to SI units, 2004 V1: 40
plant noise, 2004 V1: 197198 quality
pulsation in, 2004 V1: 197 in cost estimation, 2004 V1: 98
pump afnity laws, 2004 V1: 6 quality assurance in specications, 2004 V1: 6970, 89
pump journals, 2004 V1: 196 quality control section in specications, 2004 V1: 71,
pump speeds, 2004 V1: 200201 91
Index 347
of water, 1999 V2: 33, 244245. See also water system design criteria, 1999 V2: 340343
analysis; water purication radioactivity
quantities. See also demand dened, 1999 V2: 337
clean gas agents, 2000 V3: 23 radioactive half lives, 1999 V2: 340
in creativity checklist, 2004 V1: 234 radioactive isotopes, 1999 V2: 337, 340
irrigation water, 2000 V3: 99 radiological characteristics of drinking water, 1999 V2:
water supplies, 2000 V3: 38 284, 317
quarter-circle rotary sprinkler heads, 2000 V3: 102 Radiological Safety Ofcers, 1999 V2: 340
quarts (qt, QT) radium 226, 1999 V2: 340
converting to SI units, 2004 V1: 40 RADN (radiation). See radiation
symbols for, 2004 V1: 15 radon gas in water, 1999 V2: 284, 317
questions in value engineering presentations, 2004 V1: 258 radwaste (waterborne radioactive waste), 1999 V2: 337
quick-coupling method of irrigation, 2000 V3: 100, 101 Rainbird Company, 2000 V3: 105
quick-disconnect couplings, 2000 V3: 210 rainwater and precipitation
quick-opening devices, 2000 V3: 13 capturing rainwater, 2004 V1: 135, 264, 267
quick-response sprinklers, 2004 V1: 29 cisterns, 1999 V2: 247
quick valve closure, 1999 V2: 131, 132 duration, 2000 V3: 244
quieting pipes, 1999 V2: 15 ow rates, 1999 V2: 68
in gray-water systems, 1999 V2: 21
R imperviousness factor, 2000 V3: 242243
inlet times, 2000 V3: 244
R (hydraulic radii), 2004 V1: 1
R, R- (refrigerants), 2004 V1: 15, 151 intensity-duration-frequency curves, 2000 V3: 242, 243
R, R (rankines), 2004 V1: 15 precipitation, 2004 V1: 27
R, R (thermal resistance), 2004 V1: 16 rainfall rates, 1999 V2: 6978, 97, 2000 V3: 242, 243
R (radii), 2004 V1: 15 rainwater drains (SD, ST). See storm-drainage systems
R-13 and R-13A re-protection systems, 2003 V4: 58 return periods, 2000 V3: 243244
R-595 gas, 2000 V3: 22 slow-release storm-water systems, 1999 V2: 106
ra, RA (return air), 2004 V1: 15 storing in controlled ow systems, 1999 V2: 9394
Rack Storage of Materials (NFPA 231C), 2000 V3: 2, 29 storm-drainage systems, 1999 V2: 6768, 95107
rad, RAD (radians). See radians subsurface water and, 1999 V2: 99105
RAD (radiating or radiators), 2004 V1: 15 swimming pools and, 2000 V3: 139
RAD (radiation). See radiation raised-oor areas, 2000 V3: 23
rad/s (radians per second), 2004 V1: 33 ramp-drain grates, 1999 V2: 11
rad/s2 (radians per second squared), 2004 V1: 33 rankines (R, R), 2004 V1: 15
radians (RAD) ranking functions in value engineering, 2004 V1: 243
measurement unit conversions, 2004 V1: 33 rapid sand/direct ltration package plants, 1999 V2: 318
radians per second, 2004 V1: 33 rate of corrosion
radians per second squared, 2004 V1: 33 acidity, 2004 V1: 145
symbols for, 2004 V1: 15 Faradays Law, 2004 V1: 144
radiant heating in swimming pools, 2000 V3: 138, 146 lm formation, 2004 V1: 145
radiating (RAD), 2004 V1: 15 homogeneity in, 2004 V1: 145
radiation (RADN, RAD) oxygen content, 2004 V1: 145
heat loss and, 2000 V3: 121 temperature, 2004 V1: 145
nature of, 1999 V2: 337338 velocity in, 2004 V1: 145
radiation equivalent to man (rem), 1999 V2: 339 rate of ow. See ow rates
rads (radioactive dosage), 1999 V2: 339 rate of temperature rise detection, 2000 V3: 13
symbols for, 2004 V1: 15 rated vacuum levels, 1999 V2: 257258
treatment facilities, 1999 V2: 340 ratings for portable re extinguishers, 2000 V3: 27
radiators (RAD), 2004 V1: 15, 2000 V3: 178, 181, 184 Rational Method, 2004 V1: 7, 1999 V2: 9598, 98, 107,
radicals (ions), 2004 V1: 144, 153, 1999 V2: 329 2000 V3: 242244
radii (R), 2004 V1: 15 raw sewage, 2004 V1: 28
radioactive waste drainage and vents raw water, 1999 V2: 280, 320
allowable radiation levels, 1999 V2: 339 RCIR (recirculate), 2004 V1: 15
approval process and applications, 1999 V2: 340 RCP (reinforced concrete pipe), 2003 V4: 32
diluting radwaste, 1999 V2: 342 RCRA (Resource Conservation and Recovery Act), 1999
introduction, 1999 V2: 337 V2: 345, 2000 V3:8788, 2000 V3: 8990, 154
measuring radiation, 1999 V2: 338339 rcvr, RCVR (receivers), 2004 V1: 15, 199, 1999 V2: 260,
nature of radiation, 1999 V2: 337338 262
pipe selection, 1999 V2: 341342 re-evaporation, 2000 V3: 197
radioactive-material-processing plants, 1999 V2: 147 re-ashing, 2000 V3: 20
radioactive materials, 1999 V2: 340 reaction forces in earthquakes, 2004 V1: 186
shielding systems, 1999 V2: 339340 reactive silencers, 2000 V3: 202
348 ASPE Plumbing Engineering Design Handbook Volume 1
reactive silica, 1999 V2: 283 red brass, 2004 V1: 144
reagent grade water, 1999 V2: 317, 319 red brass piping, 1999 V2: 14, 2003 V4: 27
real costs, 2004 V1: 223 red water in pools, 2000 V3: 147
rear wall grab bars, 2004 V1: 114 reduced noise transmission, 1999 V2: 15
reasoning against value engineering, 2004 V1: 232 reduced pressure
REC (receivers), 2004 V1: 15, 199, 1999 V2: 260, 262 conditions in water storage tanks, 1999 V2: 248
receiver tanks in pressure-regulated valves, 1999 V2: 152
medical air compressors, 2000 V3: 66 reduced-pressure backow preventers, 1999 V2: 115,
vacuum systems, 2000 V3: 70 144, 145, 148, 149
receivers (rcvr, RCVR, REC) reduced pressure zones (RPZ), 2000 V3: 223, 226
receivers of noise, 2004 V1: 199 reduced pressure zones (RPZ), 2000 V3: 223, 226
symbols for, 2004 V1: 15 reduced-size venting
in vacuum systems, 1999 V2: 260, 262 conuent vent sizing, 1999 V2: 51
receiving costs, 2004 V1: 223 example, 1999 V2: 53, 54
receptors, 2004 V1: 28 installation, 1999 V2: 52
recessed-box hose bibbs, 2004 V1: 10 introduction, 1999 V2: 49
recessed sprinklers, 2004 V1: 29 reduced size vents, dened, 2004 V1: 28
recharge basins, 2000 V3: 247 sizing, 1999 V2: 5053
rechargeable air chambers, 1999 V2: 132, 143 Reduced-size Venting Design, 1999 V2: 65
recharging aquifers, 1999 V2: 240 reduced water-ow rates, 2004 V1: 126127
reciprocating air compressors, 2000 V3: 65, 66, 201, 205 reduced zone backow preventers (RZBP), 2004 V1: 10
reciprocating (rotary) piston pumps, 1999 V2: 259 reducers, dened, 2004 V1: 28
recirculate (recirc., RECIRC, RCIR, RECIR), 2004 V1: 15 redundancy
recirculating hot-water systems, 2004 V1: 265 fountain pumps, 2000 V3: 115
recirculating sand lter sewage systems, 1999 V2: 227, 232 hazardous waste systems, 2000 V3: 90
recirculation rates reference standard specications, 2004 V1: 6667
gutters and, 2000 V3: 142 references
swimming pools, 2000 V3: 140 cold water systems, 1999 V2: 155
recirculation systems compressed air systems, 2000 V3: 214
for high purity water, 2000 V3: 47 conserving energy, 2004 V1: 137
for hot water, 1999 V2: 165 designing for people with disabilities, 2004 V1: 123
reclaimed water. See gray-water systems re-protection systems, 2000 V3: 29
Recommendation phase in value engineering, 2004 V1: formulae, symbols, and terminology, 2004 V1: 40
213 gasoline and diesel-oil systems, 2000 V3:173
pre-recommendation questions, 2004 V1: 254257 gray-water systems, 1999 V2: 34
Recommendations for a New ADAAG, 2004 V1: 123 health-care facilities, 2000 V3: 86
Recommended Minimum Requirements for Plumbing in irrigation systems, 2000 V3: 105
Dwellings and Similar Buildings, 1999 V2: 65 reecting pools and fountains, 2000 V3: 125126
Recommended Practice for Handling Releases of sanitary drainage systems, 1999 V2: 19
Flammable and Combustible Liquids and Gases seismic protection, 2004 V1: 191
(NFPA 329), 2000 V3: 154 special-waste drainage systems, 1999 V2: 350
recovered energy, 2004 V1: 137 steam and condensate systems, 2000 V3: 197
recovering heat from water heaters, 1999 V2: 158159 swimming pools, 2000 V3: 151
recovery in reverse osmosis, 1999 V2: 309 vacuum systems, 1999 V2: 277
recovery rooms vents, 1999 V2: 65
xtures, 2000 V3: 36 water treatment and purication, 1999 V2: 325
health-care facilities, 2000 V3: 32 references section in specications, 2004 V1: 69, 88
medical gas stations, 2000 V3: 52, 58 reecting pools
medical vacuum, 2000 V3: 54 controls, 2000 V3: 120121
recreational establishments dened, 2004 V1: 28
estimating sewage quantities, 1999 V2: 235, 237 design, 2000 V3: 107111
septic tank/soil-absorption systems for, 1999 V2: discharge devices, 2000 V3: 119120
231232 displays, 2000 V3: 108110, 111, 113115
recreational pools, 2000 V3: 128 ltration systems, 2000 V3: 112113, 115116
rectangles, calculating area, 2004 V1: 3 ow rates, 2000 V3: 108110
rectangular bath seats, 2004 V1: 122 inlets, outlets, and devices, 2000 V3: 110111
rectangular gutters, 1999 V2: 81, 86 lighting, 2000 V3: 112, 121
rectangular leaders, 1999 V2: 81 makeup-water systems, 2000 V3: 112, 124125
rectangular solids, calculating volume, 2004 V1: 4 multilevel pools, 2000 V3: 108
rectiers, 2004 V1: 150, 151 overow and drainage, 2000 V3: 112, 125
recycled water in landscaping, 2004 V1: 264 overview, 2000 V3: 107
recycled water systems. See gray-water systems piping and valves, 2000 V3: 111112, 116119
Index 349
pumps, 2000 V3: 113116 remote secondary-containment enclosures, 2000 V3: 167
references, 2000 V3: 125126 Remove Organics by Activated Carbon Adsorption, 1999
systems and components, 2000 V3: 111112 V2: 325
valves, 2000 V3: 118119 rems (radiation equivalent to man), 1999 V2: 339
water-heating system, 2000 V3: 112, 121122 renovations, cost estimating and, 2004 V1: 98
water-treatment systems, 2000 V3: 112, 122124 repetition in value engineering presentations, 2004 V1:
reformatories, numbers of xtures for, 2003 V4: 20 258
refrigerant after-coolers, 2000 V3: 203 replacements for Halon gases, 2000 V3: 22
refrigerants (R, R-), 2004 V1: 15, 151 Report on Hydraulics and Pneumatics of Plumbing
refrigerated air dryers, 2000 V3: 204, 207 Drainage Systems, 1999 V2: 19
refrigeration mechanical rooms, 2004 V1: 166 required costs, 2004 V1: 223
refrigeration piping, 2003 V4: 34, 36 res, RES (resistance or resistors), 2004 V1: 16
refrigeration systems research facilities, radiation in, 1999 V2: 340
heat reclamation, 2004 V1: 131 reserves (connected standbys), 2000 V3: 23
waste heat usage, 2004 V1: 131, 132 reservoirs
refuse bins, 2004 V1: 196 municipal, 2000 V3: 8
refuse disposal installations, soundproong, 2004 V1: 196 private, 1999 V2: 239
regenerable ion exchange, 1999 V2: 301 residential care facilities, numbers of xtures for, 2003 V4:
regenerants, dealkalizing and, 1999 V2: 295 20
regeneration cycle residential kitchen sinks
in dealkalizing, 1999 V2: 295 faucets, 2003 V4: 13
in deionizing, 1999 V2: 302, 304 types and requirements, 2003 V4: 1112
in demineralizers, 2000 V3: 46 residential systems
in ion exchange, 1999 V2: 305 cold-water systems, 1999 V2: 115116, 154155
in water softeners, 1999 V2: 307 estimating sewage quantities, 1999 V2: 233
regional authorities, 1999 V2: 327 reghting demand ow rates, 2000 V3: 232
registers in fuel dispensers, 2000 V3: 165 xture drainage loads, 1999 V2: 3
regulated substances, 2000 V3: 153 hot-water systems. See hot-water systems
regulations. See codes and standards irrigation, 2000 V3: 100
regulators. See specic types of regulators lavatory ow rates, 2003 V4: 10
Rehabilitation Act of 1973 (93-112), 2004 V1: 106 liqueed petroleum gas, 1999 V2: 194
reinforced concrete pipe (RCP), 2003 V4: 32 natural gas appliance demand, 1999 V2: 175
reinforcing ribs in tanks, 2000 V3: 155 numbers of xtures, 2003 V4: 20
reject stream from reverse osmosis, 1999 V2: 309 pool lters, 2000 V3: 112
relative discharge curves, 2000 V3: 220 reduced-size venting, 1999 V2: 50
relative humidity (rh, RH), 2004 V1: 15, 2000 V3: 200, 201 sewage-disposal systems. See private sewage-disposal
Relative Importance of Time and Surface Temperature in systems
the Causation of Cutaneous Burns, 1999 V2: 170 sprinklers, 2004 V1: 30, 2000 V3: 2
relay interface controls, 2000 V3: 73 typical gray-water supply and demand, 1999 V2: 25
reliability of water supplies, 2000 V3: 3, 8 water supply. See domestic water supply
relief valves residual pressure
re pumps, 2000 V3: 25 dened, 2004 V1: 28, 1999 V2: 123
gas regulators, 2000 V3: 251 determining available pressure and, 1999 V2: 131
hot-water systems, 1999 V2: 166167 domestic water supply, 2000 V3: 217221
liqueed petroleum gas, 1999 V2: 197 re hydrants, 2000 V3: 4, 8
sizing, 1999 V2: 167 sprinkler hydraulic calculations, 2000 V3: 16
water storage tanks, 1999 V2: 248 residual radiation, 1999 V2: 341
relief vents resilient mounts
circuit and loop venting, 1999 V2: 43 illustrated, 2004 V1: 207
dened, 2004 V1: 28, 1999 V2: 64 noise and vibration control, 2004 V1: 199, 205
gas trains, 2000 V3: 251 pipe run installations, 2004 V1: 209
soil and waste stacks, 1999 V2: 44, 45 seismic danger and, 2004 V1: 206
sovent systems, 1999 V2: 61 resilient pipe supports, 2004 V1: 199, 206
remote-control fountain controls, 2000 V3: 120 resin beads, 1999 V2: 304305
remote-control irrigation valves, 2000 V3: 103 resins, ion-exchange
remote-control pool panels, 2000 V3: 111 continuous deionization, 1999 V2: 306
remote earth (remote electrodes), 2004 V1: 153 dened, 1999 V2: 300
remote electrodes, 2004 V1: 153 in diluting compartments, 1999 V2: 307
remote ll ports, 2000 V3: 156, 167 overview, 1999 V2: 301302
remote leakage from tanks, 2000 V3: 162163 regenerating, 1999 V2: 304
remote portions of re design areas, 2000 V3: 16 strong-acid and weak-acid, 1999 V2: 302
remote-readout water meters, 1999 V2: 116 volatile organic compounds in, 1999 V2: 284
350 ASPE Plumbing Engineering Design Handbook Volume 1
resistance ratings (re loads), 2000 V3: 23 reversible potential, dened, 2004 V1: 153
resistance (res, RES, OHMS), 2004 V1: 15 revolutions (rev, REV)
resistivity revolutions per minute (rpm, RPM), 2004 V1: 15
dened, 2004 V1: 154 revolutions per second (rps, RPS), 2004 V1: 16
soil, 2004 V1: 150 Reynolds number for turbulence, 2004 V1: 2, 1999 V2: 41
resistors (res, RES, OHMS), 2004 V1: 15 rgh, RGH (roughness), 2004 V1: 16. See also roughness
resonant air compression systems, 2000 V3: 212 rh, RH (relative humidity). See relative humidity
resource conservation, 2004 V1: 124 RHO (density). See density
Resource Conservation and Recovery Act, 2004 V1: 124, rhomboids, calculating area, 2004 V1: 4
1999 V2: 345, 2000 V3:8790, 2000 V3: 96, 154 rhombuses, calculating area, 2004 V1: 4
resources RI (Ryzner stability index), 1999 V2: 292
gasoline and diesel-oil systems, 2000 V3:173 Richardson, D.W., Sr., 1999 V2: 325
health-care facilities, 2000 V3: 86 right-angle triangles, calculating area, 2004 V1: 4
industrial wastewater treatment, 2000 V3: 97 rigid ceiling medical-gas columns, 2000 V3: 58
irrigation systems, 2000 V3: 105 rigid plastic piping, 2000 V3: 169
respirators. See breathing apparatus rim top test, 2003 V4: 6
response in pressure-regulated valves, 1999 V2: 152 rims
response spectrum in earthquakes, 2004 V1: 160161, 186 dened, 2004 V1: 28
restaurants, 1999 V2: 231232, 2003 V4: 19, 22. See also on urinals, 2004 V1: 116117
food-processing areas and kitchens rim top test, 2003 V4: 6
restrained-spring mountings, 2004 V1: 204 water closets, 2003 V4: 45
restraint systems ring-securing methods around drains, 1999 V2: 17
for earthquakes, 2004 V1: 166, 189 rinsing in regeneration cycle, 1999 V2: 304, 305
for re-protection joints, 2000 V3: 229 riser clamps, 1999 V2: 86
restricted areas (facilities with radiation), 1999 V2: 339 riser-mounted sprinkler heads, 2000 V3: 102
restrooms. See water-closet compartments; water closets risers
retail stores, numbers of xtures for, 2003 V4: 20 bracing, 2004 V1: 171, 178
retard chambers, 2000 V3: 9 checklists, 2004 V1: 102
retention basins, 2000 V3: 247 dened, 2004 V1: 28, 2000 V3: 85
retirement costs, in labor costs, 2004 V1: 94 earthquake protection and joints, 2004 V1: 168
retractable ceiling medical gas columns, 2000 V3: 58 low-pressure steam (lps, LPS), 2000 V3: 187
return air (ra, RA), 2004 V1: 15 riser clamps, 1999 V2: 86
return circuits, 2004 V1: 139 riser down (elbows), 2004 V1: 10
return offsets, 2004 V1: 28 riser-mounted sprinkler heads, 2000 V3: 102
return periods in rainfall, 1999 V2: 6978, 2000 V3: riser up (elbows), 2004 V1: 10
243244 steam piping, 2000 V3: 182, 185
returns symbols for, 2004 V1: 12
condensate returns, 2000 V3: 186189 rises or drops, 2004 V1: 11
fountain ltration, 2000 V3: 115, 117 risk cabinets, 1999 V2: 344
parallel ow piping designs, 2000 V3: 178179 Risk Guides in value engineering, 2004 V1: 254, 257
return lines, 2000 V3: 195, 196 riveted steel piping, 1999 V2: 122
returning water to pools, 2000 V3: 119120 RO (reverse osmosis). See reverse osmosis
swimming pools, 2000 V3: 143144 roadblocks to creativity, 2004 V1: 231232
reusing water. See gray-water systems roadway drainage pipes, 2003 V4: 32
rev, REV (revolutions), 2004 V1: 15 rock ll in seepage beds, 1999 V2: 224
revent pipes, 2004 V1: 28. See also individual vents rock guards for lights, 2000 V3: 121
reverse osmosis rock salt, 1999 V2: 307
cartridges, 1999 V2: 289 Roentgens, 1999 V2: 339
continuous deionization and, 1999 V2: 307 roll-in shower compartments, 2004 V1: 119120
dened, 1999 V2: 308309 roll-out gutters, 2000 V3: 137
health-care facilities, 2000 V3: 47 roof drainage, 1999 V2: 7994
membrane congurations, 1999 V2: 309 adjacent buildings and surfaces, 1999 V2: 80
membrane selection, 1999 V2: 310 avoiding septic tank disposal, 1999 V2: 231
polymer membranes, 1999 V2: 311 controlled ow systems, 1999 V2: 88, 9394
silica and, 1999 V2: 283 coordination with other designers, 1999 V2: 79, 81, 84
small drinking water systems, 1999 V2: 318 drain locations, 1999 V2: 7980
VOCs in membranes, 1999 V2: 284 drain types and components, 1999 V2: 8081
water supply (RO), 2004 V1: 8 expansion, 1999 V2: 85, 87
Reverse Osmosis and Nanoltration System Design, 1999 Form 4-1, 1999 V2: 109
V2: 325 green roof designs, 2004 V1: 266
reverse osmosis water supply (RO), 2004 V1: 8 gutters and downspouts, 1999 V2: 81
reverse-trap water closets, 2003 V4: 3 horizontal branches, 1999 V2: 88
Index 351
sales tax, in plumbing cost estimation, 2004 V1: 94 oor leveling around drains, 1999 V2: 17
salesmanship in value engineering, 2004 V1: 257 ow in, 1999 V2: 12
salt-air dryers, 2000 V3: 207 force mains, 2000 V3: 236240
salt splitting, 1999 V2: 295 connections, 2000 V3: 239
salts sizing, 2000 V3: 236
disinfecting water with, 2000 V3: 150 sizing ejector pumps and pits, 2000 V3: 236
ions in reverse osmosis, 1999 V2: 280 gray-water systems and, 1999 V2: 22
in irrigation water, 2000 V3: 99 health-care facilities, 2000 V3: 3942
saltwater pools, 2000 V3: 147 joining methods, 1999 V2: 1718
samples kitchen areas, 1999 V2: 1617
acid wastes, 2000 V3: 4142 laboratories
infectious waste systems, 1999 V2: 345 acid-waste metering, 2000 V3: 4142
pure water systems, 1999 V2: 324 acid-waste neutralization, 2000 V3: 4041
radioactive waste efuent, 1999 V2: 342 acid-waste solids interceptors, 2000 V3: 41, 43
sampling manholes, 2000 V3: 4142, 44 discharge to sewers, 2000 V3: 40
