Integrated

Air Conditioning System


a smart solution for every building

60Hz
Contents
About Trane ................................................................................................ 04
TVR System ............................................................................................... 05
TVR Advantage .......................................................................................... 07
TVR Applications ........................................................................................ 08
Features
DC Inverter System .........................................................,.............. 10
Higher Reliability ............................................................................ 11
Enhanced Comfort ........................................................................ 12
Unique Fan Characteristics ........................................................... 13
Easier Installation & Service.......................................................... 14
Easy Selection Software ............................................................... 15
Mini TVR 5G
Features ........................................................................................ 17
Outdoor Unit Specifications ........................................................... 22
Outdoor Unit Dimensions .............................................................. 25
TVR 5G (All Inverter)
Recommended Combination Table ............................................... 28
Features ........................................................................................ 29
Outdoor Unit Specifications ........................................................... 34
Outdoor Unit Dimensions .............................................................. 36
TVR 5G (Heat Recovery/3 Pipes)
Recommended Combination Table ............................................... 38
Features ........................................................................................ 39
Outdoor Unit Specifications ........................................................... 44
TMS Specifications ........................................................................ 45
Dimensions .................................................................................... 46
TVR 5G (Inverter+Fixed)
Recommended Combination Table ............................................... 48
Features ........................................................................................ 49
Outdoor Unit Specifications ........................................................... 53
Corrosion Resistance unit ............................................................. 54
Outdoor Unit Dimensions .............................................................. 55
TVR 5G (All Inverter-T3/High Ambient)
Features ........................................................................................ 57
Outdoor Unit Specifications ........................................................... 59
Outdoor Unit Dimensions .............................................................. 60
Contents
Nomenclature
Outdoor Unit................................................................................... 61
Indoor Unit...................................................................................... 62
Combination of Outdoor Units .................................................................... 63
Indoor Units Lineup
Indoor Units Offering Summary .................................................... 68
Description Summary-Indoor Units Range.................................... 69
One-way Cassette ........................................................................ 72
Two- way Cassette ....................................................................... 74
Compact Four-way Cassette ........................................................ 76
Four-way Cassette ....................................................................... 78
Low Static Pressure Unit .............................................................. 80
Concealed Duct Unit (A5 Type) .................................................... 82
High Static Pressure Unit ............................................................. 84
Ceiling & floor type ........................................................................ 86
Wall mounted S Type .................................................................... 88
Wall mounted C Type .................................................................... 90
Wall mounted R Type .................................................................... 91
Console ......................................................................................... 92
Fresh Air-processing Unit ............................................................. 94
ERV- Energy Recovery Ventilator .............................................................. 96
Control Systems
Network Control ............................................................................ 100
Wireless Remote Controller .......................................................... 103
Wired Controller ............................................................................ 104
Centralized Controller ................................................................... 106
Accessories .................................................................................. 110
Building Management System (BMS) ........................................................ 115
Piping Accessories
Outdoor/ Indoor Branch Specifications ........................................ 120
Outdoor branch Drawings ............................................................ 121
Indoor branch Drawings ............................................................... 122

3
About Trane
Trane is all about air - cool air, warm air, clean air. As a world
leader in air conditioning systems, services and solutions, we
control the comfort of the air for people in homes and many of
the world's largest and most famous commercial, industrial and
institutional buildings. And we're applying Trane's expertise in
environmental technology and energy conservation to make a
difference in energy efficiency around the globe.

Our Products, Services, Brands and Reputation

We offer a broad range of energy-efficient heating, ventilation


and air conditioning (HVAC) systems; dehumidifying and air
cleaning products; service and parts support and advanced
building controls. Our systems and services have leading
positions in premium commercial, residential, institutional and
industrial markets; a reputation for reliability, high quality and
product innovation; and a powerful distribution network.

03
4
4
System

Presenting a new and excellent heating and cooling option from Trane - with legendary
Trane benefits. Best- in-class energy efficiency. Truly customizable comfort. Available
simultaneous heating and cooling throughout a building. All with small footprints and
multiple installation options for a wide variety of building types.

These are just some of the benefits of Integrated TVR 5G system, our newest heating
and cooling options that bring a new level of choice to our customers. TVR 5G can be
perfect as stand-alone heating and cooling systems - or perfect as supplemental
heating and cooling systems.

For a wide variety of customers, applications and building types, TVR 5G can be the
solution youve been looking for to improve the comfort of your building - and improve
the lives of the people in it. Large and small buildings. Old and new buildings. Schools
and offices. TVR 5G can serve as a stand-alone or supplemental system for a wide
variety of buildings and applications, offering comfort, efficiency and user control
without compromise.

BEST OF ALL, ITS A TRANE !

5
System
The new Variable Refrigerant, TVR A single TVR system fully integrates
air conditioning concept is a modular all functions necessary for filtration,
HVAC system designed to provide the cooling/heating, and ventilation. The
ideal climate in offices, retail establish- indoor climate quality can be improved
ments, hotels, luxury apartments, and when pretreated outside air is connect-
villas. Furthermore, it is equally suited ed either directly to the indoor units or
to new construction and retrofit introduced as a separate system. The
projects. In the global arena, TVR TVR system offers advantages
systems have gained significant popu- throughout the lifecycle of the project;
larity with airco ditioning professionals from design, installation, commission-
and discerning end users who recog- ing, operation and mainte - nance. The
nize its considerable benifits. Independent Zone Control delivers
energy savings for the end user by
TVR can be installed as the main ensuring that the indoor units for unoc-
HVAC system in a facility or as a cupied rooms remain off.
supplemental one that coordinates with
an existing HVAC installation to meet
different application requirements.
TVR (Trane Variable Refrigerant)
technology systems combine one or
more centralized DC Inverter, aircooled
compressors and condensers connect-
ed to many indoor (fan coil) units
throughout the building.

6
Advantage
Energy Efficient:

The TVR systems automatic power


consumption adjustment matches the
cooling load perfectly to the changing
needs of all the individual zones, thus
realizing energy savings. The capacity
is controlled intelligently and distributed Energy Management
evenly over the different zones without
wasting energy. The optional centralized control system
of TVR already has all the power
management data or information points
of each individual zone. Adding the
power measurement softwares allows
the user to calculate the individual power
consumption per zone, per floor or per
building. The control software will
require a Digital ammeter per condenser
and the outdoor centralized controller.

7
Applications

Benefits for Installers


TVR systems are easy to install; deploy-
ment and installation costs are significantly
lower. The TVR systems are light and can
easily fit into a standard elevator. Large
commercial equipment by comparison are
bulky and require specialist material handling
equipment.

Since the units are modular, large cooling


capacities can be achieved by combining
systems offer compelling multiple units.

benefits along the entire Modularity of the design also enables


value chain stages, floor by floor or zone by zone
installation, for example when a building is
Benefits for Designers
not fully occupied.
Design Flexibility. A single condensing unit
can be connected to many indoor units of Trane, with its range of standard TVR
varying capacity and configurations (i.e., modules and sophisticated electronic
Hi wall, Cassette, Convertible and Ducted controls aims to provide near plug-and-play
Split). commissioning.

The relative light weight of the system


reduces requirements for structural
reinforcement of roofs. Because ductwork
is used only for the ventilation system, it
can be smaller than the ducting required in
standard ducted systems, reducing building
height and costs.

TVR systems are ideally suited to buildings


with diverse, multiple zones requiring
individual control, such as office buildings,
hospitals, or hotels.

8
Applications

Benefits for Owners TVR systems typically have multiple


Comfort : TVR Systems can be deployed compressor units. System redundancy
over several zones, each with its individual is therefore improved, as is the ability
set point control. Since TVR systems use of the system to provide cooling while
DC Inverter compressors with wide capacity any maintenance or repair work is being
modulation, precise temperature control can undertaken.
be achieved.

Benefits for Operators

TVR systems involve lower maintenance


eliminated in a TVR system, which in
costs compared to other systems.
a conventional ducted version can be as
Since these are variations of DX systems,
much as 10 to 20% of the total airflow.
water treatment issues are avoided.
Furthermore, a TVR system can include
one, two or three compressors, one of which Normal maintenance for a TVR, similar to

is DC Inverter + Fixed or both inverters. that of any DX system, consists mainly of

These factors constitute to higher system cleaning and changing filters and cleaning

operational efficiency. outdoor coils.

9
Features -
DC Inverter System
High efficiency DC Inverter compressor
Trane Air Conditioner achieves the industry's top class energy efficiency of cooling EER and heating COP
by utilizing the Brushless Reluctance DC compressor control, improved performance heat exchanger by
innovative design and numerous high performance key parts. High efficiency DC inverter compressor reduces
power consumption by 25%.

New structure enhances mid-frequency performance


Specially designed scroll profile for R410A

More compact, weight reduced by 50%

Advanced permanent magnet DC motor


improves low-frequency band performance

Powerful magnets provide high torque and efficiency and achieve 70% reduction in volume.

Compressor efficiency New DC motor-centralized winding


Efficiency-Rotor Speed Curve

Common DC motor-distributing winding

Centralizing winding

Rotor speed(s-1)
20 40 60 80 100
Distributing winding

Smooth 180 sine wave DC Inverter


Adopting the 180 Sine Wave Inverter to smooth motor rotation greatly improves operating efficiency
compared with traditional sawtooth wave.

Common Sawtooth Wave 180 Sine Wave DC Inverter

10
Features -
Higher Reliability
Cycle duty operation
In one combination, any of the outdoor unit can run as the master unit and master unit can cycle in a period, to
realize the equal lifespan among the outdoor units. As a result extend the system lifespan significantly.

Priority Priority

Priority Priority

Backup operation
In a multiple system, if one module is failed, other modules can be backup instead of the failed one for continuing
operation.

Running state

Stand by state

Fault or stop state

Start backup operation

Precise oil control technology


5 stage oil control technology ensures every outdoor
unit & compressors oil always keep in the safe level,
completely solve the compressor oil lack problem. 2nd stage 4th stage

1st stage: compressor internal oil separate


2nd stage: high efficiency oil separator (separation
efficiency up to 99%)
3rd stage: oil balance technology between compressors 5th stage

1st stage
4th stage: oil balance technology between modules
3rd stage
5th stage: intelligent system oil return program

11
Features -
Enhanced Comfort
Quick warm-up & cool-down design
Fluctuation of room temperature

By utilizing the benefits of the inverter compressor,


the system can reach full load quickly and shorten 1
the warm-up and cool-down times to provide an 2
immediate and comfortable air solution.
Less temperature fluctuation will create a better
living environment.

Cooling operation

Night silent operation mode


High comfort outdoor units multi-choice of silent mode during the night.
Super silent operation mode can reduce sound level further, minimum 46.8dB (A).
Load % Capacity %

Peak value of ambient temp.


Night silent operation will be
100
activated X hours after the peak
temperature during daytime,
and it will go back to normal 50
operation after Y hours.
8hrs 10hrs
Noise dB

-Mode 1X: 6 hours, Y: 10 hours Night silent Mode


noise
-Mode 2X: 8 hours, Y: 10 hours Max.-10dB(10Hp)

-Mode 3X: 6 hours, Y: 12 hours Start End

-Mode 4X: 8 hours, Y: 8 hours 08:00 14:00 22:00 08:00


Notes:
This function can be activated by setting at site. Temperature(load) curve shown in the graph is just an example.

