Professional Documents
Culture Documents
Catalogue-8djh en PDF
Catalogue-8djh en PDF
Catalogue-8djh en PDF
com/medium-voltage-switchgear
R-HA40-110.eps
R-HA40-112.eps
R-HA40-111.eps
2 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Contents
www.siemens.com/medium-voltage-switchgear Components
Three-position switch-disconnector 24 to 26
Vacuum circuit-breaker 27 to 29
Busbar extension 30
HV HRC fuse assembly 31 to 36
Current and voltage transformers 37 to 41
Intelligent current and voltage sensors 42 and 43
Cable connections, cable plugs 44 to 50
Interlocks, locking devices 51
Indicating and measuring equipment 52 to 60
Transformer monitoring 61
Intelligent transformer substation 62 and 63
Protection systems 64
Low-voltage compartment, low-voltage niche 65
Dimensions
Room planning, switchgear installation 66 to 68
Individual panels and modules, panel combinations 69 to 81
Outdoor enclosure 82
Floor openings and xing points 83 to 86
Installation
Shipping data, transport 87 and 88
Standards
Standards, specications, guidelines 89 to 91
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 3
Application
Types
R-HA40-150.eps
R-HA40-156.eps
R-HA40-149.eps
4 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Application
Typical uses, ratings, approvals
8DJH switchgear is a factory-assembled, type-tested, Electrical data (maximum values) and dimensions
3-pole metal-enclosed single-busbar switchgear for indoor Rated voltage kV 7.2 12 15 17.5 24
installation. Rated frequency Hz 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60
8DJH switchgear is used in public and industrial energy Rated short-duration kV 20 1) 28 2) 36 38 50
systems of the secondary distribution level, e.g. in power-frequency
withstand voltage
Local ring-main units, customer transfer substations and
Rated lightning impulse kV 60 1) 75 2) 95 95 125
switching substations of power supply and public utilities withstand voltage
Wind power and solar plants, hydroelectric power plants Rated peak kA 63 63 63 63 50
Water and sewage treatment plants withstand current
Airports, railway stations, underground railway stations Rated short-circuit kA 63 63 63 63 50
making current
Open-cast mining facilities
Rated short-time kA 20 20 20 20 20
High-rise buildings. withstand current 3 s
Rated short-time kA 25 25 25 25 20
withstand current 1 s
Rated normal current A 630 630 630 630 630
of the busbar
Rated normal current A 200 / 250 / 400 / 630 3)
of feeders
Width (feeders) mm 310 / 430 / 500 3)
Depth
without pressure
relief duct mm 775 775 775 775 775
with pressure
relief duct mm 890 890 890 890 890
Height
without low-voltage
compartment and
pressure relief duct mm optionally 1040 / 1200 / 1400 / 1700
1) 32 kV / 60 kV according to some national requirements
2) 42 kV / 75 kV according to some national requirements
3) Depending on the feeder function and the selected design options
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 5
Requirements
Features Safety
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 7
Requirements
Classication
1) Design option
2) The rated normal currents apply to ambient air temperatures of max. 40 C.
The 24-hour mean value is max. 35 C (according to IEC / EN 62271-1 / VDE 0671-1)
3) Depending on HV HRC fuse-link
4) Depending on the secondary equipment used
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 9
Technical Data
Switching capacity and classication of switching devices
Three-position switch-disconnector
Switching capacity for general-purpose switches according to IEC / EN 62271-103 (former: IEC / EN 60265-1 / VDE 0670-301)
Rated voltage Ur kV 7.2 12 15 17.5 24
Test duty Rated mainly active load 100 operations Iload [I1] A 630
TDload breaking current Iload 20 operations 0.05 Iload [I1] A 31.5
Test duty Rated closed-loop breaking current Iloop [I2a]
TDloop A 630
Test duty Rated cable-charging breaking current Icc [I4a]
TDcc A 68
Test duty TDlc Rated line-charging breaking current Ilc [I4b]
A 68
Test duty TDma Rated short-circuit making current Ima 50 Hz up to kA 63 63 63 63 50
60 Hz up to kA 65 65 65 65 55
Test duty TDef1 Rated earth-fault breaking current Ief1 [I6a]
A 200
Test duty TDef2 Rated cable-charging breaking current and line-charging breaking
current under earth-fault conditions Ief2 [I6b (3 I4a) or I6b (3 I4b)] A 115
Cable-charging breaking current under earth-fault conditions
with superimposed load current I1 + 3 I4a A 630 +115
Number of operating cycles, mechanical / Classication n 1000 / M1
Number of operating cycles, electrical with Iload / Classication n 100 / E3
Number of short-circuit making operations with Ima / Classication n 5 / E3 5 / E3 5 / E3 5 / E3 5 / E3
C-classication for general-purpose switches (no restrikes, TD: Icc, Ilc) C2 C2 C2 C2 C2
Switching capacity for make-proof earthing switch according to IEC / EN 62271-102 / VDE 0671-102
Rated short-circuit making current Ima 50 Hz up to kA 63 63 63 63 50
60 Hz up to kA 65 65 65 65 55
Number of operating cycles, mechanical / Classication n 1000 / M0
Number of short-circuit making operations n 5
Classication E2
Switching capacity for make-proof earthing switch, feeder side, in transformer feeder with HV HRC fuses
Rated short-circuit making current Ima 50 Hz kA 5
60 Hz kA 5.2
Rated short-time withstand current Ik with tk = 1 s kA 2
Vacuum circuit-breaker
Switching capacity according to IEC / EN 62271-100 / VDE 0671-100
Type 1.1 with three-position disconnector
Rated voltage Ur kV 7.2 12 15 17.5 24
Rated normal current of feeders Ir A 630
50 Hz Rated short-time for switchgear with tk = 1 s up to kA 25 25 25 25 20
withstand current Ik for switchgear with tk = 3 s up to kA 20
Rated peak withstand current Ip up to kA 63 63 63 63 50
Rated short-circuit breaking current Isc up to kA 25 25 25 25 20
Rated short-circuit making current Ima up to kA 63 63 63 63 50
60 Hz Rated short-time for switchgear with tk = 1 s up to kA 25 25 25 25 21
withstand current Ik for switchgear with tk = 3 s up to kA 21
Rated peak withstand current Ip up to kA 65 65 65 65 55
Rated short-circuit breaking current Isc up to kA 25 25 25 25 21
Rated short-circuit making current Ima up to kA 65 65 65 65 55
Number of mechanical operating cycles for disconnector n 1000
Number of mechanical operating cycles for earthing switch n 1000
Number of mechanical operating cycles for earthing switch n 10,000
Classication of circuit-breaker M2, E2, C2, S2
Classication of disconnector M0
Classication of make-proof earthing switch E2
Rated operating sequence O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO on request
Number of short-circuit breaking operations n 25 or 50
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 11
Product Range
Individual panels and modules freely congurable for up to 4 functions in the block
HA40-2291 eps
Vacuum
HA40-2125a eps
Three-position
switch-disconnector
Three-position
disconnector
Capacitive voltage
detecting system
HV HRC fuse
HA40-2127a eps
Cable connection
with outside cone
(not included in the
scope of supply)
HA40-2123.eps
Surge arrester
or limiter
Make-proof
earthing switch
Transformer feeder
Type T
HA40-2126a eps
430 mm wide
1)
HA40-2129a eps
430 mm wide 430 mm wide
Three-position
switch-disconnector
Three-position
disconnector
Capacitive voltage
detecting system
HA40-2131c eps
HA40-2123.eps
Plug-in voltage
transformer
4MT3
HA40-2133b eps
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 13
Product Range
Individual panels
HA40-2135b eps
Type R(500) Type L(500) circuit-breaker
500 mm wide (with circuit-
1) 1)
breaker
type 1.1 or
4MT3 4MT3
type 2)
Three-position
500 mm wide
switch-disconnector
*) *)
Capacitive voltage
detecting system
4MT8 4MT8 *)
Three-phase
current transformer
Surge arrester
or limiter
HA40-2123.eps
4MT3 4MT3 Plug-in voltage
transformer
Type E
HA40-2138a eps
HA40-2136a eps
Type E(500)
310 mm wide 500 mm wide
1) 1)
4MT3
Billing metering panels as transfer panel to the right, with cable connection
Current transformer,
cast-resin insulated
HA40-2139a eps
Voltage transformer,
cast-resin insulated
P1 P2
P1 P2
P2 P1
P2 P1
Capacitive voltage
detecting system
Fixed earthing
points for
busbar earthing
P1 and P2
HA40-2123.eps
Billing metering panels as transfer panel to the left, with cable connection
are terminal
designations of
HA40-2140a eps
the current
transformer
P1 P2
P1 P2
P2 P1
P2 P1
Billing metering panels as transfer panel with busbar connection on both sides
HA40-2141a eps
P1 P2 P2 P1 P1 P2 P2 P1
Billing metering panels as transfer panel with cable connection on both sides
P1 P2
P1 P2
P2 P1
P2 P1
HA40-2142a eps
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 15
Product Range
Product range overview of panel blocks (preferred versions)
Panel blocks with transformer feeders, Panel blocks with circuit-breaker feeders,
optionally with busbar extension optionally with busbar extension
KT 1 transformer feeder, KL 1 circuit-breaker feeder,
K Radial cable 1 radial cable connection
HA40-2108b eps
HA40-2113a eps
K Radial cable 1 radial cable connection
connection as connection as
incoming feeder 740 775 1200 incoming feeder 740 775 1200
1400 1400
1700 1700
HA40-2219a eps
1400 1400
1700 1700
HA40-2114a eps
1 circuit-breaker feeder
HA40-2110b eps
HA40-2116a eps
2 circuit-breaker feeders
HA40-2117a eps
(type 2)
1480 775 1200 1480 775 1200
1400 1400
1700 1700
16 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Product Range
Product range overview of panel blocks (preferred versions)
Panel blocks with ring-main feeders, Panel blocks with transformer feeders,
optionally with busbar extension optionally with busbar extension
RR 2 ring-main feeders TT 2 transformer feeders
HA40-2121b eps
HA40-2118a eps
