60Hz
Contents
About Trane ................................................................................................ 04
TVR System ............................................................................................... 05
TVR Advantage .......................................................................................... 07
TVR Applications ........................................................................................ 08
Features
DC Inverter System .........................................................,.............. 10
Higher Reliability ............................................................................ 11
Enhanced Comfort ........................................................................ 12
Unique Fan Characteristics ........................................................... 13
Easier Installation & Service.......................................................... 14
Easy Selection Software ............................................................... 15
Mini TVR 5G
Features ........................................................................................ 17
Outdoor Unit Specifications ........................................................... 22
Outdoor Unit Dimensions .............................................................. 25
TVR 5G (All Inverter)
Recommended Combination Table ............................................... 28
Features ........................................................................................ 29
Outdoor Unit Specifications ........................................................... 34
Outdoor Unit Dimensions .............................................................. 36
TVR 5G (Heat Recovery/3 Pipes)
Recommended Combination Table ............................................... 38
Features ........................................................................................ 39
Outdoor Unit Specifications ........................................................... 44
TMS Specifications ........................................................................ 45
Dimensions .................................................................................... 46
TVR 5G (Inverter+Fixed)
Recommended Combination Table ............................................... 48
Features ........................................................................................ 49
Outdoor Unit Specifications ........................................................... 53
Corrosion Resistance unit ............................................................. 54
Outdoor Unit Dimensions .............................................................. 55
TVR 5G (All Inverter-T3/High Ambient)
Features ........................................................................................ 57
Outdoor Unit Specifications ........................................................... 59
Outdoor Unit Dimensions .............................................................. 60
Contents
Nomenclature
Outdoor Unit................................................................................... 61
Indoor Unit...................................................................................... 62
Combination of Outdoor Units .................................................................... 63
Indoor Units Lineup
Indoor Units Offering Summary .................................................... 68
Description Summary-Indoor Units Range.................................... 69
One-way Cassette ........................................................................ 72
Two- way Cassette ....................................................................... 74
Compact Four-way Cassette ........................................................ 76
Four-way Cassette ....................................................................... 78
Low Static Pressure Unit .............................................................. 80
Concealed Duct Unit (A5 Type) .................................................... 82
High Static Pressure Unit ............................................................. 84
Ceiling & floor type ........................................................................ 86
Wall mounted S Type .................................................................... 88
Wall mounted C Type .................................................................... 90
Wall mounted R Type .................................................................... 91
Console ......................................................................................... 92
Fresh Air-processing Unit ............................................................. 94
ERV- Energy Recovery Ventilator .............................................................. 96
Control Systems
Network Control ............................................................................ 100
Wireless Remote Controller .......................................................... 103
Wired Controller ............................................................................ 104
Centralized Controller ................................................................... 106
Accessories .................................................................................. 110
Building Management System (BMS) ........................................................ 115
Piping Accessories
Outdoor/ Indoor Branch Specifications ........................................ 120
Outdoor branch Drawings ............................................................ 121
Indoor branch Drawings ............................................................... 122
3
About Trane
Trane is all about air - cool air, warm air, clean air. As a world
leader in air conditioning systems, services and solutions, we
control the comfort of the air for people in homes and many of
the world's largest and most famous commercial, industrial and
institutional buildings. And we're applying Trane's expertise in
environmental technology and energy conservation to make a
difference in energy efficiency around the globe.
03
4
4
System
Presenting a new and excellent heating and cooling option from Trane - with legendary
Trane benefits. Best- in-class energy efficiency. Truly customizable comfort. Available
simultaneous heating and cooling throughout a building. All with small footprints and
multiple installation options for a wide variety of building types.
These are just some of the benefits of Integrated TVR 5G system, our newest heating
and cooling options that bring a new level of choice to our customers. TVR 5G can be
perfect as stand-alone heating and cooling systems - or perfect as supplemental
heating and cooling systems.
For a wide variety of customers, applications and building types, TVR 5G can be the
solution youve been looking for to improve the comfort of your building - and improve
the lives of the people in it. Large and small buildings. Old and new buildings. Schools
and offices. TVR 5G can serve as a stand-alone or supplemental system for a wide
variety of buildings and applications, offering comfort, efficiency and user control
without compromise.
5
System
The new Variable Refrigerant, TVR A single TVR system fully integrates
air conditioning concept is a modular all functions necessary for filtration,
HVAC system designed to provide the cooling/heating, and ventilation. The
ideal climate in offices, retail establish- indoor climate quality can be improved
ments, hotels, luxury apartments, and when pretreated outside air is connect-
villas. Furthermore, it is equally suited ed either directly to the indoor units or
to new construction and retrofit introduced as a separate system. The
projects. In the global arena, TVR TVR system offers advantages
systems have gained significant popu- throughout the lifecycle of the project;
larity with airco ditioning professionals from design, installation, commission-
and discerning end users who recog- ing, operation and mainte - nance. The
nize its considerable benifits. Independent Zone Control delivers
energy savings for the end user by
TVR can be installed as the main ensuring that the indoor units for unoc-
HVAC system in a facility or as a cupied rooms remain off.
supplemental one that coordinates with
an existing HVAC installation to meet
different application requirements.
TVR (Trane Variable Refrigerant)
technology systems combine one or
more centralized DC Inverter, aircooled
compressors and condensers connect-
ed to many indoor (fan coil) units
throughout the building.
6
Advantage
Energy Efficient:
7
Applications
8
Applications
These factors constitute to higher system cleaning and changing filters and cleaning
9
Features -
DC Inverter System
High efficiency DC Inverter compressor
Trane Air Conditioner achieves the industry's top class energy efficiency of cooling EER and heating COP
by utilizing the Brushless Reluctance DC compressor control, improved performance heat exchanger by
innovative design and numerous high performance key parts. High efficiency DC inverter compressor reduces
power consumption by 25%.
Powerful magnets provide high torque and efficiency and achieve 70% reduction in volume.
Centralizing winding
Rotor speed(s-1)
20 40 60 80 100
Distributing winding
10
Features -
Higher Reliability
Cycle duty operation
In one combination, any of the outdoor unit can run as the master unit and master unit can cycle in a period, to
realize the equal lifespan among the outdoor units. As a result extend the system lifespan significantly.
Priority Priority
Priority Priority
Backup operation
In a multiple system, if one module is failed, other modules can be backup instead of the failed one for continuing
operation.
Running state
Stand by state
1st stage
4th stage: oil balance technology between modules
3rd stage
5th stage: intelligent system oil return program
11
Features -
Enhanced Comfort
Quick warm-up & cool-down design
Fluctuation of room temperature
Cooling operation
Time
12
Features -
Unique Fan Characteristics
DC Fan Motor
According to the running load and system pressure, the system controls the speed of DC fan to achieve the
minimum energy consumption and best performance.
Motor speed(RPM)
DC inverter stepless
adjustment
AC inverter
multistep adjustment
System pressure
Fan grille
Optimized fan blade shape with new air outlet grille enhanced air flow volume
which greatly improves fan performance and decreases noise.
Standard 0~20Pa, 20~40Pa to be customised.
13
Features -
Easier Installation & Service
PQ E PQ E PQ E PQ E
XY E X Y E P Q E
Auto addressing
Easy to transport
14
Features -
Easy Selection Software
Selection software
To meet consultants and distributors requirements,
Trane has developed a new program for designing
TVR systems. The software provides quick and
convenient selectable options for users, supports
multiple languages, and greatly improves the selection
process.
15
Mini TVR 5G
Mini TVR5G with DC inverter compressor and DC fan motor delivers a highly efficient solution for small
commercial buildings. Four to nine rooms require only one outdoor unit, and individual control is enabled in
each room.
NEW
16
Mini TVR 5G - Features
Wide range
Wide of of
range outdoor units
outdoor units
The outdoor units capacity range from 10.5kW to 18kW which is ideal for small offices, villas,
The outdoor units capacity range from 10.5kW to 18kW which is ideal for small offices, villas,
apartment and shops, making it perfect for commercial and residential application.
apartment and shops, making it perfect for commercial and residential application.
10.5kW 12/14/16/18kW
10.5kW 12/14/16/18kW
Flexible indoor
Flexible units
indoor connection
units connection
MiniMini
TVRTVR
5G with intelligent
5G with control
intelligent gives
control you
gives independent
you independentzoning
zoningcontrol
controlwith
withmaximum
maximum flexibility.
flexibility.
A single outdoor
A single unitunit
outdoor supports up up
supports to nine indoor
to nine units,
indoor freeing
units, freeingupupconsiderable
considerablespace
spaceoutside.
outside. Use your
your
backyard more
backyard wisely
more withwith
wisely muchmuchmore space
more spaceavailable
availablecreated
createdbybyless
lessnumber
numberof
ofoutdoor
outdoor units.
Max.Max.
9 indoor unitsunits
9 indoor for afor18kW outdoor
a 18kW unitunit
outdoor installation
installation
Max.Max.
7 indoor unitsunits
7 indoor for afor16kW outdoor
a 16kW unitunit
outdoor installation
installation
Max.Max. 6 indoor
6 indoor unitsunits
for afor14kW
a 14kW outdoor
outdoor unitunit installation
installation
Max.Max. 6 indoor
6 indoor unitsunits
for afor12kW
a 12kW outdoor
outdoor unitunit installation
installation
Max.Max. 5 indoor
5 indoor unitsunits
for afor10.5kW
a 10.5kW outdoor
outdoor unitunit installation
installation
Mini
Mini VRF
VRF
Wide
Wide operation
operation temperature
temperature range
range
MiniMini
TVRTVR 5G system
5G system operates
operates stably
stably at extreme
at extreme temperaturerange
temperature rangefrom
fromminus
minus15C
15C to
to 43C
43C
COOLING MODE
COOLING MODE
-15C 43C
-15C 43C
HEATING MODE
HEATING MODE
-15C 27C
-15C 27C
17
Mini TVR 5G - Features
Actual length 45 60
Level difference between IDUs is 8m
branch joint
*1: Total pipe length is equal to all the liquid pipe or all the gas pipe length.
8kW 10.5kW 12kW 14kW 16kW 18kW 8kW 10.5kW 12kW 14kW 16kW 18kW
The new designed window fins enlarge the heat-exchanging area , decrease the air resistance, save more
power and enhance heat exchange performance.
Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency.
The specially coated blue fins enhance durability and protect against corrosion from air, water and other
corrosive agents, assures a longer coil service life.
18
Mini TVR 5G - Features
Easy installation
Easy to transport
Easy installation: No special area is required for outdoor
units.
Easy transportaion: All outdoor units can be transported
by elevator, which greatly simplifies installation and
reduces time and labor.
The Mini TVR 5G indoor and outdoor units are almost as
easy to install as residential air conditioning systems,
making them ideal for small offices and shops.
Auto addressing
Addresses of indoor units can be set automatically by outdoor units.
Wireless controller can inquire and modify every indoor units address.
Outdoor unit can
distribute addresses
to indoor unit.
TCONKJR29B TCONTRM05A
19
Mini TVR 5G - Features
More convenience in installation
A four-direction space is available for connecting pipes and wiring in
various installation sites.
Right side
Front side
Bottom side
20
Mini TVR 5G - Features
Full DC Inverter technology
At the heart of our system, there is a highly intelligent inverter driven compressor. This advanced
technology enables the output of the outdoor unit to be modulated by the cooling or heating demands
of the zone that it controls. This advanced system ensures precise temperature regulation and highly
efficient energy usage, making a significant contribution to the unit,limiting the impact on the environment.
Highly Efficient DC Motor:
- Creative motor core design
- High density neodymium magnet
- Concentrated type stator
-Wider operating frequency range
Better balance and Extremely Low Vibration:
- Twin eccentric cams
- 2 balance weights
Highly Stable Moving Parts:
- Optimal material matching rollers and vanes
-Optimize compressor drive technology
Compressor - Highly robust bearings
(Twin Rotary) structure
-Compact structure
DC inverter stepless
adjustment
AC inverter
multistep adjustment
System pressure
Air deflector
New grille
New fan
66
21
Mini TVR 5G -
Outdoor Unit Specifications
Model 4TVV0042AK000AA 4TVV0048AK000AA 4TVV0055AK000AA
59
22
Mini TVR 5G -
Outdoor Unit Specifications
Model 4TVV0036A1000AA 4TVV0042A1000AA 4TVV0048A1000AA 4TVV0055A1000AA 4TVV0060A1000AA
Mini VRF
Fan motor Type DC DC DC DC DC
Quantity 1 2 2 2 2
Air flow rate m3/h 5,100 6,000 6,000 6,000 6,800
CFM 3,000 3,531 3,531 3,531 4,002
Motor output W 170 852 852 852 1002
Compressor Type Rotary Rotary Rotary Rotary Rotary
Quantity 1 1 1 1 1
Capacity kW 7.13 9.88 9.88 13.98 13.98
kBtu/h 24.3 33.7 33.7 47.7 47.7
Crankcase heater W 25 25 25 25 25
Oil type FV50S FV50S FV50S FV50S FV50S
Oil charge gal.(ml) 0.18(670) 0.23(870) 0.23(870) 0.37(1400) 0.37(1400)
Refrigerant Type R410A R410A R410A R410A R410A
Factory charging Ibs.(kg) 6.6(3.0) 7.3(3.3) 8.6(3.9) 8.6(3.9) 9.9(4.5)
Design pressure (High/Low) MPa 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6
PSI 640/380 640/380 640/380 640/380 640/380
Net dimension (WHD) inch 42-5/1638-1/3215-19/32 35-7/1452-1/415-3/4 35-7/1452-1/412.598
mm 1075966396 9001327400 9001327320
Packing size (WHD) inch 44-3/3243-5/1617-1/8 40-35/6457-21/6417-1/8
mm 11201100435 10301456435
Net weight lbs.(kg) 172(78) 203(92) 209(95) 225(102) 225(107)
Gross weight Ibs.(kg) 187(85) 234(106) 234(106) 249(113) 249(118)
Operating Cooling F(C) 5~118.4(-15~48)
temperature range Heating F(C) 5~80.6(-15~27)
Note:
1. The cooling conditions: indoor temp.: 27C DB(80.6F), 19C WB(60 F) outdoor temp.: 35C DB(95F) equivalent pipe length: 5m drop length: 0m.
