Trasnformer VD Per %Z Calculation

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 1

Trasnformer Type 1-Phase Padmount

Primary Voltage [V] 16000V


Secondary Voltage [V] 120/240V
Size [kVA] 100 kVA
1-Phase XMFR
%Z 3.3 Suggested %Z 3.3
X/R 3.1 Suggested X/R 3.1
Tap Changer 0.00%
Nominal Voltage @ Secondary_Bus [v] 120/240V
Voltage @ Secondary_Bus(No Load) [V] 120/240V
Service Load 1-Phase
Nominal Service Voltage L-L [V] 240V

Sum of Peak Loads [kVA] 408 kVA


Total No of Services 17
Load @ XFMR_Secondary [kVA] 230.52 kVA
Voltage Drop XFMR (%) 5.26%
Voltage L-L @ XFMR_Secondary 227.38V