Professional Documents
Culture Documents
Load Modelling PDF
Load Modelling PDF
Meter Infrastructure
Bimal Shah, Anjan Bose, Anurag Srivastava
The School Of Electrical Enginerring and Computer Science,
Washington State University
Pullman,WA
bimal.shah@email.wsu.edu
AbstractVoltage Var Control and Optimization (VVC&O) useful tasks has its own challenges. Modeling of EPDS
mechanism in distribution system assisted by local controllers including load models is necessary to use these measurements
and Distributed Management System (DMS) helps in meeting for specific smart grid goals. For load modeling, several
operating criterion and achieving energy savings. Conservation research approaches were developed like least square
Voltage Reduction (CVR) with VVC&O allows reduction in optimization, regression analysis to calculate ZIP (constant
peak load and energy consumption, by having flat voltage impedance, constant current and constant power) parameter
profile near lower bound of ANSI Standards (114V), while and Conservation Voltage Reduction (CVR) factor [1]. This
maintaining power factor within limit. To estimate the energy approach may not work, since all the loads are not always
saving, CVR factor is needed and accurate load modeling is
static or time-invariant. So we may not get accurate CVR
required to estimate CVR factors. In this work, distribution
system was modeled and simulated utilizing data from one of the
factor for the particular feeder.
feeder in Pullman, WA. This paper presents the results of the In this paper, we classified load Models into two broad
study done on improving the VVC capabilities by integrating categories: static and dynamic. Static model are ZIP load with
Smart Meter Infrastructure. Load Modeling was done by combination of constant impedance, constant current and
observing the behavior of loads at each house and comparing the constant power loads while dynamic model has time series
smart meter data with the simulation results. Precision of simulation of end user loads mainly HVAC (Heating
developed load model provides enough information to make a
Ventilation and Air Conditioning) and water-heater. This
decision on required changes in voltage at a substation at a given
paper focuses both on static as well as dynamic load models
time for energy saving without violating operation criterion.
Results of VVC&O show that energy saving of 4-5% can be
since we are trying to do voltage optimization using
achieved at the typical distribution substation. Distribution Management System (DMS) and smart meter
data. Analysis in this paper utilizes a typical feeder from
Index TermsConservation Voltage Reduction, Energy Savings, Avista Utility in northwest USA. It was assumed that utility
Load Modeling, Peak Load Reduction, Smart Metering wants to have voltage at primary side of distribution
Infrastructure, VVC&O (Volt-Var Control and Optimization) transformer to be at 120V [2] and power factor to be above
0.95 lagging.
I. INTRODUCTION
This paper uses actual real time data at 5 minute interval
Efficiency of Electric Power Distribution System (EPDS) provided by the utility for one of the feeder and comparing
is critical in designing sustainable power grid infrastructure. that real time data to the simulation results in GridLAB-D [3].
Automation in the distribution system allows utilities to Once the comparison of real time data and simulation results
implement flexible control of distribution systems to enhance are in reasonable range we can divide the loads into number of
efficiency, reliability, and quality of electric service.1 houses and run the simulation to record the individual house
To estimate energy saving and get better situational data. Now the goal is to compare the simulation results with
awareness of EPDS, it is necessary to get measurements at the Smart Meter data available from the utility. The procedure
strategic locations and estimate the load characteristics. As is explained in detail for load modeling in section III.
part of smart grid initiative, smart meters were installed for The rest of paper is organized as follows: section II gives
better monitoring and possibly control end user loads. brief information on the feeder and exporting feeder model
Analyzing these massive set of collected smart meter data for from Synergee [4] to GridLAB-D. Further, load modeling
concept is explained in section III followed by Volt-Var
The author would like to thank DOE and AVISTA Utility for funding the ongoing
control scheme implementation in section IV. Section V
research. Moreover, the authors would also like to thank Avista for providing the models and all
combines Volt-Var control scheme and load modeling to
the required data for the analysis. Authors are also thankful to PNNL for providing help with
validate load model based on real time DMS and Smart Meter
GridLAB-D.