2. The heating conditions: indoor temp.: 20C DB(68C), 15C WB(44.6F) outdoor temp.: 7C DB(42.8F ) equivalent pipe length: 5m drop length: 0m.
3. Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of *m(0.9m for 80model, 1m for 105 model,1.2m for 120~160model). During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
4. The above data may be changed without notice for future improvement on quality and performance.
23
Mini TVR 5G -
Outdoor Unit Specifications
Model 4TVV0068AK000AA 4TVV0077AK000AA 4TVV0089AK000AA
RT 6.3 7 8.1
Max. quantity 10 11 12
Quantity 2
Crankcase heater W 25 25 25
Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC DB/19oC WB; Outdoor temperature 35oC DB/24oC WB.
Heating: Indoor temperature 20oC DB/15oC WB; Outdoor temperature 7oC DB/6oC WB.
Piping length: Interconnecting piping length is 7.5m, level difference is zero.
Sound values are measured in a semi-anechoic room, at a position 1m in front of the unit and 1.3m above the floor.
24
Mini TVR 5G -
Outdoor Unit Dimensions
10.5kW Unit: mm
624
966
396
366
336
354
990
1075
12/14/16/18kW
600
1327
360
400
320
348
900
25
Mini TVR 5G -
Outdoor Unit Dimensions
2. Dimensions
4TVV0068AK000AA 4TVV0077AK000AA 4TVV0089AK000AA
Unit:
2. mmDimensions
4TVV0068AK000AA 4TVV0077AK000AA 4TVV0089AK000AA
Unit: mm
1558
1558
1120
668 205.8
1120
494
528
414
400
668 205.8
494
528
414
400
26
TVR 5G(All Inverter)
TVR 5G (All Inverter) achieve worlds largest capacity of 72HP with the industry's top class energy
efficiency of cooling and heating. It supports a long piping length of 1000m and a longer level
difference of 110m, making it perfect for big-sized and high-rise buildings for wide application.
27
TVR 5G(All Inverter) -
Recommended Combination Table
No of Outdoor Unit Combination Maximum No Capacity (kW)
Model No of
Outdoor of Connectable
Compressors 8HP 10HP 12HP 14HP 16HP 18HP* Cooling Heating
Units Indoor Units
8HP 1 1 1 13 25.2 27
10HP 1 1 1 16 28 31.5
14HP 1 2 1 23 40 45
16HP 1 2 1 26 45 50
18HP 1 2 1 29 50 56
20HP 2 2 2 33 56 63
22HP 2 3 1 1 36 61.5 69
24HP 2 3 1 1 39 68 76.5
26HP 2 3 1 1 43 73 81.5
28HP 2 3 1 1 46 78 87.5
30HP 2 4 1 1 50 85 95
32HP 2 4 1 1 53 90 101
34HP 2 4 1 1 56 95 106
Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC DB/19oC WB; Outdoor temperature 35oC DB/24oC WB.
Heating: Indoor temperature 20oC DB/15oC WB; Outdoor temperature 7oC DB/6oC WB.
Piping length: Interconnecting piping length is 7.5m, level difference is zero.
The above combination models are factory-recommended models.
*18HP model can be customized.
28
TVR 5G(All Inverter) - Features
Wide range of outdoor units
The outdoor units capacity range from 8HP up to 72HP in 2HP increment. Maximum 64 indoor units
with capacity up to 130% of total outdoor units can be connected in one refrigeration system.
8, 10HP 12, 14, 16HP 18HP 20, 22, 24, 26, 28, 30, 32, 34, 36HP
38, 40, 42, 44, 46, 48, 50, 52, 54HP 56, 58, 60, 62, 64, 66, 68, 70, 72HP
65 63 64
59
60 56
55
53
50
50 46
45 43
39
40 36
35 33
29
30 26
25 23
20
20
16
15
13
10
5
8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40-72HP
29
25
TVR 5G(All Inverter) - Features
Wide operation range
COOLING MODE
-5C Outdoor Temperature 48C
V4 Plus S Series
HEATING MODE*
-20C Outdoor Temperature 24C
-2 0 -1 0 0 10 20 30 40 50
Outdoor temperature (DB)
The TVR 5G (All Inverter) system operates stably at extreme temperatures ranging from -20C
. to 48C
Longest piping
length
Equivalent length 200
Outdoor unit up 70
Level difference
*Total pipe length is equal to two times pipe length plus pipe length.
*When the piping length from the farthest IDU to the first indoor branch joint is
more than 40m, it needs to meet specific conditions according to the installation
part of the technical manual to achieve 90m.
modules.
30
26
TVR 5G(All Inverter) - Features
High COP/EER values
The cooling EER up to 4.29 and the heating COP up to 4.39 in the 8HP catagory.
EER COP
4.29 4.39 4.17 4.17
3.97 4.02 3.91 3.89
3.81
3.54 3.5 3.38
8HP 10HP 12HP 14HP 16HP 18HP 8HP 10HP 12HP 14HP 16HP 18HP
According to the running load and system pressure, the system controls the speed of DC fan to achieve the
minimum energy consumption and best performance.
Motor speed(RPM)
DC inverter stepless
adjustment
AC inverter
multistep adjustment
System pressure
31
TVR 5G(All Inverter) - Features
High performance heat exchanger
New design Original design
Windage& air flow
0.6
0.4
Original design
V4 Plus S Series
Reduce
0.2
Reduce air resistance. 28% New design
0
0 200 400 600 800 1000 Re
Frost contrast
The new designed window fins enlarge the heat-exchanging area , decrease the air resistance, save more power
and enhance heat exchange performance.
Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency.
Original design
Gas Liquid
New design
Gas Liquid
Innovative designed high efficiency heat exchanger, which can reach up to 12C subcooling degree,
reduces the system resistance and improves reliability.
When the outdoor temperature is 35C, the refrigerant can be cooled down to 37.1C, thus achieving high
heat-exchanging efficiency with only 2.1C temperature difference.
32
TVR 5G(All Inverter) - Features
Night silent operation mode
High comfort outdoor units multi-choice of silent mode during the night.
Super silent operation mode can reduce sound level further, minimum 45dB (A).
Load % Capacity %
Usual defrosting
the heating loss by unnecessary defrosting and make
the indoor side more comfortable.
Defrosting time can be shortened to 4 min. due to the
t min t
specialized defrosting valve.
Time
PQ E P Q E P Q E P Q E
X Y E X Y E P Q E
Auto addressing
Outdoor unit can distribute addresses for indoor
unit automatically.
Wireless and wired controllers can query and
modify each indoor unit's address.
33
TVR 5G(All Inverter) -
Outdoor Unit Specifications
Model 4TVV0086BK000AA 4TVV0096BK000AA 4TVV0115BK000AA
V4 Plus S Series
Heating Capacity kW 27 31.5 37.5
RT 7.7 9.0 10.7
kBtu/h 92 108 128
kcal/h 23,220 27,090 32,250
Power input kW 6.15 7.554 8.993
COP kW/kW 4.39 4.17 4.17
Connectable indoor unit Total capacity % 50-130 50-130 50-130
Max. quantity 13 16 20
Sound pressure level dB(A) 57 57 59
Pipe connections Liquid pipe in.(mm) 3/8( 9.53) 1/2( 12.7)
Gas pipe in.(mm) 7/8( 22.2) 1( 25.4)
Oil balance pipe in.(mm) 1/4( 6) 1/4( 6)
Fan motor Type DC DC
Quantity 1 1+1
Air flow rate m3/h 11,242 13,000
CFM 6,611 7,645
Motor output W 750 560+380
ESP in.WG(Pa) 0-0.08(0-20)(default) 0-0.08(0-20)(default)
in.WG(Pa) 0.08~0.16(20-40)(customized) 0.08~0.24(20-40)(customized)
DC inverter compressor Quantity 1 1+1
Capacity kW 31.59 31.59+11.80
kBtu/h 107.8 107.8+40.3
Crankcase heater W 27.62 27.622
Oil type FVC68D FVC68D
Oil charge gal.(ml) 0.132(500) 0.132(500)+0.132(500)
Refrigerant Type R410A R410A
Factory charging Ibs.(kg) 22(10) 26.5(12)
Design pressure (High/Low) MPa 4.4/2.6 4.4/2.6
PSI 640/380 640/380
Net dimension (WHD) inch 37-25/3263-9/1630-1/8 49-7/3263-9/1630-1/8
mm 9601,615765 1,2501,615765
Packing size (WHD) inch 40-3/870-1/232-11/16 51-3/870-15/3232-9/32
mm 1,0251,790830 1,3051,790820
Net weight lbs.(kg) 466(212) 634(288)
Gross weight Ibs.(kg) 499(227) 678(308)
Operating temperature range Cooling F(C) 23~118.4(-5~48)
Heating F(C) -4~75.2(-20~24)
Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC(80.6oF) DB/19oC(66.2oF) WB; Outdoor temperature 35oC(95oF) DB/24oC(75.2oF) WB.
Heating: Indoor temperature 20oC(68oF) DB/15oC(59oF) WB; Outdoor temperature 7oC(44.6oF) DB/6oC(42.8oF) WB.
Piping length: Interconnecting piping length is 7.5m(24.6ft.), level difference is zero.
Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90m(295.2ft.). When the total equivalent liquid length is more than 90m(295.2ft.),
please refer to technical manual to choose the connection piping diameter.
Sound values are measured in a semi-anechoic room, at a position 1m(3.28ft.) in front of the unit and 1.3m(4.264ft.) above the floor.
34
TVR 5G(All Inverter) -
Outdoor Unit Specifications
380~415V-3Ph-60Hz
Model 4TVV0140BK000AA 4TVV0155BK000AA 4TVV0182BK000AA
Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC(80.6oF) DB/19oC(66.2oF) WB; Outdoor temperature 35oC(95oF) DB/24oC(75.2oF) WB.
Heating: Indoor temperature 20oC(68oF) DB/15oC(59oF) WB; Outdoor temperature 7oC(44.6oF) DB/6oC(42.8oF) WB.
Piping length: Interconnecting piping length is 7.5m(24.6ft.), level difference is zero.
Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90m(295.2ft.). When the total equivalent liquid length is more than 90m(295.2ft.),
please refer to technical manual to choose the connection piping diameter.
Sound values are measured in a semi-anechoic room, at a position 1m(3.28ft.) in front of the unit and 1.3m(4.264ft.) above the floor.
*18HP model can be customized.
35
TVR 5G(All Inverter) -
Outdoor Unit Dimensions
Dimension Unit: mm
1615
1615
960
1250
765
765
Installation dimension
Unit: mm
36
TVR 5G (Heat Recovery/3pipes)
The all DC inverter TVR 5G (Heat Recovery/3pipes) series, which can offers simultaneous cooling and heating
operation in one system. The energy by-product from cooling or heating is transferred to where it is required by
using the balanced heat exchanger function, which saves up to 50% in costs compared with a conventional
heat pump system.
37
TVR 5G (Heat Recovery/3pipes)
Recommended Combination Table
No of Outdoor Unit Combination Maximum No Capacity (kW)
Model No of
Outdoor of Connectable
Compressors
Units 8HP 10HP 12HP 14HP 16HP Indoor Units Cooling Heating
8HP 1 1 1 13 25.2 27
10HP 1 1 1 16 28 31.5
14HP 1 2 1 23 40 45
16HP 1 2 1 26 45 50
20HP 2 2 2 33 56 63
V4 Plus R Series
22HP 2 2 1 1 36 61.5 69
24HP 2 3 1 1 39 68 76.5
26HP 2 3 1 1 43 73 81.5
28HP 2 4 2 46 80 90
30HP 2 4 1 1 50 85 95
32HP 2 4 2 53 90 100
34HP 3 4 2 1 56 96 108
Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC DB/19oC WB; Outdoor temperature 35oC DB/24oC WB.
Heating: Indoor temperature 20oC DB/15oC WB; Outdoor temperature 7oC DB/6oC WB.
Piping length: Interconnecting piping length is 7.5m, level difference is zero.
The above combination models are factory-recommended models.
38
TVR 5G (Heat Recovery/3pipes)
Features
Wide range of outdoor units
The outdoor units capacity range from 8HP up to 64HP in 2HP increment. Maximum 64 indoor units with
capacity up to 130% of total outdoor units can be connected as one refrigeration system.
34-48HP 50-64HP
Longest piping
Piping
Equivalent length 200
length
Equivalent piping length from the farthest
40/90*
IDU to the first indoor branch joint
between IDU~IDU 30m
Outdoor unit up 70
90m
*Total pipe length is equal to two times pipe length plus pipe length.
*When the piping length from the farthest IDU to the first indoor branch joint is
39
more than 40m, it needs to meet specific conditions according to the installation
part of the technical manual to achieve 90m.