Intelligent defrosting technology


Intelligent defrosting program will judge the defrosting Intelligent defrosting

time according to the system real requirement, reduce


Heating capacity

the heating loss by unnecessary defrosting and make Usual defrosting

the indoor side more comfortable.


Defrosting time can be shortened to 4 min. due to the
specialized defrosting valve. t min t

Time

12
Features -
Unique Fan Characteristics
DC Fan Motor
According to the running load and system pressure, the system controls the speed of DC fan to achieve the
minimum energy consumption and best performance.
Motor speed(RPM)

DC inverter stepless
adjustment

AC inverter
multistep adjustment

System pressure

Fan grille
Optimized fan blade shape with new air outlet grille enhanced air flow volume
which greatly improves fan performance and decreases noise.
Standard 0~20Pa, 20~40Pa to be customised.

New profile fan blade


A new blade with sharp edges and a slight curve increases the airflow rate and lowers vibration and airflow
resistance.

Multi solenoid valves control technology

Multi solenoid valves control technology in one system.


All the solenoid valves equipped in the unit ensure
temperature-control precisely, system running steadily
and economicaly to provide a comfortable environment.

13
Features -
Easier Installation & Service

Simple signal line connection


Centralized controller (TCONTCCM03A/30A) can be connected from indoor side or outdoor side (XYE terminals)
at will. Only one group of communication wire of PQE, achieved both of communication for indoor & outdoor
unit. Its more convenient for communication wiring.

PQ E PQ E PQ E PQ E

XY E X Y E P Q E

Auto addressing

Outdoor unit can distribute addresses for indoor


unit automatically.
Wireless and wired controllers can query and
modify each indoor unit's address.

Compact design for effective use of space

Easy to transport

Compact size and light weight design minimizes the


installation footprint, reduces the installation floor load,
and is easier for transportation. For some projects the
units can even be transported through the elevator or
forklift, reduce access problem at the jobsite.

14
Features -
Easy Selection Software

Selection software
To meet consultants and distributors requirements,
Trane has developed a new program for designing
TVR systems. The software provides quick and
convenient selectable options for users, supports
multiple languages, and greatly improves the selection
process.

Project Load calculation


Contains project information such as project name, Provides two calculation methods: (1)Directly put the
country, location, and detailed climate data to ensure room load, or; (2) Detailed parameters, including
the optimum system is selected. room area, estimated cooling/heating load index,
heating capacity and cooling capacity.

A/C selection Piping drawing


There are 12 types and over 100 models of indoor Displays the detailed layout of an A/C system and
units and all kinds of different power of outdoor units the parameters for piping and branch distributors.
for choosing.

Controller selection Report output


Provides a selection of controllers for indoor units and Outputs a comprehensive selection report as a
outdoor units, including wireless and remote control- Word or XL document.
lers for indoor units.

15
Mini TVR 5G
Mini TVR5G with DC inverter compressor and DC fan motor delivers a highly efficient solution for small
commercial buildings. Four to nine rooms require only one outdoor unit, and individual control is enabled in
each room.

NEW

16
Mini TVR 5G - Features
Wide range
Wide of of
range outdoor units
outdoor units
The outdoor units capacity range from 10.5kW to 18kW which is ideal for small offices, villas,
The outdoor units capacity range from 10.5kW to 18kW which is ideal for small offices, villas,
apartment and shops, making it perfect for commercial and residential application.
apartment and shops, making it perfect for commercial and residential application.
10.5kW 12/14/16/18kW
10.5kW 12/14/16/18kW

Flexible indoor
Flexible units
indoor connection
units connection
MiniMini
TVRTVR
5G with intelligent
5G with control
intelligent gives
control you
gives independent
you independentzoning
zoningcontrol
controlwith
withmaximum
maximum flexibility.
flexibility.
A single outdoor
A single unitunit
outdoor supports up up
supports to nine indoor
to nine units,
indoor freeing
units, freeingupupconsiderable
considerablespace
spaceoutside.
outside. Use your
your
backyard more
backyard wisely
more withwith
wisely muchmuchmore space
more spaceavailable
availablecreated
createdbybyless
lessnumber
numberof
ofoutdoor
outdoor units.
Max.Max.
9 indoor unitsunits
9 indoor for afor18kW outdoor
a 18kW unitunit
outdoor installation
installation
Max.Max.
7 indoor unitsunits
7 indoor for afor16kW outdoor
a 16kW unitunit
outdoor installation
installation
Max.Max. 6 indoor
6 indoor unitsunits
for afor14kW
a 14kW outdoor
outdoor unitunit installation
installation
Max.Max. 6 indoor
6 indoor unitsunits
for afor12kW
a 12kW outdoor
outdoor unitunit installation
installation
Max.Max. 5 indoor
5 indoor unitsunits
for afor10.5kW
a 10.5kW outdoor
outdoor unitunit installation
installation

Mini
Mini VRF
VRF

Wide
Wide operation
operation temperature
temperature range
range
MiniMini
TVRTVR 5G system
5G system operates
operates stably
stably at extreme
at extreme temperaturerange
temperature rangefrom
fromminus
minus15C
15C to
to 43C
43C

COOLING MODE
COOLING MODE
-15C 43C
-15C 43C

HEATING MODE
HEATING MODE
-15C 27C
-15C 27C

-20 -10 0 10 20 30 40 50 C(D.B.)


-20 -10 0 10 20 30 40 Outdoor 50 C(D.B.)
temperature
Outdoor temperature

17
Mini TVR 5G - Features

Flexible piping design


The Mini TVR 5G provides a total piping length possibility of 100m, a maximum height difference between
outdoor and indoor units of 30m. The height difference between indoors unit can be up to 8m. These
generous allowances facilitate an extensive array of system designs.

Permitted value (m)


10.5kW 12/14/16/18kW
Level difference between IDU and ODU is 30m

Actual total piping length*1 100 100

Actual length 45 60
Level difference between IDUs is 8m

The longest piping length is 70m

Piping Longest piping


length Equivalent length 50 70

Equivalent piping length from the


The first branch joint to
The IDU to the nearest

thefarthest IDU is 20m

farthest IDU to the first indoor 20 20


branch joint is 15m

branch joint

Level difference Outdoor unit up 30 30


between indoor
Level and outdoor units Outdoor unit down 20 20
difference

Level difference between indoor units 8 8

*1: Total pipe length is equal to all the liquid pipe or all the gas pipe length.

High COP and EER values


EER COP
3.9 3.92 3.78 4.02 3.97
3.8 3.7 3.8
3.54 3.43 3.56
3.4

8kW 10.5kW 12kW 14kW 16kW 18kW 8kW 10.5kW 12kW 14kW 16kW 18kW

High performance heat exchanger


Reduce air resistance

High efficiency inner-threaded pipe,


New design Original design enhance heat transfer.
Hydrophilic fins + inner-threaded pipes

The new designed window fins enlarge the heat-exchanging area , decrease the air resistance, save more
power and enhance heat exchange performance.
Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency.
The specially coated blue fins enhance durability and protect against corrosion from air, water and other
corrosive agents, assures a longer coil service life.

18
Mini TVR 5G - Features

Easy installation
Easy to transport
Easy installation: No special area is required for outdoor
units.
Easy transportaion: All outdoor units can be transported
by elevator, which greatly simplifies installation and
reduces time and labor.
The Mini TVR 5G indoor and outdoor units are almost as
easy to install as residential air conditioning systems,
making them ideal for small offices and shops.

Space saving design


The Mini TVR 5G units are slimmer and more compact, resulting in significant savings in installation space.
In some large residential and light commercial areas, such as villas, restaurants, usually it need more
than one indoor unit, which in turn requires multiple outdoor units.
Trane's Mini TVR 5G system removes this problem, and retains buildings' original aesthetics.

Auto addressing
Addresses of indoor units can be set automatically by outdoor units.
Wireless controller can inquire and modify every indoor units address.
Outdoor unit can
distribute addresses
to indoor unit.

Shield signal wire

TCONKJR29B TCONTRM05A

19
Mini TVR 5G - Features
More convenience in installation
A four-direction space is available for connecting pipes and wiring in
various installation sites.

Front side Right side Back side Bottom side


Back side

Right side

Front side
Bottom side

More convenient piping connector - branch box


Easier and safer installation thanks to a branch box that simplifies piping work and the adoption of screw connection.
Both left and right pipe flare connectin from outdoor unit to branch box is reserved, which greatly simplifies field installation.
Two sets of pipe size converter are packed with branch box to transfer the pipe size from 6.35mm to 9.53mm
and from 12.7mm to 15.9 mm .
Low noise
The branch pipe is linear expansion design regulates the flow of
refrigerant and reduces the noise. By locating the branch box in the
ceiling or outside ,noise generated by the branch box can be kept
clear of living spaces, thus makes noise level to a minimum.
Brazing-free quick installation
All the piping leading to and from the branch box is connected using screw joints,which can be
installed quickly and easily.
Indoor installation
The branch box can be installed in the ceiling rather than outside. Removing the side and
bottom covers provides easy access for maintaining inner components such as circuit boards.

New piping connection design

20
Mini TVR 5G - Features
Full DC Inverter technology
At the heart of our system, there is a highly intelligent inverter driven compressor. This advanced
technology enables the output of the outdoor unit to be modulated by the cooling or heating demands
of the zone that it controls. This advanced system ensures precise temperature regulation and highly
efficient energy usage, making a significant contribution to the unit,limiting the impact on the environment.
Highly Efficient DC Motor:
- Creative motor core design
- High density neodymium magnet
- Concentrated type stator
-Wider operating frequency range
Better balance and Extremely Low Vibration:
- Twin eccentric cams
- 2 balance weights
Highly Stable Moving Parts:
- Optimal material matching rollers and vanes
-Optimize compressor drive technology
Compressor - Highly robust bearings
(Twin Rotary) structure
-Compact structure

High efficiency DC fan motor saved power up to 50%.


Motor speed(RPM)

DC inverter stepless
adjustment

AC inverter
multistep adjustment

System pressure

Noise reducing design


Optimally designed fan shape and air discharge grille increases air volume and reduces running noise.