Infrastructure (SMI) data provided by the utility. Last section
and has been used in this paper to make the end user model 7.96
more accurate. There are total of 13 feeders in Pullman, WA
with smart meters and of the feeder-1 (F-1) has been used in 7.94
this study for load modeling and voltage optimization as
Voltage (kV)
shown in figure 1. 7.92
substations. Avista uses Synergee as distribution tool for Section numbers across the feeder (F-1)
distribution system analysis. Model is exported to GridLAB-
D, which is open source distribution module developed by Synergee Va (kV) GridLAB-D Va (kV)
7.92
A distribution system generally originates from the
7.9
substation where electric power is converted from high
voltage to lower voltage for delivery to customers. Usually, a 7.88
distribution system has a radial topological structure. There
7.86
are two primary requirements for analysis: a. modeling must
reflect the actual behavior of the system components. b. the 7.84
solution algorithm must be robust and efficient. In this work,
7.82
Newton Raphson method was chosen to solve the power flow
Section numbers across the feeder (F-1)
Synergee Vb (kV) GridLAB-D Vb (kV)
7.96
7.94
Voltage (kV)
7.92
7.9
7.88
7.86
7.84
L o a d (k W )
of line measurements [12]. This method is preferred for 3000
2400
Moreover, we move one step further, since our end use
customer loads changes frequently we need to run the power 2200
flow continuously and obtain the optimal set points for the
2000
desired objective of optimization. Analysis is done for one of 0 5 10 15 20 25 30 35 40 45 50
Timestamp (every hour for 2 days)
the season in a year but similar analysis can be carried out for
rest of the year. Figure 3 shows the Regulator Tap Settings
Figure 4 Comparison of Regulator Real Power between Base Case and
behavior for given feeder F-1 with three different cases:
VVC Case
Tap Setting for Phase A Regulator real power, reactive power were calculated
10
for Case 2 and Case 3 for every 5 minute interval. Figure
Utility-Data Base-Case(GLD) VVC-Case(GLD) 4 shows the regulator real power comparison for Case 2
R ange
10
Utility-Data Base-Case(GLD) VVC-Case(GLD) 4.5
R ange
0 4
-10
% C h n a g e in E n e r g y (k W h )
3.5
0 1.5
-10 1
Percent Energy Saving for an individual house (Watt-Hour) Comparision Between Smart Meter Data and Simulated Result for 1 Section along the feeder
2.5 35
30
2
25
% C h a n g e in E n e r g y ( W -h )
R eal P ow er kW
1.5
20
15
0.5
10
0 5
0 50 100 150 200 250 0 5 10 15 20 25
Timestamp(every hour for 11 days) Timestamp(every hour for a day)
Figure 6 Percent change in Energy at individual house Figure: 7 Smart Meters and Simulated Result in GridLAB-D
the feeder. To clearly show the simulation result, only 1 day REFERENCES
analysis is shown. Now to validate the load model we will use [1] Sadeghi, M., Sarvi G.A., "Determination of ZIP parameters with least
CVR factor as a comparison. We calculated CVR factor at square optimization method, "Electrical Power and Energy Conference
substation and we calculated CVR factor at each individual (EPEC), 2009 IEEE.
houses. If we take an average of all the CVR factors for all [2] ANSI Standards, Voltage Ratings for Electric Power Systems and
individual houses it should come out to be equal to CVR Equipment (60 Hz).
[3] D. Chassin, Schneider, K.P., Gerkensmeyer, C, "GridLAB-D: An Open
factor at the substation. Average of all the individual houses Source Power Systems modeling and simulation environment, "
C VR came out to be 0.725. Transmission and Distribution conference and Exposition, 2008.
f [4] Stoner Software, SynerGEE Electric 4.0, 2011.
[5] Avista Utility, "Pullman Smart Grid Project"
Now once we have validated CVR factor comparison, [6] William H. Kersting, Distribution System Modeling and Analysis
utility can easily determine the energy saving and peak load (Second Edition): CRC Press, 2006.
reduction as by equation (4). Moreover distribution [7] Schneider, K.P., Fuller, J.C, "Evaluation of Conservation Voltage
transformer loss, underground line losses, overhead line losses Reduction on a national level, "Pacific Northwest National Laboratory,
2010.
was also determined but it does not have a significant impact
[8] Weather Forecast and Reports-Long Range and Local.
when compared with VVC&O and without VVC&O scheme. [9] K.P. Schneider, J.C. Fuller, D. Chassin, "Evaluating Conservation
voltage Reduction: An application of GridLAB-D: An open source
VI. CONCLUSION
software package, "Power and Energy Society General Meeting, 2011
Volt-Var control and optimization scheme were IEEE.
implemented with smart meter infrastructure on one of the [10] Jeff Doty, Jared Burns, Luis Perez, and Anjan Bose, "Preliminary On-
line evaluation of the smart grid additions to the Spokane distribution
distribution feeder in Pullman, WA. Simulation of load system," Washington State University, 2011.
modeling was done in GridLAB-D, which is open source [11] Schneider, K.P., Fuller, J.C, "Detailed End Use load Modeling for
distribution tool. Load modeling was performed considering Distributed System Analysis, "Power and Energy Society General
static and dynamic Loads. Simulation was done for 11 days Meeting ,2010 IEEE.
for one of the season. Results show that 2-3% reduction in [12] Vesna Borozan, Mesur Baran, and Damir Novosel, "Integrated
Volt/Var Control in Distribution Systems," in Power Engineering
voltage gives an average of 3-4% of reduction in energy at the Society Winter Meeting, IEEE, vol. 3, 2001, pp. 1485-1495.
feeder. Annual simulation can be performed by extending [13] Nokhum Markushevich, Wenpeng Luan, "Achieving Greater VVO
same analysis. Further, losses occurring due to reactive power Benefits through AMI Implementation, "Power and Energy Society
also decrease due to optimization. Once the end user load General Meeting, 2011 IEEE .
model for any of the feeder on distribution system is obtained, [14] R.T. Guttromson, D.P. Chassin, S.E. Widergren, "Residential Energy
more smart grid features like demand response program, Resource Models for Distribution Feeder Simulation, "Power and
Energy Society General Meeting, 2003 IEEE.
distributed generation coordination, electric vehicle [15] Prabha Kundur, Power System Stability and Control: McGraw-Hill Inc,
integration can be added for energy saving and efficiency. 1993.