TVR 5G (Heat Recovery/3pipes)
Features
Wide operation temperature range
Cooling Mode
-5C 48C
Heating Mode
-20C 24C
-20 -10 0 10 20 30 40 50
Outdoor temperature (DB)
The TVR 5G (Heat Recovery/3Pipes) series system operates stably at extreme temperatures ranging
from -20C to 48C
modules.
High Efficiency
High EER
Heat recovery is achieved by diverting exhaust heat from indoor units in cooling mode to areas requiring
heating, maximising energy efficiency, reducing electricity costs and leading to high partload efficiencies (up to
7.0 in the 8HP catagory).
EER 7.0
7.0
8HP, up to 7.0
6.0 10HP, up to 6.8
12HP, up to 6.7
14HP, up to 6.5
EER
4.0
3.0
75% cooling 50% cooling 25% cooling
100% cooling 100% heating
25% heating 50% heating 75% heating
EER in simultaneous cooling and heating mode are based on the following condition:
Outdoor temperature 7CDB/6CWB, indoor temperature 27CDB/19CWB for cooling, indoor temperature 20CDB for heating.
36
High
HighCOP/EER
COP/EERvalues
values
The cooling EER up to 4.40 and the heating COP up to 4.50 in the 8HP catagory.
COP
EER 4.50
4.40 4.20 4.30 4.30
4.15 4.02 3.91
3.54 3.40
8HP 10HP 12HP 14HP 16HP 8HP 10HP 12HP 14HP 16HP
40
TVR 5G (Heat Recovery/3pipes)
Features
All DC inverter technology
All DC inverter compressors make the capacity output better distributed.
According to the running load and system pressure, the system controls the speed of DC fan to achieve the
minimum energy consumption and best performance.
All DC Fan Motors
Motor speed(RPM)
DC inverter stepless
adjustment
AC inverter
multistep adjustment
System pressure
41
TVR 5G (Heat Recovery/3pipes
Features
Enhanced Comfort
The indoor units connect to the same TMS can realize simultaneous cooling and
heating operation.
Heat
Heat
Heat Exchanger 2 Heat Exchanger 2 Heat Exchanger 2
Heating Defrosting heat exchanger 1 Defrosting heat exchanger 2
42
TVR 5G (Heat Recovery/3pipes)
Features
Easier Installation and Service
Remote addressing
Addressing indoor units are able to be done just by pressing the
button of the controller.
No need to set the address by the DIP switch one by one.
Wired controller and wireless controller can enquire and modify
Remote addressing
every indoor units address.
X, Y, E
H1, H2, E
P, Q, E P, Q, E
P, Q, E P, Q, E P, Q, E P, Q, E P, Q, E P, Q, E
Compressor is near the outside, and there is simple pipe system for convenient maintenance.
The newly designed rotating control box is so excellent that it can rotate in a wide angle.
It is convenient for the inspection and maintenance of the pipeline system and greatly reduced the time of
dismount the electric control box.
Rotating electric
control box
43
TVR 5G (Heat Recovery/3pipes)
4TVV0140BK000AA
Outdoor Unit Specifications
4TVV0165BK000AA
380~415V-3Ph-60Hz
Model 4TVR0086BK000AA 4TVR0096BK000AA 4TVR0115BK000AA 4TVR0140BK000AA 4TVR0155BK000AA
V4 Plus R Series
RT 7.7 8.9 10.7 12.8 14.2
kBtu/h 92.1 107.5 128.0 153.5 170.6
kcal/h 23,220 27,090 32,250 38,700 43,000
Power input kW 6.00 7.33 8.72 11.19 12.79
COP kW/kW 4.50 4.30 4.30 4.02 3.91
Connectable Total capacity % 50-130 50-130 50-130 50-130 50-130
indoor unit Max. quantity 13 16 20 23 26
Sound pressure level dB(A) 57 57 58 60 60
Pipe Liquid pipe in.(mm) 3/8(9.53) 1/2(12.7) 1/2(12.7) 5/8(15.9) 5/8(15.9)
connections Low pressure gas pipe in.(mm) 7/8(22.2) 7/8(22.2) 1(25.4) 1-1/8(28.6) 1-1/8(28.6)
High pressure gas pipe in.(mm) 3/4(19.1) 3/4(19.1) 3/4(19.1) 7/8(22.2) 7/8(22.2)
High pressure gas balance pipe in.(mm) 3/4(19.1) 3/4(19.1) 3/4(19.1) 3/4(19.1) 3/4(19.1)
Oil balance pipe in.(mm) 1/4(6) 1/4(6) 1/4(6) 1/4(6) 1/4(6)
Fan motor Type DC
Quantity 2 2 2 2 2
Air flow rate m3/h 12,000 12,000 13,000 15,000 15,000
CFM 7,060 7,060 7,650 8,830 8,830
Motor output W 420 420 420 750 750
ESP in.WG(Pa) 0~0.08(0~20) (default) 0~0.08(0~20) (default)
in.WG(Pa) (0.08~0.24)(20~40) (customized) (0.08~0.16)(20~40) (customized)
DC inverter Quantity 1 2
compressor Capacity kW 31.59 31.59+11.8
kBtu/h 107.8 107.8+40.3
Crankcase heater W 302 304
Oil type FVC68D FVC68D
Oil charge gal.(ml) 0.132(500) 0.132+0.132(500+500)
Refrigerant Type R410A R410A
Factory charging Ibs.(kg) 22(10) 28.6(13)
Design pressure (High/Low) MPa 4.4/2.6
PSI 640/380
Net dimension (WHD) inch 49-7/3263-9/1630-1/8
mm 12501615765
Packing size (WHD) inch 51-9/1670-1/232-1/2
mm 13051790820
Net weight Ibs.(kg) 561(255) 561(255) 561(255) 666.6(303) 666.6(303)
Gross weight Ibs.(kg) 600.6(273) 600.6(273) 600.6(273) 708.4(322) 708.4(322)
Operating Cooling F(C) 23~118.4(-5~48)
temperature range Heating F(C) -4~75.2(-20~24)
Simultaneous Cooling and Heating F(C) 23~75.2(-5~24)
Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC(80.6oF) DB/19oC(66.2oF) WB; Outdoor temperature 35oC(95oF) DB/24oC(75.2oF) WB.
Heating: Indoor temperature 20oC(68oF) DB/15oC(59oF) WB; Outdoor temperature 7oC(44.6oF) DB/6oC(42.8oF) WB.
Piping length: Interconnecting piping length is 7.5m(24.6ft.), level difference is zero.
Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90m(295.2ft.). When the total equivalent liquid length is more than 90m(295.2ft.),
please refer to technical manual to choose the connection piping diameter.
Sound values are measured in a semi-anechoic room, at a position 1m(3.28ft.) in front of the unit and 1.3m(4.264ft.) above the floor.
44
TVR 5G (Heat Recovery/3pipes)
TMS Specifications
TMS equipment which can be connected multiple indoor units
Max. number of all downstream indoor units 41=4 42=8 44=16 46=24
Connect to
High pressure gas pipe mm 15.9 19.1 22.2 22.2
outdoor unit
Piping
Low pressure gas pipe mm 19.1 25.4 31.8 31.8
connections
Connect to
High pressure gas pipe mm 19.1 22.2
outdoor unit
Piping
Low pressure gas pipe mm 25.4 31.8
connections
Gross weight kg 27 40
Note:
Sound values are measured in a semi-anechoic room, at a position 1m below the MS equipment in mode switch condition.
It is not recommended to install in the place where high noise performance is required.
41
45
TVR 5G (Heat Recovery/3pipes)
Dimensions
Dimension Unit: mm
1250
1615
765
V4 Plus R Series
HP
8/10 12 14/16
Piping
Liquid pipe 12.7 15.9 15.9
Low pressure gas pipe 22.2 25.4 28.6
High pressure gas pipe 19.1 19.1 22.2
High pressure gas balance pipe 19.1 19.1 19.1
Oil balance pipe 6 6 6
290
245
205
Oil balance pipe
Liquid pipe
230
250
High pressure
200
170
gas pipe
205
Low pressure
gas pipe
Installation dimension
1250
1120
10 Expansion bolt
Rubber shocking
proof mat Concrete
basement
736
765
46
TVR 5G (Inverter+Fixed)
Developed to facilitate more flexible system design for big-sized and high-rise buildings
TVR 5G product (Inverter+Fixed), which is designed to optimize the system and better
satisfying the market. Offering a higher capacity up to 64HP by combining maximum four
outdoor units, in 2HP as an increment.
Three types of units are included: Heat Pump Units, Corrosion Resistance Heat Pump
Units and Cooling Only Units.
05
47
TVR 5G (Inverter+Fixed) -
Recommended Combination Table
No of Outdoor Unit Combination Maximum No Capacity (kW)
Model No of
Outdoor of Connectable
Compressors
Units 8HP 10HP 12HP 14HP 16HP Indoor Units Cooling Heating
8HP 1 2 1 17 25.2 27
10HP 1 2 1 21 28 31.5
14HP 1 3 1 30 40 45
16HP 1 3 1 34 45 50
20HP 2 4 2 43 56 63
22HP 2 4 1 1 47 61.5 69
24HP 2 5 1 1 52 68 76.5
26HP 2 5 1 1 56 73 81.5
28HP 2 6 2 60 80 90
30HP 2 6 1 1 64 85 95
32HP 2 6 2 64 90 100
34HP 3 7 2 1 64 96 108
Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC DB/19oC WB; Outdoor temperature 35oC DB/24oC WB.
Heating: Indoor temperature 20oC DB/15oC WB; Outdoor temperature 7oC DB/6oC WB.
Piping length: Interconnecting piping length is 7.5m, level difference is zero.
The above combination models are factory-recommended models.
48
Features TVR 5G (Inverter+Fixed) -
Wide Application Features
Range
Wide range of outdoor units
The outdoor units capacity range from 8HP up to 64HP in 2HP increment. Maximum 64 indoor units with
capacity up to 130% of total outdoor units can be connected in one refrigeration system.
8, 10HP 12, 14, 16HP 18, 20, 22, 2 4, 26, 28, 30, 32HP
34, 36, 38, 40, 42, 44, 46, 48HP 50, 52, 54, 56, 58, 60, 62, 64HP
64
65 60
60 56
55 52
50 47
45 43
39
40
34
35
30
30 26
25
21
20 17
15
10
5
8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30-64HP
49
TVR 5G (Inverter+Fixed) -
Features
Wide operation range
COOLING MODE
-5C Outdoor Temperature 48C
HEATING MODE*
-20C Outdoor Temperature 24C
-2 0 -1 0 0 10 20 30 40 50
Outdoor temperature (DB)
The inverter+Fixed series system operates stably at extreme temperatures ranging from -20C
. to 48C
Permitted
value (m)
30HP 350
Actual total piping length
Level difference between IDU-ODU is 70m*
>30HP 500
Longest actual piping length 150m
Piping
Actual length 150
length
Longest piping
Equivalent length 175
between IDU-IDU is 15m
for all outdoor units. 20-40Pa can be customized for other modules.
50
High Efficiency TVR 5G (Inverter+Fixed) -
Features
High COP/EER values
The cooling EER up to 4.29 and the heating COP up to 4.39 in the 8HP catagory.
EER COP*
4.29 4.39
4.14 4.17
4.5 3.89 4.02 3.91
3.7 4.5
4 3.25 4
3.21
3.5 3.5
3 3
2.5 2.5
2 2
1.5 1.5
1 1
0.5 0.5
0 0
8HP 10HP 12HP 14HP 16HP 8HP 10HP 12HP 14HP 16HP
*System is without heating COP value
0.8
0.6
0.4
Original design
Reduce
0.2
Reduce air resistance. 28% New design
0
0 200 400 600 800 1000 Re
Frost contrast
Relative windage resistance
0.8 Reduce
High efficiency inner-threaded pipe, 30%
enhance heat transfer. 0.6 Original design
0.4
The new designed window fins enlarge the heat-exchanging area , decrease the air resistance, save more power
and enhance heat exchange performance.
Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency.
51
TVR 5G (Inverter+Fixed) -
Enhanced Comfort
Features
Night silent operation mode
High comfort outdoor units multi-choice of silent mode during the night.
Super silent operation mode can reduce sound level further, minimum 46.8dB (A).
Load % Capacity %
P Q E P Q E P Q E P Q E
X Y E X Y E P Q E
Auto addressing
Outdoor unit can distribute addresses for indoor
unit automatically.
Wireless and wired controllers can query and
modify each indoor unit's address.
52
TVR 5G (Inverter+Fixed) -
Outdoor Unit Specifications
380~415V-3Ph-60Hz
Model 4TVV0086AK000AA 4TVV0096AK000AA 4TVV0115AK000AA 4TVV0140AK000AA 4TVV0155AK000AA
Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC(80.6oF) DB/19oC(66.2oF) WB; Outdoor temperature 35oC(95oF) DB/24oC(75.2oF) WB.
Heating: Indoor temperature 20oC(68oF) DB/15oC(59oF) WB; Outdoor temperature 7oC(44.6oF) DB/6oC(42.8oF) WB.
Piping length: Interconnecting piping length is 7.5m(24.6ft.), level difference is zero.
Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90m(295.2ft.). When the total equivalent liquid length is more than 90m(295.2ft.),
please refer to technical manual to choose the connection piping diameter.
Sound values are measured in a semi-anechoic room, at a position 1m(3.28ft.) in front of the unit and 1.3m(4.264ft.) above the floor.
