AHU Vibration Data - Posting
AHU Vibration Data - Posting
Measurement:
Measurement was carried out at Blower (DE Pulley END), Blower (NDE- Impeller
End) & Motor (DE) . Vibration Levels are as follows:
Since the measurement shows that the problem may be Unbalance as the
vibration levels are high at 1X rpm, Single plane balancing was attempted.
After initial measurement, Trial mass of around 300 gms added on the reference
plane on the impeller. We found no changes in the vibration readings.
After removing the trial mass, we added around 500grams at the correction
angle of -64 degrees
We found no changes in the vibration reading & trim calculation showed the
same reading as above.
Since the Blower is not responding to the mass addition, we stopped the
balancing activity.
AHU Schematic Diagram:
Impeller
DE NDE
Note :