BC8001A Installation and Operating Instruction
TABLE OF CONTENTS
CHAPTER 1 DESCRIPTION 3
2. Performance Parameters 4
CHAPTER 2 INSTALLATION 6
1. Introduction 6
2. Installation 6
3. Wiring 7
4. Power Supply 11
5. Battery 12
CHAPTER 3 OPERATION 13
1. Interface Overview 13
2. User level 14
2.1 How to login 15
2.2 How to logout 15
3. System Hierarchy 16
4. Type of Information 17
5. Normal Status 18
11. Operation 24
11.1 How to do system test 25
Page 1/49
BC8001A Installation and Operating Instruction
14. About 46
CHAPTER 4 MAINTENANCE 47
1. Daily Checking 47
2. Trouble-shooting Guideline 47
3. Fuse Replacement 49
4. Battery Maintenance 49
5. Reclamation 49
Page 2/49
BC8001A Installation and Operating Instruction
CHAPTER 1 DESCRIPTION
Page 3/49
BC8001A Installation and Operating Instruction
2. Performance Parameters
Page 4/49
BC8001A Installation and Operating Instruction
Page 5/49
BC8001A Installation and Operating Instruction
CHAPTER 2 INSTALLATION
1. Introduction
This section provides general instructions for mounting and wiring of the BC8001A control Unit.
Read this section before installing the equipment to ensure proper installation. If you are not familiar with the
BC8001A system, be sure to ask Siemens Building Technologies, Inc. technical support or an authorized
representative if you have any question.
Install and use the BC8001A fire alarm system in accordance with corresponding local regulation in your country or
this installation manual for your reference.
2. Installation
Always remove power (battery or AC) and wait at least 10 seconds to allow the supply voltages to decay before
installing or removing any module or cable or wring.
Mounting height for visual and manual access to the LCD displayed
Weight and size of the enclosure
Local code and regulation
Page 6/49
BC8001A Installation and Operating Instruction
3. Wiring
Note:
1. All wirings must be in accordance with corresponding local code or regulation.
2. All wires are UL recognized.
3. All circuits are power limited to NFPA 70.
Caution!
Observe positive and negative poles!
Make sure NO SHORT TO GND and NO SHORT CIRCUIT when connection!
Power limited and Non-Power limited wiring should be separated.
Page 7/49
BC8001A Installation and Operating Instruction
Figure 2
Internal wirings
Page 8/49
BC8001A Installation and Operating Instruction
120/240VAC
L N GND 12VDC*2
BAT+
BCB8004
Power supply
BAT-
BC8001A
Main board
Terminal description
Name(label) Description Name(label) Description
24V+ 24V output1 OC OC output
24V- 24- OC output ground
24V+ 24V output2 N+ NAC +
24V- * internally connected with 24V output1 N- NAC -
PPF Primary power fault D1 Dry contact1
BF Battery fault 24- Dry contact1 ground
CCF Charging circuit fault D2 Dry contact2
COM Common ground for BF,CCF,PPF 24- Dry contact2 ground
P Detection Bus P line
S Detection Bus S line
Page 9/49
BC8001A Installation and Operating Instruction
J1101 Terminal
OC 24VDC/400~2000ohm,Supervised
External Device Power Limited
Programmable
24- Line impedance: Max. 50ohm
N+ Class B Style Y
24VDC/1.5A, Supervised
Synchronous 20K
.. resistor* Power Limited
module
Regulated 24
N- Line impedance: Max. 4ohm
(*supplied with BC8001A)
EOL83
Red 10K Orange
D1
On site Class B Style B
Dry contact1 5.0VDC/0.3mA, Supervised
10K Line impedance: Max. 50ohm
24- Black Black
EOL83
10K
D2 Red Orange
On site
Class B Style B
Dry contact2 5.0VDC/0.3mA, Supervised
10K Line impedance: Max. 50ohm
24- Black Black
P
P Class B Style 4
24VDC@250mA,Supervised
To field devices
Power Limited
S
S Line impedance: Max. 50ohm
A+
No Connection
A-
A-Bus
A+
No Connection
A-
B+
No Connection
B-
B-Bus
B+
No Connection
B-
P To field devices
P
Class B Style 4
S 24VDC@250mA,Supervised
S
Power Limited
Line impedance: max. 50ohm
Page 10/49
BC8001A Installation and Operating Instruction
4. Power Supply
Model: BCB8004
Features:
Universal AC power input 120/240VAC,60/50Hz
Alternative AC power switch
Two power outputs of 24VDC
AC fuse capacity: 5.0A; Battery fuse capacity: 10.0A
P4
P2 24V+I
120V 24V-I
240V BCB8004 24V+II
24V-II To main
PPF board
BF
P1 CCF
AC L AC Fuse CG
connection N Bat+ Battery
(input) DC Fuse Bat- connection
GND P3
Terminals blocks:
P1: AC input connector from external power supply. These connectors are non-power limited.