Air deflector

New grille

New fan

Newly Designed Fan Guard Powerful Large Propeller

66
21
Mini TVR 5G -
Outdoor Unit Specifications
Model 4TVV0042AK000AA 4TVV0048AK000AA 4TVV0055AK000AA

Power supply V/Ph/Hz 380-415/3/60


Cooling Capacity kW 12.0 14.0 15.5
RT 3.4 3.9 4.3
kBtu/h 41.0 48.0 52.9
kcal/h 10,320 12,040 13,330
Power input kW 3.25 3.95 4.52
EER kW/kW 3.69 3.54 3.43
Heating Capacity kW 13.2 15.4 17.0
RT 3.7 4.3 4.8
kBtu/h 45.0 52.5 58.0
kcal/h 11,352 13,244 14,620
Power input kW 3.47 4.16 4.77
COP kW/kW 3.80 3.70 3.56
Connectable Total capacity % 50 50 50
indoor unit Max. quantity 6 6 7
Sound pressure level dB(A) 57 57 57
Pipe connections Liquid pipe in.(mm) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53)
Gas pipe in.(mm) 5/8( 15.9) 5/8( 15.9) 3/4( 19.1)
Full DC Inverter

Fan motor Type DC DC DC


Quantity 2 2 2
Air flow rate m3/h 6,000 6,000 6,000
CFM 3,531 3,531 3,531
Motor output W 852 852 852
Compressor Type Rotary Rotary Rotary
Quantity 1 1 1
Capacity kW 9.88 9.88 13.98
kBtu/h 33.7 33.7 47.7
Crankcase heater W 25 25 25
Oil type FV50S FV50S FV50S
Oil charge gal.(ml) 0.23(870) 0.23(870) 0.37(1400)
Refrigerant Type R410A R410A R410A
Factory charging Ibs.(kg) 7.3(3.3) 8.6(3.9) 8.6(3.9)
Design pressure (High/Low) MPa 4.4/2.6 4.4/2.6 4.4/2.6
PSI 640/380 640/380 640/380
Net dimension (WHD) inch 35-7/1452-1/415-3/4
mm 9001327400
Packing size (WHD) inch 40-35/6457-21/6417-1/8
mm 10301456435
Net weight lbs.(kg) 203(92) 209(95) 225(102)
Gross weight Ibs.(kg) 234(106) 234(106) 249(113)
Operating Cooling F(C) 5~118.4(-15~48)
temperature range Heating F(C) 5~80.6(-15~27)
Note:
1. The cooling conditions: indoor temp.: 27C DB(80.6 F), 19C WB(60F) outdoor temp.: 35C DB(95F) equivalent pipe length: 5m drop length: 0m.
2. The heating conditions: indoor temp.: 20C DB(68F), 15C WB(44.6F) outdoor temp.: 7 C DB(42.8F) equivalent pipe length: 5m drop length: 0m.
3. Sound level: Anechoic chamber conversion value, measured at a point 1 m(3.28ft) in front of the unit at a height of *m( 1m(3.28ft) for 105 model,1.2m(3.94ft) for 120~160model). During
actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. The above data may be changed without notice for future improvement on quality and performance.

59

22
Mini TVR 5G -
Outdoor Unit Specifications
Model 4TVV0036A1000AA 4TVV0042A1000AA 4TVV0048A1000AA 4TVV0055A1000AA 4TVV0060A1000AA

Power supply V/Ph/Hz 208-230/1/60


Cooling Capacity kW 10.5 12.0 14.0 15.5 17.5
RT 2.9 3.4 3.9 4.3 4.98
kBtu/h 35.8 41.0 48.0 52.9 59.7
kcal/h 9,030 10,320 12,040 13,330 15,050
Power input kW 2.68 3.25 3.95 4.52 5.30
EER kW/kW 3.92 3.69 3.54 3.43 3.30
Heating Capacity kW 11.5 13.2 15.4 17.0 19.0
RT 3.2 3.7 4.3 4.8 5.4
kBtu/h 39.2 45.0 52.5 58.0 64.8
kcal/h 9,890 11,352 13,244 14,620 16,340
Power input kW 2.90 3.47 4.16 4.77 5.00
COP kW/kW 3.97 3.80 3.70 3.56 3.80
Connectable Total capacity % 50 50 50 50 50
indoor unit Max. quantity 5 6 6 7 9
Sound pressure level dB(A) 57 57 57 57 59
Pipe connections Liquid pipe in.(mm) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53)
Gas pipe in.(mm) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9) 3/4( 19.1) 3/4( 19.1)

Mini VRF
Fan motor Type DC DC DC DC DC
Quantity 1 2 2 2 2
Air flow rate m3/h 5,100 6,000 6,000 6,000 6,800
CFM 3,000 3,531 3,531 3,531 4,002
Motor output W 170 852 852 852 1002
Compressor Type Rotary Rotary Rotary Rotary Rotary
Quantity 1 1 1 1 1
Capacity kW 7.13 9.88 9.88 13.98 13.98
kBtu/h 24.3 33.7 33.7 47.7 47.7
Crankcase heater W 25 25 25 25 25
Oil type FV50S FV50S FV50S FV50S FV50S
Oil charge gal.(ml) 0.18(670) 0.23(870) 0.23(870) 0.37(1400) 0.37(1400)
Refrigerant Type R410A R410A R410A R410A R410A
Factory charging Ibs.(kg) 6.6(3.0) 7.3(3.3) 8.6(3.9) 8.6(3.9) 9.9(4.5)
Design pressure (High/Low) MPa 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6
PSI 640/380 640/380 640/380 640/380 640/380
Net dimension (WHD) inch 42-5/1638-1/3215-19/32 35-7/1452-1/415-3/4 35-7/1452-1/412.598
mm 1075966396 9001327400 9001327320
Packing size (WHD) inch 44-3/3243-5/1617-1/8 40-35/6457-21/6417-1/8
mm 11201100435 10301456435
Net weight lbs.(kg) 172(78) 203(92) 209(95) 225(102) 225(107)
Gross weight Ibs.(kg) 187(85) 234(106) 234(106) 249(113) 249(118)
Operating Cooling F(C) 5~118.4(-15~48)
temperature range Heating F(C) 5~80.6(-15~27)
Note:
1. The cooling conditions: indoor temp.: 27C DB(80.6F), 19C WB(60 F) outdoor temp.: 35C DB(95F) equivalent pipe length: 5m drop length: 0m.
2. The heating conditions: indoor temp.: 20C DB(68C), 15C WB(44.6F) outdoor temp.: 7C DB(42.8F ) equivalent pipe length: 5m drop length: 0m.
3. Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of *m(0.9m for 80model, 1m for 105 model,1.2m for 120~160model). During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
4. The above data may be changed without notice for future improvement on quality and performance.
23
Mini TVR 5G -
Outdoor Unit Specifications
Model 4TVV0068AK000AA 4TVV0077AK000AA 4TVV0089AK000AA

Power supply V/Ph/Hz 380-415/3/60

Cooling Capacity kW 20.0 22.4 26.0

RT 5.7 6.4 7.4

Power input kW 6.1 6.8 7.6

EER kW/kW 3.28 3.29 3.42

Heating Capacity kW 22.0 24.5 28.5

RT 6.3 7 8.1

Power input kW 6.1 5.9 6.8

COP kW/kW 3.61 4.15 4.19

Connectable indoor unit Total capacity % 50-130 50-130 50-130

Max. quantity 10 11 12

Sound pressure level dB(A) 59 59 60

Pipe connections Liquid pipe mm 9.53 9.53 9.53

Gas pipe mm 19.1 19.1 22.2

Fan motor Type DC

Quantity 2

Air flow rate m3/h 10,999 10,494 10,494

Motor output W 210+160 200+150 200+150

Rotary compressor Quantity 1 1 1

Capacity kW 13.98 16.86 16.86

Crankcase heater W 25 25 25

Oil type FV50S FV50S FV50S

Oil charge ml 1400 1700 1700

Refrigerant Type R410A R410A R410A

Factory charging kg 4.8 6.2 6.2

Design pressure (High/Low) MPa 4.4/2.6

Net dimension (WHD) mm 1,1201,558528

Packing size (WHD) mm 1,2701,720565

Net weight kg 137 146.5 147

Gross weight kg 153 162.5 163

Operating Cooling C -15~46


temperature range
Heating C -15~24

Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC DB/19oC WB; Outdoor temperature 35oC DB/24oC WB.
Heating: Indoor temperature 20oC DB/15oC WB; Outdoor temperature 7oC DB/6oC WB.
Piping length: Interconnecting piping length is 7.5m, level difference is zero.
Sound values are measured in a semi-anechoic room, at a position 1m in front of the unit and 1.3m above the floor.

24
Mini TVR 5G -
Outdoor Unit Dimensions

10.5kW Unit: mm

624
966

396
366
336
354

990

1075

12/14/16/18kW

600
1327

360
400
320
348

900

25
Mini TVR 5G -
Outdoor Unit Dimensions
2. Dimensions
4TVV0068AK000AA 4TVV0077AK000AA 4TVV0089AK000AA
Unit:
2. mmDimensions
4TVV0068AK000AA 4TVV0077AK000AA 4TVV0089AK000AA
Unit: mm
1558
1558

1120

668 205.8
1120
494
528
414
400

668 205.8
494
528
414
400

26
TVR 5G(All Inverter)

TVR 5G (All Inverter) achieve worlds largest capacity of 72HP with the industry's top class energy
efficiency of cooling and heating. It supports a long piping length of 1000m and a longer level
difference of 110m, making it perfect for big-sized and high-rise buildings for wide application.

27
TVR 5G(All Inverter) -
Recommended Combination Table
No of Outdoor Unit Combination Maximum No Capacity (kW)
Model No of
Outdoor of Connectable
Compressors 8HP 10HP 12HP 14HP 16HP 18HP* Cooling Heating
Units Indoor Units

8HP 1 1 1 13 25.2 27

10HP 1 1 1 16 28 31.5

12HP 1 2 1 20 33.5 37.5

14HP 1 2 1 23 40 45

16HP 1 2 1 26 45 50

18HP 1 2 1 29 50 56

20HP 2 2 2 33 56 63

22HP 2 3 1 1 36 61.5 69

24HP 2 3 1 1 39 68 76.5

26HP 2 3 1 1 43 73 81.5

28HP 2 3 1 1 46 78 87.5

30HP 2 4 1 1 50 85 95

32HP 2 4 1 1 53 90 101

34HP 2 4 1 1 56 95 106

36HP 2 4 2 59 100 112

38HP 3 4 2 1 63 106 119

40HP 3 5 1 1 1 64 113 126.5

42HP 3 5 3 64 120 135

44HP 3 5 1 1 1 64 123 137.5

46HP 3 5 1 2 64 128 143.5

48HP 3 6 1 1 1 64 135 151

50HP 3 6 1 2 64 140 157

52HP 3 6 1 2 64 145 162

54HP 3 6 3 64 150 168

56HP 4 6 2 2 64 156 175

58HP 4 7 1 1 1 1 64 163 182.5

60HP 4 7 1 1 2 64 168 188.5

62HP 4 7 1 1 2 64 173 193.5

64HP 4 7 1 3 64 178 199.5

66HP 4 8 1 1 2 64 185 207

68HP 4 8 1 3 64 190 213

70HP 4 8 1 3 64 195 218

72HP 4 8 4 64 200 224

Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC DB/19oC WB; Outdoor temperature 35oC DB/24oC WB.
Heating: Indoor temperature 20oC DB/15oC WB; Outdoor temperature 7oC DB/6oC WB.
Piping length: Interconnecting piping length is 7.5m, level difference is zero.
The above combination models are factory-recommended models.
*18HP model can be customized.

28
TVR 5G(All Inverter) - Features
Wide range of outdoor units
The outdoor units capacity range from 8HP up to 72HP in 2HP increment. Maximum 64 indoor units
with capacity up to 130% of total outdoor units can be connected in one refrigeration system.

8, 10HP 12, 14, 16HP 18HP 20, 22, 24, 26, 28, 30, 32, 34, 36HP

38, 40, 42, 44, 46, 48, 50, 52, 54HP 56, 58, 60, 62, 64, 66, 68, 70, 72HP

Large connectable indoor units quantity


The large quantity of connectable units is suitable for large buildings and projects.