HA40-2122b eps
HA40-2119a eps
RRT-R
HA40-2361 eps
RRT-RRT
HA40-2362 eps
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 17
Design
Panel design (examples)
HA40-2144e eps
HA40-2143c eps
2 2
6 6
1 1
7 7
3 3
8 9
4 4
11
9
12
13
10
10
Circuit-breaker feeder
Type L Section
5 1 Control board (for details, see page 23)
HA40-2145d eps
2 2 Busbar arrangement
6 3 Three-position switch-disconnector
1 1 4 Pressure relief device
15 5 Wiring duct, removable, for protection
14 and / or bus wires
18 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Design
Panel design (examples)
Circuit-breaker feeder
Type L(500) Section
1 Control board (for details, see page 23)
HA40-2146d eps
5 10
11
12
Type 2
Section
13 Low-voltage compartment (standard) for vacuum circuit-breaker
HA40-2263b eps
3
7
1
8
4
9
5 10
11
17
18
12
Type 1.1
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 19
Design
Panel design (examples)
3
8
4
9a
1 9b
10
12
Section
7 1 Sockets for voltage detecting system
HA40-2149d eps
2 Busbar connection
3 Busbar vessel, lled with gas
12
20 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Design
Panel design (examples)
Panel block
Type 8DJH Compact RRT Section
1 Control board (for details, see page 23)
HA40-2363 eps
11 9
2 Three-position switch-disconnector
3 Pressure relief device
4 Switchgear vessel, lled with gas
5 Operating mechanism of switching device
10 2
6 Bushing for cable plug with bolted contact (M16)
7 Cable compartment cover
1 8 Earthing busbar with earthing connection
9 HV HRC fuse assembly
5 10 Bushing for cable plug with plug-in contact
4
11 Pressure relief duct downwards for transformer
feeder (option)
6
3
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 21
Design
Outdoor enclosure
R-HA40-8DJH-179.tif
For outdoor applications on company grounds
Enclosure attached to standard indoor panels
Enclosure with three different heights, for 1200 mm
switchgear height (optionally with low-voltage compart-
ment as a 200 mm, 400 mm or 600 mm high version), or
1400 mm switchgear height (optionally with low-voltage
compartment as a 200 mm or 400 mm high version)
Enclosure with four different widths for freely congura-
ble, non-extendable switchgear rows up to a switchgear
width of 2000 mm (for dimensions, see page 82)
Internal arc classication IAC A FL or FLR to 21 kA/1 s
according to IEC 62271-200
Degree of protection IP 54.
R-HA40-8DJH-178.tif
R HA40 8DJH 178 tif
22 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Design
Operation (examples)
HA40-2265b eps
locking devices and local-remote switches are arranged
according to the panel type and version. The ready-for-service
indicator and rating plates are tted in accordance with the
panel blocks. 4
Operation is identical for transformer and circuit-breaker 5
feeders. First, the operating mechanism must be charged;
then, closing / opening is done through separate pushbuttons. 6
The condition of the energy store is indicated.
All actuating openings are functionally interlocked against
7
each other, and are optionally lockable. Separate operating
levers for the disconnecting and earthing function are
optionally available.
HA40-2266a eps
R-HA40-114.tif
HA40-2264a eps
12
11
1 4
10
5 9
2 6
8
3
3
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 23
Components
Three-position switch-disconnector
Features
Switch positions: Three-position switch-disconnector
CLOSED OPEN EARTHED
Switching functions as general-purpose switch- Busbar
disconnector (class E3) according to CLOSED
IEC / EN 62271-103 / VDE 0671-103
IEC / EN 62271-102 / VDE 0671-102 OPEN
Designed as a three-position switch with the functions
Switch-disconnector and
Make-proof earthing switch
Operation via rotary bushing welded gas-tight into the EARTHED
front of the switchgear vessel
HA40-2150b eps
Climate-independent contact in the gas-lled switchgear
vessel
Maintenance-free for indoor installation according to
IEC / EN 62271-1 / VDE 0671-1 Feeder
Individual secondary equipment.
Mode of operation
The operating shaft forms one unit together with the three
contact blades. Due to the arrangement of the xed contacts
(earth busbar), it is not necessary to interlock the CLOSE OPEN / CLOSE
and EARTHING functions.
Closing operation
During the closing operation, the operating shaft with the
moving contact blades changes from the OPEN to the OPEN / EARTH
CLOSED position.
The force of the spring-operated mechanism ensures a high
operator-independent closing speed and a reliable connec-
tion of the main circuit.
CLOSED OPEN
Opening operation
During the opening operation, the arc is caused to rotate
A40-2273 eps
Earthing operation
The EARTHING operation is implemented by changing from
the OPEN to the EARTHED position.
24 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Operating mechanisms for the three-position switch
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 25
Components
Operating mechanisms for the three-position switch, equipment (optional)
Abbreviations:
NO = Normally open contact
NC = Normally closed contact
26 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Vacuum circuit-breaker
Position indicators
Pushbuttons for CLOSING and OPENING the circuit-breaker
Interlocking between circuit-breaker and disconnector.
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 27
Components
Vacuum circuit-breaker
HA40-2271a_en eps
HA40-2270a_en eps
10,000 10,000
Permissible operating cycles
2000 2000
1000 1000
500 500
200 200
1 2 1 2
100 100
50 50
25 25
10 10
0.1 0.2 0.5 1 2 5 10 20 kA 50 0.1 0.2 0.5 1 2 5 10 25 kA 50
Breaking current (r.m.s. value) Breaking current (r.m.s. value)
HA40-2268a_en eps
10,000 10,000
5000 5000
Permissible operating cycles
2000 2000
1000 1000
500 500
200 200
100 100
50 50
3 4 3 4
20 20
10 10
6 6
2 2
1 1
0.1 0.2 0.5 1 2 5 10 16 kA 50 0.1 0.2 0.5 1 2 5 10 20 kA 50
Breaking current (r.m.s. value) Breaking current (r.m.s. value)
Max. number of
short-circuit breaking operations
n = 25 n=6
n = 50 n = 20
28 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Secondary equipment of the vacuum circuit-breakers
Closing solenoid z {
Undervoltage release { {
Shunt release
Comprising: C.t.-operated release { {
Energy store and unlatching mechanism Low-energy magnetic release {
Electromagnetic system, which is permanently connected Undervoltage release { {
to voltage while the vacuum circuit-breaker is closed; Anti-pumping z o.r.
tripping is initiated when this voltage drops. Circuit-breaker tripping signal z {
Features
Busbar extension possible on all individual panels and Interconnecting the panels
panel blocks (ordering option) 4 1 2
Plug-in unit consisting of contact coupling and screened
silicone coupling
Insensitive to pollution and condensation
Switchgear installation, extension or panel replacement is
possible without gas work
Busbar connections to metering panels are possible.
Every panel block and every individual panel is optionally
available with busbar extension on the right, on the left or
on both sides. This offers a high exibility for the creation
of switchgear congurations whose functional units can be
lined up in any order. Local installation and lining up is done
HA40-2152a eps
without gas work.
Lining up takes place as follows:
3
By the busbar couplings on the medium-voltage side.
Tolerances between adjacent panels are compensated by
spherical xed contacts and the movable contact coupling
with degrees of freedom in all axis directions.
By safe dielectric sealing with screened silicone couplings
that are externally earthed and adjustable to tolerances.
These silicone couplings are pressed on with a dened
pressure when the panels are interconnected. Surge-proof termination
On free busbar ends, screened dummy plugs are inserted, 5
each of which is pressed on through a metal cover. A com-
mon protective cover with a warning is xed over all three
covers.
By centering bolts for easier switchgear installation and
xing of adjacent panels.
By bolted panel joints with dened stops for the distances
between adjacent panels and the associated pressure for
contact pieces and silicone couplings.
Switchgear installation, extension or replacement of one
or more functional units requires a lateral wall distance
200 mm.
HA40-2215 eps
6 7
1 Contact piece
2 Silicone coupling
3 Tension spring for earthing
4 Centering bolt
5 Silicone dummy plug with insertable sleeve
6 Clamping cover for dummy plugs
7 Busbar termination cover
30 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
HV HRC fuse assembly
Features
Application in switch-disconnector / fuse combination in HV HRC fuse assembly
Transformer feeders (T)
HA40-2153c eps
Bus sectionalizer with switch-disconnector/fuse 1 2 3
combination (H)
HV HRC fuse-links according to DIN 43625
(main dimensions) with striker; medium version
according to IEC / EN 60282-1/ VDE 0670-4
As short-circuit protection for transformers
With selectivity depending on correct selection
to upstream and downstream connected equipment
1-pole insulated
Requirements according to IEC / EN 62271-105 / VDE 0671-105 9 8 5 7 6 5 4
fullled in high-voltage switch-fuse combinations
Climate-independent and maintenance-free
Fuse assembly connected to the three-position switch- 1 Fuse box
disconnector via welded-in bushings and connecting bars 2 Fuse slide
Arrangement of fuse assembly below the switchgear vessel 3 Tripping pin for spring-operated / stored-energy mechanism
Fuses can only be replaced if feeder is earthed 4 Sealing cover with seal
Fuse slide for reference dimension 292 mm and 442 mm 5 Locking cap
Fuse link in
disconnector is tripped via an articulation which is integrated
service condition
into the cover of the fuse box (see gure).