Input voltages: 120/240VAC,60/50Hz
Rated input current: 700mA@120VAC, 400mA@240VAC
P2: AC input switch for 120V or 240V.
P3: Connects the back-up battery to the power supply. These connectors are non-power limited.
P4: Connects the power supply to the main board. These connectors are power limited.
24V+/24V-: 24VDC power limited output terminals,
24V+/24V-: 24VDC power limited output terminals,
PPF: Main power fault. When main power fault happens, a fault event will be reported on fault window.
BF: Battery fault. When battery fault happens, a fault event will be reported on fault window.
CCF: Charge circuit fault. When charge circuit fault happens, a fault event will be reported on fault window.
CG: Ground of PPF, BF and CCF.
AC fuse: To change AC fuse.
DC fuse: To change DC fuse.
Technical Specification:
Items Standard value
Input voltage 120/240 VAC
Input frequency 60/50 Hz
Rated input current 700mA@120VAC, 400mA@240VAC
Output 24VDC
Page 11/49
BC8001A Installation and Operating Instruction
5. Battery
Battery Maintenance - + - +
Check battery regularly, if the following things happen, eg.
Battery Battery
function is not normal, housing is distorted, liquid releases,
the battery must be changed. If the battery is dirty, please
use towel with warm water to clean it. Do not use petrol, or Figure 6
chemical liquid. Battery and AC power connection diagram
To be stored at -10 ~ +50 temperature and dry place.
To be stored at full chargeable status. To be charged before being used because of self discharge.
Page 12/49
BC8001A Installation and Operating Instruction
CHAPTER 3 OPERATION
1. Interface Overview
Number keys are used to input numbers, Chinese and English characters
Cancel and return
Confirm and enter
Scroll up/down- use to navigate up or down to choose a specific entry from a list of information displayed on the screen
Function button
Move cursor
Main menu function
LCD screen display
LEDs: Fire Alarm, Trouble, CPU Trouble, Power, Activation, Acknowledge, Alarm Silence, Reset
Buzzer: BC8001A has 4 kinds of sounds, which are used to indicate fire, trouble, isolation and active.
Page 13/49
BC8001A Installation and Operating Instruction
2. User level
BC8001A includes three kinds of user levels: Level 1, Level 2 and Level 3 (as shown with red
<Main Menu> L1A
round).
1.RT Information
Level 1 is default for everyone.
2.Set LCD Contrast
Level 2 is for safeguard.
3. Log in
Level 3 is for commissioning person.
4. About
Different level users need respective password to login and can do respective operations. See Table 1.
Page 14/49
BC8001A Installation and Operating Instruction
Password
3. Input corresponding password using number key and Press OK.
If the proper password is input, you can login level 2/3.
(Press to delete the wrong input.)
The default password for level 2 is 1234 and 4321 for level 3. The password can be changed
by configuration tool BF8001.
3. Press OK to logout.
Notes:
1 If current user interface is the first level, operators can directly log in second or third user level. If current user
interface is the second level (or third level), operators must return to the first user level, and then log in the third level
(or second level) again.
2 If there is no operation or events within a certain time (timeout is set by BF8001), monitor back lighting will be turned
off automatically. Press any key to turn on backlight.
3 In the interface of the second or third user level, if user makes no operation or no events happen within a certain
time (timeout is set by BF8001 or by station property of control unit), interface will switch to first user level
automatically.
Page 15/49
BC8001A Installation and Operating Instruction
3. System Hierarchy
Station BC8001A
Page 16/49
BC8001A Installation and Operating Instruction
4. Type of Information
4. Press to choose one device that you want to query its property and press OK key.
The property of the queried device is displayed. Press / to scroll down/up.