65 63 64
59
60 56
55
53
50
50 46
45 43
39
40 36
35 33
29
30 26
25 23
20
20
16
15
13
10
5

8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40-72HP

29
25
TVR 5G(All Inverter) - Features
Wide operation range

COOLING MODE
-5C Outdoor Temperature 48C

V4 Plus S Series
HEATING MODE*
-20C Outdoor Temperature 24C

-2 0 -1 0 0 10 20 30 40 50
Outdoor temperature (DB)

The TVR 5G (All Inverter) system operates stably at extreme temperatures ranging from -20C
. to 48C

Long piping length


Permitted
value (m)

Actual total piping length 1000*


Level difference between IDU-ODU is 110m

Actual length 175


Piping
Longest actual piping length 175m

Longest piping
length
Equivalent length 200

Equivalent piping length from the farthest


40/90*
between IDU-IDU is 30m

IDU to the first indoor branch joint

Outdoor unit up 70
Level difference

Level difference between


90m

Level indoor and outdoor units


Outdoor unit down 110
difference

Level difference between indoor units 30

*Total pipe length is equal to two times pipe length plus pipe length.
*When the piping length from the farthest IDU to the first indoor branch joint is
more than 40m, it needs to meet specific conditions according to the installation
part of the technical manual to achieve 90m.

High external static pressure


A standard 0-20Pa external static pressure is equipped by default
for all outdoor units. 20-40Pa can be customized for other 40Pa

modules.

30
26
TVR 5G(All Inverter) - Features
High COP/EER values
The cooling EER up to 4.29 and the heating COP up to 4.39 in the 8HP catagory.
EER COP
4.29 4.39 4.17 4.17
3.97 4.02 3.91 3.89
3.81
3.54 3.5 3.38

8HP 10HP 12HP 14HP 16HP 18HP 8HP 10HP 12HP 14HP 16HP 18HP

All DC inverter technology

All DC inverter compressors make the capacity output better distributed.

All DC Inverter Compressors

New structure enhances mid-frequency performance


Specially designed scroll profile for R410A

More compact, weight reduced by 50%

Advanced permanent magnet DC motor improves


the low frequency band performance

All DC Fan Motors

According to the running load and system pressure, the system controls the speed of DC fan to achieve the
minimum energy consumption and best performance.
Motor speed(RPM)

DC inverter stepless
adjustment

AC inverter
multistep adjustment

System pressure

31
TVR 5G(All Inverter) - Features
High performance heat exchanger
New design Original design
Windage& air flow

Relative windage resistance


0.8

0.6

0.4
Original design

V4 Plus S Series
Reduce
0.2
Reduce air resistance. 28% New design
0
0 200 400 600 800 1000 Re

Frost contrast

Relative windage resistance 0.8 Reduce


High efficiency inner-threaded pipe, 30%
enhance heat transfer. 0.6 Original design
0.4

0.2 New design


0
0 0.2 0.4 0.6 0.8 1
Relative frosting rate

Hydrophilic film fins + inner-threaded pipes

The new designed window fins enlarge the heat-exchanging area , decrease the air resistance, save more power
and enhance heat exchange performance.
Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency.

Original design

Gas Liquid

New design

Gas Liquid

Gas Gas Gas-Liquid Liquid Liquid Common Sub-cooling


Design Technology

Increase the hot liquid rate in the condenser


Improve the heat-exchange efficiency

Previous Design Delta () Simulation Design

Innovative designed high efficiency heat exchanger, which can reach up to 12C subcooling degree,
reduces the system resistance and improves reliability.
When the outdoor temperature is 35C, the refrigerant can be cooled down to 37.1C, thus achieving high
heat-exchanging efficiency with only 2.1C temperature difference.

32
TVR 5G(All Inverter) - Features
Night silent operation mode
High comfort outdoor units multi-choice of silent mode during the night.
Super silent operation mode can reduce sound level further, minimum 45dB (A).
Load % Capacity %

Peak value of ambient temp.


Night silent operation will be
100
activated X hours after the peak
temperature during daytime,
and it will go back to normal 50
operation after Y hours.
8hrs 10hrs
Noise dB

-Mode 1X: 6 hours, Y: 10 hours Night silent Mode


noise
-Mode 2X: 8 hours, Y: 10 hours Max.-10dB(10Hp)

-Mode 3X: 6 hours, Y: 12 hours Start End

-Mode 4X: 8 hours, Y: 8 hours 08:00 14:00 22:00 08:00


Notes:
This function can be activated by setting at site. Temperature(load) curve shown in the graph is just an example.

Intelligent defrosting technology


Intelligent defrosting

Intelligent defrosting program will judge the defrosting


time according to the system real requirement, reduce
Heating capacity

Usual defrosting
the heating loss by unnecessary defrosting and make
the indoor side more comfortable.
Defrosting time can be shortened to 4 min. due to the
t min t
specialized defrosting valve.
Time

Simple signal line connection


Centralized controller (TCONTCCM03A or TCONTCCM30A) can be connected from indoor side or outdoor
(XYE terminals) at will. Only one group of communication wire of PQE, achieved both of communication
for side indoor & outdoor unit. Its more convenient for communication wiring.

PQ E P Q E P Q E P Q E

X Y E X Y E P Q E

Auto addressing
Outdoor unit can distribute addresses for indoor
unit automatically.
Wireless and wired controllers can query and
modify each indoor unit's address.

33
TVR 5G(All Inverter) -
Outdoor Unit Specifications
Model 4TVV0086BK000AA 4TVV0096BK000AA 4TVV0115BK000AA

Power supply V/Ph/Hz 380-415/3/60 380-415/3/60 380-415/3/60


Cooling Capacity kW 25.2 28.0 33.5
RT 7.2 8.0 9.5
kBtu/h 86.0 95.5 114.3
kcal/h 21,672 24,080 28,810
Power input kW 5.88 7.05 8.79
EER kW/kW 4.29 3.97 3.81

V4 Plus S Series
Heating Capacity kW 27 31.5 37.5
RT 7.7 9.0 10.7
kBtu/h 92 108 128
kcal/h 23,220 27,090 32,250
Power input kW 6.15 7.554 8.993
COP kW/kW 4.39 4.17 4.17
Connectable indoor unit Total capacity % 50-130 50-130 50-130
Max. quantity 13 16 20
Sound pressure level dB(A) 57 57 59
Pipe connections Liquid pipe in.(mm) 3/8( 9.53) 1/2( 12.7)
Gas pipe in.(mm) 7/8( 22.2) 1( 25.4)
Oil balance pipe in.(mm) 1/4( 6) 1/4( 6)
Fan motor Type DC DC
Quantity 1 1+1
Air flow rate m3/h 11,242 13,000
CFM 6,611 7,645
Motor output W 750 560+380
ESP in.WG(Pa) 0-0.08(0-20)(default) 0-0.08(0-20)(default)
in.WG(Pa) 0.08~0.16(20-40)(customized) 0.08~0.24(20-40)(customized)
DC inverter compressor Quantity 1 1+1
Capacity kW 31.59 31.59+11.80
kBtu/h 107.8 107.8+40.3
Crankcase heater W 27.62 27.622
Oil type FVC68D FVC68D
Oil charge gal.(ml) 0.132(500) 0.132(500)+0.132(500)
Refrigerant Type R410A R410A
Factory charging Ibs.(kg) 22(10) 26.5(12)
Design pressure (High/Low) MPa 4.4/2.6 4.4/2.6
PSI 640/380 640/380
Net dimension (WHD) inch 37-25/3263-9/1630-1/8 49-7/3263-9/1630-1/8
mm 9601,615765 1,2501,615765
Packing size (WHD) inch 40-3/870-1/232-11/16 51-3/870-15/3232-9/32
mm 1,0251,790830 1,3051,790820
Net weight lbs.(kg) 466(212) 634(288)
Gross weight Ibs.(kg) 499(227) 678(308)
Operating temperature range Cooling F(C) 23~118.4(-5~48)
Heating F(C) -4~75.2(-20~24)

Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC(80.6oF) DB/19oC(66.2oF) WB; Outdoor temperature 35oC(95oF) DB/24oC(75.2oF) WB.
Heating: Indoor temperature 20oC(68oF) DB/15oC(59oF) WB; Outdoor temperature 7oC(44.6oF) DB/6oC(42.8oF) WB.
Piping length: Interconnecting piping length is 7.5m(24.6ft.), level difference is zero.
Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90m(295.2ft.). When the total equivalent liquid length is more than 90m(295.2ft.),
please refer to technical manual to choose the connection piping diameter.
Sound values are measured in a semi-anechoic room, at a position 1m(3.28ft.) in front of the unit and 1.3m(4.264ft.) above the floor.

34
TVR 5G(All Inverter) -
Outdoor Unit Specifications
380~415V-3Ph-60Hz
Model 4TVV0140BK000AA 4TVV0155BK000AA 4TVV0182BK000AA

Power supply V/Ph/Hz 380-415/3/60 380-415/3/60 380-415/3/60


Cooling Capacity kW 40.0 45.0 50.0
RT 11.4 12.8 14.2
kBtu/h 136.5 153.5 170.5
kcal/h 34,400 38,700 43,000
Power input kW 11.30 13.25 14.79
EER kW/kW 3.54 3.40 3.38
V4 Plus S Series

Heating Capacity kW 45.0 50.0 56.0


RT 12.8 14.2 15.9
kBtu/h 153.5 170.6 191.0
kcal/h 38,700 43,000 48,160
Power input kW 11.19 12.79 14.40
COP kW/kW 4.02 3.91 3.89
Connectable indoor unit Total capacity % 50-130 50-130 50-130
Max. quantity 23 26 29
Sound pressure level dB(A) 61 62 62
Pipe connections Liquid pipe in.(mm) 1/2( 12.7) 1/2( 12.7) 5/8( 15.9)
Gas pipe in.(mm) 1( 25.4) 1-1/8( 28.6) 1-1/8( 28.6)
Oil balance pipe in.(mm) 1/4( 6) 1/4( 6) 1/4( 6)
Fan motor Type DC
Quantity 1+1
Air flow rate m3/h 15,620
CFM 9,185
Motor output W 560+380
ESP in.WG(Pa) 0-0.08(0-20)(default)
in.WG(Pa) 0.08~0.16(20-40)(customized)
DC inverter compressor Quantity 1+1
Capacity kW 31.59+11.80
kBtu/h 107.8+40.3
Crankcase heater W 27.622
Oil type FVC68D
Oil charge gal.(ml) 0.132(500)+0.132(500)
Refrigerant Type R410A
Factory charging Ibs.(kg) 33.1(15) 37.5(17)
Design pressure (High/Low) MPa 4.4/2.6
PSI 640/380
Net dimension (WHD) inch 49-7/3263-9/1630-1/8
mm 1,2501,615765
Packing size (WHD) inch 51-3/870-15/3232-9/32
mm 1,3051,790820
Net weight lbs.(kg) 634(288) 683(310)
Gross weight Ibs.(kg) 678(308) 728(330)
Operating temperature range Cooling F(C) 23~118.4(-5~48)
Heating F(C) -4~75.2(-20~24)

Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC(80.6oF) DB/19oC(66.2oF) WB; Outdoor temperature 35oC(95oF) DB/24oC(75.2oF) WB.
Heating: Indoor temperature 20oC(68oF) DB/15oC(59oF) WB; Outdoor temperature 7oC(44.6oF) DB/6oC(42.8oF) WB.
Piping length: Interconnecting piping length is 7.5m(24.6ft.), level difference is zero.
Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90m(295.2ft.). When the total equivalent liquid length is more than 90m(295.2ft.),
please refer to technical manual to choose the connection piping diameter.
Sound values are measured in a semi-anechoic room, at a position 1m(3.28ft.) in front of the unit and 1.3m(4.264ft.) above the floor.
*18HP model can be customized.

