Explanation of reports.
Minor Condition: Temp Rise of 1-20 F. Repair during regular maintenance, little chance of
physical damage.
Alert Condition: Temp Rise of 21-40 F. Repair within 30 days. Watch amperage load and
inspect for physical damage.
The Reference temperature is shown to provide a reference to a similar object under the same
conditions as the object showing the high temperature.
The High temperature is the highest temperature registered either inside an area box, as seen
in IR images, or in the entire image.
The Temperature rise is shown to indicate the difference in temperature between the
Reference temperature and the High temperature.
If anyone has any questions about this report please call Scott Easter at 678-641-0163 or
email scotteaster@piedmontinfrared.com
Identification
Description:
Main Disconnect in cabinet - phase A.
Temp rise of 68.7 F
Thermogram
FLIR Systems
189.2 F
180
Sp1
Label Value
160
Sp1 84.2 F
Sp2 98.7 F
Sp2 140
Sp3 122.6 F
Sp4 191.3 F
Sp3 120
Sp4
Comment:
Identification
Description:
Combustion Air breaker- B Phase.
Thermogram
FLIR Systems
135.6 F
Label Value
Sp1 80.6 F
Sp1 120
Sp2 104.3 F
Sp3 112.5 F
Sp2 Sp4 Sp4 139.0 F
Sp3
100
80
60.2
Comment:
Identification
Description:
Agg Trun Breaker (next to the main)
Thermogram
FLIR Systems
166.7 F
100
Sp1
80
71.5
Comment:
Identification
Description:
Located in the cabinet on the dryer side of the control
house. Starter M 5d on the AGG Trun. (next to the
main) C Phase.
Temp rise of 45.7F above other two phases.
Thermogram
FLIR Systems
179.3 F
80
60
54.8
Comment:
Identification
Description:
Cabinet on end of baghouse next
to exhaust fan.
Exh. Fan breaker Line side A
Phase.
Temp rise of 155 F
Thermogram
FLIR Systems
250.9 F
250
Sp1
200 Label Value
Sp1 90.4 F
Sp4 Sp2 98.4 F
150 Sp3 101.6 F
Sp3
Sp4 256.5 F
100
Sp2 CRITICAL CONDITION!
50
34.2
Comment:
Identification
Description:
Cabinet labeled Chip Plant
16M Chip Plant 5 ft. short head crusher breaker.
Temp rise of 25.4F
Thermogram
FLIR Systems
94.0 F
90
80
Label Value
Sp2 Sp4 Sp3 70 Sp1 72.5 F
Sp2 71.0 F
Sp1 Sp3 72.6 F
60 Sp4 98.0 F
50
41.7
Comment: