` MonthlyHighlights

1. D8313hydrogenrecontractortopflangeleaked.HDTshutdownfor4hours.
2. D8VXX14catalystunloadedandmeshreplaced.Afterloadingofcatalyst,impregnation
processcompleted.
3. DesalternewpumpD2214Ainstalledonsite.
4. CDUemergencyshutdownduetopowerfailure.AftershutdownD2203openupfor
inspection.Itsseparationplatesdamagedand09tubesfoundleaked.Afterjobleakage
rectified.AlongwithCDU,LSUsystemalsoshutdownfor1.5days.
5. D2202A/BonetubeleakedduringCDUemergencyshutdown.
6. D3316A/B/C/Dtubesidecoolingwateroutletlinepinholeleakageobservedlateron
rectifiedbyclamped.
7. D3316A/B/C/Dtubesideleakageobservedduetowhichplantshutdownfor1day,later
onmodificationofexchangerbypassdonetoavoidproductionloss.
8. JPproductioncarriedoutfrom15052017to18052017and29052017tilldate.
9. Coolingwaterlineleakagesobservedonplant.Inspectionrecommendedtoreplaceall
lines.
10. Coolingwatermakeuplineundergroundleakagerectifiednearoldboiler.
11. D2611A/B4tubesleakagerectified.