35
TVR 5G(All Inverter) -
Outdoor Unit Dimensions
Dimension Unit: mm

8/10 HP 12/14/16 /18 HP

1615
1615

960
1250
765

765

Installation dimension

Unit: mm

Screw bolt position


8/10HP: 960
12/14/16/18HP: 1250
8/10HP: 830
12/14/16/18HP: 1120
10 Expansion bolt
Rubber shocking
proof mat Concrete
basement
765
736

Solid ground h=200


or roofing
200

1523long U-shape hole

36
TVR 5G (Heat Recovery/3pipes)

The all DC inverter TVR 5G (Heat Recovery/3pipes) series, which can offers simultaneous cooling and heating
operation in one system. The energy by-product from cooling or heating is transferred to where it is required by
using the balanced heat exchanger function, which saves up to 50% in costs compared with a conventional
heat pump system.

Offers simultaneous cooling and


heating operation in one system

37
TVR 5G (Heat Recovery/3pipes)
Recommended Combination Table
No of Outdoor Unit Combination Maximum No Capacity (kW)
Model No of
Outdoor of Connectable
Compressors
Units 8HP 10HP 12HP 14HP 16HP Indoor Units Cooling Heating

8HP 1 1 1 13 25.2 27

10HP 1 1 1 16 28 31.5

12HP 1 1 1 20 33.5 37.5

14HP 1 2 1 23 40 45

16HP 1 2 1 26 45 50

18HP 2 2 1 1 29 53.2 58.5

20HP 2 2 2 33 56 63

V4 Plus R Series
22HP 2 2 1 1 36 61.5 69

24HP 2 3 1 1 39 68 76.5

26HP 2 3 1 1 43 73 81.5

28HP 2 4 2 46 80 90

30HP 2 4 1 1 50 85 95

32HP 2 4 2 53 90 100

34HP 3 4 2 1 56 96 108

36HP 3 4 2 1 59 101 113

38HP 3 4 1 1 1 63 106.5 119

40HP 3 5 1 1 1 64 113 126.5

42HP 3 6 3 64 120 135

44HP 3 6 2 1 64 125 140

46HP 3 6 1 2 64 130 145

48HP 3 6 3 64 135 150

50HP 4 6 1 1 2 64 143.2 158.5

52HP 4 6 2 2 64 146 163

54HP 4 6 1 1 2 64 151.5 169

56HP 4 7 1 1 2 64 158 176.5

58HP 4 8 3 1 64 165 185

60HP 4 8 2 2 64 170 190

62HP 4 8 1 3 64 175 195

64HP 4 8 4 64 180 200

Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC DB/19oC WB; Outdoor temperature 35oC DB/24oC WB.
Heating: Indoor temperature 20oC DB/15oC WB; Outdoor temperature 7oC DB/6oC WB.
Piping length: Interconnecting piping length is 7.5m, level difference is zero.
The above combination models are factory-recommended models.

38
TVR 5G (Heat Recovery/3pipes)
Features
Wide range of outdoor units
The outdoor units capacity range from 8HP up to 64HP in 2HP increment. Maximum 64 indoor units with
capacity up to 130% of total outdoor units can be connected as one refrigeration system.

8, 10, 12, 14, 16HP 18-32HP

34-48HP 50-64HP

Long piping length


The solution supports an incredible piping length of 1,000m and level difference of 110m, making it perfect for
large projects. Permitted
value (m)

Actual total piping length 1000*

Actual length 175


Level difference between IDU~ODU 110m
Longest actual piping length 175m

Longest piping
Piping
Equivalent length 200
length
Equivalent piping length from the farthest
40/90*
IDU to the first indoor branch joint
between IDU~IDU 30m

Equivalent piping length from MS to its


40
downstream indoor unit
Level difference

Outdoor unit up 70
90m

Level difference between


Level indoor and outdoor units
Outdoor unit down 110
difference

Level difference between indoor units 30

*Total pipe length is equal to two times pipe length plus pipe length.
*When the piping length from the farthest IDU to the first indoor branch joint is
39
more than 40m, it needs to meet specific conditions according to the installation
part of the technical manual to achieve 90m.
TVR 5G (Heat Recovery/3pipes)
Features
Wide operation temperature range

Cooling Mode
-5C 48C

Heating Mode
-20C 24C

Simultaneous Cooling and Heating Mode


-5C 24C

-20 -10 0 10 20 30 40 50
Outdoor temperature (DB)

The TVR 5G (Heat Recovery/3Pipes) series system operates stably at extreme temperatures ranging
from -20C to 48C

High external static pressure


A standard 0-20Pa external static pressure is equipped by default
for all outdoor units. 20-40Pa can be customized for other 40 Pa

modules.

High Efficiency
High EER
Heat recovery is achieved by diverting exhaust heat from indoor units in cooling mode to areas requiring
heating, maximising energy efficiency, reducing electricity costs and leading to high partload efficiencies (up to
7.0 in the 8HP catagory).
EER 7.0
7.0

8HP, up to 7.0
6.0 10HP, up to 6.8
12HP, up to 6.7
14HP, up to 6.5
EER

5.0 16HP, up to 6.5

4.0

3.0
75% cooling 50% cooling 25% cooling
100% cooling 100% heating
25% heating 50% heating 75% heating
EER in simultaneous cooling and heating mode are based on the following condition:
Outdoor temperature 7CDB/6CWB, indoor temperature 27CDB/19CWB for cooling, indoor temperature 20CDB for heating.
36

High
HighCOP/EER
COP/EERvalues
values
The cooling EER up to 4.40 and the heating COP up to 4.50 in the 8HP catagory.

COP
EER 4.50
4.40 4.20 4.30 4.30
4.15 4.02 3.91
3.54 3.40

8HP 10HP 12HP 14HP 16HP 8HP 10HP 12HP 14HP 16HP

40
TVR 5G (Heat Recovery/3pipes)
Features
All DC inverter technology
All DC inverter compressors make the capacity output better distributed.

All DC Inverter Compressors


New structure enhances mid-frequency performance
Specially designed scroll profile for R410A

More compact, weight reduced by 50%

Advanced permanent magnet DC motor improves


the low frequency band performance

According to the running load and system pressure, the system controls the speed of DC fan to achieve the
minimum energy consumption and best performance.
All DC Fan Motors
Motor speed(RPM)

DC inverter stepless
adjustment

AC inverter
multistep adjustment

System pressure

Heat recovery, more efficiency


Simultaneous heating and cooling in different zones, more energy saving by heat recovery from one space to
another which saves up to 50% in costs compared with a conventional heat pump system.
Cooling
Power
Heating
consumption
No power
consumption
for heat
recovery

Simultaneous Cooling and Heating Operation

2-pipe system 3-pipe system

Heating capacity automatic adjustment


Two parts condenser individual design, the unit can distribute a part of evaporator to be as condensing area
according to the heating load requirement to improve the utilization rate of the condenser.

Cooling Cooling Cooling Cooling Heating Heating


14kW 14kW 14kW 14kW 14kW 14kW
(47.8kBtu/h) (47.8kBtu/h) (47.8kBtu/h) (47.8kBtu/h) (47.8kBtu/h) (47.8kBtu/h)
Partial Using

41
TVR 5G (Heat Recovery/3pipes
Features
Enhanced Comfort

Cooling and heating simultaneous


Simultaneous cooling and heating achieved for new designed TMS (Mode Switch) equipment.
The outdoor unit individual controls the operation mode of each group indoor
unit to achieve simultaneous heating and cooling in one system under the MS
equipment which adopts solenoid valve to precise control refrigerant flow rate.

The indoor units connect to the same TMS can realize simultaneous cooling and
heating operation.

cooling cooling heating heating


Max. 4 Indoor Units Max. 4 Indoor Units

cooling cooling heating heating cooling


Max. 4 Indoor Units

heating heating cooling heating cooling heating cooling cooling


Max. 4 Indoor Units Max. 4 Indoor Units

Auto mode control


At the auto mode, the indoor unit can change the operation mode, to control the indoor side temperature at a
constant temperature demanded. Setting temperature Ts Indoor temperature Ti
Temperature

Unit change to cooling mode at daytime,


when indoor temperature is higher than
setting temperature, and change to
TiTs TiTs
heating mode at nighttime, when indoor Cooling mode Heating mode
temperature is lower than setting temp.

Mode change automatically

Continuous heating during defrost operation


Each heat exchanger is defrosted by using heat transferred from one heat exchanger to the other in the outdoor
unit. Defrost has no impact on the indoor unit on heating mode.
Outdoor Unit Outdoor Unit Outdoor Unit
Heat Exchanger 1 Heat Exchanger 1 Heat Exchanger 1

Heat

Heat
Heat Exchanger 2 Heat Exchanger 2 Heat Exchanger 2
Heating Defrosting heat exchanger 1 Defrosting heat exchanger 2

42
TVR 5G (Heat Recovery/3pipes)
Features
Easier Installation and Service
Remote addressing
Addressing indoor units are able to be done just by pressing the
button of the controller.
No need to set the address by the DIP switch one by one.
Wired controller and wireless controller can enquire and modify
Remote addressing
every indoor units address.

Simple communication wiring


Centralized controller (TCONTCCM03A) can connect from indoor side or outdoor side (XYE terminals) at will.
Only one group of communication wire of PQE, achieved both of communication for indoor & outdoor unit and
network. Its more convenient for communication wiring.

X, Y, E
H1, H2, E

P, Q, E P, Q, E

P, Q, E P, Q, E P, Q, E P, Q, E P, Q, E P, Q, E

Professional structure design for easy maintainence


The check window reserved on electric control box provides a convenient spot checking and status enquiry.
With the 4 bits digital tube LED display, it is very convenient to show the data of the system, such as pressure,
compressor frequency, error code, discharge temperature etc., which can make the maintenance, installation
and commissioning easier.

Compressor is near the outside, and there is simple pipe system for convenient maintenance.
The newly designed rotating control box is so excellent that it can rotate in a wide angle.
It is convenient for the inspection and maintenance of the pipeline system and greatly reduced the time of
dismount the electric control box.