San Diego Gas & Electric Company, 2004 V1: 137 sink traps, 2000 V3: 42
San Francisco Earthquake, 2004 V1: 162 waste and vent piping, 2000 V3: 42
SAN (sanitary sewers), 2004 V1: 8, 28. See also sanitary materials for, 1999 V2: 1415
drainage systems overview, 2000 V3: 232
sand ltration pipes, 2004 V1: 44
aluminum sulfate, 2000 V3: 149150 pneumatic pressures in, 1999 V2: 23
cleaning, 2000 V3: 150 preliminary information, 2000 V3: 215216
compared to diatomaceous earth, 2000 V3: 135137 protection from damage, 1999 V2: 1819
drinking water, 1999 V2: 244, 318 public sewer availability, 2000 V3: 234
earthquake damage to lters, 2004 V1: 162 research, 1999 V2: 19
fountains, 2000 V3: 112 sample letters, 2000 V3: 232
gravity and pressure systems, 2000 V3: 132 sanitary sewers (SAN, SS), 2004 V1: 8, 28
high-rate pressure lters, 2000 V3: 113 sanitation and cleaning, 1999 V2: 16
laboratory water, 1999 V2: 300 sizing, 2000 V3: 232233
pressure sand lters, 2000 V3: 132133, 134 sloping drain capacities, 1999 V2: 59
pumps and, 2000 V3: 140 sovent systems, 1999 V2: 19, 20
pure water systems, 1999 V2: 322323 stack capacities, 1999 V2: 35
sand lters dened, 2004 V1: 28 storm-drainage systems and, 1999 V2: 67
sewage treatment, 1999 V2: 227, 232 thermal expansion, 1999 V2: 18
swimming pools, 2000 V3: 130 trenching and bedding, 2000 V3: 234, 235
tanks, 2000 V3: 131 waterproong, 1999 V2: 17
types of, 2000 V3: 139 sanitary joints, 2000 V3: 48
sand points, 1999 V2: 241 sanitary sewer pipe codes, 2004 V1: 44
sand traps, 2000 V3: 113 sanitary sewer systems. See sanitary drainage systems
sands sanitary tees
backlling around water system pipes, 1999 V2: 250 common vents and, 1999 V2: 43
ll above subsurface drainage pipes, 1999 V2: 103 ow capacity and, 1999 V2: 4
gray-water irrigation systems and, 1999 V2: 26, 27 water closet installation, 2003 V4: 67
imperviousness factors, 2000 V3: 243 sanitaryware. See xtures
porous soils, 2000 V3: 99100, 105 sanitation. See also cleanouts
in soil texture, 1999 V2: 218 feed water, 1999 V2: 289
sanitary building drains. See also sanitary drainage xture materials and, 2003 V4: 1
systems oor drains, 2003 V4: 17
cast-iron soil pipe, 2003 V4: 27 precautions for wells, 1999 V2: 243
dened, 2004 V1: 20 sanitary seals on wells, 1999 V2: 240
sanitary drainage tting codes, 2004 V1: 44 water softeners, 1999 V2: 308
sanitary drainage systems, 2000 V3: 232240 sanitizers, 2000 V3: 38
alternative disposal methods, 2000 V3: 240 Sansone, John T., 1999 V2: 114
building sewers (house drains), 1999 V2: 15, 2003 V4: SARA Title III act (Superfund Amendment and
27 Reauthorization Act of 1986), 2000 V3: 154
components, 1999 V2: 914, 2000 V3: 234236 sat., SAT (saturation). See saturation
connections, 2000 V3: 234, 236 saturated steam, 2000 V3: 175, 176
dened, 1999 V2: 1 saturation (sat., SAT)
drainage loads, 1999 V2: 3 of soils, 1999 V2: 219
drainage structures, 2000 V3: 234236 symbols for, 2004 V1: 16
ttings, 2004 V1: 44 of water with calcium carbonate, 1999 V2: 291
xture discharge characteristics, 1999 V2: 3 SAVE. See Society of American Value Engineering
Index 353
sawcutting trenches, labor productivity rates, 2004 V1: 96 vacuum calculations for, 1999 V2: 269
Saybolt Seconds Furol (ssf, SSF), 2004 V1: 16, 2000 V3: scope lines, 2004 V1: 227
154 screening
Saybolt Seconds Universal (ssu, SSU), 2004 V1: 16, 2000 in downspouts, 1999 V2: 81
V3: 154 in gray-water treatment, 1999 V2: 27
SAZ (solar azimuth), 2004 V1: 14 urinals, 2003 V4: 10
SBCCI (Southern Building Code Congress International, vacuum exhaust piping, 1999 V2: 274
Inc.), 1999 V2: 114, 2000 V3: 154 screw compressors, 2000 V3: 201, 205
SC (shading coefcients), 2004 V1: 16 screw pumps, 1999 V2: 259
scalars, dened, 2004 V1: 93 screw threads, 2004 V1: 17
scalding water, 1999 V2: 157, 169170 screwed ttings, 2004 V1: 162
scale and scale formation screwed mechanical joints, 1999 V2: 334
boilers, 1999 V2: 314 scrub-up sinks, 2000 V3: 32, 3536, 38
chlorides and sulfates, 1999 V2: 283 scuff-buff grates, 1999 V2: 11
cooling towers, 1999 V2: 316 scum
hardness and, 1999 V2: 283 in septic tanks, 1999 V2: 227, 228, 229, 230
heat transfer surfaces, 2000 V3: 190 in swimming pools, 2000 V3: 150
Langelier saturation index, 1999 V2: 291292 scuppers, 1999 V2: 79, 88, 93
magnesium and, 1999 V2: 283 SCW (soft cold water), 2004 V1: 8
pool water heaters and, 2000 V3: 138 SD (storm or rainwater drains). See storm-drainage
predicting water deposits and corrosion, 1999 V2: systems
290292 SDI (silt density index), 1999 V2: 288289
removing with water softening, 1999 V2: 307 SDR (standard dimension ratio)
Ryzner stability index, 1999 V2: 292 HDPE pipe, 2003 V4: 61
sequestering agents, 2000 V3: 150 SDR21 PVC pipe, 2003 V4: 62
swimming pools, 2000 V3: 147 SDR26 PVC pipe, 2003 V4: 62
total dissolved solids and, 1999 V2: 288 SE (sea level). See sea level
water deposits and corrosion, 1999 V2: 289290 sea level (sl, SL, SE)
water piping systems, 1999 V2: 244 atmospheric pressure, 2000 V3: 200
scanning electron microscopy, 1999 V2: 282. See also symbols for, 2004 V1: 16
electron microscopes vacuum ratings, 1999 V2: 257
scavenging adapters, 2000 V3: 71 sealed sprinklers, 2000 V3: 9, 11
SCCC (Spill Containment Control and Countermeasures), sealing grouts in wells, 1999 V2: 243
2000 V3: 165 seals
scfh (standard cfh), 1999 V2: 180 acoustic pipe-penetration seals, 2004 V1: 201
scfm, SCFM (standard cubic feet per minute) ashing rings, 1999 V2: 12
abbreviation, 2004 V1: 14 oor drains in infectious waste systems, 1999 V2: 345
ambient free air and, 1999 V2: 255256 seal liquids in vacuum pumps, 1999 V2: 260
compressed air pipe sizing, 2000 V3: 210 sound insulation, 2004 V1: 193
compressed air tools, 2000 V3: 208 trap seals in oor drains, 1999 V2: 10
dened, 2000 V3: 85, 200 water closets, 2003 V4: 6
medical air compressors, 2000 V3: 65, 66 well xtures, 1999 V2: 243
medical vacuum systems, 2000 V3: 69 seamless copper pipe, 2003 V4: 3436
scfs, SCFS (cubic feet per second), 2004 V1: 33 seamless copper water tube, 2003 V4: 3444
Schedule 10 steel pipe, 2003 V4: 48 seamless steel piping, 2003 V4: 48
Schedule 40 brass pipe, 2003 V4: 27 seasonable condensate drains, 1999 V2: 13
Schedule 40 polyvinyl pipe, 2003 V4: 62 seats
Schedule 40 PVC plastic, 2000 V3: 17, 116, 2003 V4: 62 accessible shower compartments, 2004 V1: 120
Schedule 40 steel pipe, 2003 V4: 5152 bathtub and shower seats, 2004 V1: 115, 117, 122123
Schedule 80 brass pipe, 2003 V4: 27 seat fouling tests, 2003 V4: 6
Schedule 80 polyvinyl pipe, 2003 V4: 62 water closets, 2003 V4: 5
Schedule 80 PVC plastic, 2003 V4: 62 second-guessing designs, 2004 V1: 213
Schedule 80 steel pipe, 2003 V4: 5354 secondary containment
schedules (project) of hazardous wastes, 2000 V3: 90
checklist, 2004 V1: 102 of infectious wastes, 1999 V2: 343
section in specications, 2004 V1: 70, 90, 92 secondary containment tanks
school laboratories. See laboratories aboveground types, 2000 V3: 165, 167
schools interstitial monitoring, 2000 V3: 160161
numbers of xtures for, 2003 V4: 19, 22 interstitial spaces, 2000 V3: 156
septic tank systems for, 1999 V2: 231232 underground tanks, 2000 V3: 155
shower room grates, 1999 V2: 11 secondary functions, 2004 V1: 225, 227, 230
swimming pools and, 2000 V3: 129 secondary pipe liquid monitoring, 2000 V3: 162
354 ASPE Plumbing Engineering Design Handbook Volume 1
secondary pipe vapor monitoring, 2000 V3: 162 Seismic Restraint Manual Guidelines for Mechanical
secondary storm-drainage systems Systems, 2004 V1: 191
controlled-ow systems, 1999 V2: 94 selective attack corrosion, 2004 V1: 141
pipe sizing, 1999 V2: 69 selectivity coefcients, 1999 V2: 302
piping systems, 1999 V2: 81 self-bracing problems in seismic protection, 2004 V1: 190
planning for in design, 1999 V2: 70 self-closing valves, 2000 V3: 33
rainfall frequency and, 1999 V2: 79 self-contained breathing units, 1999 V2: 332, 333
scuppers, 1999 V2: 93 self-contained fountains, 2000 V3: 107
types of, 1999 V2: 88 self-jetting well points, 1999 V2: 241
Seconds Redwood, 2000 V3: 154 self-metering faucets, 2003 V4: 13
seconds (s, SEC), 2004 V1: 16, 33 self-priming dry pumps, 2000 V3: 113, 129130, 142
Seconds Saybolt Furol (SSF), 2000 V3: 154 self-regulating heat-trace systems, 1999 V2: 165166
Seconds Saybolt Universal (SSU), 2000 V3: 154 self-scouring traps, 1999 V2: 36
Sectionformat, 2004 V1: 65, 6871 self-scouring velocity in sewers, 2000 V3: 232
sections self-siphonage
in Manual of Practice, 2004 V1: 8892 dened, 1999 V2: 36
of pump equipment, 1999 V2: 245 in xture drains, 1999 V2: 2
in specications, 2004 V1: 63, 6871 tests, 1999 V2: 38
security of oxygen storage areas, 2000 V3: 63 self-venting in sovent systems, 1999 V2: 19, 54
sediment selling functions, 2004 V1: 225
removing, 1999 V2: 294 SEMI (Semiconductor Equipment Manufacturers
in water, 1999 V2: 282 Institute), 1999 V2: 279, 317
sediment buckets semi-ambulatory individuals
kitchen drains, 1999 V2: 16 semi-ambulatory disabilities, 2004 V1: 107
materials, 1999 V2: 14 water closet requirements, 2004 V1: 116
in oil collectors, 1999 V2: 13 semi-circular gutters, 1999 V2: 81, 86
in sanitary drainage systems, 1999 V2: 12 semi-circular lavatories, 2003 V4: 11
sediment pits, 1999 V2: 105 semi-instantaneous water heaters, 1999 V2: 160
sedimentation semi-permeable membranes, 2000 V3: 47
in gray-water treatment, 1999 V2: 27 Semiconductor Equipment Manufacturers Institute, 1999
in water treatment, 1999 V2: 294 V2: 279, 317
seepage beds, 1999 V2: 217, 220, 224225, 232 Sendelbach, M.G., 1999 V2: 325
seepage anges, 1999 V2: 17 sensible heat (SH)
seepage pits, 2004 V1: 28, 1999 V2: 27, 220, 225226, 2000 condensate drainage and, 2000 V3: 189
V3: 240 dened, 2004 V1: 137
SEFF (surface efciency), 2004 V1: 14 sensible heat gain (SHG), 2004 V1: 15, 16
seiches, 2004 V1: 158 sensible heat ratio (SHR), 2004 V1: 16
seismic, dened, 2004 V1: 191 symbols for, 2004 V1: 16
Seismic Design for Buildings, 2004 V1: 183, 191 sensitivity in pressure-regulated valves, 1999 V2: 152
seismic joints, crossing, 2004 V1: 162 sensors
seismic protection corrosive-waste systems, 2000 V3: 40
air compressors and, 2000 V3: 213 electrical makeup water method, 2000 V3: 124, 125
calculating seismic forces, 2004 V1: 183186 faucet controls, 2004 V1: 135
causes and effects of earthquakes, 2004 V1: 156158 hazardous material level sensors, 2000 V3: 90
codes and standards, 2004 V1: 171184 line-pressure sensors, 2000 V3: 72
computer analysis of piping systems, 2004 V1: 186 liquid fuel leakage, 2000 V3: 163
damage from earthquakes, 2004 V1: 158 pH sensors, 2000 V3: 40
design considerations, 2004 V1: 186188 water-level sensors, 2000 V3: 124
earthquake measurement and seismic design, 2004 V1: separating systems
160161 for acid waste, 1999 V2: 329, 334
equipment protection, 2004 V1: 163171 for oil, 1999 V2: 347349
glossary, 2004 V1: 191 separator/lters in air compressors, 2000 V3: 203
introduction, 2004 V1: 155156 separators in vacuum cleaning systems
learning from past earthquakes, 2004 V1: 161163 kinds of materials, 1999 V2: 275
pipe restraints, 2004 V1: 166182, 1999 V2: 14, 19, location, 1999 V2: 270
2000 V3: 15 pressure loss, 1999 V2: 274
potential problems, 2004 V1: 188191, 189 types of systems, 1999 V2: 266, 268
references, 2004 V1: 191 septic tanks
seismic loads, dened, 2004 V1: 155 biological treatment of sewage in, 1999 V2: 227
seismic risk maps, 2004 V1: 155157 chemicals in, 1999 V2: 230231
underground storage tanks and, 2000 V3: 155 cleaning, 1999 V2: 229230
vibration isolation and, 2004 V1: 206 clogging materials, 1999 V2: 231
Index 355
emergency showers, 1999 V2: 332, 333, 344, 2003 V4: signals for re alarms, 2000 V3: 9
1718 signicant digits, 2004 V1: 32
enclosures, 2004 V1: 120 silencers
xture-unit loads, 1999 V2: 3 on air compressors, 2000 V3: 202, 212
ow rates, 2003 V4: 15 on vacuum systems, 1999 V2: 268
grab bars, 2004 V1: 121122 silica, 1999 V2: 283
grates in school shower rooms, 1999 V2: 11 silica gel, 2000 V3: 204
gray-water supply and demand, 1999 V2: 25 silicates, 1999 V2: 282, 2000 V3: 147
gray-water systems, 2004 V1: 135 silicon, 1999 V2: 281
health-care facilities, 2000 V3: 32, 38 silicon iron piping, 1999 V2: 15
heat recovery systems, 2004 V1: 266 silt
hydrotherapy, 2000 V3: 35 content of water, 2000 V3: 99
labor rooms, 2000 V3: 36 loams, 2000 V3: 100
minimum numbers of, 2003 V4: 1822 removing, 1999 V2: 294
patient rooms, 2000 V3: 34 silt density index, 1999 V2: 288289
public areas in health-care facilities, 2000 V3: 33 in soil texture, 1999 V2: 218
rates of sewage ows, 1999 V2: 237 in water, 1999 V2: 282
reduced water usage, 2004 V1: 126 silt density index (SDI), 1999 V2: 288289
reducing ow rates, 2004 V1: 135 silver, 2004 V1: 139, 141, 144
requirements, 2003 V4: 1415 Silver-level LEED certication, 2004 V1: 263
resilient-mounting design, 2004 V1: 206 silver salt, 2000 V3: 150
seats, 2004 V1: 122123 silver solder, 2004 V1: 141
shower compartment accessibility, 2004 V1: 119122 A Simple Method for Retention Basin Design, 1999 V2: 114
showerhead acoustic ratings, 2004 V1: 195 simplex air compressors, 2000 V3: 213
spray units, 2004 V1: 118, 120 simplex gas booster systems, 1999 V2: 181
standards, 2003 V4: 2 simultaneous operators of vacuum systems, 1999 V2: 269,
stop levers, 2004 V1: 136 272
swimming pool bathhouses, 2000 V3: 130 simultaneous-use factors. See diversity factor
temperatures, 2000 V3: 45 single-acting altitude valves, 1999 V2: 249
thresholds, 2004 V1: 120 single-acting cylinders in compressors, 2000 V3: 201
water xture unit values, 2000 V3: 217 single-compartment septic tanks, 1999 V2: 229
SHP (shaft horsepower), 2004 V1: 16 single-compartment sinks, 2003 V4: 11
SHR (sensible heat ratio), 2004 V1: 16 single-degree-of-freedom systems, 2004 V1: 160, 161
Shreir, L.L., 2004 V1: 154 single-family dwellings, 2003 V4: 20, 21
shrinkage of ceramic xtures, 2003 V4: 1 single-occupant toilet rooms, 2003 V4: 18, 23
shrub sprinkler heads, 2000 V3: 103 single-seated pressure-regulated valves, 1999 V2: 152
Shumann, Eugene R., 1999 V2: 114 single-side-entry ttings in sovent systems, 1999 V2: 62
shut-off devices single-stage distillation, 1999 V2: 295
dened, 1999 V2: 214 single-step deionization (mixed bed), 1999 V2: 302, 303,
fuel dispensers, 2000 V3: 165 305
shut-off valves single-tank residential lters, 2000 V3: 134
earthquake-sensitive valves, 2004 V1: 162 single-wall tanks, 2000 V3: 156
fountains, 2000 V3: 118 sinistans, 2000 V3: 38
gas hose connectors, 1999 V2: 196 sink-disposal units. See food waste grinders
medical gases, 2000 V3: 71, 72 sinks and wash basins. See also lavatories
natural gas, 1999 V2: 176 accessibility, 2004 V1: 117
shutdown relays, 2000 V3: 24 faucets, 2003 V4: 13
Shweitzer, 2000 V3: 97 xture-unit loads, 1999 V2: 3
SI units. See International System of Units food-preparation, 2000 V3: 36
siamese re-department connections, 2004 V1: 12, 28, general category of, 2003 V4: 13
2000 V3: 11. See also re-protection systems gray-water supply and demand, 1999 V2: 25
side reach for wheelchairs, 2004 V1: 109, 112 health-care facilities, 2000 V3: 32, 38
side spray accessories, 2003 V4: 12, 14 infectious waste drainage, 1999 V2: 344
side vents, 2004 V1: 28 kitchen sinks, 2003 V4: 1112
sidesway prevention, 2004 V1: 189 laboratory rooms, 2000 V3: 37
sidewalk re-department connections, 2004 V1: 12 laboratory sink drainage rates, 1999 V2: 337
sidewall grab bars, 2004 V1: 114 laundry sinks, 2003 V4: 13
sidewall heat loss in pools, 2000 V3: 144 neutralizing acid from, 1999 V2: 336
sidewall sprinklers, 2004 V1: 13, 30 pharmacies and drug rooms, 2000 V3: 35
Siegrist, R., 1999 V2: 34 public areas in health-care facilities, 2000 V3: 33
siemens, 2004 V1: 33 rates of sewage ows, 1999 V2: 237
sight disabilities, 2004 V1: 107 service sinks, 2003 V4: 1213
Index 357
sodium bisulfate, 1999 V2: 245, 2000 V3: 93, 148, 149, 150 solar (SOL), dened, 2004 V1: 16
sodium carbonate (soda ash), 1999 V2: 283, 2000 V3: 148, solar energy sources, dened, 2004 V1: 137
149 water heaters, 2004 V1: 130, 265
sodium chloride, 1999 V2: 283 soldering
sodium cycle ion exchange, 1999 V2: 307 clearance for, 2003 V4: 25
sodium hexametaphosphate, 2004 V1: 151, 1999 V2: 244 copper water tube, 2003 V4: 37
sodium hydroxide (lye), 1999 V2: 230, 305, 2000 V3: 93, corrosion and, 2004 V1: 146
149, 150 reducing, 2004 V1: 266
sodium hypochlorite, 1999 V2: 245, 2000 V3: 93, 149, soldered joints and earthquake protection, 2004 V1:
150151 167
sodium silicate, 2004 V1: 151 solenoid valves
sodium sulfate, 1999 V2: 281 makeup water systems, 2000 V3: 124
sodium thiosulfate, 1999 V2: 245 solenoid valve trap primers, 1999 V2: 14
soft cold water (SCW), 2004 V1: 8 symbols for, 2004 V1: 9
soft conversions, 2004 V1: 32 solid angles, 2004 V1: 33
soft water (SW). See water softeners solid chlorine, 2000 V3: 123
softening water. See water softeners solid expansion traps, 2000 V3: 182
softness of vibration control materials, 2004 V1: 202 solid toilet seats, 2003 V4: 5
software. See computer programs solid waste disposal
soil-absorption sewage systems, 1999 V2: 217224 as energy source, 2004 V1: 130131
allowable rates of sewage application, 1999 V2: 237 solid waste incineration systems, 2004 V1: 130131
estimating sewage quantities, 1999 V2: 233238 solids removal in septic tanks, 1999 V2: 227228
estimating soil absorption potential, 1999 V2: 217220 solids
individual wastewater treatment plants, 1999 V2: 232 loading in ltration beds, 2000 V3: 132
inspection, 1999 V2: 238 rectangular, 2004 V1: 4
institutional and recreational establishments, 1999 V2: solids interceptors, 2000 V3: 41, 43
231232 in water, 1999 V2: 288, 2000 V3: 132
leaching trenches, 1999 V2: 220 soluble silica, 1999 V2: 283
locations, 1999 V2: 220 solute. See treated water
mound systems, 1999 V2: 226 solution sinks, 2000 V3: 35
percolation rates for soils, 1999 V2: 219220 solutions to puzzles, 2004 V1: 261
seepage beds, 1999 V2: 224225 solvents
seepage pits, 1999 V2: 225226 PEX piping and, 2003 V4: 61
selecting systems, 1999 V2: 220221 in pure-water systems, 2000 V3: 48
Soil Conservation Service, 1999 V2: 107, 114 sonic cleaners, 2000 V3: 38
soil-moisture monitors, 2000 V3: 104 sound power
soil pipes, 2004 V1: 28 dened, 2004 V1: 208
soil sewers (S, SS), 2004 V1: 8 levels, 2004 V1: 194, 208
soil vents. See stack vents sound pressure, 2004 V1: 209
soils sounds. See acoustics in plumbing systems
color, 1999 V2: 218219 sour gas, 2000 V3: 250
depth, 1999 V2: 219 source shut-off valves, 2000 V3: 71
gray-water irrigation systems and, 1999 V2: 26, 27 source water
inltration rates, 1999 V2: 96 dened, 1999 V2: 280
irrigation and, 2000 V3: 99100, 104105 pure-water systems, 1999 V2: 320
K factors of, 1999 V2: 101, 104105 sources of acoustic problems, 2004 V1: 199
maps of, 1999 V2: 218 sources of information in value engineering, 221, 2004 V1:
percolation tests, 1999 V2: 219220 214
proles, 2000 V3: 99100, 216 sources, vacuum, 1999 V2: 259261, 262, 263264
resistivity, 2004 V1: 150 Southern Building Code Congress International, Inc.
