1.2 Standard values of rated thermal short time current (Ith) 25 times the rated current (Ir) for 2 s ; for Ir equal or
greater than 4000A, Ith is always 100kA
1.3 Overload conditions (IEC 354): Bushing selected with Ir not less than 120% of the rated current of the transformers
are considered to be able to withstand the overload conditions according to IEC 354.
2.1 Cantilever operating load (bushing installed less than 30 from vertical)
Ur Ir
kV 800 A 1600 A 2500 A 3150 A
36 500 N 625 N 1000 N 1575 N
52 500 N 625 N 1000 N 1575 N
2.2 Cantilever operating load ( bushing installed more than 30 from vertical)
Ur Ir
kV 800 A 1600 A 2500 A 3150 A
36 300 N 375 N 600 N 945 N
52 300 N 375 N 600 N 945 N
Ur Ir
kV 800 A 1600 A 2500 A 3150 A
36 1000 N 1250 N 2000 N 3150 N
52 1000 N 1250 N 2000 N 3150 N
Size Torque
M10 15 Nm
M12 25 Nm
M16 40 Nm
Size Torque
M10 25 Nm
M12 40 Nm
M16 90 Nm
Standard scope of supply does not include any surface treatment or plating.
Upon request, particularly for use in highly polluted environmental conditions or in tropical climate, all metal parts (in
copper or brass) air side can be supplied with 6-8 micron thickness electrolytic tinplating
5.0 Gaskets
During the impregnation of the transformer it is possible to reach the max temperature of 110C in oil and 120C in air for
24 hours, without damaging the gaskets.
Unless contrary request, the material normally used for the gaskets is NBR (nitrile rubber) suitable for use with mineral
oils with MIN ambient temperature of -30C and MAX temperature of +120C (up to 130C during drying process/vapour
phase).
Upon request available cork rubber impregnated gaskets, or in Viton, or in silicon rubber.
NBC (Cork TD1120): Temp. range: -30C/+120C (up to 130C during drying process/vapour phase).
Cork TD7000: Temp. range: -45C/+120C (up to 130C during drying process/vapour phase)
VITON: Temp. range: -20C/+150C (recommended when bushing is installed inside a cable box or a cable duct)
Drg 3800/1/2- Page 3.3 - 4 - 5EN: Bushings 12-24-36/1000-2000-3150 according to European standard EN50180
pollution level I-II-III-IV or b,c,d,e (IEC/TS 60815-1 2008).
Drg 3129 Bushings 36/1000-2000-3150-P3-OL300, in deviation to above, with special porcelain
with long oil tail 300mm/BIL 200 kV
Drg 3803- Page 3.7EN: Arcing horn kit to suit all above bushings.
Drg 3810 -Page 3.7: Arcing horn kit to suit above bushings.
Normally supplied according fig. A1 drg 3782-page 3.1, draw lead type, without a/horns, with brass bolt "D" tapped
M20x2,5 (Style A1) for the connection to the copper wire.
Upon request, the bushing can be supplied according to fig T1 drg 3782-page 3.1 with long rigid rod, and/or with arching
horns (see drg 3783-page 3.2) with "V" bracket for bottom a/horn (UNEL execution) or without bracket (DIN style).
COMPONENT LIST
FIG. A1
Pos.
Description
DIN ref.
Pos. 1 Porcelain
Pos. 2 Brass bolt "D" (usually DIN execution, on request execution "EL").
Pos. 3 Cap "E"
Pos. 5 Ring gasket "J"
Pos. 6 Fiber gasket "O
Pos. 7 Vent screw
Pos. 8 Nylon or fiber gasket
Pos. 9 Flange gasket "N"
Pos. 11 Brass nut M20 DIN 934
Pos. 12 Brass washer dia 21 DIN 125
Pos. 13 Spring washer dia 21 DIN 127
Pos. 14 Nut M10 (steel zinkplated or Aisi 304 on demand)
Pos. 15 Flat Washer dia. 10,5 mm (steel zinkplated or AISI304 on demand)
Fixing ring "B" DIN 42531 (in mild steel zinkplated or, upon request, in aluminium or
Pos. 17 AISI304)
FIG. T1
Pos.