L3 A
Addr 1.03.1
Press C to return to previous window. Text Room 102 Heat Detector
Type BDS031 Heat Point Dete
Status Fire
Page 17/49
BC8001A Installation and Operating Instruction
5. Normal Status
Page 18/49
BC8001A Installation and Operating Instruction
Status:
LCD will display fire event automatically as Fire alarm screen. <RT Alarm:1> L1 A
The red fire alarm LED is on. * 1 Room 102 heat detector
Acknowledge LED is flashing.
Alarm Silence LED is flashing.
The buzzer and NAC devices are sounding. Fire alarm screen
How to do:
1. Press Acknowledge button to acknowledge the alarm :
If current user level is 1, login window will be popup automatically. After
inputting level 2/3 password, press OK to enter alarm window. All alarm
events are acknowledged at the same time:
Symbol * will be changed to # automatically
Buzzer is silent
Acknowledge LED will change from flashing to steady
If current user level is 2/3, all alarm events are acknowledged at the same
time.:
Symbol * will be changed to # automatically
Buzzer is silent
Acknowledge LED will change from flashing to steady
2. Press alarm silence button to stop NAC devices. These allow operator to
deactivate or reactivate the NAC devices. When NAC devices are silenced, the
silence LED is on.
5. If the fire is emergency, call 119 at once. If the fire is minor incident, press reset
to return to normal status.(password is required.)
Property display: select one fire information and press OK and screen will display as
L3 A
figure 4. After finishing checking, press C to return to the previous window.
Addr 01.003.001
Text Room 102 Heat Detector
Type BDS031 Heat Point Dete
One or more alarms happen: Status Fire
One or more alarm locations
First alarm message is selected
Alarm message can be scrolled with / key
Notes:
<RT-Alarm: 01> means there are 1 alarm event in total.
01 represents the number of alarms.
# represents the event is acknowledged and *represents the event is not
acknowledged.
Page 19/49
BC8001A Installation and Operating Instruction
Status:
LCD will display trouble event automatically as Trouble Screen. <RT Trouble:1> L1 A
The trouble LED is on. * 1 Room 102 heat detector
Acknowledge LED is flashing.
The buzzer is sounding.
Trouble Screen
How to do:
1. Press Acknowledge button to acknowledge the trouble:
If current user level is 1, login window will be popup automatically. After
inputting level 2/3 password, press OK to enter trouble window. All trouble
events are acknowledged at the same time.
Symbol * will be changed to # automatically
Buzzer is silent
Acknowledge LED will change from flashing to steady
If current user level is 2/3, all trouble events are acknowledged at the same
time.
Symbol * will be changed to # automatically
Buzzer is silent
Acknowledge LED will change from flashing to steady
If you can solve the problem by yourself, the trouble LED and acknowledge LED is off
and trouble window is disappeared automatically. If you can not remove the trouble by
yourself, please call your local service office of Siemens Building Technologies. But if a
trouble event is acknowledged and it is not removed within 24 hours, the buzzer will
release trouble sound again but the current window on controller will remain unchanged
and no new event is displayed. Now if you want to acknowledge it, you have to query
trouble information (refer to How to query real time information) and press
Acknowledge button, the trouble event can be acknowledged again. If the system
consists of more than one controller, the other controllers have to be done as above
steps one by one.
L3 A
Property display: select one trouble information and press OK and screen will display Addr 01.003.001
as figure 4. After finishing checking, press C to return to the previous window. Text Room 102 Heat Detector
Type BDS031 Heat Point Dete
Status Trouble
Note:
If current window is fire, a trouble occurs. The trouble event will not be displayed
automatically because trouble priority is lower than fire priority. You have to query
trouble information (refer to How to query real time information) and press
Acknowledge button.
Page 20/49
BC8001A Installation and Operating Instruction
CPU Trouble:
When application software crash or CPU hardware is damaged, system can not work
normally and CPU trouble LED is on. Any key is not available. Now you have to switch
off power and call for service from Siemens Building Technologies.
Page 21/49
BC8001A Installation and Operating Instruction
Status:
LCD will display isolation event automatically as Isolation Screen. <RT Isolation:1> L1 A
The isolation LED is on. - 1 Room 102 heat detector
Acknowledge LED is flashing.
The buzzer is sounding.
Isolation Screen
How to do:
1. Press Acknowledge button to acknowledge the isolation:
If current user level is 1, login window will be popup automatically. After inputting
level 2/3 password, press OK to enter trouble window. All isolation events are
acknowledged at the same time.