53
TVR 5G (Inverter+Fixed)
Corrosion Resistance Unit
The unit adopts special anti-corrosion treatment on the heat exchanger, electronic parts
and other components of the unit, which is about 5 times as anti-salt effective as the normal
ones, it makes the unit more suitable for the project nearby the sea.
V4 plus series
54
TVR 5G (Inverter+Fixed)
Outdoor Unit Dimensions
Dimension Unit: mm
8/10HP 12/14/16HP
1615
1615
960
1250
765
765
Liquid pipe
A
B Gauge point
Cooling only type without
Gas pipe
HP
220
208
A 199 169
B 159 209
C 195 169
C Liquid pipe 12.7 15.9
R: Pipe connection
R section view Gas pipe 25.4 31.8
Installation dimension
55 53
TVR 5G (All Inverter-T3/High
Ambient)
The outdoor units capacity range is from 8HP up to 72HP in 2HP increment. Maximum 64
indoor units with the capacity up to 130% of total outdoor units can be connected in one
refrigeration system. With all DC inverter compressors and all DC fan motors, the
efficiency is improved greatly. Together with lots of latest technologies, it supports an
incredible piping length of 1000m and longer level difference of 110m, making it perfect for
big-sized and high-rise buildings for wide application.
05
56
TVR 5G (All Inverter-T3/High
Ambient)-Features
8, 10HP 12, 14, 16HP 18HP 20, 22, 24, 26, 28, 30, 32, 34, 36HP
38, 40, 42, 44, 46, 48, 50, 52, 54HP 56, 58, 60, 62, 64, 66, 68, 70, 72HP
65 63 64
59
60 56
55
53
50
50 46
45 43
39
40 36
35 33
29
30 26
25 23
20
20
16
15
13
10
5
8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40-72HP
57
25
TVR 5G (All Inverter-T3/High
Ambient)-Features
Wide operation range
COOLING MODE
-5C Outdoor Temperature 54C
V4 Plus S Series
HEATING MODE*
-20C Outdoor Temperature 24C
-2 0 -1 0 0 10 20 30 40 50
Outdoor temperature (DB)
The TVR 5G (All Inverter) system operates stably at extreme temperatures ranging from -20C
. to 54C
Longest piping
length
Equivalent length 200
Outdoor unit up 70
Level difference
*Total pipe length is equal to two times pipe length plus pipe length.
*When the piping length from the farthest IDU to the first indoor branch joint is
more than 40m, it needs to meet specific conditions according to the installation
part of the technical manual to achieve 90m.
modules.
58 26
TVR 5G (All Inverter-T3/High Ambient)-
Outdoor Units Specifications
Quantity 1 1 2 2 2 2
Pa 20~40 (optional)
Factory charging kg 10 10 12 15 15 16
Design pressure (High/Low) MPa 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6
Notes:
Heating
59
TVR 5G (All Inverter-T3/High Ambient)
Outdoor Unit Dimensions
Dimension Unit: mm
8HP/10HP
Combinable Dimensions: 12HP/14HP/16HP/18HP
Combinable Dimensions:
Installation dimension
A 830 1120
B 960 1250
C 736 736
D 765 765
60
Nomenclature - Outdoor Unit
4 T V V 0 0 8 6 B D 0 0 0 A A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
D = 380-415/60Hz/3phase
4 = R -410a 1 = 208-230V~60Hz/1phase
K = 380-415V 3N~60Hz/3phase
T = Trane
086 = 86000Btu/h
A = Inverter + Fixed
B = All Inverters
61
Nomenclature - Indoor Unit
4 T V D 0 0 2 4 C B 0 W E A A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Digit # 10
Digit #2 = Brand Name = Electric Power Supply Characteristics
T = Trane 1 = 208-230V/60Hz/1phase -
K = 220-240V/60Hz/3phase
Digit #11
V = Variable Refrigerant Flow = Type of function
0 = Standard Cooling / HP
A = 1-Way Cassette
Digit #12
B = 4-Way Compact Cassette (650mm x 650mm) = Controls
Digit #13
L = Low Static Pressure DuctType = Special Features
Digit #14
X = Convertible Floor / Ceiling Mount = Minor Design Sequence
B = Design Sequence
024 = 24000Btu/h
09
62
TVR 5G (Inverter + Fixed)
Combination of Outdoor Units
Capacity Capacity Maximum
Maximum
Model Number Outdoor Unit
Capacity indoorIndoor
Units
Model
Model Number
Number Outdoor
Outdoor Unit Unit Module Combination
Btu / Hr HP kW Units Combination
Combination
Btu/h HP kW
4TVV0086AD000AA 4TVV0086AD000AA 1 86000 8 25 17
4TVV0086AK000AA 4TVV0086AK000AA1 86,000 8 25 17
4TVV0096AD000AA 4TVV0096AD000AA 1 96000 10 28 21
4TVV0096AK000AA 4TVV0096AK000AA1 96,000 10 28 21
4TVV0115AD000AA 4TVV0115AD000AA 1 115000 12 34 26
4TVV0115AK000AA 4TVV0115AK000AA1 115,000 12 34 26
4TVV0140AD000AA 4TVV0140AD000AA 1 140000 14 40 30
4TVV0140AK000AA 4TVV0140AK000AA1 140,000 14 40 30
4TVV0155AD000AA 4TVV0155AD000AA 1 155000 16 45 34
4TVV0155AK000AA 4TVV0155AK000AA1 155,000 16 45 34
4TV4TVV0182AD000AA
V0182AK000AA 4TVV0086AK0004TVV0086AD000AA
AA+4TVV0096AK000A+A4TVV0096AD000AA 182,000 182000
18 18 53 53 39 39
4TV4TVV0192AD000AA
V0192AK000AA 4TVV0096AK0004TVV0096AD000AA
AA+4TVV0096AK000A+A4TVV0096AD000AA 192,000 192000
20 20 56 56 43 43
4TV4TVV0211AD000AA
V0211AK000AA 4TVV0096AK0004TVV0096AD000AA
AA+4TVV0115AK000A+A4TVV0115AD000AA 211,000 211000
22 22 62 62 47 47
4TV4TVV0236AD000AA
V0236AK000AA 4TVV0096AK0004TVV0096AD000AA
AA+4TVV0140AK000A+A4TVV0140AD000AA 236,000 236000
24 24 68 68 52 52
4TVV0251AD000AA 251000 26 73 56
4TVV0251AK000AA 4TVV0096AK0004TVV0096AD000AA
AA+4TVV0155AK000A+A4TVV0155AD000AA 251,000 26 73 56
4TVV0270AD000AA 4TVV0140AD000AA 2 270000 28 80 60
4TVV0270AK000AA 4TVV0140AK000AA2 270,000 28 80 60
4TVV0295AD000AA 4TVV0140AD000AA + 4TVV0155AD000AA 295000 30 85 64
4TVV0295AK000AA 4TVV0140AK000AA+4TVV0155AK000AA 295,000 30 85 64
4TVV0310AD000AA 4TVV0155AD000AA 2 310000 32 90 64
4TVV0310AK000AA 4TVV0155AK000AA2 310,000 32 90 64
4TV4TVV0425AD000AA
V0450AK000AA 4TVV0140AK0004TVV0140AD000AA
AA+4TVV0155AK000AA2
2+ 4TVV0155AD000AA 450,000 425000
46 44 130 125 64 64
4TVV0450AD000AA 4TVV0140AD000AA + 4TVV0155AD000AA 2 450000 46 135 130 64
4TVV0465AK000AA 4TVV0155AK000AA3 465,000 48 64
4TVV0465AD000AA 4TVV0155AD000AA 3 465000 48 135 64
4TVV0492AK000AA 4TVV0086AK000AA+4TVV0096AK000AA+4TVV0155AK000AA2 492,000 50 143 64
4TVV0502AD000AA
4TVV0546AK000AA 4TVV0096AD000AA 2 + 4TVV0155AD000AA 2 546,000
4TVV0096AK000AA+4TVV0140AK000AA+4TVV0155AK000AA2 502000
56 52 158 146 64 64
4TV4TVV0521AD000AA
V0561AK000AA 4TVV0140AK0004TVV0096AD000AA
AA3+4TVV0155AK00+0A
4TVV0115AD000AA
A + 561,000 58
521000 54 165 152 64 64
4TVV0155AD000AA 2
4TVV0580AK000AA 4TVV0140AK000AA2+4TVV0155AK000AA2 580,000 60 170 64
4TVV0096AD000AA + 4TVV0140AD000AA +
4TVV0546AD000AA
4TVV0605AK000AA 4TVV0140AK000AA+4TVV0155AK000AA3 605,000 546000
62 56 175 158 64 64
4TVV0155AD000AA 2
4TVV0561AD000AA
4TVV0620AK000AA 4TVV0140AD000AA 3 + 4TVV0155AD000AA
4TVV0155AK000AA4 620,000 561000
64 58 180 165 64 64
Note:
The system enables the connection of indoor units with a total capacity within 50% to 130% of that of the corresponding outdoor unit, but
when this capacity ratio exceeds 100% then the actual capacity of each indoor unit will decrease compared to rated capacity when all the
units operate simultaneously.
63
TVR 5G (All Inverter)
Combination of Outdoor Units
Capacity
Capacity Capacity Maximum
Maximum indoor Units
Indoor
Model Number Outdoor Unit Module Combination
Model Number Outdoor Unit Model Number Outdoor Unit Combination
Btu / Hr
Btu/h HP HPkW Units
kW Combination
4TVV0086BD000AA
4TVV0086BK000AA 4TVV0086BD000AA
4TVV0086BK000AA 86000
86,000 8 8 25 25 13 13
4TVV0096BD000AA
4TVV0096BK000AA 4TVV0096BD000AA
4TVV0096BK000AA 95,500 10
95500 10 28 28 16 16
4TVV0115BD000AA 4TVV0115BD000AA 114300 12 34 20
4TVV0115BK000AA 4TVV0115BK000AA 114,300 12 34 20
4TVV0140BD000AA 4TVV0140BD000AA 136500 14 40 23
4TVV0140BK000AA 4TVV0140BK000AA 136,500 14 40 23
4TVV0155BD000AA 4TVV0155BD000AA 153500 16 45 26
4TVV0155BK000AA 4TVV0155BK000AA 153,500 16 45 26
4TVV0182BD000AA 4TVV0182BD000AA 170600 18 50 29
4TVV0182BK000AA 4TVV0182BK000AA 170,600 18 50 29
4TVV0236BK000AA
4TVV0236BD000AA 4TVV0096BK000AA+4TVV0140BK000AA
4TVV0096BD000AA + 4TVV0140BD000AA 232,000 24
232000 24 68 68 39 39
4TVV0251BD000AA
4TVV0251BK000AA 4TVV0096BD000AA + 4TVV0155BD000AA
4TVV0096BK000AA+4TVV0155BK000AA 249,100 26
249100 26 73 73 43 43
4TVV0278BD000AA
4TVV0278BK000AA 4TVV0096BD000AA + 4TVV0182BD000AA
4TVV0096BK000AA+4TVV0182BK000AA 266100
266,100
28 28
78 78 46 46
4TVV0295BD000AA 4TVV0140BD000AA + 4TVV0155BD000AA 290000 30 85 50
4TVV0295BK000AA 4TVV0140BK000AA+4TVV0155BK000AA 290,000 30 85 50
4TVV0322BD000AA 4TVV0140BD000AA + 4TVV0182BD000AA 307100 32 90 53
4TVV0322BK000AA 4TVV0140BK000AA+4TVV0182BK000AA 307,100 32 90 53
4TVV0337BD000AA 4TVV0155BD000AA + 4TVV0182BD000AA 327100 34 96 56
4TVV0337BK000AA 4TVV0155BK000AA+4TVV0182BK000AA 327,600 34 95 56
4TVV0364BD000AA 4TVV0182BD000AA + 4TVV0182BD000AA 341200 36 100 59
4TVV0364BK000AA 4TVV0182BK000AA+4TVV0182BK000AA 341,200 36 100 59
4TVV0573BK000AA 4TVV0096BK000AA+4TVV0140BK000AA+4TVV0155BK000AA+4TVV0182BK000AA
4TVV0096BD000AA + 4TVV0096BD000AA + 556,200 58 163 64
4TVV0566BD000AA 532300 56 156 64
4TVV0182BD000AA + 4TVV0182BD000AA
4TVV0600BK000AA 4TVV0096BK000AA+4TVV0140BK000AA+4TVV
4TVV0096BD000AA + 4TVV0140BD000AA 018+2BK000AA*2 573,200 60 168 64
4TVV0576BD000AA 556200 58 163 64
4TVV0155BD000AA + 4TVV0182BD000AA
4TVV0615BK000AA 4TVV0096BK000AA+4TVV0155BK000AA+4TVV
4TVV0096BK000AA + 4TVV0140BK000AA 018+2BK000AA*2 590,300 62 173 64
4TVV0600BD000AA 573200 62 168 64
4TVV0182BK000AA + 4TVV0182BK000AA
4TVV0642BK000AA 4TVV0096BK000AA+4TVV0182BK000AA+4TVV
4TVV0096BD000AA + 4TVV0155BD000AA +BK000AA*2
018 2 607,300 64 178 64
4TVV0615BD000AA 590300 62 173 64
. 4TVV0182BD000AA + 4TVV0182BD000AA
4TVV0659BK000AA 4TVV0140BK000AA+4TVV0155BK000AA+4TVV
4TVV0096BD000AA + 4TVV0182BD000AA 018+2BK000AA*2 631,200 66 185 64
4TVV0642BD000AA 607300 64 178 64
4TVV0182BD000AA + 4TVV0182BD000AA
4TVV0686BK000AA 4TVV0140BK000AA+4TVV0182BK000AA*3
4TVV0140BD000AA + 4TVV0155BD000AA + 648,300 68 190 64
4TVV0659BD000AA 631200 66 185 64
4TVV0182BD000AA + 4TVV0182BD000AA
4TVV0701BK000AA 4TVV0155BK000AA+4TVV0182BK000AA*3 665,300 70 195 64
4TVV0140BD000AA + 4TVV0182BD000AA + 648300 68 190 64
4TVV0686BD000AA 4TVV0182BD000AA + 4TVV0182BD000AA
4TVV0728BK000AA 4TVV0182BK000AA*4 682,400 72 200 64
4TVV0701BD000AA 4TVV0155BD000AA + 4TVV0182BD000AA + 665300 64
4TVV0182BD000AA + 4TVV0182BD000AA 70 195
4TVV0182BD000AA + 4TVV0182BD000AA + 682400 72 200 64
4TVV0728BD000AA 4TVV0182BD000AA + 4TVV0182BD000AA
Note:
The system enables the connection of indoor units with a total capacity within 50% to 130% of that of the corresponding outdoor unit, but
when this capacity ratio exceeds 100% then the actual capacity of each indoor unit will decrease compared to rated capacity when all the
units operate simultaneously.