In the event that the fuse tripping fails, e.g. if the fuse has
been inserted incorrectly, the fuse box is protected by ther- Fuse tripping
mal protection. The overpressure generated by overheating through striker
trips the switch via the diaphragm in the cover of the fuse
box and via an articulation. This prevents the fuse box from
incurring irreparable damage. Fuse tripping through
overpressure, e.g. if HV
This thermal protection works independently of the type HRC fuse-link has been
and design of the HV HRC fuse used. Like the fuse itself, it is inserted incorrectly
maintenance-free and independent of any outside climatic
effects.
Note to HV HRC fuse-links
Furthermore, the HV HRC fuses (e.g. make SIBA) release
the striker depending on the temperature and trip the According to IEC 60282-1 (2009) Clause 6.6, the break-
switch-disconnector as early as in the fuse overload range. ing capacity of HV HRC fuses is tested within the scope of
the type test at 87% of their rated voltage. In three-phase
Impermissible heating of the fuse box can be avoided in
systems with resonance-earthed or isolated neutral, under
this way.
double earth fault and other conditions, the full phase-to-
Replacement of HV HRC fuse-links phase voltage may be available at the HV HRC fuse during
(without tools) breaking. Depending on the size of the operating voltage of
such a system, this applied voltage may then exceed 87%
Isolate and earth the transformer feeder
of the rated voltage. It must therefore already be ensured
Open the cover of the fuse access during conguration of the switching devices and selection
Replace the HV HRC fuse-link. of the HV HRC fuse that only such fuse-links are used, which
either satisfy the above operating conditions, or whose
breaking capacity was tested at least with the maximum sys-
tem voltage. In case of doubt, a suitable HV HRC fuse must
be selected together with the fuse manufacturer.
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 31
Components
Allocation of HV HRC fuses and transformer ratings
32 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Allocation of HV HRC fuses and transformer ratings
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 33
Components
Allocation of HV HRC fuses and transformer ratings
34 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Allocation of HV HRC fuses and transformer ratings
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 35
Components
Allocation of HV HRC fuses and transformer ratings
36 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Cable-type current transformers 4MC70 33 and 4MC70 31
Features
According to Cable-type current transformer Cable-type current transformer
IEC / EN 61869-1 and -2/ 4MC70 33, 4 overall heights 4MC70 31
VDE 0414-9-1 and -2
Designed as ring-core
R-HA41-024a.eps
R-HA41-025.eps
current transformers, 1-pole
H
Free of dielectrically
H
stressed cast-resin parts
(due to design)
Insulation class E
Inductive type
Secondary connection by
means of a terminal strip
in the panel.
Installation
The mounting location is out-
side the switchgear vessel,
around the cable at the panel
connection; installation on
the cable on site. Technical data Technical data
Note: Installation inside or Cable-type current transformer 4MC70 33 Cable-type current transformer 4MC70 31
underneath the panel depend-
Primary data Primary data
ing on the panel type and
Highest voltage 0.72 kV Highest voltage 0.72 kV
the overall transformer
for equipment Um for equipment Um
height.
Rated current IN 20 A to 600 A Rated current IN 50 A to 600 A
Rated short-duration 3 kV Rated short-duration 3 kV
power-frequency withstand power-frequency withstand
voltage (winding test) voltage (winding test)
Rated short-time up to 25 kA / 1 s Rated short-time up to 25 kA / 1 s
thermal current Ith or 20 kA / 3 s thermal current Ith or 14.5 kA / 3 s
Rated continuous 1.2 x IN Rated continuous 1.2 x IN
thermal current ID thermal current ID
Transient overload 1.5 x ID / 1 h or Transient overload 1.5 x ID / 1 h or
current 2 x ID / 0.5 h current 2 x ID / 0.5 h
Rated dynamic 2.5 x Ith Rated dynamic 2.5 x Ith
current Idyn current Idyn
Dimensions Dimensions
Overall height H, mm 65 110 170 285 Overall height H 89 mm
depending on
core data
Outside diameter 150 mm Width x depth 85 mm x 114 mm
Inside diameter 55 mm Inside diameter 40 mm
For cable diameter 50 mm For cable diameter 36 mm
Other values on request Other values on request
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 37
Components
Three-phase current transformer 4MC63
Features
According to Three-phase current transformer 4MC63
IEC / EN 61869-1 and -2/
VDE 0414-9-1 and -2
R-HA41-022.eps
Designed as ring-core
current transformer, 3-pole
Free of dielectrically
stressed cast-resin parts
(due to design)
Insulation class E
Inductive type
Climate-independent
Technical data Technical data
Secondary connection by Three-phase current transformer 4MC63 10 Three-phase current transformer 4MC63 11
means of a terminal strip for IN 150 A and ID = 630 A for IN 400 A and ID = 630 A
in the panel.
Primary data Primary data
Installation Highest voltage 0.72 kV Highest voltage 0.72 kV
Mounting location: for equipment Um for equipment Um
For individual panels type Rated current IN A 150 100 75 50 Rated current IN A 400 300 200
R(500) and L(500) (optional) Rated short-duration 3 kV Rated short-duration 3 kV
Arranged outside the power-frequency withstand power-frequency withstand
switchgear vessel on voltage (winding test) voltage (winding test)
the bushings of the cable Rated short-time up to 25 kA / 1 s Rated short-time up to 25 kA / 1 s
connection thermal current Ith or 20 kA / 3 s thermal current Ith or 20 kA / 3 s
Factory-assembled. Rated continuous 630 A Rated continuous 630 A
thermal current ID thermal current ID
Further designs
Transient overload 1.5 x ID / 1 h Transient overload 2 x ID / 0.5 h
(option) current current
For protection equipment Rated dynamic 2.5 x Ith Rated dynamic 2.5 x Ith
based on the current-trans- current Idyn current Idyn
former operation principle:
Secondary data Secondary data
Protection system 7SJ45 as
Rated current A 1 0.67 0.5 0.33 Rated current A 1 0.75 0.5
denite-time overcurrent
Rating VA 2.5 1.7 1.25 0.8 Rating VA 4 3 2
protection
Current at ID 4.2 A Current at ID 1.575 A
Denite-time overcurrent
Protec- Class 10 P Protec- Class 10 P
protection relay,
tion Overcurrent factor 10 tion Overcurrent factor 10
make Woodward / SEG, core core
type WIP 1
Denite-time overcurrent
protection relay,
make Woodward / SEG,
type WIC.
38 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Bus / cable-type current transformer 4MC70 32
Features
According to Bus / cable-type current transformer
IEC / EN 61869-1 and -2/ 4MC70 32
VDE 0414-9-1 and -2
R-HA41-027.eps
Designed as ring-core
current transformer, 1-pole
Free of dielectrically
stressed cast-resin parts B
(due to design)
Insulation class E
Inductive type
Secondary connection by
means of a terminal strip Technical data Panel section type V
in the panel. Bus / cable-type current transformer 4MC70 32
HA40-2154a eps
Mounting location: Highest voltage 0.72 kV
Arranged outside the for equipment Um
switchgear vessel on the Rated current IN 200 A to 600 A
screened busbar section in Rated short-duration 3 kV
bus sectionalizer panels power-frequency withstand
type S and V with the voltage (winding test)
option of busbar current Rated short-time up to 25 kA / 1 s
transformers thermal current Ith or 20 kA / 3 s
Arranged outside the Rated continuous 1.2 x IN
switchgear vessel around thermal current ID
the cable at the panel Transient overload 1.5 x ID / 1 h or
connection for 310 mm current 2 x ID / 0.5 h
panel width (cable feeders Rated dynamic 2.5 x Ith
type R and K), transformers current Idyn
mounted on a supporting Secondary data
plate at the factory;
Rated current 1 A (option: 5 A) 1
nal assembly around the
Mea- Class 0.2 0.5 1
cables on site.
suring Overcurrent factor without FS5 FS10
Note: Depending on core 130 130
Rating 2.5 VA to 10 VA
the transformer overall
height: Installation inside Protec- Class 10 P 5P *)
tion Overcurrent factor 10 10
or underneath the panel.
core
Rating 2.5 VA to 15 VA
Dimensions
Overall width B, 80 mm / 150 mm
depending on core data
and mounting location 1 Bus / cable-type current transformer
4MC70 32
Outside diameter 125 mm
Inside diameter 55 mm
Other values on request *) On request
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 39
Components
Plug-in voltage transformers 4MT3 and 4MT8
Common features
According to Plug-in Plug-in
IEC / EN 61869-1 and -3/ voltage transformer 4MT3 voltage transformer 4MT8
VDE 0414-9-1 and -3
1-pole, plug-in design
Inductive type
Connection with
plug-in contact
R-HA41-020.eps
Safe-to-touch due
R-HA35-120.eps
to metal cover
Secondary connection by
means of plugs inside the
panel.