Symbol * will be changed to # automatically
Buzzer is silent
Acknowledge LED will change from flashing to steady
If current user level is 2/3, all isolation events are acknowledged at the same
time.
Symbol * will be changed to # automatically
Buzzer is silent
Acknowledge LED will change from flashing to steady
When the isolated point is open, the panel will revert to normal status.
Status:
LCD will display activation event automatically as Activation Screen. <RT Active:1> L1 A
The activation LED is on. - 1 Floor 02 BDS221(A) Outpu
Page 22/49
BC8001A Installation and Operating Instruction
This function can be done by level 2/3 user. If current level is 1, login should be done first (Refer to login on page 14) and then
follow these steps:
Notes:
<Alarm Record: 01> means there are 1 alarm event in total.
01 represents the number of alarm record.
+ represents the event is not recovered and -represents the event is recovered.
Page 23/49
BC8001A Installation and Operating Instruction
11. Operation
This function can be done by level 2/3 user. If current level is 1, login should be done first (Refer to login on page 14).
Page 24/49
BC8001A Installation and Operating Instruction
How to do:
1. Press to enter main menu. <Main Menu> L3A
1. RT Information
The main menu is displayed. 2. History Record
3. Operation
4. Configure
Note:
Checking standard:
Screen--Normal state is normal display of all screen area.
Sound -- Normal state is that buzzer sends out 4 kinds of sounds (fire alarm, fault,
active and isolate).
LED -- Normal state is all LEDs brightening.
Page 25/49
BC8001A Installation and Operating Instruction
Isolate/Open Line
Function: This is only necessary in exceptional situations, for example, while some part of
the construction is in process. As soon as conditions have returned to normal, the isolated <RT Isolation:1> L1 A
line must be immediately restored to normal status again. - 1 Room 102 heat detector
Status:
LCD will display isolation event automatically as Isolation Screen. Isolation Screen
The isolation LED is on.
The buzzer sounds.
3. Press to choose one station which include the desired line and press OK key.
6. Press to choose 2.Isolate / 3.Open and press OK key. <Operate Lines > L3 A
Isolation status is shown/disappeared. 1. Points
2. Isolate
3. Open
4. Test
Page 26/49
BC8001A Installation and Operating Instruction
Isolate/Open Point
Function: only when it is damaged or defective until it is replaced. An isolated point can not
generate any messages. As soon as replacement is finished, the isolated point must be
immediately restored to normal status again.
Status:
LCD will display isolation event automatically as Isolation Screen.
<RT Isoaltion:1> L1 A
The isolate LED is on.
- 1 Room 102 heat detector
The buzzer sounds.
Page 27/49
BC8001A Installation and Operating Instruction
2. Press to choose 3.Operation and press OK key. 001 BC8001A Compact Stati
3. Press to choose one station which includes the desired line and press OK key. 1.Line
2.System Property
5. Press to choose one line which includes the desired point and press OK key. <Operate Lines > L3 A
1. Points
2. Isolate
3. Open
4. Test
6. Press to choose 1.Points and press OK key.
All points connected with the chosen line are displayed.
<Operate Points> L3 A
001 BDS051(A) 001
002 BDS031(A) 002
003 BDS121(A) 003
004 BDS221(A) 004
7. Press to choose one desired point and press OK key.
Page 28/49
BC8001A Installation and Operating Instruction
Function: Allow to test the correct function of alarm devices. At test/walk-test mode alarm
can be normally generated if alarm condition is fulfilled. But alarm devices are not really
activated. After the test work is completed immediately restore the test mode. The test <RT Test:1> L1 A
/walk-test events are not saved in history record. The difference of test and walk-test: - 1 Room 102 BDS031 Heat
Status:
No message is displayed.
How to test:
1. Press to enter main menu.
The main menu is displayed. <Main Menu> L3A
1. RT Information
2. History Record
3. Operation
4. Configure
3. Press to choose one station which includes the desired line and press OK key.
<Operate Points> L3 A
001 BDS051(A) 001
002 BDS031(A) 002
003 BDS121(A) 003
004 BDS221(A) 004
Page 29/49
BC8001A Installation and Operating Instruction
Page 30/49
BC8001A Installation and Operating Instruction
12. Configure
Functions: Configure system, including property and parameters of station, loops and field devices, showing interlock
relationship, set system date & time, set LCD contrast, set volume of buzzer, set LCD switch off time, set language, automap,
save configuration etc.