in seismic force calculations, 2004 V1: 183 (SBCCI), 1999 V2: 114, 2000 V3: 154
structure, 1999 V2: 218 sovent aerators, 1999 V2: 5456, 60, 62
swelling characteristics, 1999 V2: 219 sovent deaerators, 1999 V2: 54, 56, 60, 61, 62
swimming pool locations and, 2000 V3: 128 sovent single-stack plumbing systems
texture, 1999 V2: 218 building drain connections, 1999 V2: 6061
underground tanks and, 2000 V3: 155 components and sizing, 1999 V2: 5463
SOL (solar), 2004 V1: 16 illustrated, 1999 V2: 20
solar (SOL), dened, 2004 V1: 16 installation, 1999 V2: 62
solar azimuth (SAZ), 2004 V1: 14 introduction, 1999 V2: 19
solar energy pressure-equalizing lines, 1999 V2: 60
copper pipe, 2003 V4: 35, 36 sizing, 1999 V2: 5762
heating for swimming pools, 2000 V3: 138 venting, 1999 V2: 4647
360 ASPE Plumbing Engineering Design Handbook Volume 1
sp, SP (static pressure), 2004 V1: 15, 16 symbols for, 2004 V1: 16
sp ht, SP HT (specic heat) Specication for Copper Drainage Tube (DWV), 2003 V4:
measurements, 2004 V1: 33 35
sp ht at constant pressure (ccp, cp, CP), 2004 V1: 16 Specication for Seamless Copper Tube for Medical Gas
sp ht at constant volume (cv, cv, CV), 2004 V1: 16 Systems, 2003 V4: 35
symbols for, 2004 V1: 16 Specication for Seamless Copper Water Tube, 2003 V4: 35
sp vol, SP VOL (specic volume). See specic volume specications (spec, SPEC). See also construction contract
space heating with natural gas, 1999 V2: 174 documents; project manuals; names of specic
spacing listing agencies; titles of specic documents
around water closets, 2003 V4: 67 checklist, 2004 V1: 102
drinking fountains, 2003 V4: 14 computer production of, 2004 V1: 7172
grab bars for accessibility, 2004 V1: 121122 contents of sections, 2004 V1: 6871
lavatories, 2003 V4: 11 costs associated with, 2004 V1: 223
of leaching trenches, 1999 V2: 222 in FAST approach, 2004 V1: 230
manholes, 2000 V3: 236, 240 formats, 2004 V1: 6364
swimming pool inlets, 2000 V3: 143 introduction, 2004 V1: 61
urinals, 2003 V4: 910 MasterFormat, 2004 V1: 64
of vacuum inlets, 1999 V2: 269 MasterFormat 2004, 2004 V1: 7788
spas, 2000 V3: 107 MasterFormat Level Four (1995), 2004 V1: 76
spec, SPEC (specications). See specications MasterFormat Level One (1995), 2004 V1: 73
special sprinklers, 2004 V1: 30 MasterFormat Level Three (1995), 2004 V1: 76
special-waste drainage systems MasterFormat Level Two (1995), 2004 V1: 7375
acid-waste systems, 1999 V2: 329, 332334 methods for creating, 2004 V1: 6668
chemical-waste systems, 1999 V2: 345346 problems with reuse, 2004 V1: 63
codes and standards, 1999 V2: 327328 in project manuals, 2004 V1: 62
re-suppression water drainage, 1999 V2: 346347 questioning in value engineering, 2004 V1: 212
ammable and volatile liquids, 1999 V2: 347349 specications as incorrect term, 2004 V1: 61
future growth of systems, 1999 V2: 329 symbols for, 2004 V1: 16
general design considerations, 1999 V2: 329 Uniformat, 2004 V1: 64, 73
infectious and biological waste systems, 1999 V2: Specications for Making Buildings and Facilities Usable
343345 by the Physically Handicapped, 2004 V1: 105
introduction, 1999 V2: 327 Specications Group, 2004 V1: 65, 7788
pH values in waste, 1999 V2: 329 specimen-type water closets, 2000 V3: 35
piping and joint selection, 1999 V2: 328 Spectext, 2004 V1: 71
planning for larger systems, 1999 V2: 329 speculation in creativity, 2004 V1: 232
radioactive waste drainage and vents, 1999 V2: 337 speed of pumps, 2004 V1: 6
343 Speller, Frank N., 2004 V1: 154
references, 1999 V2: 350 Spencer Turbine Co., 1999 V2: 277
separating systems, 1999 V2: 329 spherical soil structure, 1999 V2: 218
sizing piping, 1999 V2: 328329, 329, 330, 331 spigot outlets, 1999 V2: 18
special wastes dened, 2004 V1: 28 Spill Containment Control and Countermeasure (40 CFR
system approval requirements, 1999 V2: 328 112) (SCCC), 2000 V3: 154, 165
specialty water closets, 2004 V1: 136 spill lips on weirs, 2000 V3: 109
specic conductance, 1999 V2: 287 spills
specic energy, converting to SI units, 2004 V1: 39 aboveground tank systems, 2000 V3: 167
specic functionality, dened, 2004 V1: 225 acids, 1999 V2: 332
specic gravity (SG) controlled substances, 1999 V2: 277
dened, 1999 V2: 214, 2000 V3: 154 industrial waste, 2000 V3: 90
fuel gases, 1999 V2: 212 oil, 1999 V2: 347349
natural gas, 1999 V2: 173, 185 underground liquid fuel tanks, 2000 V3: 157
plastic pipe, 2003 V4: 60 spiral wound modules
plastic pipe and, 2003 V4: 61 in cross-ow ltration, 1999 V2: 311
PVC pipe, 2003 V4: 62 in reverse osmosis (SWRO), 1999 V2: 289, 309
symbols for, 2004 V1: 16 Spitzglass formula, 2004 V1: 7, 1999 V2: 183, 210211
specic heat (sp ht, SP HT, C) splash screens for backow devices, 1999 V2: 148
measurements, 2004 V1: 33 split-case horizontal end-suction pumps, 1999 V2: 245,
sp ht at constant pressure (ccp, cp, CP), 2004 V1: 16 2000 V3: 25, 115
sp ht at constant volume (cv, cv, CV), 2004 V1: 16 split rim toilet seats, 2003 V4: 5
symbols for, 2004 V1: 16 sply., SPLY (supplies), 2004 V1: 16
specic resistance in water, 1999 V2: 285287, 2000 V3: 46 sponge rubber isolators, 2004 V1: 204
specic volume (sp vol, SP VOL, V, CVOL) sports facilities, numbers of xtures for, 2003 V4: 19
measurements, 2004 V1: 33 spout location on water fountains, 2004 V1: 109
Index 361
spray effects in fountains, 2000 V3: 108109, 119120 supports and hangers, 2000 V3: 15
spray heads on irrigation sprinklers, 2000 V3: 101102 system design, 2000 V3: 218
spray nozzle waterfall aerators, 1999 V2: 293 water demands, 1999 V2: 243244, 2000 V3: 38
spray units sprinkler systems (irrigation)
in bathtubs, 2004 V1: 118 concepts, 2000 V3: 100101
in showers, 2004 V1: 120 impact heads, 2000 V3: 102103
spring isolators lawn sprinklers, 2004 V1: 8, 1999 V2: 121
concrete bases and, 2004 V1: 205 sample information sheet, 2000 V3: 106
problems in seismic protection, 2004 V1: 188, 189 shrub heads, 2000 V3: 103
pump isolation and, 2004 V1: 205 spray heads, 2000 V3: 101102
stored energy in, 2004 V1: 166 trickle irrigation, 2000 V3: 103
spring-loaded check valves, 2000 V3: 118 spurs, 2000 V3: 234
spring-operated double-check valve devices, 1999 V2: 149 sq., SQ (squares). See squares
spring-operated pressure-regulating devices, 1999 V2: 122 square feet, 2000 V3: 29
spring supports, 2004 V1: 186 square feet EDR, 2000 V3: 178
springing pipes, 2003 V4: 25 square foot [m2] method, dened, 2004 V1: 9798
Sprinkler Irrigation, 2000 V3: 105 squares (sq., SQ)
Sprinkler Irrigation Systems, 2000 V3: 105 calculating area, 2004 V1: 3
sprinkler systems (re protection) converting to SI units, 2004 V1: 40
automatic sprinkler system types, 2004 V1: 29 symbols for, 2004 V1: 16
combined dry-pipe and pre-action, 2000 V3: 15 sr (steradians), 2004 V1: 33
concealed sprinklers, 2004 V1: 29 SS (sanitary sewers), 2004 V1: 8, 28. See also sanitary
corrosion-resistant sprinklers, 2004 V1: 29 drainage systems
dened, 2004 V1: 2837 SSD (subsoil or footing drains), 2004 V1: 8, 30
deluge systems, 2000 V3: 1315 ssf, SSF (Saybolt Seconds Furol), 2004 V1: 16, 2000 V3:
design density, 2000 V3: 15 154
drop nipples on pendent sprinklers, 2004 V1: 13 ssu, SSU (Saybolt Seconds Universal), 2004 V1: 16, 2000
dry upright sprinklers, 2004 V1: 29 V3: 154
earthquake damage to, 2004 V1: 162 ST (storm or rainwater drains). See storm-drainage
effectiveness statistics, 2000 V3: 2 systems
in elevator shafts, 2000 V3: 25 stability index (Ryzner), 1999 V2: 292
extended-coverage sidewall sprinklers, 2004 V1: 29 stabilization ponds, 1999 V2: 232
re hazard evaluation, 2000 V3: 23 stack groups, 2004 V1: 30
re pumps for, 2000 V3: 25 stack inlets in deaerators, 1999 V2: 56
reghting water drainage, 1999 V2: 346347 stack vents
ush sprinklers, 2004 V1: 29 air in, 1999 V2: 2
foam extinguishers, 2000 V3: 21 dened, 2004 V1: 30, 1999 V2: 64
fully-sprinklered spaces, 2004 V1: 12 xtures and, 1999 V2: 41, 43
gaseous re-suppression systems and, 2000 V3: 22 overview, 1999 V2: 4749
heads, 2004 V1: 13 sizing, 1999 V2: 50
history of, 2000 V3: 12 stack venting dened, 2004 V1: 30
hydraulic design, 2000 V3: 1518 vent headers, 1999 V2: 45
intermediate-level sprinklers, 2004 V1: 29 stacks. See vertical stacks
large-drop sprinklers, 2004 V1: 29 stadiums, numbers of xtures for, 2003 V4: 19
nippled-up sprinklers, 2004 V1: 13 staff areas (health-care facilities), 2000 V3: 3334
non-sprinklered spaces, 2004 V1: 12 staff lounges, 2000 V3: 32
numbers of sprinklers in operation, 2000 V3: 16 staged evaporation, 1999 V2: 298
occupancy classication, 2004 V1: 29 stages in pump equipment, 1999 V2: 245
open sprinklers, 2004 V1: 29 stain-resistance testing, 2003 V4: 2
ornamental sprinklers, 2004 V1: 29 stainless steel
partially-sprinklered spaces, 2004 V1: 12 commercial sinks, 2003 V4: 12
pendent sprinklers, 2004 V1: 13, 29 electromotive force series, 2004 V1: 144
pipe materials, 2000 V3: 12 ltration tanks, 2000 V3: 131
pre-action systems, 2000 V3: 13 xtures, 2000 V3: 33, 2003 V4: 2
quick-response sprinklers, 2004 V1: 29 fountains and, 2000 V3: 116
recessed sprinklers, 2004 V1: 29 glass pipe couplings, 2003 V4: 48
residential sprinklers, 2004 V1: 30 nickel content, 2003 V4: 2
sediment buckets in drains, 1999 V2: 12 passivation, 2004 V1: 146147
seismic protection and, 2004 V1: 183184 pump shafts, 2000 V3: 145
sidewall sprinklers, 2004 V1: 13, 30 stainless-steel drains, 1999 V2: 342, 2000 V3: 143
special sprinklers, 2004 V1: 30 stainless-steel grates, 1999 V2: 16
sprinkler types, 2004 V1: 29, 2000 V3: 815 stainless-steel piping
362 ASPE Plumbing Engineering Design Handbook Volume 1
compressed air systems, 2000 V3: 210 at atmospheric pressure (scfm). See scfm, SCFM
exposed piping on storage tanks, 2000 V3: 165 (standard cubic feet per minute)
fountains and, 2000 V3: 119 in vacuum sizing calculations, 1999 V2: 263
industrial waste pipe, 1999 V2: 341 standard gallons per hour, 2004 V1: 15
pure-water system, 2000 V3: 4748 Standard Handbook for Mechanical Engineers, 2004 V1: 1
soil and waste pipe, 1999 V2: 14 Standard Method of Test of Surface Burning
USP water, 1999 V2: 324 Characteristics of Building Materials (NFPA 255),
vacuum systems, 1999 V2: 262 2000 V3: 77
stainless-steel storage tanks, 1999 V2: 323, 2000 V3: 91 Standard on Flow Testing and Marking of Fire Hydrants
stairs and stairwells (NFPA 291), 2000 V3: 3
aboveground storage tanks, 2000 V3: 165, 166167 standard plumbing and piping symbols, 2004 V1: 713
stairwell drains, 1999 V2: 69 Standard Plumbing Code, 1999 V2: 79, 114
standpipe systems, 2000 V3: 19 Standard Practice for Making Capillary Joints by
stale sewage, 2004 V1: 30 Soldering of Copper and Copper Alloy Tube and
stall urinals, 2003 V4: 9, 10 Fittings, 2003 V4: 37
standard (std, STD), 2004 V1: 16 standard reference points (compressed air), 2000 V3: 200
standard air, 2004 V1: 18, 2000 V3: 200 Standard Specication for Concrete Sewer, Storm Drain,
standard atmospheric pressure and Culvert Pipe for Non-reinforced Concrete,
dened, 2000 V3: 200 2003 V4: 32
in vacuums, 1999 V2: 254 Standard Specication for Copper Drainage Tube (DWV),
standard cartridge depth ltration, 1999 V2: 300 2003 V4: 45
standard cfh (scfh), 1999 V2: 180 Standard Specication for Joints for Circular Concrete
standard cubic feet per minute (scfm). See scfm, SCFM Sewer and Culvert Pipe, Using Rubber Gaskets,
(standard cubic feet per minute) 2003 V4: 32
standard dimension ratio (SDR), 2003 V4: 61 Standard Specication for Liquid and Paste Fluxes for
standard re-protection symbols, 2004 V1: 1213 Soldering Applications of Copper and Copper Alloy
standard re tests, 2000 V3: 3 Tube, 2003 V4: 37
Standard for Bulk Oxygen Systems at Consumer Sites Standard Specication for Reinforced Concrete Culverts,
(NFPA 50), 2000 V3: 61, 86 Storm Drain, and Sewer Pipe, 2003 V4: 32
Standard for Color-marking of Compressed Gas Cylinders Standard Specication for Reinforced Concrete D-
Intended for Medical Use (CGA C-9), 2000 V3: 86 Load Culvert Storm Drain and Sewer Pipe for
Standard for Health Care Facilities, 2003 V4: 45 Reinforced Concrete Pipe, 2003 V4: 32
Standard for Health-care Facilities (NFPA 99), 1999 V2: Standard Specication for Seamless Copper Pipe,
262, 2000 V3: 86 Standard Sizes, 2003 V4: 34
Standard for Hypochlorites, 1999 V2: 155 Standard Specication for Seamless Copper Tube for
Standard for Liquid Chlorine, 1999 V2: 155 Medical Gas Systems, 2003 V4: 45
Standard for Portable Fire Extinguishers (NFPA 10), 2000 Standard Specication for Seamless Red Brass Standard
V3: 27, 29 Sizes, 2003 V4: 27
Standard for Public Swimming Pools (ANSI/NSPI-1), standard time meridian (STM), 2004 V1: 16
2000 V3: 125, 151 standard water closets, 2003 V4: 4
Standard for Residential, In-ground Swimming Pools standard-weight brass pipe (Schedule 40), 2003 V4: 27
(ANSI/NSPI-5), 2000 V3: 151 standard-weight steel pipe, 2003 V4: 48
Standard for Tank Vehicles for Flammable and standards. See codes and standards
Combustible Liquids (NFPA 385), 2000 V3: 154 standby losses
Standard for the Installation of Nitrous Oxide Systems at in circulating systems, 2004 V1: 127
Consumer Sites (CGA G-8.1), 2000 V3: 86 water heaters, 2004 V1: 265
Standard for the Installation of Sprinkler Systems, 2004 standpipe systems
V1: 191 classications and characteristics, 2000 V3: 1819
Standard for the Machining and Finishing of Aluminum dened, 2004 V1: 24, 30
and the Production and Handling Aluminum re pumps for, 2000 V3: 25
Products (NFPA 651), 2000 V3: 20 at land storage tanks, 1999 V2: 247
Standard for the Processing and Finishing of Aluminum overow standpipes, 2000 V3: 125
(NFPA 65), 2000 V3: 20 standpipe air chambers, 1999 V2: 132, 143
Standard for the Production, Processing, Handling and swimming pools and, 2000 V3: 139
Storage of Titanium (NFPA 481), 2000 V3: 20 symbols for, 2004 V1: 13
Standard for the Production, Processing, Handling and system classes of service, 2004 V1: 30
Storage of Zirconium (NFPA 482), 2000 V3: 20 system types, 2004 V1: 30
Standard for the Storage, Handling and Processing of starting unloaders, 2000 V3: 205
Magnesium Solids and Powders (NFPA 480), 2000 startup conditions for gas appliances, 1999 V2: 178
V3: 20 state agencies, 1999 V2: 327, 340, 2000 V3: 88
standard free air state frost lines, 2000 V3: 226
adjusting, 1999 V2: 257 state rainfall rate tables, 1999 V2: 6978
Index 363
states in creativity checklist, 2004 V1: 234 steam traps, 2000 V3: 182186
static deection for pump vibration, 2004 V1: 205 collection legs and, 2000 V3: 191
static fountain displays, 2000 V3: 111, 119 oversizing, 2000 V3: 191, 196
static head parallel trapping, 2000 V3: 196
calculating, 2004 V1: 2 pressure differentials, 2000 V3: 191
swimming pool gutters and, 2000 V3: 142 seat pressure ratings, 2000 V3: 193
velocity head and, 2004 V1: 5 strainers, 2000 V3: 195
well pumps, 1999 V2: 245 symbol, 2004 V1: 11
static pressure (SP) steam vaporizers, 2000 V3: 61
domestic water supply, 2000 V3: 217221 steatite xtures, 2003 V4: 2
re hydrants, 2000 V3: 45 steel. See also stainless steel; steel piping
irrigation ow, 2000 V3: 105 beam connections in pipe bracing, 2004 V1: 175, 176
sprinkler hydraulic calculations, 2000 V3: 16 in electromotive force series, 2004 V1: 144
symbols, 2004 V1: 15, 16 ttings, 1999 V2: 196
water mains, 2000 V3: 216 xtures, 2003 V4: 2
static pressure loss, 1999 V2: 123 oor decks in earthquakes, 2004 V1: 167
static wells, 1999 V2: 241243 in galvanic series, 2004 V1: 141
stations (medical gas and vacuum) roong drains, 1999 V2: 82
ceiling outlets, 2000 V3: 57 springs, 2004 V1: 204, 208
estimating number, 2000 V3: 50, 5152 steel substrate roong drains, 1999 V2: 82
inlets, 2000 V3: 85 storage tanks, 2000 V3: 155
medical gas diversity factors, 2000 V3: 75 underground tanks, 2000 V3: 172
medical vacuum, 2000 V3: 54 water tanks, 1999 V2: 247
order of gas outlets, 2000 V3: 56 Steel Above Ground Tanks for Flammable and Combustible
outlets, 2000 V3: 85 Liquids (UL 142), 2000 V3: 95, 154, 165