Rotating electric
control box

Outer layout compressor


and simple pipe system

43
TVR 5G (Heat Recovery/3pipes)
4TVV0140BK000AA
Outdoor Unit Specifications
4TVV0165BK000AA
380~415V-3Ph-60Hz
Model 4TVR0086BK000AA 4TVR0096BK000AA 4TVR0115BK000AA 4TVR0140BK000AA 4TVR0155BK000AA

Power supply V/Ph/Hz 380-415/3/60


Cooling Capacity kW 25.2 28.0 33.5 40.0 45.0
RT 7.2 8.0 9.5 11.4 12.8
kBtu/h 86.0 95.5 114.3 136.5 153.5
kcal/h 21,672 24,080 28,810 34,400 38,700
Power input kW 5.73 6.67 8.07 11.30 13.24
EER kW/kW 4.40 4.20 4.15 3.54 3.40
Heating Capacity kW 27.0 31.5 37.5 45.0 50.0

V4 Plus R Series
RT 7.7 8.9 10.7 12.8 14.2
kBtu/h 92.1 107.5 128.0 153.5 170.6
kcal/h 23,220 27,090 32,250 38,700 43,000
Power input kW 6.00 7.33 8.72 11.19 12.79
COP kW/kW 4.50 4.30 4.30 4.02 3.91
Connectable Total capacity % 50-130 50-130 50-130 50-130 50-130
indoor unit Max. quantity 13 16 20 23 26
Sound pressure level dB(A) 57 57 58 60 60
Pipe Liquid pipe in.(mm) 3/8(9.53) 1/2(12.7) 1/2(12.7) 5/8(15.9) 5/8(15.9)
connections Low pressure gas pipe in.(mm) 7/8(22.2) 7/8(22.2) 1(25.4) 1-1/8(28.6) 1-1/8(28.6)
High pressure gas pipe in.(mm) 3/4(19.1) 3/4(19.1) 3/4(19.1) 7/8(22.2) 7/8(22.2)
High pressure gas balance pipe in.(mm) 3/4(19.1) 3/4(19.1) 3/4(19.1) 3/4(19.1) 3/4(19.1)
Oil balance pipe in.(mm) 1/4(6) 1/4(6) 1/4(6) 1/4(6) 1/4(6)
Fan motor Type DC
Quantity 2 2 2 2 2
Air flow rate m3/h 12,000 12,000 13,000 15,000 15,000
CFM 7,060 7,060 7,650 8,830 8,830
Motor output W 420 420 420 750 750
ESP in.WG(Pa) 0~0.08(0~20) (default) 0~0.08(0~20) (default)
in.WG(Pa) (0.08~0.24)(20~40) (customized) (0.08~0.16)(20~40) (customized)
DC inverter Quantity 1 2
compressor Capacity kW 31.59 31.59+11.8
kBtu/h 107.8 107.8+40.3
Crankcase heater W 302 304
Oil type FVC68D FVC68D
Oil charge gal.(ml) 0.132(500) 0.132+0.132(500+500)
Refrigerant Type R410A R410A
Factory charging Ibs.(kg) 22(10) 28.6(13)
Design pressure (High/Low) MPa 4.4/2.6
PSI 640/380
Net dimension (WHD) inch 49-7/3263-9/1630-1/8
mm 12501615765
Packing size (WHD) inch 51-9/1670-1/232-1/2
mm 13051790820
Net weight Ibs.(kg) 561(255) 561(255) 561(255) 666.6(303) 666.6(303)
Gross weight Ibs.(kg) 600.6(273) 600.6(273) 600.6(273) 708.4(322) 708.4(322)
Operating Cooling F(C) 23~118.4(-5~48)
temperature range Heating F(C) -4~75.2(-20~24)
Simultaneous Cooling and Heating F(C) 23~75.2(-5~24)

Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC(80.6oF) DB/19oC(66.2oF) WB; Outdoor temperature 35oC(95oF) DB/24oC(75.2oF) WB.
Heating: Indoor temperature 20oC(68oF) DB/15oC(59oF) WB; Outdoor temperature 7oC(44.6oF) DB/6oC(42.8oF) WB.
Piping length: Interconnecting piping length is 7.5m(24.6ft.), level difference is zero.
Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90m(295.2ft.). When the total equivalent liquid length is more than 90m(295.2ft.),
please refer to technical manual to choose the connection piping diameter.
Sound values are measured in a semi-anechoic room, at a position 1m(3.28ft.) in front of the unit and 1.3m(4.264ft.) above the floor.

44
TVR 5G (Heat Recovery/3pipes)
TMS Specifications
TMS equipment which can be connected multiple indoor units

Model TMSBOX01A TMSBOX02A TMSBOX04A TMSBOX06A

Max. indoor unit groups 1 2 4 6

Max. number of each group indoor units 4 4 4 4

Max. number of all downstream indoor units 41=4 42=8 44=16 46=24

Max. capacity of each group indoor units kW 16 16 16 16

Total capacity of all downstream indoor units kW 16 28 45 45

Liquid pipe mm 9.53 12.7 15.9 15.9

Connect to
High pressure gas pipe mm 15.9 19.1 22.2 22.2
outdoor unit
Piping
Low pressure gas pipe mm 19.1 25.4 31.8 31.8
connections

Liquid pipe mm 9.53 9.53 9.53 9.53


Connect to
indoor unit
Gas pipe mm 15.9 15.9 15.9 15.9

Sound pressure level dB(A) 33 33 33 40

Net dimension (WHD) mm 630225600 630225600 960225600 960225600

Packing size (WHD) mm 725325685 725325685 1055325685 1055325685

Net weight kg 18 19.5 31 35

Gross weight kg 25 27 40 44.5

TMS equipment which can be connected only one indoor unit

Model TMSEBOX02A TMSEBOX04A

Max. number of all downstream indoor units 1 1

Capacity of downstream indoor unit kW 20~28 40~56

Liquid pipe mm 12.7 15.9

Connect to
High pressure gas pipe mm 19.1 22.2
outdoor unit
Piping
Low pressure gas pipe mm 25.4 31.8
connections

Liquid pipe mm 9.53 9.53


Connect to
indoor unit
Gas pipe mm 15.9 15.9

Sound pressure level dB(A) 33 33

Net dimension (WHD) mm 630225600 960225600

Packing size (WHD) mm 725325685 1055325685

Net weight kg 19.5 31

Gross weight kg 27 40

Note:
Sound values are measured in a semi-anechoic room, at a position 1m below the MS equipment in mode switch condition.
It is not recommended to install in the place where high noise performance is required.

41

45
TVR 5G (Heat Recovery/3pipes)
Dimensions
Dimension Unit: mm

1250
1615

765

V4 Plus R Series
HP
8/10 12 14/16
Piping
Liquid pipe 12.7 15.9 15.9
Low pressure gas pipe 22.2 25.4 28.6
High pressure gas pipe 19.1 19.1 22.2
High pressure gas balance pipe 19.1 19.1 19.1
Oil balance pipe 6 6 6

290
245
205
Oil balance pipe

Liquid pipe
230
250

High pressure
200

170

gas pipe
205

Low pressure
gas pipe

R section view High pressure


R: Pipe connection gas balance pipe

Installation dimension

Screw bolt position

1250

1120
10 Expansion bolt
Rubber shocking
proof mat Concrete
basement
736

765

Solid ground h=200


or roofing
200

1523long U-shape hole

46
TVR 5G (Inverter+Fixed)

Developed to facilitate more flexible system design for big-sized and high-rise buildings
TVR 5G product (Inverter+Fixed), which is designed to optimize the system and better
satisfying the market. Offering a higher capacity up to 64HP by combining maximum four
outdoor units, in 2HP as an increment.
Three types of units are included: Heat Pump Units, Corrosion Resistance Heat Pump
Units and Cooling Only Units.

05

47
TVR 5G (Inverter+Fixed) -
Recommended Combination Table
No of Outdoor Unit Combination Maximum No Capacity (kW)
Model No of
Outdoor of Connectable
Compressors
Units 8HP 10HP 12HP 14HP 16HP Indoor Units Cooling Heating

8HP 1 2 1 17 25.2 27

10HP 1 2 1 21 28 31.5

12HP 1 2 1 26 33.5 37.5

14HP 1 3 1 30 40 45

16HP 1 3 1 34 45 50

18HP 2 4 1 1 39 53.2 58.5

20HP 2 4 2 43 56 63

22HP 2 4 1 1 47 61.5 69

24HP 2 5 1 1 52 68 76.5

26HP 2 5 1 1 56 73 81.5

28HP 2 6 2 60 80 90

30HP 2 6 1 1 64 85 95

32HP 2 6 2 64 90 100

34HP 3 7 2 1 64 96 108

36HP 3 7 2 1 64 101 113

38HP 3 7 1 1 1 64 106.5 119

40HP 3 8 1 1 1 64 113 126.5

42HP 3 9 3 64 120 135

44HP 3 9 2 1 64 125 140

46HP 3 9 1 2 64 130 145

48HP 3 9 3 64 135 150

50HP 4 10 1 1 2 64 143.2 158.5

52HP 4 10 2 2 64 146 163

54HP 4 10 1 1 2 64 151.5 169

56HP 4 11 1 1 2 64 158 176.5

58HP 4 12 3 1 64 165 185

60HP 4 12 2 2 64 170 190

62HP 4 12 1 3 64 175 195

64HP 4 12 4 64 180 200

Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC DB/19oC WB; Outdoor temperature 35oC DB/24oC WB.
Heating: Indoor temperature 20oC DB/15oC WB; Outdoor temperature 7oC DB/6oC WB.
Piping length: Interconnecting piping length is 7.5m, level difference is zero.
The above combination models are factory-recommended models.

48
Features TVR 5G (Inverter+Fixed) -
Wide Application Features
Range
Wide range of outdoor units
The outdoor units capacity range from 8HP up to 64HP in 2HP increment. Maximum 64 indoor units with
capacity up to 130% of total outdoor units can be connected in one refrigeration system.

8, 10HP 12, 14, 16HP 18, 20, 22, 2 4, 26, 28, 30, 32HP

34, 36, 38, 40, 42, 44, 46, 48HP 50, 52, 54, 56, 58, 60, 62, 64HP

Large connectable indoor units quantity


The large quantity of connectable units is suitable for large buildings and projects.

64
65 60
60 56
55 52
50 47
45 43
39
40
34
35
30
30 26
25
21
20 17
15
10
5

8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30-64HP

49
TVR 5G (Inverter+Fixed) -
Features
Wide operation range

COOLING MODE
-5C Outdoor Temperature 48C

HEATING MODE*
-20C Outdoor Temperature 24C

-2 0 -1 0 0 10 20 30 40 50
Outdoor temperature (DB)

The inverter+Fixed series system operates stably at extreme temperatures ranging from -20C
. to 48C

Long piping length

Permitted
value (m)

30HP 350
Actual total piping length
Level difference between IDU-ODU is 70m*

>30HP 500
Longest actual piping length 150m

Piping
Actual length 150
length
Longest piping
Equivalent length 175
between IDU-IDU is 15m

Equivalent piping length from the farthest


IDU to the first indoor branch joint 40
Level difference
40m

Outdoor unit up 70*


Level difference between
Level indoor and outdoor units
Outdoor unit down 70
difference

Level difference between indoor units 15

*Total piping length is equal to gas pipe or liquid pipe length.


*Level difference above 50m are not supported by default but are available on
request for customized.

High external static pressure

A standard 0-20Pa external static pressure is equipped by default 40Pa

for all outdoor units. 20-40Pa can be customized for other modules.

50
High Efficiency TVR 5G (Inverter+Fixed) -
Features
High COP/EER values
The cooling EER up to 4.29 and the heating COP up to 4.39 in the 8HP catagory.

EER COP*
4.29 4.39
4.14 4.17
4.5 3.89 4.02 3.91
3.7 4.5
4 3.25 4
3.21
3.5 3.5
3 3
2.5 2.5
2 2
1.5 1.5
1 1
0.5 0.5
0 0
8HP 10HP 12HP 14HP 16HP 8HP 10HP 12HP 14HP 16HP
*System is without heating COP value

High performance heat exchanger


New design Original design
Windage& air flow
Relative windage resistance

0.8

0.6

0.4
Original design
Reduce
0.2
Reduce air resistance. 28% New design
0
0 200 400 600 800 1000 Re

Frost contrast
Relative windage resistance

0.8 Reduce
High efficiency inner-threaded pipe, 30%
enhance heat transfer. 0.6 Original design
0.4

0.2 New design


0
0 0.2 0.4 0.6 0.8 1
Relative frosting rate

Hydrophilic film fins + inner-threaded pipes

The new designed window fins enlarge the heat-exchanging area , decrease the air resistance, save more power
and enhance heat exchange performance.
Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency.