This function can be done by level 2/3 user. If current level is 1, login should be done first (Refer to login on page 14).
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard
for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to
specific values or not used at all as indicated below.
Program feature or option Permitted in UL 864? (Y/N) Possible settings Settings permitted in UL 864
Buzzer Volume Y 01 1
<Configure System> L3 A
5. Press OK to save the modification and return to the previous window.
Page 31/49
BC8001A Installation and Operating Instruction
<Configure Station> L 3 A
5. Press to choose one desired station and press OK key. 001 BC8001A Compact 01
Press / to scroll down/up. 002 BC8001A Compact 02
003 BC8001A Compact 03
Note:
1. Now the modified text is saved temporarily. If the control unit is reset, the modified text <Station 02> L3A
Address 02.000.000
will be lost. If you want to save the modification for long time, please do the Save
Type BC8001A Compact
Configuration operation(refer to Page 44). Text BC8001A 02
2. A-Bus is a drop-down list. When it is active, press F and the drop-down list is displayed. Status Normal
Page 32/49
BC8001A Installation and Operating Instruction
Note:
1. Now the modified text is saved temporarily. If the control unit is reset, the modified text <Config Line004> L 3 A
will be lost. If you want to save the modification for long time, please do the Save Address 02.004.000
Type BDS Line
Configuration operation(refer to Page 44).
Text BDS Line 004
2. The function of operability is reserved. Status Normal
<Config Line004> L 3 A
Mode Normal
Operability Yes
Page 33/49
BC8001A Installation and Operating Instruction
Note:
1. Now the modified text is saved temporarily. If the control unit is reset, the modified text <Config Point: 02> L3A
Address 02.004.002
will be lost. If you want to save the modification for long time, please do the Save
Type BDS051(A) Smoke
Configuration operation(refer to Page 44).
2. Type is a drop-down list. When it is active, press F and the drop-down list is displayed. Text BDS051(A) 002
Press / to select corresponding type. Press OK. Status Trouble
3. Sensitivity is a drop-down list. When it is active, press F and the drop-down list is
displayed. Press / to select High, Std and Low according to site situation. <Config Point: 02> L 3 A
Press OK. Mode Normal
4. AnalogVal: relative value of smoke density. Sensitivity Std
AnalogVal 0
Page 34/49
BC8001A Installation and Operating Instruction
Page 35/49
BC8001A Installation and Operating Instruction
Note:
1. Now the modified text is saved temporarily. If the control unit is reset, the modified text
will be lost. If you want to save the modification for long time, please do the Save
Configuration operation(refer to Page 44).
2. Explanation of logic expressions:
Page 36/49
BC8001A Installation and Operating Instruction
+~+*~* : Both are valid abbreviations. It is not applicable to [ ]N; For example:
{T1,T2}: T1, delay time; T2 duration of the interlocking command. For T1 and T2:
0-255 seconds are valid; For example: 01.011.001+01.011.002+01.011.003
=01.011.004{3020}, which means after a delay of T1, the controller starts to issue
a interlocking command, and after the interlocking command has lasted for T2, it
stops issuing command.
Page 37/49
BC8001A Installation and Operating Instruction
4. Press to delete current date and time, and enter new date and time. Date: 2006-01-01 12:30:30
Page 38/49
BC8001A Installation and Operating Instruction
Use Up/Down 52
4. Press or to increase or decrease the value.
No message is displayed. But with each keystroke the contrast is slightly increased and
decreased. Repeat this step until the desired contrast is reached.
Page 39/49
BC8001A Installation and Operating Instruction
Use Up/Down 1
4. Press or to change the value.
0 means buzzer is off; 1 means buzzer is on.
Page 40/49
BC8001A Installation and Operating Instruction
Function: If no key is pressed within a certain time, LCD turns off automatically. LCD can be lighted up by pressing any key. But
if fire or faults happen, the LCD turns on immediately.
Valid(0~60) 5 (min)
Page 41/49
BC8001A Installation and Operating Instruction
Language English
Page 42/49
BC8001A Installation and Operating Instruction
Function: Automap can find address of all field devices which are connected with control unit and list them as
points. When you navigate points, for those points which are configured will remain unchanged and display its text
content and for those points which are not configured will display with ?New?Automap. Then it can be configured
on site. It is convenient for configuration of new added point on site.
