DETAILED FEM ANALYSIS OF SEISMIC BEHAVIORS CODIFIED METHOD CONCEPT FOR AN ECONOMICAL SOLUTION
jec ts
e PINEERING ro INC.
p l
Sam LL ENG
by J
2
STEEL JOIST
.
TYP
TOP CHORD
600
CONNECTION OF
CABLE TRAY HANGER ROD TO
1 STRUCTURE BY
(TYP.)
CONTRACTOR, DCA, REFER TO
TYP
REFER TO SCHEDULE SCHEDULE
A B
.
ATTACHMENT CONCRETE
ON DRAWINGS: INSTALLATION:
RESTRAINT GREATER THAN 600 RESTRAINT GREATER THAN 600 FROM CABLE
FROM CENTRE LINE CENTRE LINE - INSTALL AS 2 TRANSVERSE TRAY
.
TYP
AND 2 LONDITUDINAL SSA OR WELD BRACKET
TO STEEL ON 3 SIDES,
1 1 REFER TO SCHEDULE
600 > 600
STEEL BEAM
2 ATTACHMENT
2
> 600
STRUT
(TYP.)
1
BRACKETS
2
DETAIL C2
NOTES:
C
1. REFER TO PLANS FOR LOCATION OF TRANSVERSE STRUTS.
NOTES:
2. IF INSTALLED ROD LENGTH IS GREATER THAN MAXIMUM ROD LENGTHS
NOTED ON PROJECT DETAILS PD04 AND PD05, THEN CONTACT HALSALL
1 TRANSVERSE RESTRAINT. REFER TO PROJECT DETAILS PD03.
ASSOCIATES FOR A MODIFIED DESIGN.
2 LONGITUDINAL RESTRAINT. STRUT REQUIRED ON BOTH SIDES OF CABLE
TRAY. LOCATE AT TRANSVERSE RESTRAINT LOCATIONS.
Linstall
19 835 2.0 3.5 3.9 5.0 L
LOWER SECTION allow
MAXIMUM ROD LENGTH 990 1470 2000 1950
ROD GEOMETRY
TABLE NOTES:
1. DETERMINE INSTALLED ROD LENGTH (Linstall). SUPPORTING
2. IF Linstall > L allow THEN A ROD STIFFENER IS REQUIRED. STRUCTURE
IF Linstall < L allow THEN A ROD SITFFENER IS NOT REQUIRED.
3. IF "ROD BUCKLING" GOVERNS THE ROD DESIGN, THEN:
<L
A. CALCULATE THE RATIO BETWEEN Linstall AND L allow (R) AND ROUND THE NUMBER UP TO THE NEAREST FIRST allow/2
DECIMAL PLACE.
EXAMPLE: IF THE INSTALL LENGTH IS 920 AND THE MAXIMUM ALLOWED LENGTH IS 410 THEN THE RATIO,
R = 920/410 = 2.24 --> 2.3 (ROUNDED UP)
B. BASED ON THE KNOWN HANGER ROD DIAMETER, SELECT AN ANGLE STIFFENER FROM THE UPPER SECTION
WHOSE FACTOR IS GREATER THAN R.
EXAMPLE: IF 9.6 DIAMETER HANGER ROD WITH Linstall /L allow = 2.3 IS USED, THEN SELECT
L25x25x3.2 WITH R=5.2. IT
/UN
C. ENSURE THAT Linstall IS LESS THAN THE MAXIMUM STIFFENER LENGTH IN THE LOWER SECTION. IF Linstall CT
EXCEEDS THIS VALUE, THEN CHOOSE A LARGER STIFFENER. DU
EXAMPLE: IF A HANGER ROD IS 1200 LONG (990 MAXIMUM ROD LENGTH FOR L25x25x9.6 STIFFENER),
SELECT L38x38x6.4 STIFFENER.
5. IF "ROD GEOMETRY" GOVERNS THE ROD DESIGN, THEN: NUT AT TOP AND
A. SELECT THE STIFFENER SIZE BASED ON THE LOWER SECTION OF THE TABLE. BOTTOM OF SLEEVE
THREADED ROD CONNECTION
EXAMPLE: IF A HANGER ROD IS 1200 LONG, SELECT L38x38x6.4 STIFFENER. BY CONTRACTOR. PROVIDE
6. A MINIMUM OF TWO CLAMPS MUST ANCHOR THE STIFFENER TO THE HANGER ROD. THE SPACING BETWEEN CLAMPS 100 MAX
TOP & SHOP DRAWINGS.