64
TVR 5G (Heat Recovery/3 pipes)
Combination of Outdoor Units
Capacity
Model Number Outdoor Unit Module Combination Capacity Capacity Maximum
Maximum
indoorIndoor
Units
Model Number Outdoor Unit Model Number Outdoor Unit Combination
Btu/h Btu / Hr
HP HP kW
HP kW Units Combination
4TVR0086BD000AA
4TV R0086BK000AA 4TVR0086BK004TVR0086BD000AA
0 A A *1 1 86,000 86000
25 8 8 25 13 13
4TVR0096BD000AA
4TV R0096BK000AA
4TVR0096BD000AA 1
4TVR0096BK000AA*1 96,000 96000
28 10 10 28 16 16
4TVR0332BD000AA
4TV R0347BK000AA 4TVR0096BK004TVR0096BD000AA A2
0AA*2+4TVR0155BK000A + 4TVR0140BD000AA 347,000 332000
101 34 36 96 59 56
4TVR0347BD000AA
4TV R0366BK000AA 4TVR0096BK004TVR0096BD000AA
0AA+4TVR0115BK000AA
+42TV+R4TVR0155BD000AA
0155BK000AA 366,000 347000
107 36 38 101 63 59
4TVR0096BD000AA + 4TVR0115BD000AA +
4TVR0366BD000AA
4TV R0391BK000AA 4TVR0096BK000AA+4TVR0140BK000AA+4TVR0155BK000AA 391,000 366000
113 38 40 107 64 64
4TVR0155BD000AA
4TVR0406BK000AA 4TVR0140BK000AA*3 406,000 120 42 64
4TVR0096BD000AA + 4TVR0140BD000AA +
4TVR0391BD000AA 391000 40 113 64
4TVR0425BK000AA 4TVR0140BK004TVR0155BD000AA
0AA*2+4TVR0155BK000AA 425,000 125 44 64
4TVR0406BD000AA 4TVR0140BD000AA 3 406000 42 120 64
4TVR0450BK000AA 4TVR0140BK000AA+4TVR0155BK000AA*2 450,000 130 46 64
4TVR0425BD000AA 4TVR0140BD000AA 2 + 4TVR0155BD000AA 425000 44 125 64
4TVR0465BK000AA 4TVR0155BK000AA*3 465,000 135 48 64
4TVR0450BD000AA 4TVR0140BD000AA + 4TVR0155BD000AA 2 450000 46 130 64
4TVR0492BK000AA 4TVR0086BK000AA+4TVR0096BK000AA+14TVR0155BK000AA*2 492,000 143 50 64
4TVR0465BD000AA 4TVR0155BD000AA 3 465000 48 135 64
4TVR0502BK000AA 4TVR0096BK000AA*2+4TVR0155BK000AA*2 502,000 146 52 64
502000 52 146 64
4TVR0502BD000AA
4TV R0561BK000AA 4TVR0140BK004TVR0096BD000AA
0AA*3+4TVR0155BK000AA2 + 4TVR0155BD000AA 2 561,000 165 58 64
4TVR0096BD000AA + 4TVR0115BD000AA +
4TVR0521BD000AA
4TV R0580BK000AA 4TVR0140BK000AA*2+4TVR0155BK000AA*2 580,000 521000
170 54 60 152 64 64
4TVR0155BD000AA 2
4TVR0605BK000AA 4TVR0140BK000AA+4TVR0155BK000AA*3 605,000 175 62 64
4TVR0096BD000AA + 4TVR0140BD000AA +
4TVR0546BD000AA 546000 56 158 64
4TVR0620BK000AA 4TVR0155BK004TVV0155AD000AA
0 A A *4 2 620,000 180 64 64
Note:
The system enables the connection of indoor units with a total capacity within 50% to 130% of that of the corresponding outdoor unit, but
when this capacity ratio exceeds 100% then the actual capacity of each indoor unit will decrease compared to rated capacity when all the
units operate simultaneously.
65
TVR 5G (All Inverter + T3/High Ambient)
Combination of Outdoor Units
Capacity Capacity
Capacity Maximum Indoor
Model Number Outdoor Unit Model Number Outdoor Unit Maximum indoor Units
Model Number Outdoor Unit Module Combination Btu / Hr HP HP kW Units Combination
Combination
Btu/h HP kW
4TVVT086BD000AA 4TVVT086BD000AA 86000 8 25 13
4TVVT086BK000AA 4TVVT086BK000AA 86,000 8 25 13
4TVVT096BD000AA 4TVVT096BD000AA 95500 10 28 16
4TVVT096BK000AA 4TVVT096BK000AA 95,500 10 28 16
4TVVT115BD000AA 4TVVT115BD000AA 114300 12 34 20
4TVVT115BK000AA
4TVVT140BD000AA 4TVVT115BK000AA
4TVVT140BD000AA 114,300 14 1240 34 20
136500 23
4TVVT155BD000AA
4TVVT140BK000AA 4TVVT155BD000AA
4TVVT140BK000AA 136,500 16
153500 1445 40 26 23
4TVVT182BD000AA
4TVVT155BK000AA 4TVVT182BD000AA
4TVVT155BK000AA 170600
153,500 18 1650 45 29 26
4TVVT337BD000AA
4TVVT322BK000AA 4TVVT155BD000AA + 4TVVT182BD000AA
4TVVT140BK000AA+4TVVT182BK000AA 327100
307,100 34 3295 90 56 53
4TVVT364BD000AA
4TVVT337BK000AA 4TVVT182BD000AA + 4TVVT182BD000AA
4TVVT155BK000AA+4TVVT182BK000AA 341200
327,600 36 34100 95 59 56
4TVVT391BD000AA
4TVVT391BK000AA 4TVVT096BD000AA + 4TVVT140BD000AA + 4TVVT155BD000AA
4TVVT096BK000AA+4TVVT140BK000AA+4TVVT155BK000AA 385,600 40
385600 40113 113 64 64
4TVVT406BD000AA
4TVVT406BK000AA
4TVVT096BD000AA + 4TVVT155BD000AA + 4TVVT155BD000AA
4TVVT096BK000AA+4TVVT155BK000AA*2 402,600 42
402600 42118 118 64 64
4TVVT519BD000AA
4TVVT519BK000AA 4TVVT155BD000AA + 4TVVT182BD000AA + 4TVVT182BD000AA
4TVVT155BK000AA+4TVVT182BK000AA*2 494,700 52
494700 52145 145 64 64
4TVVT546BD000AA
4TVVT546BK000AA 4TVVT182BD000AA + 4TVVT182BD000AA + 4TVVT182BD000AA
4TVVT182BK000AA*3
511800
511,800
54 54
150 150
64 64
66
Indoor Units Lineup
One-way Cassette
Two-way Cassette
Compact Four-way Cassette
Four-way Cassette
Low Static Pressure Duct
Concealed Duct Unit (A5 Type)
High Static Pressure Duct
Ceiling&Floor
Wall-mounted
Console
Fresh Air Processing Unit
67
Offering Summary
Indoor Units Offering Summary
TVR Indoor Units
Indoor Unit capacity in Kw 1.8 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 10 11.2 12.5 14 16 20 25 28 40 45 56
Indoor unit capacity in Btu/hr 6,000 7,500 9,500 12,300 15,000 19,000 24,000 27,000 31,000 34,1000 38,000 42,000 48,000 55,000 75,000 85,300 95,500 140,000 155,000 190,000
One-way Cassette x x x x x x
Two-way Cassett x x x x x x
Convertible x x x x x x x x x
Console x x x x
23
68
Description Summary -
Indoor Units Range
Model number TYPE OF UNITS BTU/H Capacity (kW)
69
09
Description Summary -
Indoor Units Range
Model number TYPE OF UNITS BTU/H Capacity (kW)
70
Description Summary -
Indoor Units Range
Model number TYPE OF UNITS BTU/H Capacity (kW)
26
71
09
One-way Cassette
Indoor Units Lineup
One-way Cassette Power supply
Model
Cooling capacity
Follow Me
Auto Addressing Anti-Cold Air Function
Cleanable Panel
FollowLED
LED Me Display Super
Anti-Cold High Air Flow
Air Function
DISPLAY Heating capacity
Cooling
Airflow rateH/M/L
Thickness 6-1/32in.
Sound pressure lev
(153mm) only UItra Thin
Thickness 6-1/32in.
Sound pressure level(H/M/L)
(153mm) only UItra Thin Single-flow design suits Refrigerant
Standard built-in drain pump with 29-17/32in.(750mm) pump corner installation
Single-flow design suits Refrigerant
head. built-in drain pump with 29-17/32in.(750mm) pump
Standard corner installation
29-17/32in.(750mm) NetGross
Net dim.(W
Panel
Drain pipin
Standard Controlle
Standard Controller
Notes:
Notes: 1. Nominal cooling cap
(horizontal)
1. Nominal cooling capacities are ba
(horizontal)
2. Nominal heating cap
Acetaldehyde 2. Nominal heating capacities are b
(horizontal)
Acetaldehyde (horizontal)
3. Sound Level is mea
3. Sound Level is measured 4.59ft(1
Acetic acid Formol NH3
Acetic acid Formol NH3
72
Model 4TVA0006A10REAA 4TVA0007A10REAA 4TVA0009A10REAA 4TVA0012A10REAA 4TVA0015A10REAA 4TVA0019A10REAA
Cooling 41 41 41 41 80 85
Rated input W
Heating 41 41 41 41 80 85
Sound pressure level(H/M/L) dB(A) 37/34/30 38/34/30 39/37/34 40/38/34 41/39/35 42/40/36
Type R410A
Refrigerant Control
method EXV
45-5/327-7/825-13/64
Net dim.(WHD) 41-1/26-21/3216-47/64(1054169425) (1147200640)
in.(mm)
54-21/6410-7/1630-33/64
Indoor Unit Gross dim.(WHD) 45-15/329-41/6419-19/64(1155245490) (1380265775)
L(flare) in.(mm) 1/4 ( 6.35) 1/4( 6.35) 1/4( 6.35) 3/8( 9.53)
Piping connections G(flare) in.(mm) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 5/8( 15.9)
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temp. : 80.6F(27C)DB,66.2F(19C)WB,and outdoor temp.: 95F(35C)DB,equivalent ref. piping: 26.25ft. (8m)
(horizontal)
2. Nominal heating capacities are based on the following conditions: return air temp.: 68F(20C)DB, outdoor temp.: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref. Piping: 26.25ft. (8m)
(horizontal)
3. Sound Level is measured 4.59ft(1.4m) below the unit
73
Indoor Units Lineup
Two-way Cassette
Power
Coolin
Auto Restart Fresh Air
Rated
Optimized airflow duct with low resistance makes High airflow for high ceiling application guaran-
noise level get reduced greatly, min. 24dB(A). tees equal comfort of large space. It makes Sound
12in.(305mm)
11-13/16in.(300mm)
Piping
connec
Standard built-in drain pump with 29-17/32in.(750mm)
pump head (higher pumphead can be customized).
Standa
Notes:
29-17/32in.
1. Nomina
(750mm)
26.25ft(
2. Nomina
26.25ft
3.Sound L
74
Model 4TVE0007A10REAA 4TVE0009A10REAA 4TVE0012A10REAA 4TVE0015A10REAA 4TVE0018A10REAA 4TVE0024A10REAA
Sound pressure level(H/M/L) dB(A) 33/29/24 36/32/29 36/32/29 39/35/30 39/35/30 44/40/34
Type R410A
Refrigerant Control
method EXV
Piping
G(flare) in.(mm) 1/2(12.7) 1/2(12.7) 1/2(12.7) 1/2(12.7) 5/8(15.9) 5/8(15.9)
connections
Drain piping in.(mm) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32)
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature : 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref. piping:
26.25ft(8m) (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB,outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref. piping:
26.25ft (8m) (horizontal)
3.Sound Level is measured 4.59ft.(1.4m) below the unit
75
Indoor
Compact Four-way Units
Cassette Lineup
Compact Four-way Cassette
Model 4TVB0007A10
Power supply
Cooling 51
Super High Air Flow
Super High Air Flow Power input W
Heating 43
Cooling 0.175
Rated current A
Heating 0.175
(57
0m the ambient decoration. Little space is required for
6in
(22-7
/1 (22-7
Extremely compact casing makes it perfectly
/16in installation into a shallow ceiling.
