Steam valves Initial Requirement for new 10.

45 MW project
HP steam line - Design- 78 kg/cm2 500 *C

Flow max
Sno. Description Size QTY Class #
( TPH)

1 50 TPH New boiler to HP header inlet 150 1 60 1500


2 75 TPH New boiler to HP header inlet 200 1 90 1500
3 67X4.5 PRDS outlet 150 1 75 1500
4 67X11.5 PRDS outlet 150 1 60 1500
5 75 TPH Old boiler to HP header inlet 200 1 90 1500
6 Spare 200 1 90 1500
7 Drain valves 15 25 1500
8 Main steam line turbine -5 vent isolation valve 50 1 10 1500
9 Main steam line turbine -5 initial heating isolation valve 50 1 10 1500
10 Ejector to PRDS isolation valve 25 2 2 1500

MP steam line - Design- 15 kg/cm2 300 *C

Sno. Description Size QTY Class


1 MP header to header 250 1 50 300
2 PRDS 67X11.5 inlet 250 1 50 300
3 Drain valves 15 25 800

LP steam line - Design- 4.5 kg/cm2 200 *C

Sno. Description Size QTY Class


1 LP header to Dearator 50 TPH 250 1 12 150
2 PRDS 67X4.5 inlet 400 1 75 150
10.45 MW project

End Connection Integral Byepass Gear operated


Type Globe

gate BW Y Y
gate BW Y Y
gate BW Y Y
gate BW Y Y
gate BW Y Y
gate BW Y Y
gate BW N N
gate BW N N
gate BW N N
gate BW N N

Type End Integral Byepass Geared


gate BW N N
gate BW N N
gate BW N N

Type End Integral Byepass Geared


gate BW N N
gate BW N N