MUST NOT EXCEED L allow.
7. IF ROD LENGTH EXCEEDS 2000mm, REFER TO PD05 FOR ALTERNATE STIFFENER. BOTTOM
8. ANGLE STIFFENERS TO BE GRADE 300W MINIMUM. 6.4 CAP PLATE AT TOP AND
BOTTOM WELDED TO SLEEVE
HSS 51x51 SLEEVE
(350 MPa MIN)
CT 1 100x300 9.5 DIA DCA 12.7 12.2 2.0 24.4 4.0 DCA 9.5 ROD BUCKLING GOVERNS HANGER ROD DESIGN PD02-03
CT 2 100x300 9.5 DIA SSA 12.7 12.2 3.5 24.4 6.5 SSA 9.5 ROD BUCKLING GOVERNS HANGER ROD DESIGN PD02-03
NOTE:
1. UNITS ARE mm AND kN UNLESS NOTED OTHERWISE.
2. REFER TO ANCHOR SCHEDULE ON DRAWING B350-60220-006-01-DD-E FOR ANCHOR TYPES.
3. PROPOSED STRUT AND CONNECTIONS MUST BE CAPABLE OF SUPPORTING TENSION AND COMPRESSION FORCE (T/C)
INDICATED IN SCHEDULE.
4. STRUT MATERIAL TO BE 12 GA MINIMUM. MAXIMUM SLENDERNESS RATIO KL/R = 200. CONTRACTOR TO CONFIRM ALL
STRUT LENGTHS ON SITE.
5. STRUTS TO BE AT A MAXIMUM OF 45 DEGREES FROM HORIZONTAL.
6. FOR SPACING OF HANGER RODS, REFER TO SPECIFICATIONS AND MANUFACTURER'S INSTRUCTIONS.
7. CONTRACTOR TO SUMBIT SHOP DRAWINGS INDICATING PROPOSED STRUT AND STRUT CONNECTIONS FOR EACH
UNIT.
8. CONTRACTOR TO SUBMIT SHOP DRAWINGS FOR THREADED HANGER ROD CONNECTION TO SUPPORTING STRUCTURE.
REQUIRED CAPACITY IS 8.5kN AT LOCATIONS OF SEISMIC BRACING AND 4.5kN AT GRAVITY HANGERS.
9. MINIMUM GRADE OF HANGER ROD IS A36.
ON DRAWINGS: INSTALLATION:
TRANSVERSE AND LONGITUDINAL 1
TRANSVERSE AND
TRANSVERSE ONLY - AS 600
LONGITUDINAL ON STRAIGHT
SHOWN ON PLANS
PIPE - AS SHOWN ON PLANS
A
600
D
1
1 1
PIPE PIPE
DETAIL A
PIPE 2 PIPE
HANGER ROD
(WITH STIFFENER B
A B IF REQUIRED) LONGITUDINAL
RESTRAINT AS E
PER F1
PIPE TRAPEZE
ELEVATION
2
LONGITUDINAL
RESTRAINT
C F
LONGITUDINAL
RESTRAINT 2
PLAN F1 ACCEPTED STRUT CONFIGURATION FOR
TRANSVERSE SEISMIC RESTRAINT OF TRAPEZED PIPES
NOTES:
1 TRANSVERSE REFER TO PROJECT DETAIL PD07, PD09, & PD10.
j ec ts
e PINEERING ro INC.
p l
S am ENG LL
by J
INTERPRETATION OF SEISMIC
RESTRAINT LAYOUT FOR PIPING
PD06
AUG 13
ts
SSA WITHIN 100 OF CONCRETE
JOIST PANEL POINT, SLAB
j ec
ro INC.
REFER TO SCHEDULE
p le PINEERING
S am ENGLL
STEEL JOIST CONNECTION OF
by J
X
TOP CHORD
MA
HANGER ROD TO
STRUCTURE,
REFER TO
SCHEDULE
DCA, REFER TO
ROD SCHEDULE
MA
STIFFENER
X
STEEL JOIST CONCRETE
CLAMPS
ATTACHMENT ATTACHMENT
MAXIMUM
STRUT HANGER ROD
(TYP.) SPACING AS
PER SPECS STRUT
BEAM TOP (TYP.)
FLANGE
CLEVIS
HANGER
X
MA
SSA OR WELD
BRACKET TO STEEL
ON 3 SIDES, REFER
TO SCHEDULE
STEEL BEAM SUPPORTING
ATTACHMENT BRACKETS STRUCTURE
PIPE DIAMETER 100
VARIES
RISER CLAMP AND NUTS
STANDARD AS SUPPLIED BY
MECHANICAL TRADE.
NOTES:
NUT AT TOP AND
1. REFER TO PLANS FOR LOCATIONS OF LONGITUDINAL SEISMIC RESTRAINTS. BOTTOM OF SLEEVE
THREADED ROD CONNECTION
100 MAX BY CONTRACTOR. PROVIDE
TOP & SHOP DRAWINGS.
BOTTOM
6.4 CAP PLATE AT TOP AND
BOTTOM WELDED TO SLEEVE
HSS 51x51 SLEEVE
(350MPa MIN.)
e P EERING INro C.
l
mp NGIN
Saby JLL E STIFFENER
Linstall
L
allow
L allow L25X25X3.2 L38X38X6.4 L51x51x3.2 L51x51x6.4
TABLE NOTES:
1. DETERMINE INSTALLED ROD LENGTH (Linstall).
2. IF Linstall > L allow THEN A ROD STIFFENER IS REQUIRED.
IF Linstall < L allow THEN A ROD SITFFENER IS NOT REQUIRED.
3. IF "ROD BUCKLING" GOVERNS THE ROD DESIGN, THEN:
A. CALCULATE THE RATIO BETWEEN Linstall AND L allow (R) AND ROUND THE NUMBER UP TO THE NEAREST FIRST
DECIMAL PLACE.
EXAMPLE: IF THE INSTALL LENGTH IS 920 AND THE MAXIMUM ALLOWED LENGTH IS 410 THEN THE RATIO,
R = 920/410 = 2.24 --> 2.3 (ROUNDED UP)
B. BASED ON THE KNOWN HANGER ROD DIAMETER, SELECT AN ANGLE STIFFENER FROM THE UPPER SECTION
WHOSE FACTOR IS GREATER THAN R.
EXAMPLE: IF 9.6 DIAMETER HANGER ROD WITH Linstall /L allow = 2.3 IS USED, THEN SELECT A B C
L25x25x3.2 WITH R=5.2.
C. ENSURE THAT Linstall IS LESS THAN THE MAXIMUM STIFFENER LENGTH IN THE LOWER SECTION. IF Linstall
EXCEEDS THIS VALUE, THEN CHOOSE A LARGER STIFFENER.
EXAMPLE: IF A HANGER ROD IS 1200 LONG (990 MAXIMUM ROD LENGTH FOR L25x25x9.6 STIFFENER),
SELECT L38x38x6.4 STIFFENER.
5. IF "ROD GEOMETRY" GOVERNS THE ROD DESIGN, THEN:
A. SELECT THE STIFFENER SIZE BASED ON THE LOWER SECTION OF THE TABLE.
EXAMPLE: IF A HANGER ROD IS 1200 LONG, SELECT L38x38x6.4 STIFFENER.
6. A MINIMUM OF TWO CLAMPS MUST ANCHOR THE STIFFENER TO THE HANGER ROD. THE SPACING BETWEEN CLAMPS
MUST NOT EXCEED L allow.
7. IF ROD LENGTH EXCEEDS 2000mm, REFER TO PD12 FOR ADDITIONAL STIFFENER OPTIONS.
8. ANGLE STIFFENERS TO BE GRADE 300W MIN.
CONNECTION OF
STEEL JOIST HANGER ROD TO
X
TOP CHORD STRUCTURE,
MA
REFER TO
SCHEDULE
MA
SCHEDULE
ts
STIFFENER
X
STEEL JOIST
CLAMPS
j ec
ro INC.
ATTACHMENT CONCRETE
STRUT
ATTACHMENT
p le PINEERING
am ENG
MAXIMUM
(TYP.) HANGER ROD
SPACING AS PER S by J
LL
SPECS
BEAM TOP
FLANGE
ANGLE OR
UNISTRUT
X
MA
STRUT
(TYP.)
BRACKETS
e PINEERING ro INC.