Features
Current transformer 4MA7 Current transformer 4MA7 Voltage transformer 4MR
According to
R-HA41-030.eps
R-HA41-029.eps
IEC / EN 61869-1 and -2/
VDE 0414-9-1 and -2
Dimensions according to
DIN 42600-8 (small design)
Designed as indoor support-
type current transformer,
1-pole
Cast-resin insulated
Insulation class E
Secondary connection by
means of screw-type
terminals. Technical data Technical data
Voltage transformer 4MR Current transformer 4MA7, 1-pole Voltage transformer 4MR, 1-pole
According to Primary data Primary data
IEC/EN 61869-1 and -3/ Highest voltage up to 24 kV Highest voltage for equipment 1.2 x Un
VDE 0414-9-1 and -3 for equipment Um Rated voltage (8 h) = 1.9 x Un
Dimensions according to Rated short-duration up to 50 kV Rated voltage Ur Operating voltage Un
DIN 42600-9 (small design) power-frequency
kV kV / 3
withstand voltage Ud
Designed as indoor voltage 3.6 3.3
Rated lightning impulse up to 125 kV
transformer: 7.2 3.6
withstand voltage Up
Type 4MR, 1-pole
Rated current IN 20 A to 600 A 4.2
Option: Type 4MR, 2-pole
Rated short-time up to 25 kA / 1 s 4.8
Cast-resin insulated
thermal current Ith 5.0
Insulation class E Rated continuous 1.2 x IN 6.0
Secondary connection by thermal current ID 6.3
means of screw-type Rated dynamic max. 2.5 x Ith 6.6
terminals. current Idyn
12 7.2
Secondary data 10.0
Rated current 1 A or 5 A 11.0
Mea- Class 0.2 0.5 1 11.6
suring Overcurrent factor without FS5 FS10 17.5 12.8
core
Rating 2.5 VA to 30 VA 13.2
Secondary data
Rated voltage 1st winding 100 / 3
in V 110 / 3
120 / 3
Auxiliary 100 / 3
winding 110 / 3
(option) 120 / 3
Rating Class
in VA up to 20 0.2
60 0.5
100 1.0
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 41
Components
Current sensors
Common features
According to
IEC 61869-8
R-HA40-152.tif
R-HA40-147.tif
(current sensors)
Example for available
secondary devices that can
be connected: Ring-core current sensor Ring-core current sensor
SICAM FCM SMCS-JW 1001 SMCS/T-JW 1002, divisible
7SJ81
Current sensors
(make Zelisko)
R-HA40-148.tif
R-HA40-151.tif
The current sensors are
inductive current transfor-
mers whose secondary
winding delivers a voltage Three-phase ring-core current sensor Ring-core current sensor
signal through a precision SMCS3-JW1004 with integrated GAE120/SENS-JW 1003 for
shunt. At the rated primary earth-fault detection sensor earth-fault detection, divisible
current, this is 225 mV.
Depending on their version,
the sensors have a dual
accuracy class; the output
signal can be equally used for
measuring, protection and, Technical data
if required, earth-fault detec- SMCS-JW1001 SMCS/ GAE120/ SMCS3-
tion. The outgoing leads of T-JW1002 SENS-JW1003 JW1004
the sensors are directly
Primary data
connected to the secondary
Highest voltage
device (SICAM FCM, 7SJ81). for equipment Un
0.72 / 3 kV 0.72 / 3 kV 0.72 / 3 kV 0.72 / 3 kV
Secondary data
Output signal 225 mV 225 mV 225 mV 225 mV
Class 0.5; 1; 3 1; 3 0,5; 1; 3
Measuring
Overcurrent factor
Class 5P 5P 5P
Protection
Overcurrent factor 10 20 10; 20 10
Class 1 1
Earth-fault Angle error 120' 120'
detection 10 % (at 0.4 A) 10 %
Composite error e
20 % (at 200 A) (at 0.4 A)
Rated burden 20 kOhm 20 kOhm 20 kOhm 20 kOhm
1) Usable up to 2 x I n = 600 A (output signal 2 x 225 mV) at constant accuracy class and
half overcurrent factor
2) Mounting location at the bushings around the screened cable plug
42 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Voltage sensors
Common features
According to
IEC 61869-7
(voltage sensors)
R-HA40-154.tif
R-HA40-153.tif
Example for available
secondary devices that can
be connected:
SICAM FCM Voltage sensor Voltage sensor
7SJ81 SMVS-UW 1001 SMVS-UW 1002
Voltage sensors
(make Zelisko)
The voltage sensors are
resistor dividers which
provide an output signal
of 3.25 V / 3 at the rated Technical data
primary voltage. The out- SMVS-UW1001 SMVS-UW1002
going leads of the sensors
are directly connected to the Primary data
secondary device Highest voltage
(SICAM FCM, 7SJ81). for equipment Um 1.2 x Un 1.2 x Un
Rated voltage (8 h) 1.9 x Un 1.9 x Un
Rated voltage Ur 12 kV 24 kV 12 kV 24 kV
Operating voltage Un 10 kV 20 kV 10 kV 20 kV
Secondary data
Rated voltage 3.25 V / 3 3.25 V / 3
Class 0.5; 1; 3 0.5; 1; 3
Rated burden 200 kOhm 1% 200 kOhm 1%
Installation
Mounting location On the screened cable plugs On the screened cable plugs
make Nexans type 440TB, K440TB; make TE Connectivity type RSTI-58,
other types and makes on request RSTI-CC58xx,
make nkt cables type CB-24 and
CC-24; other types and makes
on request
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 43
Components
Cable connection for feeders with bolted contact and outside cone type C
Features
Access to the cable compart- Cable compartment
ment only if the feeder has
HA40-2156b eps
HA40-2155a eps
HA40-2157b eps
been disconnected and
earthed
Bushings according to
DIN EN 50181 with outside
C
B
cone and bolted connection
M16 as interface type C. L1 L2 L3 L1 L2 L3 L1 L2 L3
60 95 95 60 85 130 130 85 100 150 150 100
Connection of
Cable elbow plugs or cable
T-plugs with bolted contact Panel width 310 mm Panel width 430 mm Panel width 500 mm
M16 for 630 A
Paper-insulated mass-
impregnated cables via
customary adapters
Thermoplastic-insulated
Switchgear height 1040 2) 1200 1400 without 1400 with
cables (1-core and 3-core without low-voltage absorber base absorber base,
cables). compartment 1) or 1700
Option Typical K, R 500 660 860 1160
Panel width 310 mm A
Mounted cable clamps on Typical R (8DJH Compact) 200 500
cable bracket. Panel width 430 mm Typical K(E), L B 660 860 1160
Panel width 500 mm Typical R(500), L(500) C 510 710 1010
Cable plugs
As screened (semi-conduc-
tive) design independent of 1) Option: With low-voltage compartment
the site altitude, 2) Only for panel blocks RR, RRR, RT, RRT and RTR
or
as unscreened (insulated) Connection options
design, but then dependent
185260 290298
on the site altitude.
Surge arresters
Pluggable on cable T-plug, 1 1 3
2
275380
HA40-2163a eps
44 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Cable plugs for feeders with bolted contact and outside cone type C (further types on request)
HA40-2164b eps
HA40-2277 eps
(not for 8DJH Compact). The assignment to selected types
of cable plugs and cable plug / surge arrester combinations is
given in the following tables. 300 a 480 a
63 b 63 b
775 775
775 + (a+10) 775 + (a+10)
1) Applies to panels of 310- and 430-mm. For individual panels of 500 mm, no deep cable compartment cover
and oor opening are required except for serial no. 2 and no. 5 with cable compartment cover deeper by 105 mm (a).
2) In connection with current transformers or sensors on the cable, use only screened systems.
3) See drawing on page 46.
K = Cable plug = Surge arrester
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 47
Components
Cable connection for transformer feeders with plug-in contact and outside cone type A
Features
Access to the cable compartment only if the feeder has Cable compartment
been disconnected and earthed
Bushings according to DIN EN 50181 with outside cone
and plug-in contact as interface type A.
HA40-2165a eps
Connection of
Cable elbow plugs or straight cable plugs
Connection cross-sections up to 120 mm2.
B1
B2
Option
L1 L2 L3
Mounted cable clamps on cable bracket
HA40-2364 eps
Bushings according to DIN EN 50181 with outside cone 80 135 135 80
and bolted contact as interface type C for cable routing
downwards.
Panel width 430 mm (standard) 8DJH Compact
210300
HA40-2365 eps
At the top with cable elbow plug: To the rear (standard)
HA40-2166a eps
Cable plugs
Cable routing downwards Cable routing to the rear
As screened (semi-conductive) design independent of the with cable elbow plug with cable elbow plug
site altitude,
or
as unscreened (insulated) design, but then dependent on
the site altitude.
270310
1700
Panel Typical T A 62 222 422 722
width Typical T B1 1245 1545
430 mm (8DJH Compact) B2 1143 1443 Cable routing downwards Cable routing upwards
with straight plug with straight plug
HA40-2366 eps
HA40-2168 eps
Cable testing
For circuit-breaker and switch-disconnector feeders Cable testing
Cable testing equipment can be connected after removing
the protective cap and / or the end stopper from the cable
plug
Cable testing equipment and cable T-plug each of the 2 1
same make
DC voltage test
HA40-2035d eps
Before the test:
Remove any voltage transformers available at the cable
connection; short-circuit voltage indicators with earthing
points of test sockets.