Description
DIN ref.
Pos. 1 Porcelain
Pos. 2 Brass bolt "D" (usually DIN execution)
Pos. 3 Cap "E"
Pos. 4 Ring gasket "J"
Pos. 5 Fiber spacer O Ring gasket "J
Pos. 6 Flange gasket "N
Pos. 7 Brass nut M20 DIN 934
Pos. 8 Brass washer dia. 21 DIN 125
Pos. 9 Nut M10 (steel zinkplated or Aisi 304 on demand)
Pos. 10 Flat Washer dia. 10,5 mm (steel zinkplated or AISI304 on demand)
Pos. 11 Spring washer dia. 21 DIN 127 (steel zinkplated or AISI304 on demand)
Pos. 13 Fixing ring "B" DIN 42531 (in steel zinkplated or, on demand, in aluminium or AISI304)
Pos. 14 Aluminium clamping piece "E" DIN 42538
Pos. 1 Porcelain
Pos. 2 Copper rod
Pos. 3 Brass nut DIN 934
Pos. 4 Brass top washer F
Pos. 5 NBR ring gasket J
Pos. 6 Brass cap "E"
Pos. 7 Fiber gasket
Pos. 8 Vent/screw R
Pos. 9 NBR gasket "M
Pos. 10 Fiber spacer O
Pos. 11 Brass ring P
Pos. 12 Locking screw
Pos. 13 Copper ring S
Pos. 14 Nut M12 DIN 934 AISI304
Pos. 15 Flat washer dia. 13 mm AISI304
Pos. 16 Fixing ring C-D DIN 42538 (aluminium) or EN 1000 / EN 3150 (AISI304)
Pos. 17 Aluminium clamping piece F DIN 42538
Pos. 18 NBR flange gasket N
Pos. 19 Centering ring
These bushings are normally supplied in accordance to the customer's own specifications: in particular oil and air side
connections, rod elongation for CT accommodation, separable conductors design and other.
With this new catalogue we have the pleasure to propose a unified design and aligne the oil side connection to the
EN50180 design using only one oil side rod length either you use nuts of flags (old fig. T1, B1 will be replaced by new
fig E1); the consequence is a conductive rod few mm longer on the oil side, compared to the old Din style without any
practical impact on the transformer design, while on the contrary the logistic will take a lot of advantages with only one
solution.
Also we propose some typical elongation for CT accommodation and split conductor.
For the air side connection, normally the bushing is fitted with flags EP/FP DIN 43675
A/horns are supplied, only upon request, in two executions shown at page 3.7.
Pos. 1 Porcelain
Pos. 2 Copper rod conductor
Pos. 3 Brass cap "E"
Pos. 4 Brass top washer F
Pos. 7 NBR ring gasket "J"
Pos. 8 Gasket "O
Pos. 9 NBR gasket M
Pos. 10 NBR flange gasket N
Pos. 11D Flag EP / FP DIN 43675
Pos. 11U Flag UNEL style
Pos. 12 Brass ring P
Pos. 13 Copper ring S
Pos. 14 Brass nut DIN 934
Pos. 16 Fiber gasket
Pos. 17 Vent / screw R
Pos. 18 Locking screw
Pos. 23 Bronze contact ring U
Pos. 24 Aluminium fixing ring C-D DIN 42538
Pos. 25 Aluminium clamping piece "F" DIN 42538
Pos. 26 Nuts M12 DIN 934 AISI304
Pos. 27 Flat washer dia. 13 mm AISI 304
Page 4.2: Flags EP - from 1000 to 6300 A FP DIN 43675/ UNEL 38137-67/NEMA
Page 4.3: Flags ER - FR DIN 43675 from 1000 to 4500 A
Page 4.4: Flags 250 & 630 A different styles
NOTE: All flags are fitted with locking bolts and washers in in stainless steel AISI 304.
Tightening torque on the locking bolts of the flags (suggested values, +/- 10%)
Size Torque
M10 25 Nm
M12 40 Nm
M16 90 Nm