patient headwall gas systems, 2000 V3: 5657 steel xtures, 2003 V4: 2
surgical ceiling columns, 2000 V3: 5758 steel piping. See also galvanized-steel piping; stainless-
terminals, 2000 V3: 5456 steel piping
types of, 2000 V3: 58 dimensions, 2003 V4: 5155
std, STD (standard), 2004 V1: 16 ttings, 2003 V4: 48
std gph (standard gallons per hour), 2004 V1: 15 fuel-product dispensing, 2000 V3: 169
steady ow liqueed petroleum gas, 1999 V2: 196
in horizontal drains, 1999 V2: 67, 9 Manning formula and, 2000 V3: 245
roof drainage, 1999 V2: 88 natural gas, 2000 V3: 254
steady-state heat balance equations, 1999 V2: 158 radioactive wastes, 1999 V2: 341
steam and condensate systems sizing, 1999 V2: 8992
condensate drainage, 2000 V3: 189197 surface roughness, 1999 V2: 122
ashing ow and high-pressure piping, 2000 V3: types, 2003 V4: 48, 5155
196197 water systems, 1999 V2: 250
problems, 2000 V3: 189191 Steel Tank Institute (STI), 2000 V3: 154
proper drainage, 2000 V3: 191196 Steel Tanks for Oil Storage (API 250), 2000 V3: 95
distilling water from steam, 1999 V2: 295298 Steel Underground Tanks for Flammable and Combustible
geothermal, 2004 V1: 131 Liquids (UL 58), 2000 V3: 95
high-pressure steam, 2004 V1: 9 Steele, Alfred, 2004 V1: 40, 1999 V2: 114
low-pressure steam, 2004 V1: 9, 15 Stenzel, Mark H., 1999 V2: 325
medium-pressure steam, 2004 V1: 9, 15 step heaters, 2000 V3: 144
overview, 2000 V3: 175 steradians, 2004 V1: 33
references, 2000 V3: 197 sterilization
sizing pipes, 2000 V3: 177 feed water, 1999 V2: 289
steam atmospheric vents, 2004 V1: 9 infectious waste systems, 1999 V2: 345
steam tables, 2000 V3: 176 pure water systems, 1999 V2: 324
steam traps. See steam traps ultraviolet, 2000 V3: 47
system classications, 2000 V3: 175189 sterilizers, 2000 V3: 36, 38, 39
condensate return methods, 2000 V3: 186189 Stevens Institute of Technology, 1999 V2: 65
operating pressure range, 2000 V3: 175178 Stevenss Building Technology Research Laboratory, 1999
piping arrangement classications, 2000 V3: V2: 49
178186 STI (Steel Tank Institute), 2000 V3: 154
waste heat usage of condensate, 2004 V1: 131134 sticking (manual tank gauging), 2000 V3: 159
steam deaerators, 1999 V2: 294 stilling wells, 2000 V3: 124
steam-red water heaters, 2004 V1: 130 stills, 1999 V2: 295298, 2000 V3: 39, 46
steam heat exchangers, 2000 V3: 121 STM (standard time meridian), 2004 V1: 16
steam plants, 1999 V2: 147 stop levers in showers, 2004 V1: 136
364 ASPE Plumbing Engineering Design Handbook Volume 1
stop valves, 2004 V1: 30, 2000 V3: 33 STPs (sewage treatment plants), 1999 V2: 22, 24, 147
storage straight lobe compressors, 2000 V3: 202
costs, 2004 V1: 223 strain, dened, 2004 V1: 30
re hazard evaluation, 2000 V3: 2 strainers
of gray water, 1999 V2: 23, 26, 27 backow preventers, 1999 V2: 149
of medical gases basket strainers. See basket strainers
medical compressed air, 2000 V3: 6568 downspouts, 1999 V2: 81
nitrogen, 2000 V3: 68 fountain pumps, 2000 V3: 116
nitrous oxide, 2000 V3: 6465 pressure losses, 2000 V3: 224
oxygen, 2000 V3: 5963 roof drains, 1999 V2: 80, 82
of pure water, 1999 V2: 323324 sanitary drainage systems, 1999 V2: 1012
of rainwater, 1999 V2: 9394 sediment buckets, 1999 V2: 12
section in specications, 2004 V1: 70, 8990 steam traps, 2000 V3: 195
of sewage in septic tanks, 1999 V2: 228229 symbols for, 2004 V1: 10
storage plants, 1999 V2: 147, 2003 V4: 20 strata of sites, 1999 V2: 101
storage reservoirs, 2000 V3: 90 stratication in water heaters, 1999 V2: 160, 165
storage rooms, 2000 V3: 73 stray current corrosion, 2004 V1: 141, 154
storage tanks. See tanks stream-spray irrigation sprinklers, 2000 V3: 103
stores, numbers of xtures for, 2003 V4: 20 streamline ttings (avoiding suds formation), 1999 V2: 37
storm building drains. See storm-drainage systems streams, irrigation systems and, 1999 V2: 27
Storm Drainage Design and Detention using the Rational street gutters, 1999 V2: 99
Method, 1999 V2: 114 street inlets in site storm systems, 1999 V2: 98
storm drainage pipe codes, 2004 V1: 42 stress
storm-drainage systems, 2000 V3: 240248. See also conversion factors, 2004 V1: 36
rainwater and precipitation measurements, 2004 V1: 33
building drainage systems, 1999 V2: 6894 stress-accelerated corrosion, 2004 V1: 154
calculations, 2000 V3: 244245 stress corrosion, 2004 V1: 154
cast-iron soil-pipe building drains, 2003 V4: 27 stress-corrosion cracking, 2004 V1: 141, 154, 1999 V2: 290
codes, 2004 V1: 4244, 2000 V3: 240 strip-chart recorder water meters, 1999 V2: 116
controlled-ow systems, 1999 V2: 88, 9394 strip methods in pipe manufacturing, 2003 V4: 32
design criteria, 1999 V2: 6869 strong-base regeneration, 1999 V2: 302, 305
design storms, 2000 V3: 242 strongbacks, 2004 V1: 163
disposal methods, 2000 V3: 245247 strontium 90, 1999 V2: 340
drywells, 2000 V3: 247 structural angle bracing, 2004 V1: 171
existing ow paths, 2000 V3: 247 structural channel bracing, 2004 V1: 171
limited-discharge roof drains, 2000 V3: 247 structural strength
public sewers, 2000 V3: 245247 bath and shower seats, 2004 V1: 122123
recharge basins, 2000 V3: 247 grab bars, 2004 V1: 122
retention basins, 2000 V3: 247 structure-borne sound, 2004 V1: 196, 199
equations, 1999 V2: 107108 strut bracing, 2004 V1: 173, 175
forms for calculations, 1999 V2: 109113 styrofoam blocking on glass pipe, 2003 V4: 47
green roof designs, 2004 V1: 266 sub-micron cartridge ltration, 1999 V2: 300
green uses of, 2004 V1: 264 sub-sterilizing rooms, 2000 V3: 32, 36
introduction, 1999 V2: 6768 subdrains, building, 2004 V1: 20
materials, 1999 V2: 68 submain sewers, 2004 V1: 30
overview, 2000 V3: 240 submersible pumps
pipe sizing and layout, 1999 V2: 69 fountain display pumps, 2000 V3: 113
preliminary information, 2000 V3: 215216 protection of wells, 1999 V2: 243
Rational method, 2004 V1: 7, 1999 V2: 95, 98, 107, shallow wells, 1999 V2: 247
2000 V3: 242244 sizing, 2000 V3:170
reinforced concrete pipe building drains, 2003 V4: 32 underground storage tanks, 2000 V3: 164
roof drainage, 1999 V2: 7994 well pumps, 1999 V2: 245
sample utility letters, 2000 V3: 240 submittals section in specications, 2004 V1: 69, 8889
secondary drainage systems, 1999 V2: 70, 79 subsoil drainage pipe, 2004 V1: 44
site drainage, 1999 V2: 95107 subsoil drains (SSD), 2004 V1: 8, 30
sizing, 2000 V3: 244245, 246 substances, amount (moles), 2004 V1: 33
sizing ditches, 2000 V3: 247248 substituting products
storm drains (SD, ST), 2004 V1: 8 in proprietary specications, 2004 V1: 68
storm sewers dened, 2004 V1: 30 value engineering process and, 2004 V1: 211
storm water in pools and fountains, 2000 V3: 110 subsurface drainage
swimming pool water and, 2000 V3: 131, 139 determining quantities of water, 1999 V2: 100
Storm Water Retention Methods, 1999 V2: 114 lter materials, 1999 V2: 103104
Index 365
ground water disposal, 1999 V2: 105 subsurface water disposal, 1999 V2: 106
site drainage, 1999 V2: 99105 sump pits, 1999 V2: 344, 2000 V3: 111
site investigation, 1999 V2: 100 sump pumps dened, 2004 V1: 30
trenching, 1999 V2: 102103 sumps dened, 2004 V1: 30
types of piping, 1999 V2: 102 vibration isolation, 2004 V1: 208
subsurface drip irrigation systems, 1999 V2: 27 Sun, T.Y., 2004 V1: 191
subsurface obstructions, swimming pool locations and, sunlight
2000 V3: 128 protecting against, 1999 V2: 19, 2000 V3: 116, 165
subsurface waste-disposal systems. See soil-absorption solar energy. See solar energy
sewage systems SUP (supplies), 2004 V1: 16
subsurface water. See ground water superchlorination, 2000 V3: 147, 148, 149
SUC (suction), 2004 V1: 16 supercritical ow, 1999 V2: 67. See also hydraulic jumps in
successive leaching trenches, 1999 V2: 223224 ow
suct., SUCT (suction), 2004 V1: 16 Superfund Amendment and Reauthorization Act of 1986
suction (suct., SUCT, SUC), 2004 V1: 16 (SARA Title III), 2000 V3:88, 2000 V3: 154
suction basket strainers, 2000 V3: 115 superstrut bracing, 2004 V1: 170
suction diffusers, 2000 V3: 116 supervised heat-up, 2000 V3: 191, 194
suction fuel-delivery systems, 2000 V3: 162163 supervisory (tamper) switches, 2004 V1: 30
suction inlets supplementary conditions, 2004 V1: 62
in fountains, 2000 V3: 117 supplementary units of measurement, 2004 V1: 33
in storage tanks, 1999 V2: 248 supplies (sply., SPLY, SUP)
suction piping, 2004 V1: 202, 1999 V2: 248, 249, 2000 V3: abbreviations, 2004 V1: 16
117 ongoing and one-time costs, 2004 V1: 223
suction sand lters, 2000 V3: 134 supply air (sa, SA), 2004 V1: 16
suction screens, 2000 V3: 116 supply xture units, 2004 V1: 24
suction-type pumps, 1999 V2: 241, 245 supply valves, 2000 V3: 179
suds support mats in ltration, 2000 V3: 134
factors in trap seal loss, 1999 V2: 36 supports and hangers
pressure zones, 1999 V2: 37, 38, 39 alternate attachment to hangers, 2004 V1: 174
relief vents, 1999 V2: 37, 39 clean agent gas pipes, 2000 V3: 24
sovent single-stack plumbing systems and, 1999 V2: 54 codes, 2004 V1: 43
venting, 1999 V2: 3637, 39 dened, 2004 V1: 30
sulfate-reducing bacteria, 1999 V2: 282 hanger rod connections in bracing, 2004 V1: 17l
sulfates, 1999 V2: 281, 283, 302 hanger rod gravity forces in earthquakes, 2004 V1: 186
suldes, 2004 V1: 146 installation productivity rates, 2004 V1: 96
sultes, 1999 V2: 281, 315, 2000 V3: 147 isolation hangers, 2004 V1: 203
sulfur, 1999 V2: 281 materials, 2004 V1: 43
sulfur-based joint compound, 1999 V2: 223 medical gas piping, 2000 V3: 73
sulfur dioxide, 2000 V3: 93 natural gas pipes, 1999 V2: 176
sulfuric acid resilient pipe hangers, 2004 V1: 199
pool chemicals, 2000 V3: 150 roof drainage, 1999 V2: 88
in regeneration, 1999 V2: 305 in sanitary drainage systems, 1999 V2: 14
special wastes, 1999 V2: 332333 sprinkler systems, 2000 V3: 15
storage tanks, 2000 V3: 9192 symbols for, 2004 V1: 13
in water chemistry, 1999 V2: 281 vacuum cleaning tubing, 1999 V2: 269
sulfurous acid, 1999 V2: 281 SUR (surfaces), 2004 V1: 16
SUM (summary, summation), 2004 V1: 16 SURD (surfaces, dry), 2004 V1: 16
summary section in specications, 2004 V1: 69, 88 surface abrasions
summary, summation (SUM), 2004 V1: 16 corrosion and, 2004 V1: 146
sumps and sump pumps grab bars, 2004 V1: 122
acoustic problems, 2004 V1: 197 surface efciency (SEFF), 2004 V1: 14
containment sumps, 2000 V3: 156 surface evaporation, 2000 V3: 121
duplex sump pump systems, 1999 V2: 9 surface fault slips, 2004 V1: 158
xture-unit values, 1999 V2: 9 surface res, 2000 V3: 19
exible pipe connectors, 2000 V3: 169 surface-mounted pumps, 1999 V2: 245
oor drains and, 1999 V2: 10 surface runoff. See runoff
ground water disposal, 1999 V2: 105 surface skimmers. See skimmers
liquid-waste decontamination systems, 1999 V2: 344 surface-type sprinkler spray heads, 2000 V3: 101
pool mechanical spaces, 2000 V3: 111 surface water
roof drainage and, 1999 V2: 79, 80, 88 as feed water for pure water systems, 1999 V2: 321
sanitary drainage systems, 1999 V2: 9 dened, 1999 V2: 282
storm drains and, 1999 V2: 69 discharge permits for, 2000 V3: 89
366 ASPE Plumbing Engineering Design Handbook Volume 1
private water systems, 1999 V2: 239 ow indicators, 2000 V3: 142
pumps for, 1999 V2: 245 gutters, 2000 V3: 142
Surface Water Treatment Rule, 1999 V2: 316 heaters, 2000 V3: 144145
surfaces (SUR, S) ladders, 2000 V3: 145
dry (SURD), 2004 V1: 16 main drains, 2000 V3: 143
xture materials, 2003 V4: 1 piping, 2000 V3: 145
symbols for, 2004 V1: 16 pumps, 2000 V3: 140142
wet (SURW), 2004 V1: 16 skimmers, 2000 V3: 142, 146
surge chambers, 2000 V3: 142, 143, 212 surge chambers, 2000 V3: 143
surge loads in wet-vented systems, 1999 V2: 4546 underwater lights, 2000 V3: 145
surge pits, 2000 V3: 108, 109 vacuum cleaning lines, 2000 V3: 144
surge pressure. See water hammer valves and pumps, 2000 V3: 145146
surge tanks, 1999 V2: 27, 2000 V3: 137, 140 water heaters, 2000 V3: 138139, 146
surges water supply and drainage, 2000 V3: 131
in horizontal drains, 1999 V2: 5 dened, 2004 V1: 30
pressure surges, 1999 V2: 35 design parameters, 2000 V3: 127130
swimming pool pumps, 2000 V3: 139 bathhouses, toilets, and showers, 2000 V3: 130
vacuum surges, 1999 V2: 35 location, 2000 V3: 128
surgical ceiling columns, 2000 V3: 5758 physical characteristics, 2000 V3: 128130
surgical clean-up areas, 2000 V3: 32 size and capacity, 2000 V3: 127128
surgical gas track systems, 2000 V3: 5859 disinfection, 2000 V3: 148151
surgical instruments, 2000 V3: 59, 68 algaecides, 2000 V3: 150
surgical scrub areas, 2000 V3: 32 aluminum sulfate, 2000 V3: 149150
surgical supply areas, 2000 V3: 32 breakdown chlorination, 2000 V3: 149
surgical vacuum (SV), 2004 V1: 9 calcium hypochlorite, 2000 V3: 148149
surveys in plumbing cost estimation, 2004 V1: 93 chemical feeding equipment, 2000 V3: 150151
SURW (surfaces, wet), 2004 V1: 16 chlorine gas, 2000 V3: 148
suspended equipment cleaning lters, 2000 V3: 150
xed suspended equipment, 2004 V1: 164 cyanurates, 2000 V3: 149
vibration-isolated, suspended equipment, 2004 V1: 166 ltration turnover rates, 2000 V3: 140
suspended metals in wastes, 2000 V3: 93 sodium hypochlorite, 2000 V3: 149
suspended piping, earthquake recommendations, 2004 V1: sulfuric acid, 2000 V3: 150
162 superchlorination, 2000 V3: 149
suspended solids grate materials, 1999 V2: 15
dened, 1999 V2: 280 heat loss retardants, 2000 V3: 150
ltration, 1999 V2: 298 indoor and outdoor pools, 2000 V3: 139
removing, 1999 V2: 294 numbers of xtures for, 2003 V4: 19
total suspended solids, 1999 V2: 287288 numbers of swimmers, 2000 V3: 127128
turbidity, 1999 V2: 282 overview, 2000 V3: 127
suspended tanks, 2004 V1: 162 references, 2000 V3: 151
suspension, dened, 1999 V2: 280 resources, 2000 V3: 151
sustainable design, 2004 V1: 263267 sequestering agents, 2000 V3: 150
Sustainable Sites design (LEED), 2004 V1: 263 water chemistry, 2000 V3: 146148
SV (service) cast-iron soil pipe, 2003 V4: 27, 3031 mineral deposits, 2000 V3: 147148
SV (surgical vacuum), 2004 V1: 9 pH values, 2000 V3: 147
swamp gas, 1999 V2: 284 water supply, 2000 V3: 131
sway bracing Swimming Pools: A Guide to their Design and Operations,
acceptable types, 2004 V1: 187 2000 V3: 151
horizontal loads for, 2004 V1: 185186 swing check valves, 1999 V2: 249, 2000 V3: 118
lateral and longitudinal, 2004 V1: 181182, 185186 switch-gear rooms, 2000 V3: 73
longitudinal and transverse, 2004 V1: 179, 180 SWRO (spiral wound modules), 1999 V2: 289, 309
potential problems, illustrated, 2004 V1: 189 SYGEF piping, 2000 V3: 48
sway in piping, 2004 V1: 162 symbols
swelling characteristics of soils, 1999 V2: 219 re protection, 2004 V1: 1213
swimming pools references, 2004 V1: 40
applying standards to reecting pools, 2000 V3: 107 standardized plumbing and piping symbols, 2004 V1:
components and materials 713
backwash pits, 2000 V3: 143 Synthesis phase in value engineering, 2004 V1: 213
cleaning equipment, 2000 V3: 146 synthetic ber gas lters, 2000 V3: 250
ltration systems, 2000 V3: 131137, 139140, synthetic resins, 1999 V2: 302
143144 SYS (systems), 2004 V1: 16, 137
ttings, 2000 V3: 137, 144, 145 system descriptions in specications, 2004 V1: 69, 88
Index 367
system performance criteria in specications, 2004 V1: 69, gravity tank systems, 1999 V2: 150152
88 hazardous waste incompatibilities, 2000 V3: 90, 91
Systeme International and dUnites, 2004 V1: 32 holding tanks
systems (SYS) for reghting drainage, 1999 V2: 347
dened, 2004 V1: 137 for radioactive wastes, 1999 V2: 342
diagramming, 2004 V1: 231 hydropneumatic-tank systems, 1999 V2: 150
symbols for, 2004 V1: 16 kill tanks, 1999 V2: 344345
value engineering questions, 2004 V1: 213214 liqueed natural gas tanks, 1999 V2: 194
liquid fuel tanks
T connections and access, 2000 V3: 156157
construction, 2000 V3: 156
t (metric tons), 2004 V1: 34
T STAT (thermostats), 2004 V1: 16 lling and spills, 2000 V3: 156157
t, TD (temperature differences), 2004 V1: 16, 136 installation, 2000 V3:172
T (temperature). See temperature materials, 2000 V3: 155156