(570
match with
Sound pressure level(H/M/L) dB(A) 35.8/33.4/2
) mm)
0 mm Due to its compact body and light weight, all models can
the ambient decoration. Little space is required for Type
(57
in be installed without a hoist.
/16 Refrigerant
(22
-7 installation into a shallow ceiling. Control method
Due to its compact body and light weight, all models can
Net dim.(WHD)
in.(mm)
be installed without a hoist. Body
Gross dim.(WHD)
Quiet operation, soft air supply Uniform air flow of four ways Net/gross lbs.(kg) 35.3/44.1/(16
Indoor Units Lineup
Net dim.(WHD)
Diffuser in.(mm)
Panel Gross dim.(WHD)
Quiet operation,
3-D spiral fan bladesoft air supply Uniform air flow of four ways Net/gross lbs.(kg) 6.6/11(3/5
in.(mm) 1/4(6.35
Indoor Units Lineup
L(flare)
Streamline plate ensures quietness The four air discharge port provides strong circulating Piping
Diffuser G(flare) in.(mm) 1/2(12.7
Advanced 3-D spiral fan design reduces the air air flow to cool or heat every corner of the room and connections
resistance and operation noise. realizes even temperature distribution; by choosing high Drain piping OD 63/64( 2
in.(mm)
airflow mode, high ceiling application over 1/8in.(3m)
3-D spiral fan can
blade get equal comfort. Standard Controller
resistancecirculating air flow to cool or 19-11/16 in. 3.Sound Level is measured 4.59ft. (1.4m) below the unit.
and operation noise. realizes even temperature
(500mm)
distribution; by choosing high
heat every corner of the room
airflow mode, high ceiling application over 1/8in.(3m)
and realizes even temperature
can get equal comfort.
distribution. Drain up pump with 19-11/16 in.(500mm) pump head
fitted as standard, max. up to 600mm pump head.
360Airflow outlet Lift pump N
76
Model 4TVB0007A10REAA 4TVB009A10REAA 4TVB0012A10REAA 4TVB0015A10REAA
kW 2.4 3.2 4 5
Cooling 51 52 58 58
Power input W
Heating 43 44 50 51
Type R410A
Refrigerant
Control method EXV
Piping
G(flare) in.(mm) 1/2(12.7) 1/2(12.7) 1/2(12.7) 1/2(12.7)
connections
Drain piping in.(mm) OD 63/64( 25) OD 63/64( 25) OD 63/64( 25) OD 63/64( 25)
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature : 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref. piping:
26.25ft (8m) (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB,outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref. piping:
26.25ft (8m) (horizontal)
3.Sound Level is measured 4.59ft. (1.4m) below the unit.
77
Indoor Units Lineup
Four-way Cassette
Four-way Cassette
Model
Follow Me Cooling
Follow MeAnti-Cold Air Function
Anti-Cold Air Function Power input Power input
Heating
Cooling
Built-in Drain Pump
Built-in LED
LED Drain Display
Pump LED Display Rated current Rated current
DISPLAY
LED Heating
DISPLAY
Airflow rate(SH/H/M/L)
Airflow rate(SH
Super High Air Flow
Super High Air Flow
Sound pressure level(H/M/L)
Sound pressu
Refrigerant Refrigerant
Model
Easy troubleshooting
Easy troubleshooting Uniform Uniform
airflow ofairflow
four ways
of four ways Power supply Power supply
360air outlet360air
provides strong
outlet provides strong Airflow rate(SH/H/M/L)
Airflow rate(SH
circulating aircirculating
flow to cool
air or
flow to cool or To another room
Sound pressure level(H/M/L)
Sound pressu
To another room
heat every corner of thecorner
heat every room of the room
Refrigerant Refrigerant
Fresh Air Intake
and realizes and
evenrealizes even Fresh Air Intake
Net dim.(WHD)
temperature temperature
distribution distribution Body GrossBody
dim.(WHD)
Net/gross
78
Power supply
Model
Indoor Units Lineup
4TVC0009A10REAA 4TVC0012A10REAA 4TVC0015A10REAA
kW 8 9 10 11.2 14
Cooling capacity kcal/h 6,900 7,700 8,600 9,600 12,000
Btu/h 27,300 30,700 34,100 38,200 47,800
kW 9 10 11.1 12.5 15
Heating capacity kcal/h 7,700 8,600 9,500 10,800 12,900
Btu/h 30,700 34,100 37,900 42,700 51,200
Cooling 115 160 160 160 180
Power input W
Heating 115 160 160 160 180
Cooling 0.5 0.7 0.7 0.7 0.8
Rated current A
Heating 0.5 0.7 0.7 0.7 0.8
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature : 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref. piping:
26.25ft. (8m) (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB,outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref. Piping:
26.25ft. (8m) (horizontal)
3. Sound Level is measured 4.59ft. (1.4m) below the unit
79
Indoor Units Lineup
Model 4TV
Mod
kW
Btu/h
Auto Restart Anti-Cold Air Function
Auto Restart Anti-Cold Air Function
kW
m/h 606(3
Airflow rate(SH/H/M/L)
Airflow rate(SH/H/
CFM 3
Low sound
Lowlevel
sound level Refrigerant type
Type
Refrigerant
Control type
type
Dimension Dimensi
(WHD) in.(mm)
(WHD
Utilizes the Utilizes
centrifugal
the type
centrifugal type Packing
Indoor Indoor Packing
(WHD) in.(mm)
unit (WHD
blower, provides a minimum
blower, provides a minimum
unit
Net(Gross) Net(Gro
lbs.(kg)
weight weight
noise level noise
of 24dB (A),of an
level 24dB (A), an L(flare) in.(mm)
L(flare)
CompactCompact
design design Options Options
Min.5mm Min.5mm
29-17/32in.(750mm)
29-17/32in.(750mm)
8-17/64in.(210mm)
8-17/64in.(210mm)
Ceiling Ceiling
ceiling ceiling
Uniform 8-17/64in.(210mm) in height, compact
Uniform 8-17/64in.(210mm) in height, compact A drain pump with pump
A drain 29-17/32in.(750mm)
with 29-17/32in.(750mm)
design for easy locate where
design for easy locate space ceiling
where is ceiling is
space pumphead ispumphead
an optionalisaccessory.
an optional accessory.
limited, limited,
The whole body
The adopts fireproof
whole body plastic
adopts material
fireproof plastic material
the minimumthe
weight is 30.9lbs(14kg).
minimum weight is 30.9lbs(14kg).
80
Model 4TVL0006A10WEAA 4TVL0007A10WEAA 4TVL0009A10WEAA 4TVL0012A10WEAA 4TVL0015A10WEAA 4TVL0019A10WEAA 4TVL0024A10WEAA
Cooling capacity kcal/h 1500 1900 2400 3100 3900 4800 6100
Heating capacity kcal/h 1900 2200 2800 3400 3900 5400 6900
low
Btu/h 7500 8900 10900 13600 17100 21500 27300
External Static Pressure Pa 10(10~30) 10(10~30) 10(10~30) 10(10~30) 10(10~30) 10(10~30) 10(10~30)
Sound pressure level
( H/M/L) dB(A) 35/27/24 35/27/24 35/27/24 38/32/28 39/32/29 39/32/29 41/33/30
Dimension 46-29/648-17/6418-1/2
in.(mm) 29-9/648-17/6418-1/2(740210470) 37-51/648-17/6418-1/2(960210470)
(WHD) (1180210470)
Indoor Packing
in.(mm) 35-53/649-1/1620-5/64(910230510) 44-31/649-1/1620-5/64(1130230510) 53-5/329-1/1620-5/64
unit (WHD) (1350230510)
Net(Gross)
weight lbs.(kg) 32.0/39.7(14.5/18) 39.7/49.6(18/22.5) 39.7/49.6(18/22.5) 49.6/58.5(22.5/26.5)
L(flare) in.(mm) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 3/8( 9.53) 3/8( 9.53)
Piping
connections G(flare) in.(mm) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 12.7 5/8( 15.9) 5/8( 15.9)
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temp.: 27CDB, 19CWB, and outdoor temp.:35CDB, equivalent ref. piping: 8m
(horizontal)
81
Indoor Units Lineup
Model
Cooling capacityCooling c
Auto Restart Auto Restart Fresh Air Fresh Air
Connectable ToConnectable
Duct To Duct Airflow rate(SH/H/M/L)
Airflow ra
ESP(external staticESP(exter
pressure
Refrigerant Refrigera
Net dim.(WHD
Compact size
Compact size ExternalExternal
static pressure
static pressure Indoor
Unit
Indoor
Gross dim.(WHD
Unit
Min.3/16in.(5mm)
Min.3/16in.(5mm) Four speedFour
fan motor
speed(Super high(Super
fan motor speed high
as speed as NetGross
L(flare)
an optional)an optional) Piping Piping
8-9/32in. 8-9/32in.
or 10-5/8in. connections G(flare)
connections
or 11-13/16in.
or 10-5/8in.
or 11-13/16in.
Change theChange
wiring connection from SH tofrom SH to
the wiring connection Drain piping
Ceiling Ceiling
H to change
Hthe ESP. the ESP.
to change Standard Controller
Standard
Convenient installation
Convenient installation Cooling capacityCooling c
82
Model 4TVD0007A10WEAA 4TVD0009A10WEAA 4TVD0012A10WEAA 4TVD0015A10WEAA 4TVD0019A10WEAA 4TVD0024A10WEAA
Sound pressure level(H/M/L) dB(A) 36/35/32 36/35/32 38.6/37.5/33.8 39/37.9/34 39/37.9/34 41.4/39/35
Type R410A
Refrigerant Control
method EXV
37-51/64x8-17/64x19- 37-51/64x8-17/64x19- 46-29/64x8-17/64x19-
Net dim.(WHD) 29-9/64x8-17/64x19-11/16(740x210x500) 11/16(960x210x500) 11/16(960x210x500) 11/16(1180x210x500)
Indoor in.(mm) 43-57/6411-7/ 43-57/6411-7/ 52-9/1611-7/
Unit Gross dim.(WHD) 34-1/411-7/3220-43/64(870285525) 3220-43/64 3220-43/64 3220-43/64
(1115285525) (1115285525) (1335285525)
83
Indoor Units Lineup
High Static Pressure Duct Model 4TVH0024A1
kW 7.1
Power Supply
Cooling kcal/h 6,100
Auto Restart Anti-Cold Air Function
Btu/h 24,200
Capacity
Auto Restart Anti-Cold Air Function kW 8
Auto Addressing Connectable To Duct Heating Capacity
kcal/h 6,900
Btu/h 27,300
Auto Addressing Connectable To Duct
Follow Me Cooling 414
Power input W
Heating 414
Follow Me 1.9
Cooling Power input
Wired Controller Rated current A
Heating 1.9
With 16-17/32in(420mm)
The maxthickness
distancebody,
of airthe minimum
supply distance
is about above the ceiling
45.9ft.(14m) while isthe
17-23/32in(450mm).
height of air supply is about 21.3ft.(6.5m).
kWPower Supply 14
Cooling kcal/h 12,00
With 16-17/32in(420mm) thickness body, the minimum distance above the ceiling is 17-23/32in(450mm). Btu/h 47,80
Cooling 527
Four speed fan motor(model 71 to 160) Power input W
Indoor Units Lineup
Heating 527
Convenient installation
The EXV is fixed inside the indoor unit (for 71~450 model), no need extra connection.
Heating
m3/hRated current
2.03
2,969/2,694
Indoor air flow (H/M/L)
Standard filter placed
The EXV in anisaluminum frame,the
fixed inside which is removable
indoor downwardmodel),
unit (for 71~450 from bottom.
no need extra connection. CFM 1,746/1,586
Indoor air flow (H/M/1
50(50~
Flange for air in/outlet
Standard duct filter
connection
placed is in
standard.
an aluminum frame, which is removable downward from bottom. ESP(external static pressure) Pa
Sound pressure level(H/M/L) 53/50/4
dB(A)ESP(external static
Flange for air in/outlet duct connection is standard. p
Standard Controller -
29-17/32in.(750mm) Standard Controller
Notes:
29-17/32in.(750mm) 1. Nominal cooling capacities are based on the following conditions: return air tem
Notes:
Piping:26.25ft(8m)(horizontal)
1. Nominal cooling ca
2. Nominal heating capacities are based on the following conditions: return air tem
ceiling Piping: 26.25ft(8m)(horizontal)
Piping:26.25ft(8m)
2. Nominal heating ca
Optional drain pumps with 29-17/32in.(750mm) ceiling
Double-skin drainage pan, double production for 3. Sound Level is measured 4.59ft. (1.4m) below the unit. Piping: 26.25ft(8m)
84
Model 4TVH0024A10WEAA 4TVH0027A10WEAA 4TVH0030A10WEAA 4TVH0038A10WEAA
L(flare) in.(mm) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53)
G(flare) in.(mm) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9)
Piping Connections
Drain piping in.(mm) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32)
L(flare) in.(mm) 3/8( 9.53) 3/8( 9.53) 1/2( 12.7) 1/2( 12.7)
G(flare) in.(mm) 5/8( 15.9) 5/8( 15.9) 7/8( 22.2) 7/8( 22.2)
Piping Connections
Drain piping in.(mm) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32)
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref.
