MV/LV prefabricated substation

Clipper C
Modular type of substations in G.R.C.,
up to 1250 kVA
Purpose
PM102331

Clipper C is a range of modular MV/LV prefabricated substation


dedicated to underground networks.
Rated power up to 1250 kVA.

Standards
Designed in accordance to IEC 62271-202.
Manufactured in accordance with ISO 9001 and ISO 14001.
PM102362

DM100212

Clipper C - Fully I.E.C tested

Enclosure
Outside or walk-in operated
Enclosure made of Glass Reinforced Cement
Protection degrees:
From IP 23 to IP 43 (on MV and LV
compartments)
IK 10 (mechanical resistance to impacts)
Class of enclosure: 5 k or 10 k (1250 kVA)
No corrosion risk with G.R.C. and low
internal condensation to improve electrical Equipment
equipment life time MV switchboard: FBX, RM6, Fluokit, SM6 or Flusarc
Access to MV and LV by front doors up to 5 functions 24 kV or 36 kV
Internal Arc Capability classification Transformer: Oil type up to 1250 kVA (according to dimensions)
AB 16 kA or 20 kA 1s LV switchboard with fuses or circuit breaker
Option: Earthing circuit, internal lighting
Street lighting box Optional equipment:
Finish: choice of colours and cladding Remote Terminal Unit: Eseargy T200
Thermal insulation and/or air conditioning Fault Passage Indicator: Easergy Flair or Dax
Compartmented substation Public lightning cabinet
LV metering
Clipper C
Layout
2700 3200 3650
DM100227

1960
1960

1960
2 2 4
1 2

1 3
1 3
4

Clipper C 27 I.E.C. tested Clipper C 32 walk-in fully I.E.C. Clipper C 37 for up to 5 function RMU
non-walking type up to 1250 kVA

Legend
1 MV Switchboard
2 Transformer
3 Low voltage panel
4 Remote control unit

Installation recommandation for Clipper C civil work


RIGHT SIDE FRONT SIDE
Width + 60 mm Length + 60 mm

Height

Upper flat bearing face


(Without hard point by gravel 100 1000
120

1mm / 1m) concave form 150 mini 150 mini 150 mini 150 mini
230 x 4
= = 450 230 230 230 230 OPTION
Reinforced
580

Oil Retention tank


600

REMARK: This drawing is provided


480

concrete wall to help with civil engineering work.


A technical survey should be
Polystirene wall pockets carried out to calculate the
170 x 170mm Reinforced concrete appropriate concrete basement
basement. required for a weak ground.
Subgrade with quarry-run Wall pockets are drawn as
Width of substation Length of substation example and can be positioned
where needed.
Basement made on site by the customer

Dimensions and weight


ART. xxxxxx 2011 Schneider Electric Industries SAS - All rights reserved

DIMENSIONS Outdoor Indoor Weight


In mm L I H Raised L I H Raised Empty s/station in tons
Std. Raised
CLIPPER C 27 2850 2110 2220 2680 1940 1960 4,7
CLIPPER C 27 GL 2810 2460 2220 2520 2700 2365 1960 2270 5 5.2
CLIPPER C 32 3350 2110 2220 3180 1940 1960 5.38
CLIPPER C 32 GL 3310 2460 2220 2520 3200 2365 1960 2270 5.8 6.1
CLIPPER C 37 3800 2110 2220 3630 1940 1960 6.06
CLIPPER C 37 GL 3760 2460 2220 2520 3650 2365 1960 2270 6.6 6.7

Schneider Electric Industries SAS


35, rue Joseph Monier As standards, specifications and designs change from time
CS 30323 to time, please ask for confirmation of the information given
F - 92506 Rueil Malmaison Cedex (France) in this publication.
Tl. : +33 (0)1 41 29 70 00
RCS Nanterre 954 503 439 Design: Schneider Electric Industries SAS
Capital social 896 313 776 Photos: Schneider Electric Industries SAS This document has been
www.schneider-electric.com Printed: Altavia Connexion - Made in France printed on ecological paper

NRJED111166EN 09-2011