T (tera) prex, 2004 V1: 34 overll prevention, 2000 V3: 158
T (teslas), 2004 V1: 33 venting, 2000 V3: 157158
T (time). See time protection, 2000 V3:169
T-Y ttings, 1999 V2: 61 settling tanks, 2000 V3: 93
tab, TAB (tabulation), 2004 V1: 16 storage tanks dened, 2000 V3: 153
table salt, 2000 V3: 150 suspended, 2004 V1: 164
tablespoons, converting to SI units, 2004 V1: 40 tank end deection, 2000 V3: 172
tabular take-off sheets, in cost estimations, 2004 V1: 94 tank farms, 2004 V1: 150
tabulation (tab, TAB), 2004 V1: 16 thermal expansion tanks, 1999 V2: 167
take-off estimating method, cost estimating, 2004 V1: tightness testing, 2000 V3: 161162, 171, 2000 V3:172,
9495 2000 V3: 172
Take the Guesswork out of Demineralizer Design, 1999 V2: underground tanks, 2000 V3: 9091
325 illustrated, 2000 V3: 164
tamper switches, 2004 V1: 30 liquid fuel tanks, 2000 V3: 155158
tamping ll venting, 2000 V3: 157158, 166, 2000 V3:167
leaching trenches, 1999 V2: 223 vibration isolation, 2004 V1: 205
sewers, 1999 V2: 16 water storage tanks, 1999 V2: 239, 323324, 2000 V3:
subsurface drainage pipes, 1999 V2: 102, 103 44
water pipes, 1999 V2: 250 tannin in water, 2000 V3: 147
Tanaka, T., 1999 V2: 325 tapping illegally into water lines, 1999 V2: 115
tangential-ow ltration, 1999 V2: 300, 308 tappings for cast iron radiators, 2000 V3: 179
tank-mounted product dispensers, 2000 V3: 168 taps
tank-relling acoustics, 2004 V1: 194 large wet tap excavations, 2000 V3: 222
tank-type water closets, 2004 V1: 135136 pressure loss and, 2000 V3: 221
tank-type water heaters, 2004 V1: 129 target areas in water closets, 2003 V4: 4
tankless water heaters, 2004 V1: 129130 taste of drinking water, 1999 V2: 245, 316
tanks. See also septic tanks TAU (transmissivity), 2004 V1: 16
aboveground tanks, 2000 V3: 9091, 165169 taverns and bars, numbers of xtures for, 2003 V4: 19, 22
connections and access, 2000 V3: 166 taxes
construction, 2000 V3: 165 in labor costs, 2004 V1: 94
corrosion protection, 2000 V3: 165 in plumbing cost estimation, 2004 V1: 94
lling and spills, 2000 V3: 166167 tc, TC (thermocouple), 2004 V1: 16
leak prevention and monitoring, 2000 V3:167168 Tchobanoglous, George, 2000 V3: 125
materials, 2000 V3: 165 TCPL (thermocouple), 2004 V1: 16
overll prevention, 2000 V3:167 TD (temperature differences), 2004 V1: 16, 136
product dispensing systems, 2000 V3:168 TD (turndown ratio), 1999 V2: 182
tank protection, 2000 V3:169 TDIF (temperature differences), 2004 V1: 16
vapor recovery, 2000 V3:168 TDS (total dissolved solids), 1999 V2: 288, 316
venting, 2000 V3:167 TE (temperature entering), 2004 V1: 16
carbon dioxide extinguishing systems, 2000 V3: 20, 21 teaspoons, converting to SI units, 2004 V1: 40
cryogenic, 2000 V3: 62 technetium 99, 1999 V2: 340
determining demand and capacity, 1999 V2: 151 technology advances, value engineering and, 2004 V1: 212
distilled water systems, 2000 V3: 46 Technology for the Storage of Hazardous Liquids, 2000 V3:
drinking water storage, 1999 V2: 247248 96
earthquake damage, 2004 V1: 161, 162 tectonic plates, 2004 V1: 156158
earthquake protection, 2004 V1: 163164, 188, 189 tee-wyes, ow capacity and, 1999 V2: 4
re-protection supplies, 2000 V3: 226 tees (TEE), 2004 V1: 10, 16
gauges, 2000 V3: 166 Teon, 1999 V2: 341, 2000 V3: 42
368 ASPE Plumbing Engineering Design Handbook Volume 1
temp., TEMP (temperatures). See temperature tempered hot water recirculating (TEMP. HWR, TWR),
TEMP. HW (tempered hot water), 2004 V1: 8 2004 V1: 8
TEMP. HWR (tempered hot water recirculating), 2004 V1: tennis courts, numbers of xtures for, 2003 V4: 19
8 tensile strength
temperature (temp., TEMP, T) plastic pipe, 2003 V4: 60
acid wastes, 2000 V3: 40 PVC pipe and, 2003 V4: 62
bathtub water notes, 2004 V1: 119 Tension 360 bracing, 2004 V1: 169
cast iron radiators, 2000 V3: 180 tension problems in seismic protection, 2004 V1: 190
compressed air systems and, 2000 V3: 211 TENT (temperature entering), 2004 V1: 16
conversion factors, 2004 V1: 37, 38 Tentative Provisions for the Development of Seismic
cooling air compressors, 2000 V3: 202 Regulations for Buildings, 2004 V1: 183, 191
corrosion rates and, 2004 V1: 145 tera prex, 2004 V1: 34
CPVC vs. PVC piping, 2003 V4: 62 terminal elements, dened, 2004 V1: 137
deaeration water temperatures, 1999 V2: 294 terminal length, dened, 1999 V2: 1
dew points, 2000 V3: 201 terminal velocity
feed water temperature and deposits, 1999 V2: 291, dened, 1999 V2: 1
312, 321322 stack capacities and, 1999 V2: 4
ue gas temperatures, 1999 V2: 178 stack terminal velocity, 2004 V1: 3
high-temperature withstand for hot-water systems, terminal vents. See vent stack terminals
1999 V2: 166 terminals, passenger, 2003 V4: 19
hot-water properties, 1999 V2: 168 termites, 2000 V3: 116
hot-water relief valves, 1999 V2: 166167 tertiary treatment of gray water, 1999 V2: 28, 29
hot-water temperatures, 1999 V2: 159, 161165, 165, teslas, 2004 V1: 33
2000 V3: 36, 45 test block conditions in gas boosters, 1999 V2: 182
maintenance hot-water temperatures, 1999 V2: 166 test ttings, 2000 V3: 195
measurements, 2004 V1: 33 test headers, 2004 V1: 12
microbial control in water, 1999 V2: 312 test-method standards, 2004 V1: 66
mixed-water temperatures, 1999 V2: 159160 test station cathodic protection, 2004 V1:151
natural gas, 1999 V2: 179, 180 testing
non-SI units, 2004 V1: 34 acoustic ratings of xtures and appliances, 2004 V1:
operating hot-water temperatures, 1999 V2: 166 194195
pipe expansion and contraction, 2004 V1: 3 cold-water systems, 1999 V2: 154
PVC pipe and, 2003 V4: 62 fountain piping systems, 2000 V3: 117
rate of rise detection, 2000 V3: 13 gaseous re-suppression systems, 2000 V3: 2425
scalding water, 1999 V2: 169170 hot-water relief valves, 1999 V2: 166
shower compartments, 2004 V1: 120, 2003 V4: 15 hydrants, 2000 V3: 4
special-waste efuent, 1999 V2: 328 hydraulic soil conditions, 1999 V2: 217220
specic resistance and, 1999 V2: 286 liqueed petroleum gas systems, 1999 V2: 197
sprinkler head ratings, 2000 V3: 17 liquid fuel systems, 2000 V3:170172
storage tanks and piping, 2000 V3: 172 medical-gas alarms, 2000 V3: 81
stratication, 2000 V3: 172 medical-gas systems, 2000 V3: 7783
swimming pools, 2000 V3: 139 natural gas services, 2000 V3: 252, 253
symbols for, 2004 V1: 16 percolation rates for soils, 1999 V2: 219220
temperature differences (TD, )t, TDIF), 2004 V1: 16, pipes for radioactive waste systems, 1999 V2: 342
136 plastic xtures, 2003 V4: 2
temperature differentials, 2004 V1: 125126 swimming pools, 2000 V3: 131
temperature entering (TE, TENT), 2004 V1: 16 tank tightness testing, 2000 V3: 161162, 171, 2000
temperature leaving (TL, TLEA), 2004 V1: 16 V3:172, 2000 V3: 172
temperature stratication, 2000 V3: 172 urinal tests, 2003 V4: 9
thermal support systems and earthquakes, 2004 V1: water closet ushing, 2003 V4: 56
168 welders for radioactive pipe systems, 1999 V2: 342
water heaters, 1999 V2: 157, 160 wells, 1999 V2: 243
water vapor in air and, 2000 V3: 200201 tetrauoroethylene (TFE), 2003 V4: 48
Temperature Limits in Service Hot Water Systems, 1999 text, abbreviations in, 2004 V1: 1416
V2: 170 texture of soils, 1999 V2: 218
temperature-pressure-relief valves (TPV), 2004 V1: 10, theaters
1999 V2: 166, 167 numbers of xtures for, 2003 V4: 19, 21
temperature stratication, 2000 V3: 172 vacuum calculations for, 1999 V2: 269
tempered water theft of backow preventers, 1999 V2: 149
dened, 2004 V1: 30 theoretical barometric pressure, 2000 V3: 200
tempered hot water (TEMP. HW, TW), 2004 V1: 8 theoretical standard atmospheric pressure, 2000 V3: 200
therapy pools, 2000 V3: 128
Index 369
therm, converting to SI units, 2004 V1: 40 tiles in leaching trenches, 1999 V2: 221
thermal conductivity (k, K) time (T)
measurements, 2004 V1: 33 clean agent gas re suppression, 2000 V3: 23
plastic pipe, 2003 V4: 60 of concentration in runoff, 1999 V2: 97, 2000 V3: 244
symbols for, 2004 V1: 16 in creativity checklist, 2004 V1: 234
thermal efciency intervals in hydraulic shock, 2004 V1: 6
dened, 2004 V1: 30, 136 in measurements, 2004 V1: 33
water heaters and, 1999 V2: 169 non-SI units, 2004 V1: 34
thermal expansion symbols for, 2004 V1: 16
converting to SI units, 2004 V1: 39 time in pipes, 2000 V3: 244
hot-water systems and, 1999 V2: 167168 time-temperature curves in re tests, 2000 V3: 3
plastic pipe thermal expansion, 1999 V2: 251 time delays
sanitary drainage systems, 1999 V2: 18 clean gas extinguishing systems, 2000 V3: 24
thermal expansion coefcients (TXPC), 2004 V1: 16 fountain relays, 2000 V3: 120121
thermal expansion tanks, 1999 V2: 167 time history
water pipes and, 1999 V2: 251252 computer analysis, 2004 V1: 186
thermal expansion loops, 2004 V1: 162 earthquakes, 2004 V1: 159, 160
thermal-hydraulic irrigation valves, 2000 V3: 103 time switches for fountains, 2000 V3: 121
thermal insulation thickness, 2004 V1: 127 tin
thermal movement, sound insulation and, 2004 V1: 193 corrosion, 2004 V1: 139
thermal resistance (R, R, RES), 2004 V1: 16 galvanic series, 2004 V1: 141
thermal-shock protection, 2004 V1: 120 piping, 1999 V2: 122
thermal stability for hot-water systems, 1999 V2: 166 tin-lined copper pipes, 2000 V3: 47
thermal-support systems, earthquakes and, 2004 V1: 168 tipping prevention, 2004 V1: 189
thermocompression distillation, 1999 V2: 295298 tissue-culture rooms, 2000 V3: 45
thermocouple (tc, TC, TCPL), 2004 V1: 16 titanium, 2004 V1: 141, 144, 2000 V3: 20
thermodisc traps, 2000 V3: 182, 186 TL (temperature leaving), 2004 V1: 16
thermodynamic steam traps, 2000 V3: 182, 194 TLEA (temperature leaving), 2004 V1: 16
thermometers, 2004 V1: 10 TOC (total organic carbon), 1999 V2: 288
thermoplastic pipes, 2003 V4: 58 toe clearance in toilet compartments, 2004 V1: 113, 114
thermoset plastic, 2000 V3: 155, 2003 V4: 58 toilet compartments. See water-closet compartments
thermostatic bellows, 2000 V3: 182 toilet paper
thermostatic-mixing shower valves, 2003 V4: 15, 18 dispensers, 2004 V1: 114
thermostatic-mixing tub valves, 2003 V4: 16 in septic tanks, 1999 V2: 231
thermostatic radiator vents, 2000 V3: 179 toilets. See also water closets
thermostatic steam traps, 2000 V3: 182, 186, 194, 196 composting, 2004 V1: 265
thermostats (T STAT), 2004 V1: 16 incinerating, 2004 V1: 265
thickness (thkns, THKNS, THK) tolerance, 2004 V1: 32
of soils, 1999 V2: 219 tons (TON)
symbols for, 2004 V1: 16 converting to SI units, 2004 V1: 40
Thickness Design, 2003 V4: 32 symbols for, 2004 V1: 16
thinking outside the box, 2004 V1: 232 tons of refrigeration (tons, TONS), 2004 V1: 16
THK (thickness), 2004 V1: 16, 1999 V2: 219 tools
thkns, THKNS (thickness), 2004 V1: 16, 1999 V2: 219 tool access in cleanouts, 1999 V2: 9
thousand circular mils (Mcm, MCM), 2004 V1: 16 for vacuum cleaning systems, 1999 V2: 269270
thousand cubic feet (Mcf, MCF), 2004 V1: 16 top coats, 2004 V1: 147
thousand foot-pounds (kip ft, KIP FT, KIPFT), 2004 V1: top-entry ttings in sovent systems, 1999 V2: 62
16 top-spud water closets, 2003 V4: 3, 8
thousand pounds (kip, KIP), 2004 V1: 16 torch testing, 2003 V4: 2
threaded end connections, 2004 V1: 23 Toro Company, 2000 V3: 105
threaded joints, 2004 V1: 167 torque
threaded outlets, 1999 V2: 18 conversion factors, 2004 V1: 35
three-compartment sinks, 2003 V4: 11, 12 converting to SI units, 2004 V1: 39
thresholds in shower compartments, 2004 V1: 120 measurements, 2004 V1: 33
throttling damper devices, 2000 V3: 144 torrs, 1999 V2: 254
throttling valves, 2000 V3: 118, 140, 144 TOT HT (total heat), 2004 V1: 16
thrust bearings, 2004 V1: 196 total (TOT), 2004 V1: 16
thrust blocks, 1999 V2: 250251, 2000 V3: 231 total alkalinity, 1999 V2: 283
tie-in tests, 2000 V3: 82 total connected loads, 2000 V3: 50, 249, 253
tie rods, 2000 V3: 229 total costs
tight piping systems, 2004 V1: 168 dened, 2004 V1: 222
tightness testing, 2000 V3: 161162, 171, 172 generalized, 2004 V1: 223
370 ASPE Plumbing Engineering Design Handbook Volume 1
total dissolved solids (TDS), 1999 V2: 288, 316, 2000 V3: trapeziums, calculating area, 2004 V1: 4
123 trapezoids, calculating area, 2004 V1: 4
total dynamic head, 1999 V2: 245 traps. See also trap seals
total ooding systems building traps, dened, 2004 V1: 19
carbon dioxide systems, 2000 V3: 20 condensate traps, 2000 V3: 193195, 195, 196
dened, 2004 V1: 26 dened, 2004 V1: 31
dry-chemical extinguishing systems, 2000 V3: 19 eliminating siphonage with vents, 1999 V2: 35
total head, 1999 V2: 245 xture traps and vents, 1999 V2: 40
total heat (tot ht, TOT HT), 2004 V1: 16 piping arrangement steam classications, 2000 V3:
total organic carbon (TOC), 1999 V2: 288 182186
total pumping head, 1999 V2: 245 roof drains, 1999 V2: 84
total suspended solids, 1999 V2: 287288 sink traps, 2000 V3: 42
total work force in vacuum systems, 1999 V2: 259 special-waste drainage systems, 1999 V2: 328
towers in standpipe systems, 2000 V3: 19 steam traps, 2000 V3: 180182
T&P valves (temperature and pressure relief), 1999 V2: unvented traps, 1999 V2: 46
166, 167 urinals, 2003 V4: 9
TPV (temperature-pressure-relief valves), 2004 V1: 10, vents and, 1999 V2: 36
1999 V2: 166, 167 TRC (tubular modules in reverse osmosis), 1999 V2: 309,
trace elements in water, 1999 V2: 283284 310
Trace Level Analysis of High Purity Water, 1999 V2: 325 treated water. See also water treatment
tractor-type grates, 1999 V2: 11 dened, 1999 V2: 280
trafc loads from reverse osmosis, 1999 V2: 309
automotive trafc and grates, 1999 V2: 11 systems. See gray-water systems
cleanouts and, 1999 V2: 9 Treating Cooling Water, 1999 V2: 325
grates and strainers, 1999 V2: 10 treatment of black water, 1999 V2: 28, 227, 232233
trailer parks treatment of gray water, 1999 V2: 22, 23, 2729, 28
septic tank systems for, 1999 V2: 231232 treatment of oil in water, 1999 V2: 347349
sewers, 2004 V1: 30 Treatment of Organic Chemical Manufacturing
transfer-type showers, 2004 V1: 121 Wastewater for Reuse (EPA 600), 2000 V3: 96
transferring hazardous wastes, 2000 V3: 90 treatment rooms
transition ttings, 2000 V3: 252 xtures, 2000 V3: 35
transmissibility, coefcient of (Q factor), 1999 V2: 101 health-care facilities, 2000 V3: 32
transmission loss (sound), 2004 V1: 209 medical gas stations, 2000 V3: 51
transmission of noise, 2004 V1: 199 medical vacuum, 2000 V3: 54
transmissivity (TAU), 2004 V1: 16 water demand, 2000 V3: 45
transport trucks, 2000 V3: 61 tree piping systems, 2000 V3: 16
Transportation Department. See U.S. Department of tree-root problems in leaching trenches, 1999 V2: 222
Transportation trench drains
transportation gas services, 2000 V3: 249 in chemical plants, 1999 V2: 346
transverse bracing, 2004 V1: 167, 171, 191 dened, 2003 V4: 17
transverse sway bracing, 2004 V1: 179 trenches. See also leaching trenches
trap arms absorption trenches, 1999 V2: 220
dened, 1999 V2: 64 labor productivity rates, 2004 V1: 9597
xture vents and, 1999 V2: 38, 39 near water pipes, 1999 V2: 250
length of, 1999 V2: 50 sanitary sewer services, 2000 V3: 234, 235
trap primers, 1999 V2: 1314 storage tank piping, 2000 V3: 172
trap seals in subsurface drainage, 1999 V2: 102103
controlling induced siphonage, 1999 V2: 40 Tri-Services Manual, 2004 V1: 183
dened, 2004 V1: 31, 1999 V2: 64 triage rooms, 2000 V3: 35
factors in trap seal loss, 1999 V2: 36 triangles
oor drains, 1999 V2: 10, 2003 V4: 17 calculating area, 2004 V1: 45
maintaining, 1999 V2: 14 exercise, 2004 V1: 232, 261
primer devices, 2003 V4: 17 rule for sink location, 2003 V4: 12
reduced-size venting and, 1999 V2: 49 tributary areas for runoff, 1999 V2: 97
reducing trap seal losses, 1999 V2: 3940 trichloroethylene, 2000 V3: 70
stack venting and, 1999 V2: 47 trickle irrigation, 2000 V3: 103
tests, 2003 V4: 5 trickling lters, 2000 V3: 95
trap siphonage and, 1999 V2: 35 triggering clean agent gas re suppression, 2000 V3: 24
vents and, 1999 V2: 36 trihalomethanes, 1999 V2: 311
trapeze triplex air compressors, 2000 V3: 213