51
TVR 5G (Inverter+Fixed) -
Enhanced Comfort
Features
Night silent operation mode
High comfort outdoor units multi-choice of silent mode during the night.
Super silent operation mode can reduce sound level further, minimum 46.8dB (A).
Load % Capacity %

Peak value of ambient temp.


Night silent operation will be
100
activated X hours after the peak
temperature during daytime,
and it will go back to normal 50
operation after Y hours.
8hrs 10hrs
Noise dB

-Mode 1X: 6 hours, Y: 10 hours Night silent Mode


noise
-Mode 2X: 8 hours, Y: 10 hours Max.-10dB(10Hp)

-Mode 3X: 6 hours, Y: 12 hours Start End

-Mode 4X: 8 hours, Y: 8 hours 08:00 14:00 22:00 08:00


Notes:
This function can be activated by setting at site. Temperature(load) curve shown in the graph is just an example.

Intelligent defrosting technology*


Intelligent defrosting program will judge the defrosting Intelligent defrosting

time according to the system real requirement, reduce


Heating capacity

the heating loss by unnecessary defrosting and make Usual defrosting

the indoor side more comfortable.


Defrosting time can be shortened to 4 min. due to the
specialized defrosting valve. t min t
*System is without this function.
Time

Easier Installation and Service


Simple signal line connection
Centralized controller (TCONTCCM03A or TCONTCCM30A) can be connected from indoor side or outdoor side
indoor (XYE terminals) at will. Only one group of communication wire of PQE, achieved both of communication
for & outdoor unit. Its more convenient for communication wiring.

P Q E P Q E P Q E P Q E

X Y E X Y E P Q E

Auto addressing
Outdoor unit can distribute addresses for indoor
unit automatically.
Wireless and wired controllers can query and
modify each indoor unit's address.

52
TVR 5G (Inverter+Fixed) -
Outdoor Unit Specifications
380~415V-3Ph-60Hz
Model 4TVV0086AK000AA 4TVV0096AK000AA 4TVV0115AK000AA 4TVV0140AK000AA 4TVV0155AK000AA

Power supply V/Ph/Hz 380-415/3/60


Cooling Capacity kW 25.2 28 33.5 40 45
RT 7.2 8 9.5 11.4 12.8
kBtu/h 86.0 95.5 114.3 136.5 153.5
kcal/h 21,672 24,080 28,810 34,400 38,700
Power input kW 5.87 7.2 9.05 12.31 14.02
EER kW/kW 4.29 3.89 3.7 3.25 3.21
Heating Capacity kW 27 31.5 37.5 45 50
RT 7.7 8.9 10.7 12.8 14.2
kBtu/h 92.1 107.5 128.0 153.5 170.6
kcal/h 23,220 27,090 32,250 38,700 43,000
Power input kW 6.15 7.61 8.99 11.19 12.79
COP kW/kW 4.39 4.14 4.17 4.02 3.91
Connectable Total capacity % 50-130 50-130 50-130 50-130 50-130
indoor unit Max. quantity 13 16 16 16 20
Sound pressure level dB(A) 57 57 59 60 60
Pipe Liquid pipe in.(mm) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 5/8( 15.9) 5/8( 15.9)
connections Gas pipe in.(mm) 7/8( 22.2) 1( 25.4) 1-1/8( 28.6) 1-1/8( 28.6) 1-1/8( 28.6)
Oil balance pipe in.(mm) 1/4( 6) 1/4( 6) 1/4( 6) 1/4( 6) 1/4( 6)
Fan motor Type DC DC DC
Quantity 1 2 2
Air flow rate m3/h 11,700 15,600 15,600
CFM 6,880 9,173 9,173
Motor output W 420 3602 3602
ESP in.WG(Pa) 0~0.08(0~20) (default) 0~0.08(0~20) (default) 0~0.08(0~20) (default)
in.WG(Pa) 0.08~0.16(20~40) (customized) 0.08~0.24(20~40) (customized) 0.08~0.16(20~40) (customized)
DC inverter Quantity 1 1 1
compressor Capacity kW 11.8 11.8 11.8
kBtu/h 40.3 40.3 40.3
Crankcase heater W 27.62 27.62 27.62
Oil type FVC68D FVC68D FVC68D
Oil charge gal.(ml) 0.13(500) 0.13(500) 0.13(500)
Fixed scroll Quantity 1 1 2
compressor Capacity kW 18.55 18.55 18.552
kBtu/h 63.3 63.3 63.32
Crankcase heater W 27.6 27.6 27.62
Oil type FVC68D FVC68D FVC68D
Oil charge gal.(ml) 0.13(500) 0.13(500) 0.13(500)2
Refrigerant Type R410A R410A R410A
Factory charging Ibs.(kg) 22.1(10) 26.5(12) 33.1(15)
Design pressure (High/Low) MPa 4.4/2.6 4.4/2.6 4.4/2.6
PSI 638/377 638/377 638/377
Net dimension (WHD) inch 37-25/3263-9/1630-1/8 49-7/3263-9/1630-1/8 49-7/3263-9/1630-1/8
mm 9601615765 12501615765 12501615765
Packing size (WHD) inch 40-3/870-1/232-11/16 51-9/1670-1/232-1/2 51-9/1670-1/232-1/2
mm 10251790830 13051790820 13051790820
Net weight Ibs.(kg) 560(245) 607(275) 717(325)
Gross weight Ibs.(kg) 573(260) 651(295) 761(345)
Operating Cooling F(C) 23~118.4(-5~48)
temperature range Heating F(C) -4~75.2(-20~24)

Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27oC(80.6oF) DB/19oC(66.2oF) WB; Outdoor temperature 35oC(95oF) DB/24oC(75.2oF) WB.
Heating: Indoor temperature 20oC(68oF) DB/15oC(59oF) WB; Outdoor temperature 7oC(44.6oF) DB/6oC(42.8oF) WB.
Piping length: Interconnecting piping length is 7.5m(24.6ft.), level difference is zero.
Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90m(295.2ft.). When the total equivalent liquid length is more than 90m(295.2ft.),
please refer to technical manual to choose the connection piping diameter.
Sound values are measured in a semi-anechoic room, at a position 1m(3.28ft.) in front of the unit and 1.3m(4.264ft.) above the floor.

53
TVR 5G (Inverter+Fixed)
Corrosion Resistance Unit
The unit adopts special anti-corrosion treatment on the heat exchanger, electronic parts
and other components of the unit, which is about 5 times as anti-salt effective as the normal
ones, it makes the unit more suitable for the project nearby the sea.
V4 plus series

The plastic planting grille protects against salt.


All panel parts are corrosion resistant to protect
against brine.

Corrosion resistant heat-exchange fins are suitable


for seaside areas and areas exposed to acidic
substances.

All screws are anti-rust.

All PCB parts in the unit are coated with


double-sided moisture proof paint. The outer side of
the control box metal cover is spray-painted.

54
TVR 5G (Inverter+Fixed)
Outdoor Unit Dimensions
Dimension Unit: mm
8/10HP 12/14/16HP
1615

1615

960
1250
765

765

Liquid pipe
A
B Gauge point
Cooling only type without

Oil balance pipe


For parallel connect
the modular units

Gas pipe

HP
220
208

SIZE 8/10HP 12/14/16HP


168

A 199 169

B 159 209

C 195 169
C Liquid pipe 12.7 15.9
R: Pipe connection
R section view Gas pipe 25.4 31.8

Installation dimension

Screw bolt position


8/10HP: 960
12/14/16HP: 1250
8/10HP: 830
12/14/16HP: 1120
10 Expansion bolt
Rubber shocking
proof mat Concrete
basement
765
736

Solid ground h=200


or roofing
200

1523long U-shape hole

55 53
TVR 5G (All Inverter-T3/High
Ambient)

The outdoor units capacity range is from 8HP up to 72HP in 2HP increment. Maximum 64
indoor units with the capacity up to 130% of total outdoor units can be connected in one
refrigeration system. With all DC inverter compressors and all DC fan motors, the
efficiency is improved greatly. Together with lots of latest technologies, it supports an
incredible piping length of 1000m and longer level difference of 110m, making it perfect for
big-sized and high-rise buildings for wide application.

05

56
TVR 5G (All Inverter-T3/High
Ambient)-Features

Wide range of outdoor units


The outdoor units capacity range from 8HP up to 72HP in 2HP increment. Maximum 64 indoor units
with capacity up to 130% of total outdoor units can be connected in one refrigeration system.

8, 10HP 12, 14, 16HP 18HP 20, 22, 24, 26, 28, 30, 32, 34, 36HP

38, 40, 42, 44, 46, 48, 50, 52, 54HP 56, 58, 60, 62, 64, 66, 68, 70, 72HP

Large connectable indoor units quantity


The large quantity of connectable units is suitable for large buildings and projects.

65 63 64
59
60 56
55
53
50
50 46
45 43
39
40 36
35 33
29
30 26
25 23
20
20
16
15
13
10
5

8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40-72HP

57
25
TVR 5G (All Inverter-T3/High
Ambient)-Features
Wide operation range

COOLING MODE
-5C Outdoor Temperature 54C

V4 Plus S Series
HEATING MODE*
-20C Outdoor Temperature 24C

-2 0 -1 0 0 10 20 30 40 50
Outdoor temperature (DB)

The TVR 5G (All Inverter) system operates stably at extreme temperatures ranging from -20C
. to 54C

Long piping length


Permitted
value (m)

Actual total piping length 1000*


Level difference between IDU-ODU is 110m

Actual length 175


Piping
Longest actual piping length 175m

Longest piping
length
Equivalent length 200

Equivalent piping length from the farthest


40/90*
between IDU-IDU is 30m

IDU to the first indoor branch joint

Outdoor unit up 70
Level difference

Level difference between


90m

Level indoor and outdoor units


Outdoor unit down 110
difference

Level difference between indoor units 30

*Total pipe length is equal to two times pipe length plus pipe length.
*When the piping length from the farthest IDU to the first indoor branch joint is
more than 40m, it needs to meet specific conditions according to the installation
part of the technical manual to achieve 90m.

High external static pressure


A standard 0-20Pa external static pressure is equipped by default
for all outdoor units. 20-40Pa can be customized for other 40Pa

modules.