8DJH switchgear for rated voltages up to 24 kV can be
Cable testing at the
subjected to cable tests at a DC test voltage of max. 96 kV
cable T-plug (example)
(when the switchgear is new) or, according to VDE, at 70 kV
for 15 minutes. The voltage at the busbar may be 24 kV in
this case.
Test voltages:
Rated voltage Max. test voltage applied to the 2 1
connected cable
(according to IEC / EN VDE 0278)
VLF 1)
0.1 Hz
HA40-2036d eps
1 Insulating cap
3 U0 6 U0,15 min 2 Measuring bolt
Ur U0 / U(Um) ULF Um max. Um
(kV) (kV) AC (kV) DC (kV) DC (kV)
12 6 / 10(12) 19 24 38 2) Cable testing at the
24 12 / 20(24) 38 48 70 cable elbow plug (example)
Standard interlocks
Three-position switch: Disconnecting function against Interlocking of three-position switch
earthing function (option: locking device)
Circuit-breaker feeder: Circuit-breaker against three-
position disconnector
Access to cable compartment is generally only possible if
the feeder is isolated
HA40-2225b eps
and
the feeder is earthed (EARTHED position).
For ring-main and circuit-breaker feeders
Option: Closing lockout
Prevents switching the three-position switch-disconnector
from OPEN position to CLOSED position when the cable
compartment cover is removed.
For transformer feeders Initial situation
HA40-2226b eps
Locking device for padlock
Shackle diameter 12 mm
Standard for transformer and circuit-breaker feeders
(stored-energy mechanisms)
Option for ring-main feeders (spring-operated mechanisms)
Three-position switch-disconnector lockable at the
operating mechanism in any desired switch position.
Release for disconnector operation
Key-operated interlock (option)
With cylinder locks from selected manufacturers
For the basic functionalities:
Switch-disconnector / disconnector
KF 1 Key free in OPEN
HA40-2227b eps
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 51
Components
Indicating and measuring equipment
Ready-for-service indicator
Features Gas monitoring
Self-monitoring; easy to read
Independent of temperature and pressure variations
Indicator on control board:
Independent of the site altitude
1 1 Indication:
Only responds to changes in gas density green: ready for service
Option: Alarm switch 1NO + 1NC for remote electrical red: not ready for service
HA40-2216a eps
indication. 2 Measurement box
Mode of operation 3 Magnetic coupling
HA40-2217a eps
switchgear.
2
While changes in the gas density during the loss of gas,
which are decisive for the dielectric strength, are displayed, 3
temperature-dependent changes in the gas pressure are
not. The gas in the measurement box has the same tempera-
ture as that in the switchgear vessel.
The temperature effect is compensated via the same pressure Stainless-steel vessel Ready-for-service
change in both gas volumes. lled with SF6 gas indicator
52 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Indicating and measuring equipment
R-HA40-103 eps
Plug-in A0
with plug-in indicator
voltage
with integrated indicator, type VOIS+,
VOIS R+, WEGA ZERO indicator A1
with integrated indicator, with integrated per phase at
repeat test of the interface, with integrat- the panel front A2
ed function test, type CAPDIS-S1+,
WEGA 1.2, WEGA 1.2 Vario, with integrat- A3
ed signaling relay, type CAPDIS-S2+,
WEGA 2.2. A4
R-HA40-104 eps
Plug-in voltage indicator A5
Verication of safe isolation from supply
phase by phase A6
Indicator suitable for continuous opera-
tion A7
Measuring system and voltage indicator
Integrated voltage indicator
can be tested
VOIS+, VOIS R+ A8
Voltage indicator ashes if high voltage is
present.
A0 CAPDIS-S2+: Operating voltage
VOIS+, VOIS R+
not present
Integrated display, without auxiliary
A1 Operating voltage present
R-HA35-154 eps
power
A2 Operating voltage not present
With indication A1 to A3 (see legend)
Maintenance-free, repeat test required For CAPDIS-S2+: Auxiliary power
With integrated 3-phase LRM test socket not present
for phase comparison A3 Failure in phase L1, operating vol-
With integrated signaling relay tage at L2 and L3 (for CAPDIS-Sx+
R-HA35-155 eps
CAPDIS-S1+
LRM system CAPDIS / VOIS
Without auxiliary power
plugged in installed
With indication A1 to A7 (see legend)
Without ready-for-service monitoring Voltage indication
Without signaling relays (without auxiliary via capacitive voltage divider (principle)
contacts).
C1 Capacitance integrated into bushing
CAPDIS-S2+ C2 Capacitance of the connection leads
With indication A0 to A8 (see legend) and the voltage indicator to earth
Only by pressing the Test pushbutton: ULE = UN / 3 during rated operation in the
ERROR indication (A8), e.g. in case of three-phase system
missing auxiliary voltage U2 = UA = Voltage at the capacitive interface of the
With ready-for-service monitoring switchgear or at the voltage indicator
(auxiliary power required)
With integrated signaling relay for signals
(auxiliary power required).
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 53
Components
Indicating and measuring equipment
WEGA ZERO
Voltage detecting system
according to IEC 62271-206 or Symbols shown
VDE 0671-206
R-HA35-141.eps
With indication A1 to A4 WEGA ZERO WEGA 1.2 WEGA 2.2
(see legend) WEGA 1.2 Vario
Maintenance-free L1 L2 L3 L1 L2 L3 L1 L2 L3
With integrated 3-phase test
socket for phase comparison A0
Degree of protection IP54. Integrated voltage indicator
WEGA ZERO A1
WEGA 1.2, WEGA 1.2 Vario
Voltage detecting system A2
according to IEC 61243-5 or R-HA40-2-WEGA_12.tif
VDE 0682-415 A3
With indication A1 to A5
(see legend) A4
Maintenance-free
Integrated repeat test of the A5
HA35-2758 eps
interface (self-monitoring)
With integrated function test Integrated voltage detecting system
WEGA 1.2, WEGA 1.2 Vario A6
(without auxiliary power) by
pressing the Display Test
pushbutton LC display gray: not illuminated
R-HA40-2-WEGA_22.tif
54 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Indicating and measuring equipment
Verication of correct
terminal-phase connections Phase comparison test units according to IEC 61243-5 or VDE 0682-415
Verication of correct terminal-
phase connections possible by
R-HA40-059 eps
R-HA40-089.tif
means of a phase comparison
test unit (can be ordered sepa-
rately)
Safe-to-touch handling of the
phase comparison test unit by in-
serting it into the capacitive taps
(socket pairs) of the switchgear.
R-HA35-175.eps
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 55
Components
Indicating and measuring equipment
R-HA40-136.tif
Ring-main, cable, transformer and circuit-breaker feeders
can optionally be equipped with short-circuit or earth-fault
indicators in different designs. The equipment features are
shown in the list enclosed.
Short-circuit and earth-fault indicators reduce the down-
times of a power system by limitation of fault locations
in medium-voltage systems.
ALPHA E
R-HA40-137.tif
Local ring-main unit
Short-circuit indicator has picked up
Short-circuit indicator has not picked up
SIGMA
Response of protection device with tripping
Basic functions
Adjustable pickup values
Phase-selective fault indication
Reset of fault indication: ComPass B
manually, automatically, from remote
Remote indication with relay contacts.
Short-circuit / ALPHA ALPHA SIGMA SIGMA SIGMA SIGMA ComPass ComPass ComPass ComPass EARTH /
earth-fault indicators M E F+E D D+ A AP B BP EARTH ZERO
Horstmann
Function
Short-circuit indication x x x x x x x x x x
Earth-fault indication x x x x x x x x
Indication of direction,
short circuit / earth fault x x x x
Undervoltage and
overvoltage indication x x
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 57
Components
Indicating and measuring equipment
R-HA40-141.tif
can optionally be equipped with short-circuit or earth-fault
indicators in different designs. The equipment features are
shown in the opposite table.
The three most common types of faults in medium-voltage
systems are earth faults in cables and switchgear, faults
and overloads of distribution transformers, as well as short
circuits in cables and switchgear. For fast fault location and IKI-20
minimization of downtimes, electronic fault indicators are
used:
Selective fault detection, and thus minimization of
downtimes
R-HA40-142.tif
Reliable fault detection through electronic
measured-value acquisition
Remote indication of fault events and measured values.
1. Short-circuit and earth-fault indicator IKI-20
Universally adjustable
Current-transformer supported battery version or
IKI-20CPULS
auxiliary voltage versions available
Extended commissioning and testing functions.
6. Short-circuit-to-earth indicator
Short-circuit-to-earth detection in systems with
impedance-earthed neutral or temporarily impedance
earthed-neutral
Adjustable.