bracing pipes on trapeze, 2004 V1: 175, 178 triplex vacuum pump arrangements, 1999 V2: 263
potential problems in bracing, 2004 V1: 189 trisodium phosphate, 1999 V2: 13
Index 371
TROs (tubular modules in reverse osmosis), 1999 V2: 309, Type B gas vents, 1999 V2: 213
310 Type B gray-water systems, 1999 V2: 3132
troughs for waterfalls, 2000 V3: 109 Type B vent codes, 2004 V1: 43
truss-type bracing, 2004 V1: 190 Type B-W gas vents, 1999 V2: 213
tsunamis, 2004 V1: 158 Type DWV pipes, 2003 V4: 36, 45
tub llers, 2003 V4: 16 Type G copper, 2003 V4: 36
tube ozone units, 1999 V2: 313 Type K copper
tube washers, 2000 V3: 37 copper water tube, 2003 V4: 37
tuberculation, 2004 V1: 154 dimensions and capacity, 2003 V4: 3940
tubing fuel-gas piping, 1999 V2: 196
joints, 1999 V2: 196 lengths, standards, and applications, 2003 V4: 35
liqueed petroleum gas, 1999 V2: 196 medical gas tube, 2000 V3: 77, 2003 V4: 45
vacuum cleaning hose capacity, 1999 V2: 270 Type L copper
vacuum cleaning systems, 1999 V2: 269270 cast in columns, 1999 V2: 68
tubular-bag separators, 1999 V2: 268 copper water tube, 2003 V4: 37
tubular modules in reverse osmosis, 1999 V2: 309, 310 dimensions and capacity, 2003 V4: 4142
tunnel chases for swimming pool piping, 2000 V3: 144 fountains, 2000 V3: 119
turbidity lengths, standards, and applications, 2003 V4: 35
clarication of, 1999 V2: 294 medical gas tube, 1999 V2: 196, 2000 V3: 77, 2003 V4:
dened, 1999 V2: 282 45
drinking water, 1999 V2: 316 natural gas, 2000 V3: 254
measuring, 1999 V2: 287288 pool water heating and, 2000 V3: 122
removing, 1999 V2: 244 sizing, 1999 V2: 133
turbine pumps, 1999 V2: 246, 247 Type L gas vents, 1999 V2: 214
turbine water meters, 1999 V2: 115, 116, 117 Type L vent codes, 2004 V1: 43
turbo pumps, 1999 V2: 259 Type M copper
turbo-surgical instruments, 2000 V3: 59 copper water tube, 2003 V4: 37
turbulence dimensions and capacity, 2003 V4: 4344
dened, 2004 V1: 31 lengths, standards, and applications, 2003 V4: 35
measurements, 1999 V2: 41 Type OXY/ACR pipes, 2003 V4: 36
in rate of corrosion, 2004 V1: 145 Type OXY, MED pipes, 2003 V4: 36
turbulent ow in pipes, 2004 V1: 2 Type OXY/MED pipes, 2003 V4: 36
turf imperviousness factors, 2000 V3: 243
turndown ratio (TD), 1999 V2: 182
turnover rates
U
U-factor (U), 2004 V1: 16
gutters and, 2000 V3: 142 U, U (heat transfer coefcients), 2004 V1: 15
swimming pools, 2000 V3: 140 UF membranes, 1999 V2: 284
turrets, gas, 1999 V2: 177 UFAS (Uniform Federal Accessibility Standard), 2004 V1:
TW (tempered hot water), 2004 V1: 8 105106
twin-agent dry-chemical systems, 2000 V3: 20 UFC (Uniform Fire Code), 2000 V3: 154
twin-tower air dryers, 2000 V3: 207 Uhlig, Herbert H., 2004 V1: 154
two. See also entries beginning with double-, dual-, or UL listings
multiple- address, 2004 V1: 59
two-bed deionizing units, 2000 V3: 46 gas booster components, 1999 V2: 179
two-compartment septic tanks, 1999 V2: 229 hot-water components, 1999 V2: 166, 170
two-compartment sinks, 2003 V4: 11, 12 list of standards, 2004 V1: 57
two-family dwellings, numbers of xtures for, 2003 V4: 20 pipe hangers, 2000 V3: 15
two-pipe steam systems, 2000 V3: 178, 180182, 185, ULF. See ultra-low-ow water closets
186187 ultra-high vacuum, 1999 V2: 254
two-pipe venturi suction pumps, 1999 V2: 241 ultra-low-ow xture green building credits, 2004 V1: 264
two-point vapor recovery, 2000 V3: 163 ultra-low-ow water closets
two-stage reduction, 1999 V2: 153 operation, 2004 V1: 135136
two-step deionization (dual-bed), 1999 V2: 302, 303 reduced-size venting and, 1999 V2: 19
two-valve parallel pressure-regulated valves, 1999 V2: 153 water usage rates, 2004 V1: 134135
two-word expressions of functions, 2004 V1: 225, 231 ultra-pure water systems, 1999 V2: 317
TWR (tempered hot water recirculating), 2004 V1: 8 ultralters and ultraltration
TXPC (thermal expansion coefcients), 2004 V1: 16 cross-ow ltration, 1999 V2: 300, 310311
Type 1 air compressors, 2000 V3: 65, 67 membrane lters, 1999 V2: 308311
Type 2 air compressors, 2000 V3: 65 oil spills, 1999 V2: 347
Type A gray-water systems, 1999 V2: 3132 Ultraviolet Disinfection in Biotechnology: Myth vs.
Type ACR/MED pipes, 2003 V4: 36 Practice, 1999 V2: 325
Type ACR pipes, 2003 V4: 36
372 ASPE Plumbing Engineering Design Handbook Volume 1
ultraviolet radiation treatment of water, 1999 V2: 245, gas booster components, 1999 V2: 179
311312, 318, 323, 324 hot-water components, 1999 V2: 166, 170
ultraviolet rays list of standards, 2004 V1: 57
chlorine and, 2000 V3: 149 pipe hangers, 2000 V3: 15
PVC pipes, 2000 V3: 116 UL 58: Steel Underground Tanks for Flammable and
sterilization, 2000 V3: 47 Combustible Liquids, 2000 V3: 95
swimming pool disinfection, 2000 V3: 150 UL 142: Steel Above Ground Tanks for Flammable and
unassisted creativity, 2004 V1: 232 Combustible Liquids, 2000 V3: 95, 154, 165
unbalanced motors in pumps, 2004 V1: 196 UL 2085: Fire Resistance, 2000 V3: 154
unconsolidated aquifers, 1999 V2: 241 unemployment taxes, in labor costs, 2004 V1: 94
undamped mechanical systems, 2004 V1: 160 ungridded piping systems, 2000 V3: 16
under-counter mounted lavatories, 2003 V4: 11 uniform attack corrosion, 2004 V1: 142
under-counter mounted sinks, 2003 V4: 12 Uniform Building Code (UBC), 2004 V1: 183, 191
under-lm corrosion, 2004 V1: 154 Uniform Federal Accessibility Standard (UFAS), 2004 V1:
under-oor areas, 2000 V3: 23 105106
under-table waste and vent piping, 2000 V3: 42 Uniform Fire Code (UFC), 2000 V3: 154
underdrain systems in sand lters, 2000 V3: 132 uniform ow
underground building sanitary pipe codes, 2004 V1: 44 in horizontal drains, 1999 V2: 67
underground inspections, 2004 V1: 102103 Manning formula, 2004 V1: 1
underground piping Uniform Plumbing Code, 1999 V2: 22, 34, 214, 2003 V4: 18
acid-waste piping, 1999 V2: 334 Uniformat specication system, 2004 V1: 64, 73
cast-iron soil pipe, 2003 V4: 27 uninterrupted water supplies, 2000 V3: 43
coatings, 2004 V1: 147 uninterruptible gas services, 2000 V3: 249
dened, 2004 V1: 31 unions (joins)
fountains, 2000 V3: 116 anged, 2004 V1: 10
glass pipe, 2003 V4: 47 screwed, 2004 V1: 10
materials for, 1999 V2: 1415 unions (labor), cost estimates and, 2004 V1: 98
medical gas piping, 2000 V3: 73 unisex toilet rooms, 2003 V4: 18, 23
natural gas systems, 1999 V2: 176 unit costs, in plumbing cost estimation, 2004 V1: 93
storm-drainage systems, 1999 V2: 68 United States agencies and departments. See U.S. agencies
underground building sanitary pipe codes, 2004 V1: 44 and departments
water pipes, 1999 V2: 251 United States Pharmacopoeia. See U.S. Pharmacopoeia
underground pressurized fuel delivery systems, 2000 V3: (USP)
162 units (UNIT)
underground site drainage, 1999 V2: 99105 symbols for, 2004 V1: 16
underground sprinklers, 2000 V3: 101 units of measurement. See measurement units
underground storage tanks (USTs) universities. See also laboratories
codes and standards, 2000 V3: 154 diversity factor calculations for vacuums, 1999 V2: 263
dened, 2000 V3: 153 natural gas piping, 1999 V2: 177
hazardous wastes, 2000 V3: 90 unknowns in value engineering presentations, 2004 V1:
illustrated, 2000 V3: 164 258
liquid fuel storage tanks, 2000 V3: 155158 unlined piping, 2003 V4: 26
connections and access, 2000 V3: 156157 unloading in air compressors, 2000 V3: 205
construction, 2000 V3: 156 unobstructed reach for wheelchairs, 2004 V1: 111, 112
lling and spills, 2000 V3: 156157 unoccupied buildings, conserving energy in, 2004 V1: 127
leak detection and system monitoring, 2000 V3: unrestricted areas (facilities with radiation), 1999 V2: 339
158163 unsanitary, dened, 1999 V2: 64
materials, 2000 V3: 155156 untreated sewage, 2004 V1: 28
overll prevention, 2000 V3: 158 unvented traps (s traps), 1999 V2: 46
venting, 2000 V3: 157158 unventilated spaces and gas systems, 1999 V2: 176
product dispensing systems, 2000 V3: 163165 upfeed risers, 2000 V3: 185
dispenser pans, 2000 V3: 165 uplifting of buildings, 1999 V2: 99
pressure dispensing, 2000 V3: 164 upright sprinklers, 2004 V1: 13, 29, 30
product dispensers, 2000 V3: 164165 upstream, dened, 2004 V1: 31
testing, 2000 V3:171 upward-tapered weirs, 2000 V3: 109
vapor recovery systems, 2000 V3: 163 Urban Hydrology for Small Watersheds, 1999 V2: 114
underground suction fuel delivery systems, 2000 V3: urinals. See also water closets
162163 accessibility design, 2004 V1: 116117
underwater lights, 2000 V3: 112, 121, 145 acoustic ratings of, 2004 V1: 194
underwriters. See insurance carriers Energy Policy Act requirements, 2004 V1: 264
Underwriters Laboratories, Inc. (UL) exclusion from gray-water systems, 1999 V2: 21
address, 2004 V1: 59, 2000 V3: 97 female, 2003 V4: 9
Index 373
ushing requirements, 2003 V4: 10 U.S. Federal Specications (FS), 2004 V1: 25, 58
gray water use, 2004 V1: 267, 1999 V2: 21, 25 U.S. Food and Drug Administration, 1999 V2: 279, 321,
health-care facilities, 2000 V3: 32, 33 324, 328
installation requirements, 2003 V4: 910 U.S. General Services Administration, 2004 V1: 191, 199,
minimum number for buildings, 2003 V4: 2122 263, 1999 V2: 34
reducing ow rates, 2004 V1: 134135 U.S. Government Printing Ofce
screening, 2003 V4: 10 address, 2000 V3: 97
specialty urinals, 2004 V1: 136 Clean Water Act, 2000 V3: 96
standards, 2003 V4: 2 Code of Federal Regulations, 2000 V3: 96
testing, 2003 V4: 9 Comprehensive Environmental Response,
traps, 2003 V4: 9 Compensation and Liability Act, 2000 V3: 96
types, 2003 V4: 89 Resource Conservation and Recovery Act, 2000 V3: 96
typical use, 1999 V2: 25 U.S. Green Building Council, 2004 V1: 263
ultra low ow, 2004 V1: 135136 U.S. Occupational Safety and Health Administration, 1999
water xture unit values, 2000 V3: 217 V2: 333
waterless, 2004 V1: 265, 2003 V4: 10 U.S. Pharmacopoeia (USP)
U.S. Architectural and Transportation Barriers USP nomographs, 1999 V2: 317
Compliance Board (ATBCB), 2004 V1: 106, 107 USP puried water, 1999 V2: 320, 321
U.S. Army Corps of Engineers water treatment standards, 1999 V2: 279
specications, 2004 V1: 63 U.S. Public Health Service (USPHS), 1999 V2: 238, 2000
U.S. Army Corps of Engineers Manual, 1999 V2: 214 V3: 151
value engineering, 2004 V1: 211 U.S. Veterans Administration, 2004 V1: 191
U.S. competitive swimming meets, 2000 V3: 128 U.S. War Department, 1999 V2: 114
U.S. Department of Commerce, National Information USACOE. See U.S. Army Corps of Engineers
Services, 1999 V2: 34 usages in swimming pools, 2000 V3: 128
U.S. Department of Defense, 2004 V1: 161, 185, 191, use factors
212213 air compressors, 2000 V3: 206
U.S. Department of Energy Greening Federal Facilities, compressed air systems, 2000 V3: 209
2004 V1: 134, 137 users in cost equation, 2004 V1: 223
U.S. Department of Health and Environmental Control, USGBC (U.S. Green Building Council), 2004 V1: 263
1999 V2: 170 USP. See U.S. Pharmacopoeia (USP)
U.S. Department of Health and Human Services, 2000 V3: USPHS. See U.S. Public Health Service (USPHS)
33 USTs. See underground storage tanks (USTs)
U.S. Department of Housing and Urban Development, utilities. See site utilities
2004 V1: 105, 106 utility costs, lowering, 2004 V1: 128
U.S. Department of the Army, 1999 V2: 114 utility gas. See fuel-gas piping systems
U.S. Department of Transportation (DOTn), 2004 V1: 54, utility sinks, 2000 V3: 32
58, 1999 V2: 194, 2000 V3: 88 utility water treatment, 1999 V2: 313314
U.S. Environmental Protection Agency UV (ultraviolet rays)
address, 2000 V3: 173 chlorine and, 2000 V3: 149
aggressiveness index, 1999 V2: 292 PVC pipes and, 2000 V3: 116
brass pipe standards, 2003 V4: 27 sterilization, 2000 V3: 47
chemical waste system codes and, 1999 V2: 345 swimming pool disinfection, 2000 V3: 150
Efuent Guideline program, 2000 V3: 8889 UV treatment of water, 1999 V2: 245, 311312, 318, 323,
industrial waste water dened, 2000 V3:87 324
potable water treatment technologies, 1999 V2: 279
publications, 1999 V2: 238
EPA 440: The EPA Efuent Guidelines Series, 2000
V
v, V (valves). See valves
V3: 96 V (specic volume). See specic volume
EPA 600/2-79-130: Activated Carbon Process for V (velocity of uniform ow), 2004 V1: 1
Treatment of Wastewater Containing V (velocity). See velocity
Hexavalent Chromium, 2000 V3: 96 V (vents). See vents and venting systems
EPA 600: Treatment of Organic Chemical V (volts). See volts
Manufacturing Wastewater for Reuse, 2000 v/v (volume to volume), 1999 V2: 285
V3: 96 VA (volt amperes), 2004 V1: 16
regulations, 2000 V3:88 vac, VAC (vacuum). See vacuum
Safe Drinking Water Act and, 1999 V2: 244 vacation pay, in labor costs, 2004 V1: 94
special waste drainage codes and, 1999 V2: 328 vacuum (vac, VAC)
storage tank regulations, 2000 V3: 154 dened, 2004 V1: 31, 1999 V2: 253
tank leak detection regulations, 2000 V3: 158 perfect vacuum, 2000 V3: 200
water consumption statistics, 2004 V1: 135 surgical use, 2000 V3: 57
U.S. Federal Housing Administration, 2004 V1: 199 symbols for, 2004 V1: 8, 16
374 ASPE Plumbing Engineering Design Handbook Volume 1
vacuum breakers. See backow preventers sizing, 1999 V2: 262266, 2000 V3: 74, 79
vacuum cleaning systems, 1999 V2: 266277. See also surges, 1999 V2: 35
vacuum systems swimming pools, 2000 V3: 144
cleanouts, 1999 V2: 276 time to reach rated vacuum, 1999 V2: 257258
codes and standards, 1999 V2: 266 vacuum-pressure gauges, 1999 V2: 260
components, 1999 V2: 266269, 268 vacuum reservoirs, 1999 V2: 262
friction losses, 1999 V2: 272274, 274 vacuum sources, 1999 V2: 259261, 262, 263264
inlet locations and spacing, 1999 V2: 269 velocity calculations, 1999 V2: 258259
piping, 1999 V2: 269 work forces, 1999 V2: 259
separators, 1999 V2: 275276 valence, 1999 V2: 280, 281, 302
simultaneous operators, 1999 V2: 269 value, dened, 2004 V1: 213214
sizing exhausters, 1999 V2: 272, 274275 Value Engineering Change Proposals (VECP), 2004 V1:
swimming pools, 2000 V3: 145, 146 260
types, 1999 V2: 266 Value Engineering Job Plan (VEJP), 2004 V1: 214
Vacuum Cleaning Systems, 1999 V2: 277 value engineering (VE)
vacuum condensate pumps, 2000 V3: 189 arguments against, 2004 V1: 232
vacuum deaerators, 1999 V2: 294, 295 checklists
vacuum diatomaceous earth ltration, 2000 V3: 132, 135, creativity worksheets, 2004 V1: 233234
136, 139 detail/product/material specication checklists,
vacuum levels 2004 V1: 220
dened, 1999 V2: 253254 evaluation checklists, 2004 V1: 237238
in exhauster sizing, 1999 V2: 274 function denitions forms, 2004 V1: 225227, 228
vacuum producers (exhausters), 1999 V2: 266269, 270, functional evaluation worksheets, 2004 V1: 243
272, 274275 251
vacuum product dispensers, 2000 V3: 163, 168 idea development and estimated cost forms, 2004
vacuum pumps, 1999 V2: 259, 263264, 2000 V3: 49, 70, V1: 241242
71 idea evaluation worksheets, 2004 V1: 243, 253
vacuum relief valves, 2004 V1: 31 project information checklists, 2004 V1: 215220
Vacuum Sewage Collection, 1999 V2: 238 project information sources checklists, 2004 V1:
vacuum sewers, 1999 V2: 226 221
vacuum sources, 1999 V2: 259261, 262, 263264 questions checklists, 2004 V1: 213214
Vacuum Sources, 1999 V2: 277 recommendation worksheets, 2004 V1: 258, 259
vacuum steam units, 2000 V3: 188, 189 compared to cost tting, 2004 V1: 258
vacuum systems, 1999 V2: 266277. See also vacuum contract document clauses, 2004 V1: 258, 260
cleaning systems cost information, 2004 V1: 222225
altitude adjustments, 1999 V2: 257 creativity process, 2004 V1: 231235
cast iron radiators, 2000 V3: 180 dened, 2004 V1: 211
codes and standards, 1999 V2: 262 elements of, 2004 V1: 214225
color coding, 2000 V3: 56 Evaluation phase, 2004 V1: 235243
fundamentals, 1999 V2: 253254 Function Analysis phase, 2004 V1: 224243
introduction, 1999 V2: 253 Functional Development sketches, 2004 V1: 237,
laboratory systems, 1999 V2: 262266, 2000 V3: 3739 239240
leakage, 1999 V2: 265, 267 Gut Feel Index, 2004 V1: 254
Level 1 dened, 2000 V3: 85 Information phase, 2004 V1: 214222
Level 3 dened, 2000 V3: 86 job plan phases, 2004 V1: 213