REFER TO SCHEDULE
p l
S am ENG LL
by J
STEEL JOIST
X
TOP CHORD CONNECTION OF
MA
HANGER ROD TO
STRUCTURE,
REFER TO
SCHEDULE DCA, REFER TO
MA
SCHEDULE
X
STEEL JOIST ROD
ATTACHMENT STIFFENER CONCRETE
CLAMPS ATTACHMENT
STRUT
(TYP.)
MAXIMUM
HANGER ROD
SPACING AS PER
SPECS
BEAM TOP
FLANGE
STRUT
(TYP.)
X
MA
STEEL BEAM
ATTACHMENT
BRACKETS
Linstall
19 835 2.0 3.5 3.9 5.0 L
LOWER SECTION allow
MAXIMUM ROD LENGTH 990 1470 2000 1950
ROD GEOMETRY
TABLE NOTES:
1. DETERMINE INSTALLED ROD LENGTH (Linstall).
2. IF Linstall > L allow THEN A ROD STIFFENER IS REQUIRED.
IF Linstall < L allow THEN A ROD SITFFENER IS NOT REQUIRED.
3. IF "ROD BUCKLING" GOVERNS THE ROD DESIGN, THEN:
<L
A. CALCULATE THE RATIO BETWEEN Linstall AND L allow (R) AND ROUND THE NUMBER UP TO THE NEAREST FIRST allow/2
DECIMAL PLACE.
EXAMPLE: IF THE INSTALL LENGTH IS 920 AND THE MAXIMUM ALLOWED LENGTH IS 410 THEN THE RATIO,
R = 920/410 = 2.24 --> 2.3 (ROUNDED UP)
B. BASED ON THE KNOWN HANGER ROD DIAMETER, SELECT AN ANGLE STIFFENER FROM THE UPPER SECTION
WHOSE FACTOR IS GREATER THAN R.
EXAMPLE: IF 9.6 DIAMETER HANGER ROD WITH Linstall /L allow = 2.3 IS USED, THEN SELECT
L25x25x3.2 WITH R=5.2. T
C
C. ENSURE THAT Linstall IS LESS THAN THE MAXIMUM STIFFENER LENGTH IN THE LOWER SECTION. IF Linstall DU
EXCEEDS THIS VALUE, THEN CHOOSE A LARGER STIFFENER.
EXAMPLE: IF A HANGER ROD IS 1200 LONG (990 MAXIMUM ROD LENGTH FOR L25x25x9.6 STIFFENER),
SELECT L38x38x6.4 STIFFENER.
5. IF "ROD GEOMETRY" GOVERNS THE ROD DESIGN, THEN:
A. SELECT THE STIFFENER SIZE BASED ON THE LOWER SECTION OF THE TABLE.
EXAMPLE: IF A HANGER ROD IS 1200 LONG, SELECT L38x38x6.4 STIFFENER.
6. A MINIMUM OF TWO CLAMPS MUST ANCHOR THE STIFFENER TO THE HANGER ROD. THE SPACING BETWEEN CLAMPS
MUST NOT EXCEED L allow.
7. IF ROD LENGTH EXCEEDS 2000mm, REFER TO PD09 FOR ADDITIONAL HANGER OPTIONS.
8. ANGLE STIFFENER GRADE IS 300W MIN.
2
S2 USE HILTI HSL-3 M10
DRILL HOLE SIZE 15 mm
1 HOLE DEPTH 100 mm
S3
1
S2 1
S2
ANCHOR BOLT @
GANTRY SUB-BASE
(SEE SHEET NOTES
FOR ADDITIONAL
INFORMATION).
PATIENT TABLE
FLOOR JUNCTION
BOX (REFER TO MOISTURE SENSOR
ec ts
roj C .
DETAIL 4 ON (SEE SHEET NOTES FOR
SHEET S3). ADDITIONAL INFORMATION).
le P EERING IN
mp NGIN
Saby JLL E
ANCHOR BOLT
@ PATIENT
TABLE
SUB-BASE
SHEET S2 LEGEND
(SEE SHEET
NOTES FOR = 6" [15.2] AREA AROUND
ADDITIONAL ANCHOR BOLT LOCATION TO
INFORMATION). BE KEPT CLEAR OF ALL
CONDUITS, DRAIN LINES AND
REBAR TO A MINIMUM DEPTH
OF 10" [25.4]. (12 ANCHOR
LOCATIONS TOTAL.)
= CONCRETE WALL