<Automap> L3A
4. Press OK key to confirm to automap.
Are you sure to automap?
The system will show the Configure System window.
5. Navigate points (refer to How to configure point), the points marked with <Configure System> L3A
?New?Automap are new and you can configure it now. And if you want to save it 1. System Property
2. Station
permanently, please refer to how to save configuration.
Page 43/49
BC8001A Installation and Operating Instruction
Function: To permanently save the modification of property and logic expression of system, station, line and point.
Otherwise the modification will be lost when the system reset.
In processing, waiting
Page 44/49
BC8001A Installation and Operating Instruction
Auto: The output modules will be activated automatically when their logic statements are fulfilled.
Manual: The output modules will not be activated automatically when their logic statements are fulfilled. They need
to be activated manually by user.
Page 45/49
BC8001A Installation and Operating Instruction
14. About
Function: To display system software version, license number and last download time.
How to do:
1. Press to enter main menu.
<Main Menu> L3A
The main menu is displayed. 1. RT Information
2. History Record
3. Operation
4. Configure
Page 46/49
BC8001A Installation and Operating Instruction
CHAPTER 4 MAINTENANCE
1. Daily Checking
Persons on duty should do daily check of control unit and make records. If fire alarm, troubles and other abnormal events
happen, Trouble-shooting Guideline shall be followed. After the control unit restores to normal, the events shall be well
recorded.
2. Trouble-shooting Guideline
Function keys, LED and LCD Failure of signal wire or power line; Correct connection;
1 screen are ineffective or Damage of corresponding hardware; Replace corresponding hardware;
damaged
No indication of power Main power or battery is off; Check the wiring of power supply and
supply Power connection is not firmly battery;
2
secured; Replace main board;
Power supply is damaged;
Power supply is on but the LCD brightness is not enough; Adjust LCD brightness;
LCD on control unit is black LCD without power or the adapter on Examine power supply line or replace
3
screen main board is damaged; main board;
LCD is damaged, Replace LCD;
Control unit can not display System software or configuration files download corresponding software or
4 any content. are lost; configuration files;
CPU board is damaged; Replace CPU board;
No sound No voltage; Replace power supply line or main
board;
5
Volume of buzzer is not enough; Adjust buzzers volume;
Buzzer is damaged; Replace buzzer;
Control station trouble Configuration file is unconformable Modify configuration file;
with the devices on site;
6 Main board address is not set or Modify address setting;
unconformable with configuration file;
Main board is damaged; Replace main board;
Main board input & output Configuration file configuration is Modify the configuration;
trouble wrong;
7
The input/output port of main board is Replace main board;
damaged;
Power supply trouble Power supply is wrongly configured; Check /modify configuration file;
Exterior voltage overrun power Adjust exterior voltage;
8 requirements;
Battery is damaged; Replace power supply or battery;
Power supply is damaged;
Page 47/49
BC8001A Installation and Operating Instruction
Other operating failure on Operating level is low or operating Log on higher operating level;
control unit method is not right,
16
Configuration file is lost or fault; Update configuration file;
Some hardware is damaged; Replace damaged hardware;
Date is displayed as Battery on main board is damaged Replace battery on main board
17
2000-00-00
Page 48/49
BC8001A Installation and Operating Instruction
3. Fuse Replacement
For problems with other components, please contact manufacturer for replacement.
4. Battery Maintenance
Perform the following tests at the recommended interval. Replace the battery set every four years or if any of the test criteria are
not met.
Initiation/Reacceptance:
1. Charge Test - With the batteries fully charged and connected to the charger, measure the voltage across the battery set. It
must read 26.0VDC0.3V.
2. Discharge Test With full system alarm load, the voltage on a fully charged battery must not fall below 20.4VDC after 30
minutes.
3. Load Voltage Test With full system alarm load, the voltage on a fully charged battery must not fall below 24.0VDC after 1
minute.
Testing Interval:
1. Semiannually Perform the Load Voltage Test
2. Annually Perform the Charger Test and Discharge Test
5. Reclamation
For abandoned control units, please contact local office of manufacturer to make proper treatment. Any random
discarding of control units is strictly forbidden.
Page 49/49