Piping:26.25ft(8m)(horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB, outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref.
Piping: 26.25ft(8m)(horizontal)
r 3. Sound Level is measured 4.59ft. (1.4m) below the unit.
* Specifications are subject to change without prior notice for product improvement.
85
Indoor Units Lineup
Ceiling & Floor
Ceiling & Floor P
Cooli
Cooling capacity
Airflow rate(H/M/L)
Soun
Sound pressure le
Refri
The front panel and display panel have different colors to choose: white and brown to big panel, blue and Net dimension(W
Pack
brown for small
The front panel and panel,
display and
panel the different
have other colors cantobe
colors customized
choose: whiteaccording
and browntotothe
bigcustomers demands.
panel, blue and
Packing dimension
brown for small panel, and the other colors can be customized according to the customers demands. Net/G
Convenient for installation Net/Gross weight
Convenient for installation Pipin
L(
The ceiling type can be easily installed into a corner of Piping conn
G
The ceiling
thetype can even
ceiling be easily
if theinstalled
ceiling isinto a corner
very narrowof connections
Stand
Dr
the ceilingIteven if the ceiling
is especially usefulis when
very narrow
installation of an air Standard Controller
It is especially useful in
conditioner when installation
the center ofceiling
of the an air is impossible
conditioner in to
due thea center of the
structure ceiling
such as oneis impossible
lighting
The unit can be installed either horizontally on the P
due to a structure such as one lighting ceilingeither
or vertically against Cooli
The unit can be installed horizontally on the
the wall.
ceiling or vertically against the wall. Cooling capacity
Low noise, creates quiet and comfortable environment
Low noise, creates quiet and comfortable environment Heat
Drop ceiling
Indoor Units Lineup
Heating capacity
>20
Drop ceiling
Indoor Units Lineup
>20 Powe
Co
198mm Power input
He
Rated
198mm
Co
Rated current
Air Outlet He
Airflo
Airweight
Slim and sleek design starting at just 66lbs.(30kg) in Outlet means quick,easy & neat installation. Airflow rate(H/M/L)
Soun
Low design
Slim and sleek noise operation,
starting atlowest to 36dB(A) in weight means quick,easy & neat installation.
just 66lbs.(30kg)
Sound pressure le
Refri
Low noise operation, lowest to 36dB(A)
Auto swing and wide angle air flow Refrigerant
* Specifications are su
86
Model 4TVX0012A10REAA 4TVX0015A10REAA 4TVX0018A10REAA 4TVX0024A10REAA
* Specifications are subject to change without prior notice for product improvement.
87
Indoor Units Lineup
Wall-mounted S
Wall-mounted
Auto Restart
S type p
Auto Restart M
Auto Addressing
S type panel C type panel Pow
Co
Auto Addressing
S type panel C type panel Cleanable Panel
Cooling capacity
Cleanable Panel He
Anti-Cold Air Function
Heating capacity
R type panel Anti-Cold Air Function
Follow Me Po
Rated current
LED Display Air
LED
DISPLAY
So
Airflow rate(H/M/L
Rele
Sound pressure
The EXV is built-in the indoor unit, compact size, longer the
flexible for installation. Standard Controll
Cooling capacity
stable. Auto swing louver Easy
maintenance He
auto swing louver function The front panel can be removed for easy Heating capacity
Indoor Units Lineup
Refrigerant
Ne
Swing 4
* Sp
Piping: 26.25ft(8m
3. Sound level is mea
* Specifications are
88
S type panel
Model 4TVW0007A10REBA 4TVW0009A10REBA 4TVW0012A10REBA 4TVW0015A10REBA 4TVW0018A10REBA
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature : 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref.
piping: 26.25ft(8m)(horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB, outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref.
Piping: 26.25ft(8m)(horizontal)
3. Sound level is measured 3.28ft.(1m) below the air out-let both in horizontal and vertical distance.
* Specifications are subject to change without prior notice for product improvement.
89
C type panel R
Model 4TVW0007A10REAA 4TVW0009A10REAA 4TVW0012A10REAA 4TVW0015A10REAA 4TVW0018A10REAA
* Specifications are subject to change without prior notice for product improvement.
90
R type panel
Model 4TVW0024A10REAA 4TVW0027A10REAA 4TVW0031A10REAA
* Specifications are subject to change without prior notice for product improvement.
91
Indoor Units Lineup
Console
High
Auto Restart Cleanable Panel Built
Activ
Auto Addressing Anti-Cold Air Function
Two a
Follow Me LED LED Display
DISPLAY
Four dir
two opt
only.
Air O
Air Ou
Flexible installation
Can be installed on the floor or lower wall
As a floor standing type, it can be semi or fully accessed
without losing capacity.
Cooling capa
Flexible air blow: vertical auto swing and wide angle louvers ensure that warm air reaches every corner Power input
of the room and increases the air flow coverage.
Indoor unit adopts DC motor with five fan speeds to meet different requirements. Rated curren
Applies the Fujikoki mechanical expansion valve which offers 2,000-stage element positions to ensure
Airflow rate(H
precise flow control and lower modulation noise when the EXV is operating.
Sound press
Refrigerant
Powerful mode can be selected for rapid cooling or heating Net dimensio
Packing dime
COOLING MODE HEATING MODE Net weight
Gross weight
Piping
connections
Standard Con
Notes:
1. Nominal cooling
2. Nominal heating
Quick cooling To maintain temperature Anti-cold air Normal operation 3.Sound level is me
* Specifications a
92
High efficiency filter
Built in formaldehyde nemesis filter
Active-carbon and biological anti-virus filter are optional.
on
Air Outlet
Air Outlet
Air Inlet
Air Inlet
Bottom, top, and right/left side, for better ventilation. Low noise operation, lowest to 26dB(A)
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature : 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref. piping: 26.25ft(8m) (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB, outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref. Piping: 26.25ft(8m)(horizontal)
3.Sound level is measured 3.28ft.(1m) from the air out-let in horizontal distance and 3.28ft.(1m) above the floor in vertical distance.
* Specifications are subject to change without prior notice for product improvement.
93
Indoor Units Lineup
Fresh
h Air Processing Unit Power Supply
Capacity
Power input
Rated current
Sound pressure le
Refrigerant
Net dimension
Net/Gross Weight
Fresh air is imported, provides a healthy and comfortable living environment.
Piping Connection
Indoor units and fresh air processing unit can be 2. Nominal heating c
3. Sound level is me
connected to the same refrigerant system, increasing
INDOOR UNIT * External static
design flexibility and greatly reducing total system costs. *Connection
Specifications
The height of air Conditi
Air supply Air return
supply is 6.5m The following restri
* When outdoor-a
* When outdoor-a
* Outdoor-air pro
Indoor Units Lineup
External static pressure can be up to 196Pa(125~140 models) and 280Pa(200~280 models) for more flexible duct
applications. The maximal distance of air supply is about 45.9ft.(14m) and the maximum height of air supply is
about 21.3ft.(6.5m).
Innovative air supply technology for excellent room temperature control
Layout Example:
Outdoor Units
94
Model 4TVF0042A10WEAA 4TVF0048A10WEAA 4TVF0075A10WEAA 4TVF0085A10WEAA 4TVF0096A10WEAA
kW 12.5 14 20 25 28
Type R410A
Refrigerant
Control method EXV
L(flare) in.(mm) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53)
Piping Connections G(flare) in.(mm) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9)
Notes:
1. Nominal cooling capacities are based on the following conditions: outdoor air temperature:91.4F(33C)DB75.2F(24C)WB, equivalent ref. piping:26.25ft. (8m)(horizontal).
2. Nominal heating capacities are based on the following conditions: outdoor air temperature:32F(0C)DB30.2F(-1C)WB, equivalent ref. piping:26.25ft. (8m)(horizontal).
3. Sound level is measured 4.59ft.(1.4m) from the air out-let.
* When outdoor-air processing units are connected, the total connection capacity must be within 50% to 100% of that of the outdoor units.
* When outdoor-air processing units and standard indoor units are connected, the total connection capacity of the outdoor-air processing units must not exceed 30% of that of the outdoor units.
95
ERV-
ERV - Energy Recovery
Energy Recovery Ventilator
Ventilator
RA
(Returm air
from room)
SA
Heat 14
C
Cold air
0 0C
u
Moisture
SA
(Supply air
to room)
Moisture
EA
6
C Heat Warm air
C
20C
EA
(EXhust air
to outdoors)
OA
(Fresh air from
outdoors)
96
58
ERV - Energy Recovery
ERV-
Ventilator
Energy Recovery Ventilator
Low noise
Sound proof material is used to guarantee quiet operation.
Bypass mode
In mild climates where the temperature and humidity difference between indoors and outdoors is small, the
unit works as conventional ventilation fan. Both the supply fan and exhaust fan work at the same speed
(auto/low/medium/high).
EA RA EA RA
Element Element
OA SA OA SA
59
97
ERV-- Energy Recovery
ERV
Energy Recovery Ventilator
Ventilator
Flexible control
th other indoor units via controller is possible
Interlocking control with
EA
SA RA
IDU
Centralized control
SA
TCONTCCM30A
98
60
Specifications
Model TERV0235AB0AA TERV0300AB0AA
Specifications
Model TERV0470AB0AA TERV0600AB0AA TERV0900AC0AA TERV1200AC0AA
Note:
1. Three speeds (low/med/high) are available for ERV models 200 to 1000; one speed is available for HRV models 1500 to 2000.
2. The sound level is measured at 1.4m below the body center in an anechoic chamber.
3. The airflow rate can transmit between low and high modes.
4. The temperature exchange efficiency is the mean value between cooling and heating
5. Efficiency is measured under the following conditions:
* Cooling Condition: Air Exhaust Temp. 27C DB,19.5CWB., Fresh Air Temp. 35C DB,28CWB
* Heating Condition: Air Exhaust Temp. 21C DB,13CWB., Fresh Air Temp. 5C DB,2CWB
99
Control Systems
Control System-sNetwork
-
Control
Network Control
Trane Router
Centralized Control
X,Y,E
Connectable to
various sized Gateway
Weekly Schedule
Centralized Controller
X,Y,E
TCONTIF441V4PA58 TIMSWENETMA
TCONTCCM09A
Indoor Centralized
Controller
Lonworks BMS TCONTLWGW64E
X,Y,E
TCONTCCM03A
BACnet BMS
TCONTCCM08A
Outdoor Centralized
Controller
TCONTCCM02A
Note: The wires in the diagram show the signal flows only,
while not represent the actual connecting ways.
Modbus BMS TCONTMBGW01E
100
Control Systems - Network
Control
Individual control
Wired controller
TCONTKJR10B
TCONT10BDPC
TCONTKJR12B
TCONTKJR120B
TCONTKJR86C
TCONTKJR90AE
TCONTKJR90A1E
TCONTKJR90BME
TCONTKRJ29BKE
Remote controller
TCONTR51CE
TCONTRM05A
Accessories
Card-key Interface TCONTNAM05A
TCONTNAM05A
TCONTKJR10B
Card-key
TCONTKJR10B
Outdoor units
101
Comparison of Controllers
Item Rem ote c ontroller W ired Controller Centralized Controller
TCONT TCONT
TCONT TCONT KJR10B TCONT TCONT CCM03A TCONT TCONT
RM05A R51CE TCONT KJR90AE KRJ29BKE TCONT CCM09A KJR90BME
KJR12B CCM30A
removable 1 1 1 64 64/16 16
On/Off
Vertical swing - - - - - -
Horizontal swing -
Air direction - - - - - - -
A/C control
Economic mode - - - - -
function
Group setting - - - - -
Keyboard lock - -
Mode lock - - - - - -
26 shortcut setting - - - - - - - -
Silent mode - - - - - - -
Backlight /- -
Current time - /- - - -
Display RC prohibition - - - - - -
Address - - - - - -
Error code - - - - - -
Period - - - - - - Week -
On/Off timer -
FOLLOW ME - - -/ - - - -
Emergent stop - - - - - - -
Emergent start - - - - - - -
Address setting - - - - - -
10 heat function - - - - - - - -
102
Control Systems- -
Control Systems
Wireless RemoteController
Wireless Remote Controller
Temp 1
5 Time
6 Lock
ON OFF
7 Time ON/OFF
Economic operation 8
9 Fan speed
Background light
The background light allows users to operate the
device in a dark room. The device lights up when a
button is pressed, and turns off when a given AUTO
operation is completed. Auto Mode DRY Mode HEAT Mode COOL Mode
Economic Addressing
FAN Mode Lock operation setting
Built-in timer
The built-in daily timer offers the convenience of
automatically starting and stopping the system at set ON 24C OFF
times. 0 3 6 9 12 15 18 21 Time
Setting addresses The indoor unit is set to work in automode from 8:00 to 20:00
Specifications
Model TCONTRM05A TCONTR51CE
Dimensions (HWD)(mm) 1506520 1406015
65
103
Control Systems - Wired
Control Systems -
Controller
Wired Controller
TCONTKJR10B
TCONTKJR12B TCONTKJR29BKE
TCONT10BDPC
TCONTKJR120B
Functions TCONTKJR86C
Follow me
With the FOLLOW ME function, the wired controller
Sensor part can detect the air temperature at the users altitude
instead that of the ceiling or floor. This helps making
the room environment comfortable and the
temperature accurate.
