Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

10-063-2 This

Application Only

SW4 0 = Off Clean Agent Clean Agent & Preaction Preaction Industrial
Function
Position 1 = On Application 1 Application 2 Application 3 Application 4
0/0 Clean Agent
0/1 Clean Agent & Preaction
S1 / S2 Application
1/0 Preaction
1/1 Industrial Solenoid Releasing
0 No Delay
S3 Trouble Relay
1 AC Delay ( 2 hours )
0/0 Audible Option 1

Audible 0/1 Audible Option 2


S4 / S5
Operation 1/0 Audible Option 3
1/1 Audible Option 4
0 Gentex Sync
S6 Aud. Sync
1 System Sensor Sync
0/0 0 seconds N/A

Pre-discharge 0/1 15 seconds 15 seconds


S7 / S8 Not Applicable
Delay 1/0 30 seconds 30 seconds
1/1 60 seconds 60 seconds
0/0 Abort - Type 1 Det1 activates SOL Solenoid ON continuous 0/0/0

Abort Type or 0/1 Abort - Type 2 Det2 activates SOL Solenoid ON 5 minutes 0/0/1
S9 / S10
SOL ON time 1/0 Abort - Type 3 Det1 OR 2 activates SOL Solenoid ON 10 minutes 0/1/0

S9/10/11
1/1 Abort - Type 4 Det1 AND 2 activates SOL Solenoid ON 15 minutes 0/1/1
Activation 0 Agent Release Module 0 / 0 Det1 activates SOL WF does not activate SOL Solenoid ON 20 minutes 1/0/0
S11
Control 1 24VDC Solenoid 0 / 1 WF activates SOL WF activates SOL Solenoid ON 30 minutes 1/0/1
1 / 0 Det1 OR WF activates SOL Micromist - Machinery Spc. 1/1/0
1 / 1 Det1 AND WF activates SOL Micromist - Turbine Gen. 1/1/1
0 Sequential / SDR S11/S12 Sequential / SDR
S12 Detection Type
1 Cross Zone Cross Zone