IKI-10light
58 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Indicating and measuring equipment
Short-circuit / IKI- IKI- IKI- IKI-20PULS IKI-20C IKI- IKI-22 IKI- IKI- IKI- IKI- IKI-
earth-fault indicators 20B 20T 20U 20CPULS 50_1F 50_1F_ 50_2F 50_2F_ 10-light-P
Kries EW_PULS EW_PULS
Function
Short-circuit indication x x x x x x x x x x x
Earth-fault indication x x x x x x x
Short-circuit-to-earth
x x x x x x x x x x
indication 5)
Direction indication x x x x x
Applicable for the following neutral earthing options
Impedance x x x x x x x x x x
Solid x x x x x x x x x x
Isolated x x x x x x x x x x
Compensated x x x x x x x x x x
Pickup current
Short-circuit current 100, 200, 400, 600, 800, 1000, 400, 600, 100, 200, 300, 400, 600,
100 ... 1000 A (steps of 100 A)
2000 A 800, 1000 A 800, 1000, 2000 A
Earth-fault current Transient fault detection 4 ... 30 A (steps of 1 A)
Short-circuit-to-earth 20, 40,
40, 80, 100, 150 A 40, 80, 100, 200 A 40 ... 200 A (steps of 10 A)
current 5) 60, 80 A
Pulse location x x x x
Pickup time
Short-circuit current 60, 80, 150, 200 ms 100 ms 60, 80, 150, 200 ms 60 1600 ms
Short-circuit-to-earth 70, 250
60, 80, 150, 200 ms 100 ms 60, 80, 150, 200 ms 60 1600 ms
current 5) ms
Earth-fault current Pulse Pulse
Transient fault detection 400 3000 ms
location location
Reset
Manual x x x x x x x x x x x x
Automatic x x x x x x x x x x x x
From remote x x x x x x x x x x
Remote indication
Passing contact adjustable x x x adjustable
Maintained contact adjustable adjustable
Interface
RS485 / MODBUS x x x x
Power supply
Lithium battery x x x
External auxiliary voltage Only for transient fault
x x x Buffered for 6 h by internal capacitor x
detection
Current inputs
Phase current 3 3 3 3 3 3 3 3 3 6 6
Summation current 1 1 1 1 1 1 1) 0 2) 0 2) 0 2) 1
Voltage inputs
Via CAPDIS + Y-cable 3 3 6 6
Measuring function
Current x 4) x 4) x 4) x 4)
Voltage x 4) x 4) x 4) x 4)
Load ow direction x 4) x 4) x 4) x 4)
cos phi x 4) x 4) x 4) x 4)
Frequency x 4) x 4) x 4) x 4)
Active power x 4) x 4) x 4) x 4)
Apparent power x 4) x 4) x 4) x 4)
Reactive power x 4) x 4) x 4) x 4)
Release outputs
Potential-free 13 13 13 13 2 2 4 4 4 4 4 1
Supplied by internal
2 3) 2 3) 2 3) 2 3)
capacitor
Binary inputs
Number 2 (test + reset) 2 (test + reset) 4
1) Optional for wattmetric detection of earth-fault direction 4) Momentary value, mean value and min / max value, directional
2) Creation of sum signal via 3 transformers mounted around the conductor 5) Short-circuit to earth = Earth fault in impedance-earthed system
3) 0.1 Ws, 24 V DC
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 59
Components
Indicating and measuring equipment
R-HA40-146.tif
Earth-fault function
x
(impedance-earthed system)
Indication of direction,
x
short-circuit/earth-fault
Undervoltage and overvoltage
x
indication
Applicable for the following neutral earthing options SICAM FCM
Impedance x
Solid x Short-circuit and earth-fault indicators, make Siemens
Isolated x SICAM FCM is a short-circuit and earth-fault indicator with
Compensated x direction indication, operating with protection algorithms
Pickup current and advanced low-power current and voltage sensors
Short-circuit current 50 ... 2000 A (steps of 1 A) according to IEC 60044.
Earth-fault current 1 ... 1000 A (steps of 1 A)
Pulse location Main features:
Pickup time Usable in earthed, isolated and resonance-earthed
Short-circuit current 40 ms systems
< t < 60 s
Directional short-circuit and earth-fault detection
Earth-fault current 40 ms
< t < 60 s Precise and fast fault localization reduces expenses
Reset for personnel and traveling costs
Manual x Selective fault information with direction indication as a
Automatic x basis for "self-healing" applications
From remote x Resupply times possible in the range of minutes or
Remote indication seconds (depending on the primary part of the switchgear)
Passing contact adjustable Minimum loss of power grid and end consumer revenues
Maintained contact adjustable Reliable measured values for operational management and
Interface planning
RS485 / MODBUS x Targeted application of investment funds during network
Power supply planning and grid expansion
Lithium battery x Use of low-power sensors and high-quality measuring
External auxiliary voltage x systems with a measuring accuracy of 99%.
Current inputs
Phase current 3 (2) 1) SICAM FCM operates with sensors conforming to the
Summation current 0 (1) 1) standard IEC 60044-7/8. This enables exact measurements
Voltage inputs without calibration or adjustment to the primary
Via WEGA 1.2C / WEGA 2.2C 3x magnitudes.
Measuring function
Current x
Voltage x
Load ow direction x
cos phi x
Frequency x
Active power x
Apparent power x
Reactive power x
Relay outputs
Potential-free 2 2)
Binary inputs
Number 1
60 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Transformer monitor system
Transformer monitor IKI-30 (make Kries) Low-energy magnetic release (0.02 Ws)
Optional shunt release for auxiliary voltage supply
Application with vacuum circuit-breaker
Mounting location
Protection of distribution transformers with ratings that
In the front operating mechanism box of the feeder panel
cannot or should not be protected with HV HRC fuses:
In the low-voltage compartment (option) of the circuit-
Tripping of the circuit-breaker in case of overload breaker feeder
(delayed)
Response performance
Tripping of the circuit-breaker when the short-circuit Denite-time overcurrent characteristic
current arises. Denite-time overcurrent characteristic for earth-fault
protection
Inverse-time overcurrent characteristic
extremely inverse
normal inverse
Externally undelayed instantaneous tripping
Self-test function
R-HA40-107.eps
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 61
Components
Intelligent transformer substation
62 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Components
Intelligent transformer substation
Components Function
1
Uninterruptible power supply (UPS) The task of the UPS is to continue to ensure
Depending on the requested bridging time in the communication and/or the possibility
case of power failures, an uninterruptible to telecontrol the transformer substation in
power supply based on battery or capacitor case of power failure.
modules is used.
3
Remotely controllable operating In order to reduce the reclosing times in
mechanisms case of fault, the switch-disconnectors or
Motor operating mechanisms inside the circuit-breakers are equipped with motor
ring-main unit are available in original operating mechanisms for remote control.
equipment manufacturer quality. If
required, retrofitting is easily possible.
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 63
Components
Protection systems
LSP 2339-afp.tif
R-HA35-103.eps
Siemens 7SJ46
Instrument transformer as
Cable-type current transformer (standard)
Three-phase current transformer as option for 8DJH
SIPROTEC easy 7SJ45 SIPROTEC 4 7SJ61, 7SJ62
switchgear panels L(500).
Mounting location
In 200-mm-high top low-voltage unit (option) of the
circuit-breaker feeder.
Application of simple protection systems
Operating Transformer rating (kVA)
voltage (kV) 7SJ45 / 7SJ46 WIC 1-2P
6 160 160
10 200 250
13.8 250 400
R-HA35-177.tif
15 315 400
LSP 2874-afp.eps
20 400 500
Features
Overall heights Low-voltage compartment (example 500 x 600 mm)
200 mm, 400 mm, 600 mm, 900 mm
Option: Cover
R-HA40-128.eps
Partitioned safe-to-touch from the high-voltage part
of the panel
Installation on the panel:
Possible per feeder
Standard for circuit-breaker panels type L (1.1) and
bus sectionalizer panels
Option for all other panel types, depending on the
scope of the secondary equipment
Customer-specic equipment
For accommodation of protection, control, measuring
and metering equipment
Separate wiring duct on the switchgear beside the
low-voltage compartment (option)
Door with hinge on the left (standard for heights Open low-voltage compartment
of 400, 600 and 900 mm). with built-in equipment (option)
Low-voltage cables
Control cables of the panel to the low-voltage compart-
ment via multi-pole, coded module plug connectors
Option: Plug-in bus wires from panel to panel in the
separate wiring duct on the panel.
Low-voltage niche
Only inside billing metering panels type M Low-voltage niche
For accommodation of options, e.g.:
Voltage transformer m.c.b.s
Small distribution fuse-box and fuse-links type Diazed
or Neozed. 1
2
R-HA41-042a.eps
1 Low-voltage niche
2 Built-in equipment (option)
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 65
Dimensions
Room planning
Switchgear installation
15
HA40-2101a eps
Wall-standing arrangement
1 row
2 rows (for face-to-face arrangement)
775
Option: Free-standing arrangement.
Pressure relief
50 200*
The type of pressure relief selected has an effect on the
800**
switchgear depth, and places requirements on the size of the
cable basement and/or the room height. In case of pressure
relief upwards, the room heights reproduced in the type
test are decisive for the internal arc classication acc. to
IEC / EN 62271-200 / VDE 0671-200 (see table on page 67). Top view: Switchgear without pressure relief duct at the rear
Door dimensions
*) For lined up switchgear
The door dimensions have an inuence on the size of the
**) Depending on national requirements
transport units (see page 87) and the factory assembly of
For extension or panel replacement, a control aisle
panel groups, low-voltage compartments and pressure
of at least 1000 mm is recommended
absorber systems. If required, this installation work can
also be performed on site by the customer.
15
HA40-2107 eps
Switchgear xing
For oor openings and xing points of the switchgear,
see pages 83 to 86
890
775
Foundations:
Steel girder construction
Reinforced-concrete oor.
50 200*
Panel dimensions
See illustrations on pages 69 to 86.
Weight Top view: Switchgear with pressure relief duct at the rear
2600
2300
2300
2100
2000
1900
1800
1700
1600
1400
1400
1200
Switchgear height
1200 mm 1400 mm 1700 mm
66 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Dimensions
Room planning
The following type-tested versions of the pressure relief Upwards through rear pressure relief duct (for extendable
system are available for 8DJH switchgear: and non-extendable panel blocks, internal arc classication
Downwards into the cable basement (for individual panels up to IAC A FL 16 kA /1 s, minimum room heights according
and panel blocks, internal arc classication up to IAC A FL 21 to the table below), with pressure absorber system
kA /1 s or IAC A FLR 21 kA /1 s, minimum cross-section of the Upwards through base and rear pressure relief duct (for
cable basement according to the illustration below) individual panels and panel blocks, internal arc classication
To the rear (for non-extendable panel blocks with 1400 or up to IAC A FL 21 kA/1 s and IAC A FLR 21 kA/1 s, minimum
1700 mm switchgear height, internal arc classication up to room heights according to the table below), with pressure
IAC A FL 21 kA/1 s, a rear pressure relief outlet with a mini- absorber system.
mum cross-section of 1 m2 is required in the switchgear room
and must be supplied by the site)
HA40-2103b eps
3
Side view Switchgear height Room height
2 1400 mm 2000 mm
1700, 1800 mm 2200 mm
2300 mm 2400 mm
2600 mm 2600 mm
600 8001)
Side view
Switchgear installation with rear pressure Switchgear installation with base and rear pressure
relief duct (option) for panel block relief duct (option) for panel block
with IAC A FL or FLR up to 16 kA/1 s with IAC A FL or FLR up to 21 kA/1 s
HA40-2104b eps
HA40-2276a eps
HA40-2106d eps
2 2 2
2300
1400
1800
1700
4 5 5
4 4
775 1
15 880
775 1 775 1
Side view 15 890 15 890
Side view, wall-standing Side view, free-standing
arrangement without arrangement, also metering
metering panel panel for wall-standing arrangement
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 67
Dimensions
Room planning
For 8DJH Compact, the following types of pressure relief can For 8DJH with outdoor enclosure (option), the direction of
be selected: the pressure relief can be selected as follows:
Downwards into the cable basement for all feeders (inter- Downwards into the cable basement (internal arc classica-
nal arc classication up to IAC A FL or FLR 21 kA /1 s) tion up to IAC A FL or FLR 21 kA /1 s, minimum cross-section
Downwards into the cable basement for the ring-main of the cable basement according to the illustration below)
feeders, and to the rear for the transformer feeders (inter- To the rear (internal arc classication up to IAC A FL
nal arc classication up to IAC A F 21 kA /1 s). 21 kA /1 s; for wall-standing arrangement, a rear
The dimensions for wall distances, control aisles and cable pressure relief outlet with a minimum cross-section of
basements correspond to those of the 8DJH Standard design. 1 m2 is required and must be supplied by the site)
The pressure relief to the rear was tested with a rear wall dis- Upwards through rear pressure relief duct (internal arc
tance of 3 m. This design is recommended for application in classication up to IAC A FL or FLR 21 kA/1 s, free space
prefabricated substations without control aisle, with internal above the switchgear 600 mm as a minimum).
arcing test according to IEC 62271-202. The dimensions for wall distances, control aisles and cable
basements correspond to those of the 8DJH Standard design.
The outdoor enclosure is conceived for application on
company ground.
Switchgear installation for 8DJH Compact Switchgear installation for 8DJH Compact with
with pressure relief downwards for all feeders pressure relief downwards for the ring-main
(standard) feeders, and to the rear for the transformer
feeders (option)
HA40-2368 eps
HA40-2369 eps
1700
6008001)
6008001)
Switchgear installation for outdoor enclosure Switchgear installation for outdoor enclosure
with pressure relief downwards with pressure relief to the rear or upwards
through rear duct
HA40-2372 eps
HA40-2370 eps
HA40-2371 eps
2
1 Floor opening
2 Direction of pressure relief
6
3 Expanded metal (supplied by 5
2
1 site)
500
3
working at the cable connec- 1 1
2 tion)
5 Pressure absorber system with
pressure relief duct
600 8001)
68 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Dimensions
Feeder panels (310 mm)
HA40-2173b eps
C1)
C1)
60
60
B1)
B1)
A
554
A
554
D
D
E
E
3002)
3002)
310 775 310 775
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 69
Dimensions
Feeder panels (430 mm)
HA40-2174c eps
HA40-2186c eps
C1)
C1)
60
60
B1)
B1)
A
434
A
554
D
D
E
E
3002)
3002)
C1)
60
B1)
554
D
E
3002)
430 775
8204)
1) Option: With low-voltage compartment 3) Only for panel blocks RR, RRR, RT, RRT and RTR
2) Base for switchgear height of 1700 mm, or 4) Only for circuit-breaker type 1.1
absorber --> cable connection height = D + 300 mm
70 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Dimensions
Feeder panels (500 mm)
HA40-2176e eps
HA40-2187d eps
C1)
C1)
60
60
B1)
B1)
A
A
370 370
D
D
E
E
3002)
3002)
60
HA40-2179c eps
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 71
Dimensions
Bus sectionalizer panels with switch-disconnector
HA40-2373 eps
HA40-2180c eps
C1)
C1)
60
60
B1)
B1)
A
A
E
E
3002)
3002)
C1)
C1)
60
60
B1)
B1)
A
A
E
E
3002)
3002)
72 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Dimensions
Bus sectionalizer panel with circuit-breaker
C1)
60
B1)
E
3002)
500 775
8204)
Design options
with busbar voltage transformer and / or
busbar current transformer
1)
C
60
HA40-2183c eps
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 73
Dimensions
Busbar earthing panels and busbar voltage metering panels
HA40-2185d eps
HA40-2184c eps
C1)
C1)
60
60
B1)
B1)
A
E
E
3002)
3002) 775
310 775 500
HA40-2275b eps
C1)
C1)
60
60
B1)
B1)
A
A
D
E
E
3002)
3002)
74 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Dimensions
Billing metering panel as individual panel, air-insulated
HA40-2208c eps
HA40-2209d eps
C1)
C1)
60
60
B1)
B1)
D
250 250 250 250
840 775 840 775
Connection: busbar busbar Connection: busbar on the left cable on the right
HA40-2210e eps
HA40-2211d eps
C1)
C1)
60
60
B1)
B1)
A
A
D
D
Connection: cable cable Connection: cable on the left busbar on the right
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 75
Dimensions
Panel blocks (preferred versions)
HA40-2190 eps
HA40-2188 eps
HA40-2193 eps
R R T R R R T T R R T
310 310 430 310 310 310 430 430 310 310 430
76 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Dimensions
Panel blocks (preferred versions)
HA40-2214b eps
HA40-2195 eps
HA40-2194 eps
K L K (E) L R L
HA40-2198 eps
HA40-2196 eps
R R L R R R L L R R L
310 310 430 310 310 310 430 430 310 310 430
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 77
Dimensions
Panel blocks (preferred versions)
Further versions
HA40-2201 eps
HA40-2200 eps
HA40-2199 eps
R R R R R R R R R
620 860
HA40-2203 eps
HA40-2202 eps
R K T T
78 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Dimensions
Panel blocks (8DJH Compact)
HA40-2374 eps
A1
D2
D3
A1
A1
A2
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 79
Dimensions
Panel blocks (freely conguarable)
Examples
1480 1050
HA40-2204a eps
HA40-2272 eps
R R L L L R R
1480 1050
HA40-2206a eps
HA40-2207 eps
R T T R R T R
80 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Dimensions
Panel combinations with billing metering panels (examples)
2320
HA40-2220b eps
R R S M T
2390
HA40-2221b eps
R R V M T
2320
HA40-2222b eps
R R L M T
Transfer with circuit-breaker in the panel block and cable connection (RRL-M-T...)
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 81
Dimensions
Outdoor enclosure
HA40-2378 eps
E
955
HA40-2377 eps
HA40-2196 eps
HA40-2196 eps
HA40-2196 eps
C
B
A
D
667
1070 821
1380
1740 Outdoor enclosure with pressure relief
2020 downwards or to the rear
HA40-2379 eps
downwards or to the rear E
75 955
C
B
D
667
821
871
82 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Dimensions
Floor openings and xing points
Standard *)
310
40 230
15
64
610
465 10
653
HA40-2228 eps
699
155
291
19
430
40 350
15
64
610
465 10
For bus sectionalizer panel type S with switch-disconnector
For bus sectionalizer panel type H
HA40-2229a eps
653
699 with switch-disconnector/ fuse combination
For busbar voltage metering panel type M(430)
19
215
411
500
40 420
15
64
610
250
481
840
40 760
420
15
64
610
465
653
HA40-2231 eps
699
155
19
364
476
685
821
*) For panel versions with double cables and deep cable compartment cover, as well as for other versions,
please order the dimension drawings.