FOLLOW ME Button
*The follow me function is available for
TCONTKJR12B/TCONTKRJ29BKE model.
Specifications
TCONTKJR10B
TCONTKJR12B
TCONT10BDPC
Dimensions (HWD)(mm)
Model 12012015 12012015 TCONTKRJ29BKE
Power (V) DC 5V
12012020
104
Control
Control Systems
Systems - - Wired
Controller
Wired Controller
TCONTKJR90AE
Functions
Features
General function
Small and easy to install
Suitable for all types of indoor units
Can be stored in a mounting cabinet
Built-in timer
TCONTKJR90AE
The built-in daily timer offers the convenience of automatically
starting and stopping the system at set times.
Specifications
Model TCONTKJR90AE
Power (V) DC 5V
105
Control Systems- -
Control Systems
Centralized Controller
Centralized controller
Wireless Remote
HEAT Mode Keyboard lock Controller Lock
TCONTCCM03A TCONTCCM30A
Fan Mode Cooling Lock Heating Lock
Functions
Centralized control Three lock modes
The centralized controller is a multifunctional device that can Centralized controller provides a superior
control up to 64 indoor units within a maximum connection way to manage the indoor units. Users are
length of 1,200m. able to make their own choice from locking
The device connects to the master outdoor units of Trane's the wireless controller, locking the running
newly designed products to simplify and centralize the wiring mode or lock the centralized controller's
configuration. The two connection modes are as follows: keyboard as they wish.
Locking
king king
Locking Locking
king
ning
Running mote
Remote board
Keyboard
X,Y,E X,Y,E X,Y,E X,Y,E ode
Mode troller
Controller
Indoor unit working status display Air filter cleaning reminding function
The centralized controller displays indoor units' working The air filter cleaning reminder function is only
status and error codes so users can easily identify faults available on the touch-key central controller
via checking the error codes table in the user's manual TCONTCCM30A. The "FL" icon indicates that the
before contacting a service engineer. air filter in a given indoor unit needs cleaning.
TCONTCCM30A
106
Control Systems -
Centralized Controller
Functions
Stylish design Single/unified control
CCM's stylish design suits high-end environments. The control object can be either a single unit or all
The keyboard lock function is used to prevent units, which vastly simplifies the control process.
r
cation
operational mistakes. Operation signal feedback ensures that all units are
working in the correct mode.
ote
ck
OPR.UNSUCCESS
or
re
ng
ng Easy installation
Centralized controller offers two different appearances to mostly suit the installation. The A structure must
be embedded into the wall and the B structure doesnt need. Both of them are easy to operate.
MAX.64
Indoor CCM
Specifications
Model TCONTCCM03A TCONTCCM30A
51
Model
Dimensions (H*W*D)(mm) 17911974 18012278 and 18012268
107
Control Systems -
Control Systems
Centralized -
Controller
Centralized Controller
Weekly schedule centralized AUTO
TCONTCCM09A
Cooling Lock Heating Lock Wireless Remote With the PC or gateway
Controller Lock communication
Functions
Weekly schedule
8:00 16:00 23:59
TCONTCCM09A can include up to 64 indoor units in
Sun 28C 22C 24C
the weekly schedule. Users can set up to 4 periods Mon 26C 22C 17C 23C
per day, and select the desired running mode and Tue 26C 22C 17C 23C
single indoor unit or all the indoor units. Fri 26C 22C 26C
OPR.UNSUCCESS
king
Locking king
Locking Locking
king
ning
Running mote
Remote Keyboard
board
ode
Mode troller
Controller
faults via checking the error codes table in the user's #GROUPALL 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16
(1.6)
Specifications
TCONTCCM09A
Dimensions (H*W*D)(mm)
Model 17911974
108
Control
Control Systems
Systems - -
Centralized
Centralized Controller
Controller
Functions TCONTKJR90BME
Unified control
TCONTKJR90BME offers on/off and heating/cooling
functionality for indoor units based on preset
20C
0C 28C
temperatures to ensure easy management. cooling heating
Centralized control
KJR-90B can be used to centrally control up to 16 indoor units.
Max.16
Light indicator
The LEDs on TCONTKJR90BME indicate the indoor units' running status for easy fault detection. The lights
switch off automatically to save energy once a given operation is complete. The indicators are as follows:
Easy installation
TCONTKJR90BME can be easily mounted on the built-in cabinet:
Specifications
Model TCONTKJR90BME
Power (V) DC 5V
109
Control
ControlSystems
Systems- -
Accessories
Accessories
Wired controller
TCONTKJR10B
TCONTKJR10B
220V
KM
TCONTNAM05A
TCONTNAM05A
Card key
AC contactor
Card key
Specifications
Model TCONTNAM05A
Power (V) DC 5V
TCONTDTS636
A phase
230
B phase
C phase
Specifications
Model TCONTDTS636
72
110
Control Systems -
Control Systems -
Accessories
Accessories
Forced
Cooling
Functions
ODU parameters display
Forced
TCONTCCM02A enables users to easily check
Cooling
111
Control
ControlSystems
Systems --
Accessories
Accessories
Access to network monitoring
TCONTCCM02A can connect up to 8 refrigerant systems and 32 outdoor units to the network monitoring and
building management systems.
K1,K2,E Max.4
system 1
system 2
K1,K2,E Max.4
Specifications system 8
Model TCONTCCM02A
Dimensions(HWD)(mm) 12012015
Functions
Simple design
TCONTKJR32BE is specially designed for engineering applications. It does not display the ODUs working
parameters, but it can connect to the alarm device when ODU is working abnormally, the RUN light will flash.
Specifications
Model TCONTKJR32BE
112
ControlSystems
Control Systems- -
Accessories
Accessories
Infra-red
sensor
TCONTKJR10B Display panel
TCONTKJR10B TCONTNAM09A works
CN3
together with the wired CN2
TCONTNAM09A CN1
TCONTNAM09A
controller. S1
TCONTNAM09A
Infra-red inductive
control box
Indoor main board
TCONTKJR10B
Wired controller
Specifications
Model TCONTNAM09A
Functions
ERV controller Built-in timer
TCONTKJR27B is individually designed for ERV Built-in daily timer offers the convenience of
Energy Recovery Ventilator. The ERV can work in the automatically starting and stopping the ERV at
following modes: exhaust, air supply, bypass, heat the set times.
exchange, and auto. Setup screen example
Set to wednesday: 8:00 to 20:00
Specifications
Model TCONTKJR27B
Dimensions(HWD)(mm) 12012015
Power (V) 198-242V(50/60Hz)
75
113
Control
Control Systems
Systems --
Accessories
Accessories
Control Box
TAYKITAHUKZ01
TVR 4G functions inside.
Match the new outdoor units. TAYKITAHUKZ02
TAYKITAHUKZ03
Introduction
TAYKITAHUKZ01/TAYKITAHUKZ02/TAYKITAHUKZ03 is an independent control box that can connect a AHU
to TVR system to realize centralized control with TVR system. Control box wiring is as follows:
Power supply Power supply
Centralized Controller
P/Q/E X/Y/E
Wired Controller
T1/T2/T2B/T2C
G/L pipe
Fan/pump
x EXV
Power supply
Specifications
Model TAYKITAHUKZ01/TAYKITAHUKZ02/TAYKITAHUKZ03
Dimensions(HWD)(mm) 335375150
Power (V) 220-240V~ 50Hz 208-230V~ 60Hz
Wiring diagram
The diagnostic software applies to K1, K2, E of the outdoor units. The corresponding wiring diagram is shown
in the figure on the right.
485A-I
K1,K2,E
Recommended config
Operating system WIN XP SP4/WIN 7
114
Building
Building Management
Management
System(BMS)
System (BMS)
TIMSWENETMA
TCONTIF441V4PA58
Functions
TIMSWENETMA/TCONTIF441V4PA5, designed specifically to control TVR systems, is based on a centralized
format and dedicated to the complete control and monitoring of all the systems functions. It can be used as a
flexible multi-purpose system and applied to a variety of needs, according to the scale, purpose and control
method of each building.
IDU:1024
Max.IDU:1024
115
Building Management
System (BMS)
Various Managements
Simple Operation and Management
Click & Operate, a user-friendly interface allows even non-experts to perform
the building management system easily.
Data Management
Operational information of individual indoor units are monitored, allowing for
distribution of power consumption at outdoor units.
Stores operation data on multiple systems and displays it in graphical format for
visual management.
Uses TIM software to generate tenant reports and help building owners bill for
energy use.
Hightlights
116
Building Management
System (BMS)
One TCONTCCM08A gateway can connect MAX.4 TCONTCCM02A or TCONTCCM03A,and each 485 port only
can connect one TCONTCCM02A or one TCONTCCM03A.
Outdoor units
TCONTCCM08
Indoor units
TCONTCCM02A
TCONTCCM03A
RS485
Outdoor units
HUB
TCP/IP BACnet/IP protocol
Wide compatibility
TCONTCCM08A has a wonderful adaptability to the BMS
Company BMS software Brand
APOGEE
1 SIMENS APOGEE A N Y W H E R E
TM
3 Honeywell Alerton
4 Schneider Andover
5 Johnson METASYS
117
Building
Building Management
Management
System
System(BMS)
(BMS)
Network example
Indoor Units
Modbus agreement system
P,Q,E
E Max.64
TCONTCCM03A
F1,F2,E X,Y,E
K1,K2,E
K1,K2,E
Outdoor Units
Modbus
Modbus Master
Gateway
TCONTCCM02A
E
P,Q,E Max.64
TCONTCCM03A
F1,F2 X,Y,E
K1,K2,E
Modbus K1,K2,E
A+,A-,GND
Gateway
TCONTCCM02A
Max.16
E
P,Q,E Max.64
TCONTCCM03A
F1,F2
Modbus
Gateway
TCONTCCM02A
One Modbus gateway can bridge one refrigerant system with a PC or the Modbus master.
10.5
Right Side Front Side
110
36
48
35
25.5
100 46
80
118
56
Building Management
Building Management
System (BMS)
System (BMS)
RS485 X,Y,E
TCONTLWGW64E
P,Q,E
X,Y,E X,Y,E X,Y,E X,Y,E
RS485
Lonworks
net work System 2
P,Q,E
Specifications
Model TCONTLWGW64E
BM
119
Piping Accessories
Piping Accessories
Outdoor / Indoor Branch Specification
Packing Size (mm)/
Model Features Model name Description
Gross Weight (kg)
4TRDK01C 2555090 /
A*<16.6kW
0.48
4TRDK02C 2805095 /
16.6A*<33kW
0.6
4TRDK04C
35070170 / 66kWA*<92kW
1.3
4TRDK05C
365110205 / 92kWA*
1.6
A*:The total capacity of indoor units following this branch joint
120
Piping Accessories
Piping Accessories
Outdoor branch drawing
Outdoor branch 4TODK02C 4TODK03C Packing Size (mm)/ 4TODK04C
Features Model name Description
Gross Weight (kg)
0D:31.8 0D:31.8 ID:31.8 0D:31.8 ID:31.8
ID:38.1
ID:31.8
ID:41.3
ID:34.9
Q5
Gas side
Q4 ID:38.1
Q1
ID:31.8
ID:41.3
ID:31.8 ID:31.8
ID:25.4 0D:31.8
Q5
0D:34.9 ID:41.3
Q1 ID:44.5
ID:31.8
Q3 ID:31.8
ID:25.4 0D:31.8 Q6
ID:38.1
ID:34.9 Q1
ID:31.8
ID:31.8
ID:25.4 0D:31.8
ID:19.1 ID:19.1
ID:22.2 ID:22.2
Y3 Y1 ID:15.9 Y1 ID:15.9
ID:22.2 ID:15.9 ID:15.9
0D:15.9 0D:15.9
ID:12.7 ID:12.7
ID:19.1
Y1 ID:15.9
ID:15.9
0D:15.9
ID:12.7
ID:6.4 ID:6.4
121
Name
4TRDK05C
4TRDK04C
4TRDK03C
4TRDK02C
4TRDK01C
ID:22.2
ID:19.1
ID:22.2 ID:28.6
ID:34.9
ID:28.6 ID:12.7 ID:15.9 ID:12.7
ID:34.9 ID:15.9
OD:34.9 ID:19.1
ID:15.9
ID:12.7 Indoor Branch Drawing
ID:41.3 ID:19.1 ID:22.2 (ID:19.1) (ID:15.9)
OD:34.9 (ID:19.1)
ID:41.3 ID:22.2 (ID:15.9)
ID:44.5 OD:22.2
ID:34.9 OD:28.6 OD:19.1
OD:22.2 OD:19.1
OD:28.6
Gas side joints
ID:22.2 ID:19.1
ID:28.6
Piping
BM
ID:44.5 ID:38.1 ID:31.8 ID:25.4 ID:15.9
ID:12.7 ID:15.9
ID:9.5 ID:12.7 ID:6.4
ID:6.4
ID:15.9
(ID:19.1) ID:12.7
(ID:15.9) ID:9.5
(ID:19.1) ID:9.5 ID:6.4 ID:9.5
Piping Accessories
(ID:15.9)
Accessories
OD:22.2 (ID:12.7)
OD:19.1 (ID:12.7) ID:6.4
OD:22.2 OD:19.1 ID:9.5 ID:6.4
OD:15.9 OD:12.7
ID:22.2 ID:19.1 OD:9.5
OD:15.9 OD:12.7
ID:12.7 ID:9.5
ID:15.9
OD:9.5
ID:9.5
Liquid Side Joints
122
Notes
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
123
PF/120815