medical gas system switches, 2000 V3: 72 overview, 2004 V1: 211212
medical vacuum pre-recommendation questions, 2004 V1: 254257
design checklist, 2000 V3: 4950 purpose, 2004 V1: 211212
diversity factors, 2000 V3: 75 qualitative results, 2004 V1: 212
laboratory outlets, 2000 V3: 3739 Recommendation/presentation phase, 2004 V1: 257
number of stations, 2000 V3: 50, 5152 258
oral surgery equipment, 2000 V3: 39 results of, 2004 V1: 261
patient vacuum, 2000 V3: 85 Risk Guides, 2004 V1: 254, 257
peak demand, 2000 V3: 55 salesmanship in, 2004 V1: 257
piping systems, 2000 V3: 54, 6870 science of, 2004 V1: 258260
operating pressure steam classication, 2000 V3: 178 second creativity, cost, and evaluation analysis, 2004
operating pressures, 2000 V3: 175 V1: 254
piping, 1999 V2: 262, 2000 V3: 74, 79 teams, 2004 V1: 212
pressure drop, 1999 V2: 258 value changes, 2004 V1: 212213
pressure measurement, 1999 V2: 254256 value dened, 2004 V1: 213214
pump curves, 1999 V2: 258 valve-in-head irrigation, 2000 V3: 101
references, 1999 V2: 277 valve-per-sprinkler method of irrigation, 2000 V3: 100, 101
Index 375
valved zones in irrigation systems, 1999 V2: 26 dry pumps in, 2000 V3: 115
valves (v, V, VLV). See also specic types of valves pools and fountains, 2000 V3: 111
acoustic problems, 2004 V1: 197 VAV (variable air volume), 2004 V1: 16
acoustic ratings, 2004 V1: 194 VECP (Value Engineering Change Proposals), 2004 V1:
automatic shutdown, 2000 V3: 90 260
battery-controlled, 2004 V1: 135 vegetable oil, 1999 V2: 10
closing quickly, 1999 V2: 131 vehicular trafc
codes and standards, 2004 V1: 43 grates and, 1999 V2: 11
compressed air systems, 2000 V3: 210 leaching trenches and, 1999 V2: 223
domestic pressure drops and, 2000 V3: 221 VEJP (Value Engineering Job Plan), 2004 V1: 214
fountains, 2000 V3: 116119, 118119 vel., VEL (velocity). See velocity
friction loss in, 1999 V2: 128 velocity (vel., VEL, V). See also dynamic pressure
head loss and, 2000 V3: 115 acoustic pump problems, 2004 V1: 197
infectious waste systems, 1999 V2: 345 cold-water systems, 1999 V2: 121122
irrigation systems, 2000 V3: 103104 conversion factors, 2004 V1: 37
medical air compressors, 2000 V3: 66 counterow piping designs, 2000 V3: 178
medical gas control valves, 2000 V3: 7172 dened, 2004 V1: 31
pure water systems, 1999 V2: 324 earthquakes, 2004 V1: 159
in risers, 2004 V1: 10 ow from outlets, 2004 V1: 6
sizing natural gas ttings, 1999 V2: 184 hydraulic shock, 2004 V1: 6
sulfuric acid and, 1999 V2: 332 intake air in compression systems, 2000 V3: 212
swimming pools, 2000 V3: 145146 liquid fuel piping, 2000 V3:170
symbols for, 2004 V1: 16 measurements, 2004 V1: 33
testing in medical gas systems, 2000 V3: 81 non-SI units, 2004 V1: 34
vacuum systems, 2000 V3: 70 open-channel ow, 2004 V1: 1
valve ow coefcients, 2004 V1: 14 in rate of corrosion, 2004 V1: 145
in yard boxes (YB), 2004 V1: 10 self-scouring velocity in sewers, 2000 V3: 232
vandalism site storm drainage, 1999 V2: 98
backow preventers, 1999 V2: 149 sizing method for pipes, 1999 V2: 131
dressing rooms, 2000 V3: 130 steam systems, 2000 V3: 175
fasteners on grates and strainers, 1999 V2: 11 storm water in ditches, 2000 V3: 248
protecting against, 1999 V2: 19 symbols for, 2004 V1: 16
vane-type water-ow indicators, 2000 V3: 9, 10 terminal velocity, dened, 1999 V2: 1
VAP (vapor pressure), 2004 V1: 15 vacuum cleaning systems, 1999 V2: 270272
vap pr, VAP PR (vapor pressure), 2004 V1: 15 vacuum systems, 1999 V2: 258259
vap prf, VAP PRF (vaporproof), 2004 V1: 16 water hammer and, 2004 V1: 198, 1999 V2: 144
vapor-compression distillation, 1999 V2: 295298 water supply piping and, 1999 V2: 249
vapor operating pressure, 2000 V3: 175 wind (w vel., W VEL), 2004 V1: 16
vapor pressure, 2004 V1: 15 velocity head (h), 2004 V1: 5
vapor recovery systems vent connectors, dened, 1999 V2: 214
aboveground tank systems, 2000 V3:168 vent gases, dened, 1999 V2: 214
classications, 2000 V3: 154 vent pipes
hazardous wastes, 2000 V3: 90 cast-iron soil pipe, 2003 V4: 27
testing, 2000 V3: 171 glass pipe, 2003 V4: 47
underground tank systems, 2000 V3: 163 vent stack terminals
vapor system pressure, 2000 V3: 175178 dened, 1999 V2: 3536, 64
vaporizers, 2000 V3: 61 liqueed petroleum gas, 1999 V2: 197
vaporproof (vap prf, VAP PRF), 2004 V1: 16 natural gas, 1999 V2: 177
vapors, hazardous vent stacks
acid wastes and, 1999 V2: 332, 333 air in, 1999 V2: 2
atmospheric tank venting and, 2000 V3: 157158 dened, 2004 V1: 31, 1999 V2: 64
contamination in compressed air, 2000 V3: 201 vent headers, 1999 V2: 45
hydrocarbons, 2000 V3: 154 vent systems codes, 2004 V1: 43
monitoring, 2000 V3: 160, 162 ventilated sleeves and gas piping, 1999 V2: 176
vapor pockets, 2000 V3: 172 ventilation
VOCs, 1999 V2: 284 oxygen storage areas, 2000 V3: 63
var, VAR (variables), 2004 V1: 16 swimming pools, 2000 V3: 129
variable air volume (VAV), 2004 V1: 16 ventilators, 2000 V3: 74
variable-speed drivers, 2000 V3: 25 vents and venting systems (V, vent, VENT). See also vent
variables (var, VAR), 2004 V1: 16 stack terminals; vent stacks
varnishes in septic tanks, 1999 V2: 230 1-pipe steam systems, 2000 V3: 179180
vaults aboveground tank systems, 2000 V3:167
376 ASPE Plumbing Engineering Design Handbook Volume 1
acid-waste systems, 1999 V2: 332, 334, 2000 V3: 39 vertical risers for vacuum systems, 1999 V2: 269
arterial vents, 1999 V2: 52 vertical seismic load, 2004 V1: 184
atmospheric tank venting, 2000 V3: 167 vertical shaft turbine pumps, 2004 V1: 24
chemical-waste systems, 1999 V2: 346 vertical stacks
chimney heights, 1999 V2: 178 calculating terminal velocity and length, 2004 V1: 3
circuit and loop venting, 1999 V2: 4344 dened, 2004 V1: 31
combination waste and vent systems, 1999 V2: 4546 ttings, 1999 V2: 1
common vents, 1999 V2: 41 ow in, 1999 V2: 12
conuent vents, 1999 V2: 51 hydraulic jumps and, 1999 V2: 2
duct seismic protection, 2004 V1: 155 loading tables, 1999 V2: 4
ducts in clean agent gas re suppression, 2000 V3: 23 maximum xture-unit values, 1999 V2: 4, 5
end venting, 1999 V2: 41 multistory stacks, 1999 V2: 5
factors in trap seal loss, 1999 V2: 36 pneumatic pressure in, 1999 V2: 2
re-suppression drainage and, 1999 V2: 347 sizing, 1999 V2: 5, 6
xture units, 1999 V2: 4041 sovent systems, 1999 V2: 57
xture vents, 1999 V2: 3739 stack capacities, 1999 V2: 35
ash tanks, 2000 V3: 195 storm-drainage stacks, 1999 V2: 67
force mains, 2000 V3: 241 vertical turbine pumps
glossary of terms, 1999 V2: 64 re pumps, 2000 V3: 25
gravity vents for gas appliances, 1999 V2: 178 illustrated, 1999 V2: 246
infectious waste systems, 1999 V2: 345 private water systems, 1999 V2: 245
introduction, 1999 V2: 35 shallow wells, 1999 V2: 247
laboratory waste and vent piping, 2000 V3: 42 swimming pool pumps, 2000 V3: 140, 142
loop venting, 2004 V1: 31, 1999 V2: 64 VFR (volumetric ow rates), 2004 V1: 16
main vents, 2000 V3: 184 viable-count essays, 1999 V2: 282
manholes, 2000 V3: 236, 239 vibrating ll above sewers, 1999 V2: 16
natural gas appliance vents, 1999 V2: 177178 vibration and vibration isolation
offsets, 1999 V2: 4445 dened, 2004 V1: 209
oil separators, 1999 V2: 349 earthquakes
Philadelphia system, 1999 V2: 46, 47, 48 earthquake vibration periods, 2004 V1: 160
purposes, 1999 V2: 35 oor-mounted equipment, 2004 V1: 164166
radiators, 2000 V3: 178, 184 isolators and, 2004 V1: 206
reduced-size venting, 1999 V2: 49, 53, 54 piping and, 2004 V1: 168
references, 1999 V2: 65 suspended equipment, 2004 V1: 166
relief vents, 1999 V2: 44, 45 equipment vibration criteria, 2004 V1: 202
septic tank vents, 1999 V2: 231 xtures, isolating, 2004 V1: 205, 207
sewer vents, 1999 V2: 35 natural or free vibration, 2004 V1: 160
sizes and lengths, 2004 V1: 3, 1999 V2: 4143, 5063 noise and vibration control, 2004 V1: 199200
sovent systems, 1999 V2: 4647, 5463 piping, 2004 V1: 168. See also water hammer
special-waste drainage systems, 1999 V2: 328 pumps, 2004 V1: 205, 208
storm-drainage stacks, 1999 V2: 67 static deection for pump vibration, 2004 V1: 205
suds venting, 1999 V2: 3637, 39 types of vibration control devices, 2004 V1: 203206
sumps, 1999 V2: 105 vibration isolation mounts, 2004 V1: 162, 163
symbols for, 2004 V1: 8, 16 vibration isolators, 2004 V1: 199
testing, 2000 V3: 171 video equipment, 1999 V2: 10
traps and trap seals, 1999 V2: 36, 3940 vinyl coatings, 2004 V1: 147
underground liquid fuel tanks, 2000 V3: 157158 viruses in feed water, 1999 V2: 282, 311313
vent headers, 1999 V2: 45 viscosity (visc, VISC, MU)
vented inlet tees in septic tanks, 1999 V2: 228 calculating values of, 2004 V1: 2
waste anesthetic gas management, 2000 V3: 71 dened, 2000 V3: 154
wet vents, 1999 V2: 43, 49 measurements, 2004 V1: 33
venturi action in pools, 2000 V3: 108 symbols for, 2004 V1: 16
venturi-meters, 2004 V1: 197 visitors facilities, numbers of xtures for, 2003 V4: 20, 21
venturi suction pumps, 1999 V2: 241 visualization in function analysis, 2004 V1: 227
verbs in function analysis, 2004 V1: 224, 225, 231 vitreous china xtures, 2000 V3: 33, 2003 V4: 1, 2
vert., VERT (vertical). See vertical vitried clay piping, 1999 V2: 122, 346, 2000 V3: 245, 2003
vertical (vert., VERT), 2004 V1: 16 V4: 49, 5657
vertical lters, 2000 V3: 131 vitried sewer pipes, 2004 V1: 31
vertical forces, 2004 V1: 189 VLV (valves). See valves
vertical leaders, 1999 V2: 8588, 109 VOCs (volatile organic compounds), 1999 V2: 284, 292,
vertical pipes, 2004 V1: 31 2000 V3: 154, 163
vertical pressure media lters, 1999 V2: 300 vol., VOL (volume). See volume
Index 377
volatile liquids, 1999 V2: 13, 347349 master alarms, 2000 V3: 72
volatile organic compounds (VOCs), 1999 V2: 284, 292, testing, 2000 V3: 81
2000 V3: 154, 163 warranty section in specications, 2004 V1: 70, 90
volcanoes, 2004 V1: 156 Warren, Alan W., 1999 V2: 114
volts (V, E, VOLTS) wash basins. See sinks and wash basins
decomposition potential dened, 2004 V1: 152 wash-down urinals, 2003 V4: 9
measurement conversions, 2004 V1: 33 wash-down water closets, 2003 V4: 3
symbols for, 2004 V1: 16 washing oors with gray water, 1999 V2: 22
volt amperes (VA), 2004 V1: 16 washing machines. See laundry systems and washers
volume (vol., VOL) washout urinals, 2003 V4: 9
calculating, 2004 V1: 35 washout water closets, 2003 V4: 3
conversion factors, 2004 V1: 37 waste, dened, 2004 V1: 31
ow rate measurements, 2004 V1: 33, 1999 V2: 255 waste anesthetic-gas disposal, 2000 V3: 57, 7071, 86
gas particles, 2000 V3: 199 waste brines, 1999 V2: 231, 307
non-SI units, 2004 V1: 34 waste-disposal units. See food waste grinders
symbols for, 2004 V1: 16 waste tting standards, 2003 V4: 2
volume to volume (v/v), 1999 V2: 285 waste grinders, 2000 V3: 32
volumetric ow rates (VFR), 2004 V1: 16 waste-heat usage, 2004 V1: 131134, 266
vortexes waste-heat vaporizers, 2000 V3: 61
anti-vortex grating, 2000 V3: 110 waste oil (WO), 2004 V1: 8, 2000 V3: 154
in drains, 1999 V2: 38 waste oil vents (WOV), 2004 V1: 8
from pumps, 2004 V1: 197 waste or soil vents. See stack vents
from sumps, 2004 V1: 197 waste pipes, 2004 V1: 31, 2003 V4: 27
vp, VP (dynamic pressure or velocity), 2004 V1: 15 waste sewers (W), 2004 V1: 8
waste streams
W evaluation, 2000 V3: 90
segregating, 2000 V3: 94
W, W (humidity ratios), 2004 V1: 15
W (walls). See walls Wastewater Engineering: Treatment, Disposal, and Reuse,
W (waste sewers), 2004 V1: 8 2000 V3: 125
W (watts). See watts Wastewater Engineering: Treatment/Disposal/Reuse, 1999
W/m K (watts per meter per kelvin), 2004 V1: 33 V2: 238
w vel., W VEL (velocity, wind), 2004 V1: 16 wastewater heat recovery, 2004 V1: 133
w/w (weight to weight), 1999 V2: 285 wastewater management. See also gray-water systems;
wading areas, 2000 V3: 128 private sewage-disposal systems
wafer buttery valves, 1999 V2: 268 green building technologies, 2004 V1: 264
WAG (waste anesthetic gases), 2000 V3: 7071 individual aerobic wastewater treatment, 1999 V2:
WAGD (waste anesthetic-gas disposal), 2000 V3: 57, 7071, 232233
86 industrial wastewater treatment. See industrial
wages, in labor costs, 2004 V1: 94 wastewater treatment
waiting rooms, 2000 V3: 32 reclaimed and gray water systems, 2004 V1: 135, 1999
WAL (walls). See walls V2: 2729
wall azimuth (WAZ), 2004 V1: 14 swimming pools, 2000 V3: 131
wall carriers, 2003 V4: 6 WAT (watts). See watts
wall cleanouts (WCO), 2004 V1: 11 water (WTR). See also water analysis; water chemistry
wall-hung lavatories, 2003 V4: 11 as seal liquid in liquid ring pumps, 1999 V2: 260
wall-hung urinals, 2003 V4: 10 asbestos concrete piping, 2003 V4: 26
wall-hung water closets, 2003 V4: 4, 6 clarity, 2000 V3: 135
wall hydrants (WH), 2004 V1: 10, 12 contamination in compressed air, 2000 V3: 201
wall-mounted medical gas stations, 2000 V3: 58 density, 1999 V2: 116
walls (W, WAL) kinematic viscosity, 1999 V2: 121
piping and acoustic design, 2004 V1: 195196 oil-water separation, 2000 V3: 93
symbols for, 2004 V1: 16 portable re extinguishers, 2000 V3: 27
wall penetrations of pipes, 2004 V1: 201 potable amounts present, 2004 V1: 263
wander, 2004 V1: 22, 190 samples of, 1999 V2: 155
ward rooms, 2000 V3: 34 subsurface water, 1999 V2: 99105
warehouses, numbers of xtures for, 2003 V4: 20, 21 water absorption, plastic pipe and, 2003 V4: 60
warm-up loads water analysis
automatic heat-up systems, 2000 V3: 196 aggressiveness index, 1999 V2: 292
equations, 2000 V3: 195 codes and standards, 1999 V2: 279
steam piping, 2000 V3: 187, 191, 192 example report, 1999 V2: 286
warning systems (medical gas), 2000 V3: 7273 introduction, 1999 V2: 284285
area alarms, 2000 V3: 72 pH, 1999 V2: 285, 291
378 ASPE Plumbing Engineering Design Handbook Volume 1
predicting water deposits and corrosion, 1999 V2: Water Conditional Manual, 1999 V2: 325
290292 water conditioning. See also water purication; water
references, 1999 V2: 325 softeners; water treatment
Ryzner stability index, 1999 V2: 292 dened, 1999 V2: 279
silt density index, 1999 V2: 288289 water-conditioning or treating devices, 2004 V1: 31
specic conductance, 1999 V2: 287 water conservation. See conserving water
total dissolved solids, 1999 V2: 288 water consumption tests, 2003 V4: 5, 9
total organic carbon, 1999 V2: 288 water-cooled after-coolers, 2000 V3: 202
total suspended solids, 1999 V2: 287288 water coolers
water chemistry access to, 2004 V1: 109112
elements, acids, and radicals in water, 1999 V2: 281 gray-water output, 1999 V2: 25
heat loss retardants, 2000 V3: 150 health-care facilities, 2000 V3: 32
introduction, 1999 V2: 280284 public areas in health-care facilities, 2000 V3: 33
mineral deposits, 2000 V3: 147148 standards, 2003 V4: 2
pH values, 2000 V3: 147 types, 2003 V4: 14
pools and fountains, 2000 V3: 123 wheelchair space around, 2004 V1: 112
sequestering agents, 2000 V3: 150 water damage
swimming pools, 2000 V3: 146148 sprinkler systems, 2000 V3: 2
water impurities, 1999 V2: 280284 swimming pool bathhouses, 2000 V3: 130
water-closet compartments water deposits, 1999 V2: 289, 290292
accessibility, 2004 V1: 113116 Water Distributing Systems for Buildings, 1999 V2: 155
ambulatory-accessible toilet compartments, 2004 V1: water-distribution pipes and systems. See also cold-water
114 systems; hot-water systems
kitchen areas, 2000 V3: 36 acoustic design, 2004 V1: 195196
patient rooms, 2000 V3: 34 codes, 2004 V1: 45
single-occupant unisex toilet rooms, 2003 V4: 18, 23 dened, 2004 V1: 31
spacing, 2003 V4: 67 pipe codes, 2004 V1: 45
swimming pool bathhouses, 2000 V3: 130 water supply and distribution symbols, 2004 V1: 12
trap primers in, 1999 V2: 13 water supply systems, 2004 V1: 31
water-closet anges, 2003 V4: 6 weight of water-lled pipes, 2004 V1: 184
water closets (WC). See also urinals Water Efciency design (LEED), 2004 V1: 263264
accessibility design, 2004 V1: 113116 water-ow indicators, 2000 V3: 9, 10
acoustic design, 2004 V1: 200 water for injection (WFI), 1999 V2: 317, 320, 321, 324
acoustic ratings of, 2004 V1: 194 water glass, 2004 V1: 151
