Taco Load Program Room Results 07/13/2017

ROOM Almacen Principal SYSTEM TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
13.9 16.6 11.0 .0 3 469 1 231 1 1 .0 8.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 375 0 .1 .1

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
E(-90)/Vertical(90) 14.0 1 129.8 1 2

PEAK LOAD occurs at 4 PM, June Heating for 62 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Int. Gain To RA
Window Transmission 394 362
Window Solar 1127
Wall Transmission 372 372
Wall Solar 481
Roof Transmission 1469 1469
Roof Solar 1318
Partition 0 0
Floor 69 1040
Infiltration 0 0 0
Lights 1599 1599
People 750 600 750
Equipment 1280 0 1280
Sub Total 8859 600 3243 3629
Safety Factor 0 0 0
Sub Total 8859 600 3243 3629
Ventilation 947 1472 947

Total 9806 2072 4189 3629

General Loads Flows

Cooling Heating Cooling Heating


Area (ft) 231 Total Load (BtuH) 11878 4189 Water (gpm) 2.4 .4
Volume (ft) 0 Total Load (BtuH/ft) 51.5 18.2 Air Room Peak (cfm) 420 60
Sen Heat Ratio w/o Vent .94 Total Load (Ton) 1.0 Air Room Peak (cfm/ft2) 1.8 .3
Sen Heat Ratio with Vent .83 Total Load (ft/Ton) 233 Air Room Peak (AC/hr) 0 0
Return Air (cfm) 378
Exhaust Airflow (cfm) 42
Infiltration (cfm) 0 0

You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com)