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 83
Dimensions
Floor openings and xing points
1050 1050
For For
620 740
40 540 panel blocks: 40 660 panel blocks
(preferred
15
15
RR
64
64
36 36 versions):
102 RK 102
223 223
RT
KR
319 319 RL
714
714
610
610
RRT
465 10 465 10 KT
RRL
HA40-2232a eps
HA40-2233a eps
653 653 KL
699 RRS 699
RTR
RRH
1031
1031
19
155
292
465
602
835
19
155
292
525
722
895
RLR
1240
930
For 1360
40 850 panel blocks 40 1280
For
(preferred panel blocks
15
15
64
64
36 versions): 36 (preferred
102 102
RRR versions):
223 223
319 RRRR 319 RRRT
714
714
610
610
465 10 465 10
RRRL
RRRS
HA40-2235a eps
653 653
HA40-2234 eps
699 699
RRRH
1221
1085
19
155
292
465
602
775
912
1341
1145
19
155
292
465
602
775
912
1720
For panel blocks
860
40
(preferred versions):
780
K(E)T
15
64
36 K(E)L
102
223 TT
319
714
610
LL
465 10 TTT
HA40-2236a eps
653
699 LLL
TTTT
1701
1272
1505
1075
19
215
412
645
842
LLLL
1480
740
For panel blocks
40 660 (preferred versions):
15
64
TK
36
102 LK
223 TR
319
714
610
LR
465 10
TRRT
HA40-2237a eps
653
699 LRRL
1461
1265
1032
19
215
412
585
722
895
*) For panel versions with double cables and deep cable compartment cover, as well as for other versions,
please order the dimension drawings.
84 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Dimensions
Floor openings and xing points
15
15
15
52
52
52
33 33 33
99 99 99
220 220 220
315 315 315
734
734
734
642
642
642
462 462 462
HA40-2382 eps
HA40-2380 eps
HA40-2381 eps
99
235
372
545
682
719
855
991
1165
1301
99
235
372
545
611
99
235
372
545
682
719
855
991
Panel block RRT Compact Panel block RRT-R Compact Panel block RRT-RRT Compact
15
64
64
36 36
102 102
223 223
610 / 635*
319 319
714
819
715
465 465
HA40-2241c eps
HA40-2280c eps
653 653
699
19 19 747
804
19 19
Example:
Position of oor openings and xing points for double cable connection
for panel blocks
1050 1050
40 970 40 970
15
15
64
64
36 36
102 102
223 223
319 319
714
714
610
610
819
964
465 465
653 653
747 747
HA40-2246 eps
804
897
HA40-2247a eps
949
1031
19
155
292
330
465
602
835
1031
19
155
292
330
465
602
835
* 610 mm for single cable connection; 635 mm for double cable connection with coupling T-plug
For concrete switchgear versions, please order the dimension drawings.
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 85
Dimensions
Floor openings and xing points
Versions in connection with base and rear pressure relief duct for switchgear
with IAC A FL or FLR up to 21 kA / 1 s and deep cable compartment covers**
115
115
115
217 217 217
For cable panel type K(E)
550
550
550
934
1079
580 580 580 For circuit-breaker panel
(225)*
HA40-2284b eps
200
type L
305
HA40-2285b eps
450
768 768 768
814
862 862
HA40-2286b eps
19 19 919
19 19 1012
1064
19 19
Deep cable compartment cover:
Without With base extension
(oor opening depending on selected cable connection/arrester)
Deeper by 105 mm Deeper by 250 mm
115
115
217 E, E(500)
430
217
338
829
338 434
829
434
580
HA40-2290a eps
320
580
HA40-2251b eps
768
768 814
814 19 19
19 19
500 500
40 40 For ring-main panel type R(500)
For circuit-breaker panel type L(500)
115
115
365
365
217 217
338 338
829
434 434
934
385
580 580
490
HA40-2287b eps
HA40-2288b eps
768 768
814
19 19 919
19 19
840
40 760 For billing metering panel type M
115
217
210
550
338
829
434
425
580
200
HA40-2289b eps
768
814
19
155
364
476
685
821
* 200 mm for single cable connection; 225 mm for double cable connection with coupling T-plug
** In versions with rear pressure relief duct for panel block with IAC A FL or FLR
up to 16 kA / 1 s, the depth is reduced by 10 mm.
For wall-standing arrangement, a wall distance of 15 mm must be provided.
For concrete switchgear versions, please order the dimension drawings.
86 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Installation
Shipping data, transport
HA40-2238 eps
with wooden base
Pallet
Type: Seaworthy crate (for open-top container)
Welded PE protective foil, with closed wooden crate,
with desiccant bag Crane transport with Pallet
Airfreight Type: Open
PE protective foil pulled over the switchgear,
Crane hook
with wooden base and lattice or cardboard cover
Transport dimensions
(top view)
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 87
Installation
Shipping data, transport
Transport weights Panel block Width Gross weight for switchgear height
The transport weight results from the switchgear weight per without LV compartment
transport unit and the packing weight. The packing weight 1200 mm 1400 mm 1700 mm
results from the transport dimensions and the type of trans- mm approx. kg approx. kg approx. kg
port. 2 panels
KT, TK 740 230 250 280
Switchgear weights
K(E)T 860 240 260 290
The weight of the switchgear unit results from the sum of KL 1), LK 740 230 250 280
the weights per functional unit. Depending on the design and K(E)L 1) 860 250 270 300
the degree to which it is equipped (e.g. current transformers, RK, KR 620 200 220 240
motor operating mechanism, low-voltage compartment), RT, TR 740 230 250 280
different values will result. The table shows mean values. RL 1), LR 740 230 250 280
Panel type Width Gross weight LV com- TT 860 270 290 320
for switchgear height partment RR 620 200 220 240
1200 mm 1400 mm 1700 mm 600 mm LL 1) 860 260 280 310
mm approx. kg approx. kg approx. kg approx. kg RS 740 230 250 280
R 310 100 110 120 40 RH 740 230 250 280
R(500) 500 140 150 170 60 3 panels
K 310 100 110 120 40 RRT 1050 330 360 400
K(E) 430 130 140 160 50 RRL 1) 1050 320 350 390
T 430 135 145 160 50 RTR 1050 330 360 400
L 430 130 140 155 50 RLR 1050 320 350 390
L (type 1.1) 500 210 220 240 60 RRR 930 300 330 360
without 4MT3 TTT 1290 410 440 490
L (type 2) 500 160 170 190 60 LLL 1) 1290 400 430 480
M (BC / BB / CB) 840 370 400 70 RRS 1050 320 350 390
M (CC) 840 270 300 70 RRH 1050 330 360 400
M(430) 430 220 230 245 40 4 panels
with 3x4MT3 RRRT 1360 430 470 520
M(500) 500 230 240 260 60 RRRL 1) 1360 430 470 520
with 3x4MT3
RRRR 1240 400 440 480
S 430 130 140 160 50
TRRT 1480 470 510 560
S(500) 500 150 160 180 60
LRRL 1480 460 500 550
S(620) 620 200 220 240 2x40
TTTT 1720 540 580 640
H 430 135 145 160 50
LLLL 1) 1720 520 560 620
V 500 240 250 270 60
RRRS 1360 420 460 510
E 310 100 110 120 40
RRRH 1360 430 470 520
E(500) 500 140 150 170 60
8DJH Compact
Additional weights for pressure absorber Panel block Width Gross weight for switchgear height
1400 mm 1700 mm
For panel blocks IAC A FL / FLR up to 16 kA / 1 s
mm approx. kg approx. kg
Basic switchgear height 1400 mm
RRT 2) 700 365 380
Weight / kg RRT 620 340 345
Cooler 30 RRT-R 2) 1010 475 490
Duct 16 kA FL/FLR 60 RRT-R 930 450 455
Base plate per panel approx. 5 RRT-RRT 2) 1400 730 760
Example RRT-RRT 1240 860 690
RRT with IAC A FL/FLR 16 kA/1 s 105
1) Weight data applies to design with circuit-breaker type 2
For switchgear IAC A FL / FLR up to 21 kA / 1 s 2) With lateral pressure relief duct
Basic switchgear height 1700 mm
Weight / kg Packing weights
Cooler 30 Max. width of Packing weight Packing weight
Duct 21 kA FL 70 switchgear unit Truck / rail / container Seaworthy crate / airfreight
Duct 21 kA FLR 75 mm approx. kg approx. kg
Absorber collar FLR 20 850 30 90
Base plate per panel approx. 5 1200 40 120
Example 1550 50 150
RRT with IAC A FL 21 kA / 1 s 115
1800 60 180
RRT with IAC A FLR 21 kA / 1 s 140
Metering panel with IAC A FL / FLR 21 kA / 1 s 145 2000 75 225
88 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Standards
Standards, specications, guidelines
HA40-2037c en eps
Dielectric strength the altitude cor- m=1
Altitude correction factor
The dielectric strength is veried by testing the switchgear rection factor Ka 1.40
with rated values of short-duration power-frequency with- is recommended,
stand voltage and lightning impulse withstand voltage depending on
1.30
the site altitude
according to IEC / EN 62271-1 / VDE 0671-1.
above sea level.
The rated values are referred to sea level and to normal 1.20
atmospheric conditions (1013 hPa, 20 C, 11 g/m3 humidity
according to IEC / EN 60071 and VDE 0111). 1.10
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014 89
Standards
Standards, specications, guidelines
90 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Siemens HA 40.2 2014
Standards
Standards, specications, guidelines
IP 3 X
IP 6 5
Siemens AG
Infrastructure & Cities Sector
Low and Medium Voltage Division
Medium Voltage
Postfach 3240
91050 Erlangen, Germany
www.siemens.com/medium-voltage-switchgear
www.siemens.com/8DJH