bolts, 2003 V4: 6 water hammer
composting toilets, 2004 V1: 265 acoustic control of, 2004 V1: 201
conserving water in, 1999 V2: 232 air locks, 2004 V1: 201
dual ush, 2004 V1: 265 controlling water hammer, 1999 V2: 132, 143
Energy Policy Act requirements, 2004 V1: 264 counterow piping designs, 2000 V3: 178
exclusion from gray-water systems, 1999 V2: 21 dened, 2004 V1: 31, 1999 V2: 131144
xture-unit loads, 1999 V2: 3 ow velocity and, 2004 V1: 198
ushing performance testing, 2003 V4: 56 fountains and, 2000 V3: 116
ushing systems, 2003 V4: 68 fuel dispensers, 2000 V3: 170
gray water usage, 2004 V1: 267, 1999 V2: 21, 25 shock intensity, 1999 V2: 132
in health-care facilities, 2000 V3: 32, 33, 34 sizing of arresters, 1999 V2: 143144
incinerators, 2004 V1: 265 steam systems, 2000 V3: 189, 190, 191
installation requirements, 2003 V4: 67 swimming pool pumps, 2000 V3: 139
minimum numbers of, 2003 V4: 1822 symbols on arresters, 1999 V2: 143
mounting, 2003 V4: 4 system protection and control, 1999 V2: 132, 143144
rates of sewage ows, 1999 V2: 237 velocity and, 1999 V2: 121
reducing ow rates, 2004 V1: 134135 water hammer arresters (WHA)
seats, 2003 V4: 5 acoustic design in water pipes, 2004 V1: 195
shapes and sizes, 2003 V4: 45 as protection and control, 1999 V2: 132
sovent systems, 1999 V2: 59, 62 codes, 2004 V1: 43
specimen-type, 2000 V3: 35 dened, 2004 V1: 31
standards, 2003 V4: 2, 6 ow velocity and, 2004 V1: 198
types of, 2004 V1: 135136, 2003 V4: 34 shock absorbers, 2004 V1: 198, 201
typical use, 1999 V2: 25 sizing, 1999 V2: 143144
ultra-low-ow, 2004 V1: 135136, 1999 V2: 19 symbols, 2004 V1: 10, 1999 V2: 143
water conservation, 2004 V1: 135136 water heaters. See also hot-water systems
water xture unit values, 2000 V3: 217 avoiding standby losses, 2004 V1: 127
water column (wc), 2003 V4: 5 booster water heaters, 2004 V1: 126, 129, 1999 V2: 160
Index 379
codes, 2004 V1: 43 water pipes. See cold-water systems; hot-water systems;
condensation use, 2004 V1: 267 water-distribution pipes and systems
conserving energy, 2004 V1: 124125, 127 water pressure
earthquake damage, 2004 V1: 162 booster-pump system, 1999 V2: 152
earthquake protection, 2004 V1: 162, 163 excess water pressure, 1999 V2: 152154
explosions, 1999 V2: 157 gravity-tank systems, 1999 V2: 150152
gas water heaters, 2004 V1: 129 hydropneumatic-tank systems, 1999 V2: 150
heat recovery, 1999 V2: 158 inadequate water pressure, 1999 V2: 149152
high-efciency, 2004 V1: 265 pressure-regulating devices, 1999 V2: 122
instantaneous, 2004 V1: 265 water hammer and, 1999 V2: 144
locations of, 2004 V1: 129 water purication
mineral deposits and, 2000 V3: 147 central purication equipment, 1999 V2: 323325
overview, 1999 V2: 160165 codes and standards, 1999 V2: 279, 317
point-of-use booster heaters, 2000 V3: 45 feed water, 1999 V2: 320
recovering heat from water heaters, !1999 V2: 158 high-purity water, 2000 V3: 46
reecting pools and fountains, 2000 V3: 112, 121122 methods, 2000 V3: 4647
step heaters, 2000 V3: 144 pharmaceutical systems, 1999 V2: 320
stratication in water heaters, 1999 V2: 160, 165 polishers and, 1999 V2: 308
swimming pools, 2000 V3: 138139, 144145, 146 pure-water systems dened, 1999 V2: 279
temperature, 1999 V2: 157, 160 references, 1999 V2: 325
thermal efciency, 1999 V2: 169 specic resistance of pure water, 1999 V2: 286
types of systems, 2004 V1: 129134 system design, 1999 V2: 321
water impurities water impurities, 1999 V2: 280284
alkalinity, 1999 V2: 282283 water quality
analysis and measurement, 1999 V2: 284289 Clean Water Act, 2000 V3: 88
biological fouling, 1999 V2: 289, 316 grades of laboratory water, 1999 V2: 317
dissolved gases, 1999 V2: 284 gray-water systems, 1999 V2: 33
hardness, 1999 V2: 283 introduction, 1999 V2: 244
microorganisms, 1999 V2: 282 references, 1999 V2: 325
specic resistance, 1999 V2: 285287 water-resistivity meters, 1999 V2: 286
suspended solids, 1999 V2: 282 water-reuse systems. See gray-water systems
treatment methods, 1999 V2: 292313 water rise tests, 2003 V4: 5
volatile organic compounds, 1999 V2: 284 water risers, 2004 V1: 31
water levels water-seal self-scouring traps, 1999 V2: 36
in pools, 2000 V3: 112 water-service pipes, dened, 2004 V1: 31
sensors, 2000 V3: 124 water slides, 2000 V3: 128
water-level dependent spray jets, 2000 V3: 119 water softeners
water-level independent spray jets, 2000 V3: 119 earthquake damage, 2004 V1: 162
water mains hardness of water, 1999 V2: 283
age and size, 2000 V3: 8 ion-exchange, 1999 V2: 300
copper pipe, 2003 V4: 34, 35 leakage, 1999 V2: 308
dened, 2004 V1: 31 pressure losses and, 1999 V2: 125
re-protection connections, 2000 V3: 225, 227 pure water systems, 1999 V2: 323
inspection checklist, 2004 V1: 103 types of, 1999 V2: 244, 307308
pressure and, 2000 V3: 216 utility water, 1999 V2: 314
sprinkler systems, 2000 V3: 3 waste brines, 1999 V2: 231
water makeup. See makeup water systems water sports, 2000 V3: 128
Water Management: A Comprehensive Approach for Water Spray Fixed Systems for Fire Protection (NFPA 15),
Facility Managers, 1999 V2: 34 2000 V3: 2, 29
water management plans, 2004 V1: 134135 water-spray systems, 2000 V3: 13
water meters water-storage tanks
domestic water meters, 1999 V2: 115116 earthquake damage, 2004 V1: 162
estimating sewage disposal from, 1999 V2: 233 re-protection water supply, 2000 V3: 232
ow-pressure loss averages, 1999 V2: 117 pipe installation, 1999 V2: 250252
friction losses, 1999 V2: 127 piping, 1999 V2: 249250
irrigation, 2000 V3: 105 pressure regulators, 1999 V2: 248249
locations for, 2000 V3: 217 private water systems, 1999 V2: 239
loss of pressure, 1999 V2: 123 types of, 1999 V2: 247248
pressure losses, 2000 V3: 224 water-air ratio in tanks, 1999 V2: 150
water motor gongs, 2000 V3: 9, 10 water levels in, 1999 V2: 151, 248
water, oil, and gas (WOG) pressure rating, 2000 V3: 210
380 ASPE Plumbing Engineering Design Handbook Volume 1
water-supply systems. See cold-water systems; domestic water vapor in air, 2000 V3: 200201, 201
water supply; re-protection systems; hot-water water wells. See wells
systems; private water systems; water-distribution waterborne radioactive waste (radwaste), 1999 V2: 337
pipes and systems; wells waterfall aerators, 1999 V2: 293
Water Systems for Pharmaceutical Facilities, 1999 V2: 325 waterfalls, 2000 V3: 108, 109
water tables waterfront facilities, 1999 V2: 147
underground storage tanks and, 2000 V3: 155 waterless urinals, 2004 V1: 136, 265, 2003 V4: 10
wells, 1999 V2: 241243 waterproof manholes, 2000 V3: 236, 239
Water Tanks for Fire Protection, 1999 V2: 247 waterproong drains, 1999 V2: 17, 79
water temperature watertight joints, 2003 V4: 26
bathtub water notes, 2004 V1: 119 watt-hours (Wh, WH), 2004 V1: 16
deaeration water temperatures, 1999 V2: 294 watts (W, WAT)
feed water temperature and deposits, 1999 V2: 291, converting to SI units, 2004 V1: 40
312, 321322 measurement conversions, 2004 V1: 33
high-temperature withstand for hot-water systems, symbols for, 2004 V1: 16
1999 V2: 166 W/m K (watts per meter per kelvin), 2004 V1: 33
hot-water properties, 1999 V2: 168 wave actions in water (tsunamis), 2004 V1: 158
hot-water relief valves, 1999 V2: 166167 wave pools, 2000 V3: 128
hot-water temperatures, 1999 V2: 159, 161165, 165, wax ring seals, 2003 V4: 6
2000 V3: 36, 45 WAZ (wall azimuth), 2004 V1: 14
maintenance hot-water temperatures, 1999 V2: 166 wb, WB (wet bulbs), 2004 V1: 16
mixed-water temperatures, 1999 V2: 159160 Wb (webers), 2004 V1: 33
operating hot-water temperatures, 1999 V2: 166 wbt, WBT (wet-bulb temperature), 2004 V1: 16
reecting pools and fountains, 2000 V3: 108 wc (water column), 2003 V4: 5
scalding water, 1999 V2: 169170 WCO (wall cleanouts), 2004 V1: 11
shower compartments, 2004 V1: 120, 2003 V4: 15 WD (wind). See wind
swimming pools, 2000 V3: 129, 139 wdir, WDIR (wind direction), 2004 V1: 16
water heaters, 1999 V2: 157, 160 weak-base regeneration, 1999 V2: 302, 305
water toys, 2000 V3: 128 weakly-acidic resins, 1999 V2: 308
water treatment weakly-basic resins, 1999 V2: 308
aeration, 1999 V2: 292294 weather conditions, 2004 V1: 98, 2000 V3: 100, 105, 165,
aluminum sulfate, 2000 V3: 149150 219
boiler feed water, 1999 V2: 314315 webers, 2004 V1: 33
clarication, 1999 V2: 294 weep holes, 1999 V2: 17, 2000 V3: 144, 2003 V4: 15
codes and standards, 1999 V2: 279 weight (wt, WT)
cooling towers, 1999 V2: 315316 clean agent gas re containers, 2000 V3: 23
corrosion inhibitors, 2004 V1: 151 horizontal loads of piping, 2004 V1: 184
deaeration, 1999 V2: 294295 piping, earthquake protection and, 2004 V1: 167
dealkalizing, 1999 V2: 295 in seismic force calculations, 2004 V1: 183
decarbonation, 1999 V2: 295 swimming pool ltration equipment, 2000 V3: 140
dened, 1999 V2: 279 symbols for, 2004 V1: 16
distillation, 1999 V2: 295298 weight loss in corrosion, 2004 V1: 144
drinking water, 1999 V2: 316317, 318 weight to weight (w/w), 1999 V2: 285
ltration, 1999 V2: 298, 300 weighted evaluations in value engineering, 2004 V1: 243
fountains and pools, 2000 V3: 107, 112, 122124 weighted runoff coefcients, 1999 V2: 97
ion-exchange and removal, 1999 V2: 300308 weirs
membrane ltration and separation, 1999 V2: 300, ow rates, 2000 V3: 109
308311 materials, 2000 V3: 146
microbial control, 1999 V2: 311313 sizing, 1999 V2: 93
references, 1999 V2: 325 swimming pools, 2000 V3: 142
swimming pools, 2000 V3: 130, 140, 146 water return in, 2000 V3: 119120
utility water treatment, 1999 V2: 313314 waterfall rates and, 2000 V3: 108
water impurities, 1999 V2: 280284 welded steel piping, 2003 V4: 48
water purication, 1999 V2: 317325 welding
water softening, 1999 V2: 307 clearance for, 2003 V4: 25
Water Treatment for HVAC and Potable Water Systems, corrosion and, 2004 V1: 146
1999 V2: 325 earthquake protection techniques, 2004 V1: 167
Water Use in Ofce Buildings, 1999 V2: 34 problems in seismic protection, 2004 V1: 190
Water: Use of Treated Sewage on Rise in State, 1999 V2: 34 weld decay dened, 2004 V1: 154
Water-Use Reduction Credit, 2004 V1: 264 welded ttings, 2004 V1: 24
Water Uses Study, 1999 V2: 34 welded joints in radioactive waste systems, 1999 V2:
water utility letters, 2000 V3: 216 341
Index 381
well screens, 2000 V3: 119120 wheeled re extinguishers, 2000 V3: 19, 27
wells WHEN relationship, 2004 V1: 230
bored wells, 1999 V2: 241 whirlpool bathtubs, 2003 V4: 16
driven wells, 1999 V2: 241 White, George Clifford, 1999 V2: 155
dug wells, 1999 V2: 240 Whitney, Eli, 2004 V1: 231
equilibrium equations for wells, 1999 V2: 242243 WHY logic path, 2004 V1: 230, 231, 258
re-protection connections, 2000 V3: 225 WI (width), 2004 V1: 16
gray-water irrigation systems and, 1999 V2: 26 wide seepage beds, 1999 V2: 225
hydraulics of, 1999 V2: 241 width (WI), 2004 V1: 16
initial operation and maintenance, 1999 V2: 252 wind (WD)
introduction, 1999 V2: 240 direction (wdir, WDIR), 2004 V1: 16
irrigation usage, 2000 V3: 105 effect on irrigation sprinklers, 2000 V3: 102
jetted wells, 1999 V2: 241 fountains and, 2000 V3: 115, 120121
matching water storage to pump ow, 1999 V2: 248 gas appliances and, 1999 V2: 178
monitoring fumes, 2000 V3: 162 reecting pools and, 2000 V3: 108
monitoring groundwater, 2000 V3: 162 speed and heat loss, 2000 V3: 121
pipe installation, 1999 V2: 250252 symbols for, 2004 V1: 16
protection of, 1999 V2: 243 velocity, 2004 V1: 16
pumps, 1999 V2: 245247 vent stack terminals and, 1999 V2: 36
swimming pool supplies, 2000 V3: 131 wind pressure (wpr, WPR, WP, WPRES), 2004 V1: 16
system equipment, 1999 V2: 245250 withstand for hot-water systems, 1999 V2: 166
water demand and, 1999 V2: 243244 WO (waste oil), 2004 V1: 8
water quality, 1999 V2: 244245 WOG (water, oil, and gas pressure rating), 2000 V3: 210
wet-alarm valve risers, 2000 V3: 9, 10 wood shrinkage, protecting against, 1999 V2: 19
wet-bulb temperature (wbt, WBT), 2004 V1: 16 wood stave piping, 1999 V2: 122
wet bulbs (wb, WB), 2004 V1: 16 Woodcock, J.J., 1999 V2: 34
wet-cast pipe, 2003 V4: 32 word processing of specications, 2004 V1: 7172
wet oors in chemical plants, 1999 V2: 346 work
wet gas, 2000 V3: 250 conversion factors, 2004 V1: 35
wet-niche pool lighting, 2000 V3: 145 converting to SI units, 2004 V1: 39
wet-pipe systems, 2004 V1: 29, 2000 V3: 9 dened, 2004 V1: 61
wet pits, 2000 V3: 142 measurements, 2004 V1: 33
wet returns, 2000 V3: 179 work change directives, 2004 V1: 63
wet standpipes, 2004 V1: 30 work functions in value engineering, 2004 V1: 225, 243
wet surfaces, 2004 V1: 16 working deionizers, 1999 V2: 301, 302
wet-tap excavations, 2000 V3: 222 working hours, in cost estimation, 2004 V1: 98
wet vacuum-cleaning systems (WVC) working pressure
dened, 1999 V2: 266 fuel gas, 1999 V2: 212
illustrated, 1999 V2: 276 in pipe selection, 2003 V4: 26
pitch, 1999 V2: 277 relief valves and, 1999 V2: 167
separators, 1999 V2: 268 vacuum systems, 1999 V2: 259, 262
symbols for, 2004 V1: 9 workmanship standards, 2004 V1: 66
wet venting workmens compensation, in labor costs, 2004 V1: 94
bathroom groups, 1999 V2: 43 worksheets. See checklists and forms
combination waste and vent systems, 1999 V2: 4546 worst case possibilities, radiation and, 1999 V2: 341
dened, 2004 V1: 31, 1999 V2: 64 worth, dened, 2004 V1: 213
illustrated, 1999 V2: 49 WOV (waste oil vents), 2004 V1: 8
Weymouth formula, 2004 V1: 7, 1999 V2: 183, 190, 191, WP (wind pressure), 2004 V1: 16
198209 wpr, WPR (wind pressure), 2004 V1: 16
WFI (water for injection), 1999 V2: 317, 320, 321, 324 WPRES (wind pressure), 2004 V1: 16
WH (wall hydrants), 2004 V1: 10, 12 wrapped piping
Wh, WH (watt-hours), 2004 V1: 16 plastic-wrapped steel piping, 1999 V2: 196
WHA (water hammer arresters). See water hammer sound damping, 2004 V1: 196, 201202
arresters wrapped storm piping, 1999 V2: 68
What Future Role for Pressure Sewers?, 1999 V2: 238 wrist blades on faucets, 2000 V3: 33
wheel loads in pipe selection, 2003 V4: 26 written amendments, 2004 V1: 63
wheelchairs Wrought Copper and Copper Alloy Solder-Joint Pressure
adult-sized, dimensions, 2004 V1: 108 Fittings, 2003 V4: 37
anthropometrics for wheelchairs, 2004 V1: 109 Wrought Copper and Wrought Copper Alloy Solder-Joint
approaches and reaches, 2004 V1: 110 Drainage Fittings, 2003 V4: 45
clear space for, 2004 V1: 109 Wrought Copper Braze Fittings, 2003 V4: 45
toilet and bathing rooms, 2004 V1: 112113 wrought iron piping, 1999 V2: 122, 176, 196
382 ASPE Plumbing Engineering Design Handbook Volume 1
X
x-ray areas, 2000 V3: 39, 51
x-rays, 1999 V2: 337
X#A (compressed air). See compressed air (A, X#, X#A)
XH (extra heavy) cast iron soil pipe, 2003 V4: 2930
XH (extra heavy) cast-iron soil pipe, 2003 V4: 27
XP explosion-proof construction, 1999 V2: 179
XP junction boxes, 1999 V2: 179
XPAN (expansion. See expansion
Y
y (years), 2004 V1: 16, 34
y-type strainers, 2000 V3: 116
yards (yd, YD)
converting to SI units, 2004 V1: 40
symbols for, 2004 V1: 16
yards and lawns
lawn imperviousness factors, 2000 V3: 243
lawn sprinkler supply (LS), 2004 V1: 8
sprinkler systems (irrigation)
lawn sprinklers, 1999 V2: 121
storm-drainage systems and, 1999 V2: 67
yard cleanouts (CO), 2004 V1: 11
YB (valves in yard boxes), 2004 V1: 10
yd, YD (yards), 2004 V1: 16, 40
year-round pools, 2000 V3: 129
years (yr, YR), 2004 V1: 16, 34
Yeh, K.L., 1999 V2: 325
yellow brass, 2004 V1: 144
yoke vents, 2004 V1: 31
Young, Virgil E., 2000 V3: 105
yr, YR (years), 2004 V1: 16, 34
Yrjanainen, Glen, 1999 V2: 114
Z
z, Z (zones), 2004 V1: 16, 183
Zelmanovich, Y., 1999 V2: 325
zeolite process, 1999 V2: 244
zeolites, 1999 V2: 302
zero-ow potential, 2004 V1: 153
zero governors, 2000 V3: 251
zeta potential, 1999 V2: 294
zinc
anodes, 2004 V1: 150
corrosion, 2004 V1: 139
electromotive force series, 2004 V1: 144
galvanic series, 2004 V1: 141
zirconium, 2000 V3: 20
ZN (zones), 2004 V1: 16, 183
zone valves, 2000 V3: 49, 71
zones (z, Z, ZN)
in seismic force calculations, 2004 V1: 183
symbols for, 2004 V1: 16
Index 383