58 26
TVR 5G (All Inverter-T3/High Ambient)-
Outdoor Units Specifications

Model 4TVVT086BK000AA 4TVVT096BK000AA 4TVVT115BK000AA 4TVVT140BK000AA 4TVVT155BK000AA 4TVVT182BK000AA

Power supply V/Ph/Hz 380-415/3/60

Cooling(*1) Capacity* kW 25.2 28.0 33.5 40.0 45.0 50.0

Capacity** kW 23.6 26.3 30.7 37.6 41.2 45.8

Input* kW 5.88 7.05 8.79 11.30 12.85 14.49

Input** kW 6.37 7.64 11.25 12.24 16.46 18.55

EER* kW/kW 4.29 3.97 3.81 3.54 3.50 3.45

EER** kW/kW 3.72 3.45 2.73 3.07 2.51 2.47

Heating(2*) Capacity* kW 27.0 31.5 37.5 45.0 50.0 56.0

Input* kW 6.15 7.55 8.99 11.19 12.79 14.40

COP* kW/kW 4.39 4.17 4.17 4.02 3.91 3.89

Connectable Total capacity % 50~130


indoor unit
Max. quantity 13 16 20 23 26 29
Sound pressure
dB(A) 57 57 59 61 62 62
level

Pipe Liquid pipe mm 12.7 12.7 15.9 15.9 15.9 19.1


connections
Gas pipe mm 25.4 25.4 31.8 31.8 31.8 31.8

Oil balance pipe mm 6.4 6.4 6.4 6.4 6.4 6.4

Fan motor Type DC DC DC DC DC DC

Quantity 1 1 2 2 2 2

Air flow rate m /h


3
11,242 11,242 15,620 15,620 15,620 15,770

Motor output W 454 454 232x2 383x2 383x2 560x2

ESP Pa 0~20 (default)

Pa 20~40 (optional)

DC inverter Quantity 1 1 1+1 1+1 1+1 1+1


compressor
Capacity kW 31.59 31.59 31.59+11.8 31.59+11.8 31.59+11.8 31.59 +31.59

Crankcase heater W 27.62 27.62 27.62x2 27.62 27.62 27.6x2

Oil type FVC68D FVC68D FVC68D+FVC68D FVC68D+FVC68D FVC68D+FVC68D FVC68D+FVC68D

Oil charge ml 500 500 500+500 500+500 500+500 500+500

Refrigerant Type R410a R410a R410a R410a R410a R410a

Factory charging kg 10 10 12 15 15 16

Design pressure (High/Low) MPa 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6

Net dimension (WHD) mm 9601,615765 1,2501,615765

Packing size (WHD) mm 1,0251,790830 1,3051,790820

Net weight kg 212 212 288 288 288 310

Gross weight kg 220 220 300 308 308 330

Operating Cooling C -5~54


temperature range
Heating C -20~24

Notes:

Heating

59
TVR 5G (All Inverter-T3/High Ambient)
Outdoor Unit Dimensions

Dimension Unit: mm

8HP/10HP
Combinable Dimensions: 12HP/14HP/16HP/18HP
Combinable Dimensions:

Installation dimension

Position of foot screw bolt (Unit: mm)

1523 long u-shape hole

For 8,10HP For 12,14,16,18HP

A 830 1120
B 960 1250
C 736 736
D 765 765

60
Nomenclature - Outdoor Unit
4 T V V 0 0 8 6 B D 0 0 0 A A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

D = 380-415/60Hz/3phase

Digit #10 = Electric Power Supply Characteristics


Digit #1 = Refrigerant

4 = R -410a 1 = 208-230V~60Hz/1phase

K = 380-415V 3N~60Hz/3phase

Digit #2 = Brand Name D = 380-415/60Hz/3phase

T = Trane

Digit #11 = Coil Fin Protection

Digit #3 = System Type 0 = Blue Fin

V = Variable Refrigerant Flow C = Corrosion Resistant

Digit # 12,13 = Reserved for Future Use


Digit #4 = Functional Type Outdoor Unit

V = Heat Pump, Inverter 0 = Not currently used

R = Heat Recovery / 3 Pipes, Inverter

Digit #5 = Special Application Digit #14 = Minor Design Sequence

0 = Standard Ambient A = Design Sequence

High Ambient Model


T =

Digit #15 = Device Digit

Digit #6,7,8 = Norminal Capacity (Btu/h x 1000) A = Service Design Sequence

086 = 86000Btu/h

Digit #9 = Major Development Sequence

A = Inverter + Fixed

B = All Inverters

61
Nomenclature - Indoor Unit
4 T V D 0 0 2 4 C B 0 W E A A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Digit #1 = Refrigerant Digit #9 = Major Development Sequence

4 = R - 410a A = Third Development Sequence

Digit # 10
Digit #2 = Brand Name = Electric Power Supply Characteristics

T = Trane 1 = 208-230V/60Hz/1phase -

K = 220-240V/60Hz/3phase

Digit #3 = System Type

Digit #11
V = Variable Refrigerant Flow = Type of function

0 = Standard Cooling / HP

Digit #4 = Configuration Type H = Auxiliary Electric Heater

A = 1-Way Cassette

Digit #12
B = 4-Way Compact Cassette (650mm x 650mm) = Controls

C = 4-Way Standard Cassette (950mm x 950mm) W = Wired Controls

E = 2 -Way Cassette R = Wireless Controls

F = Fresh Air Duct Type

Digit #13
L = Low Static Pressure DuctType = Special Features

D = Medium Static Pressure Duct Type 0 = None

H = High Static Pressure Duct Type E = Integrated EXV

G = Cosole Floor Mount

Digit #14
X = Convertible Floor / Ceiling Mount = Minor Design Sequence

W = High Wall Type Mount A = Design Sequence

B = Design Sequence

Digit #5 = Reserved for Future Use

Not currently used Digit #15


0 = Device Digit
=

A = Service Design Sequence


Norminal Capacity (Btu/h x 1000)
Digit #6,7,8 =

024 = 24000Btu/h

09

62
TVR 5G (Inverter + Fixed)
Combination of Outdoor Units
Capacity Capacity Maximum
Maximum
Model Number Outdoor Unit
Capacity indoorIndoor
Units
Model
Model Number
Number Outdoor
Outdoor Unit Unit Module Combination
Btu / Hr HP kW Units Combination
Combination
Btu/h HP kW
4TVV0086AD000AA 4TVV0086AD000AA 1 86000 8 25 17
4TVV0086AK000AA 4TVV0086AK000AA1 86,000 8 25 17
4TVV0096AD000AA 4TVV0096AD000AA 1 96000 10 28 21
4TVV0096AK000AA 4TVV0096AK000AA1 96,000 10 28 21
4TVV0115AD000AA 4TVV0115AD000AA 1 115000 12 34 26
4TVV0115AK000AA 4TVV0115AK000AA1 115,000 12 34 26
4TVV0140AD000AA 4TVV0140AD000AA 1 140000 14 40 30
4TVV0140AK000AA 4TVV0140AK000AA1 140,000 14 40 30
4TVV0155AD000AA 4TVV0155AD000AA 1 155000 16 45 34
4TVV0155AK000AA 4TVV0155AK000AA1 155,000 16 45 34

4TV4TVV0182AD000AA
V0182AK000AA 4TVV0086AK0004TVV0086AD000AA
AA+4TVV0096AK000A+A4TVV0096AD000AA 182,000 182000
18 18 53 53 39 39

4TV4TVV0192AD000AA
V0192AK000AA 4TVV0096AK0004TVV0096AD000AA
AA+4TVV0096AK000A+A4TVV0096AD000AA 192,000 192000
20 20 56 56 43 43

4TV4TVV0211AD000AA
V0211AK000AA 4TVV0096AK0004TVV0096AD000AA
AA+4TVV0115AK000A+A4TVV0115AD000AA 211,000 211000
22 22 62 62 47 47

4TV4TVV0236AD000AA
V0236AK000AA 4TVV0096AK0004TVV0096AD000AA
AA+4TVV0140AK000A+A4TVV0140AD000AA 236,000 236000
24 24 68 68 52 52
4TVV0251AD000AA 251000 26 73 56
4TVV0251AK000AA 4TVV0096AK0004TVV0096AD000AA
AA+4TVV0155AK000A+A4TVV0155AD000AA 251,000 26 73 56
4TVV0270AD000AA 4TVV0140AD000AA 2 270000 28 80 60
4TVV0270AK000AA 4TVV0140AK000AA2 270,000 28 80 60
4TVV0295AD000AA 4TVV0140AD000AA + 4TVV0155AD000AA 295000 30 85 64
4TVV0295AK000AA 4TVV0140AK000AA+4TVV0155AK000AA 295,000 30 85 64
4TVV0310AD000AA 4TVV0155AD000AA 2 310000 32 90 64
4TVV0310AK000AA 4TVV0155AK000AA2 310,000 32 90 64

4TVV0332AK000AA 4TVV0096AK000AA2+4TVV0140AK000AA 332,000 34 96 64


4TVV0332AD000AA 4TVV0096AD000AA 2 + 4TVV0140AD000AA 332000 34 96 64
4TVV0347AK000AA 4TVV0096AK000AA2+4TVV0155AK000AA 347,000 36 101 64
4TVV0347AD000AA 4TVV0096AD000AA 2 + 4TVV0155AD000AA 347000 36 101 64
4TVV0366AK000AA 4TVV0096AK000AA+4TVV0115AK000AA+4TVV0155AK000AA
4TVV0096AD000AA + 4TVV0115AD000AA + 366,000 38 107 64
4TVV0366AD000AA 366000 38 107 64
4TVV0155AD000AA
4TVV0391AK000AA 4TVV0096AK000AA+4TVV0140AK000AA+4TVV0155AK000AA 391,000 40 113 64
4TVV0096AD000AA + 4TVV0140AD000AA +
4TVV0391AD000AA
4TVV0406AK000AA 4TVV0140AK000AA3 406,000
391000
42
40 120 113 64
64
4TVV0155AD000AA
4TV4TVV0406AD000AA
V0425AK000AA 4TVV0140AK0004TVV0140AD000AA
AA2+4TVV0155AK000A
3A 425,000 406000
44 42 125 120 64 64

4TV4TVV0425AD000AA
V0450AK000AA 4TVV0140AK0004TVV0140AD000AA
AA+4TVV0155AK000AA2
2+ 4TVV0155AD000AA 450,000 425000
46 44 130 125 64 64
4TVV0450AD000AA 4TVV0140AD000AA + 4TVV0155AD000AA 2 450000 46 135 130 64
4TVV0465AK000AA 4TVV0155AK000AA3 465,000 48 64
4TVV0465AD000AA 4TVV0155AD000AA 3 465000 48 135 64
4TVV0492AK000AA 4TVV0086AK000AA+4TVV0096AK000AA+4TVV0155AK000AA2 492,000 50 143 64

4TVV0502AK000AA 4TVV0096AK000AA2+4TVV0155AK000AA2 502,000 52 146 64


4TVV0086AD000AA + 4TVV0096AD000AA +
4TVV0492AD000AA 492000 50 143 64
4TVV0521AK000AA 4TVV0096AK000AA+4TVV0115AK000AA+4TVV0155AK000AA2
4TVV0155AD000AA 2 521,000 54 152 64

4TVV0502AD000AA
4TVV0546AK000AA 4TVV0096AD000AA 2 + 4TVV0155AD000AA 2 546,000
4TVV0096AK000AA+4TVV0140AK000AA+4TVV0155AK000AA2 502000
56 52 158 146 64 64

4TV4TVV0521AD000AA
V0561AK000AA 4TVV0140AK0004TVV0096AD000AA
AA3+4TVV0155AK00+0A
4TVV0115AD000AA
A + 561,000 58
521000 54 165 152 64 64
4TVV0155AD000AA 2
4TVV0580AK000AA 4TVV0140AK000AA2+4TVV0155AK000AA2 580,000 60 170 64
4TVV0096AD000AA + 4TVV0140AD000AA +
4TVV0546AD000AA
4TVV0605AK000AA 4TVV0140AK000AA+4TVV0155AK000AA3 605,000 546000
62 56 175 158 64 64
4TVV0155AD000AA 2
4TVV0561AD000AA
4TVV0620AK000AA 4TVV0140AD000AA 3 + 4TVV0155AD000AA
4TVV0155AK000AA4 620,000 561000
64 58 180 165 64 64

4TVV0580AD000AA 4TVV0140AD000AA 2 + 4TVV0155AD000AA 2 580000 60 170 64

4TVV0605AD000AA 4TVV0140AD000AA + 4TVV0155AD000AA 3 605000 62 175 64

4TVV0620AD000AA 4TVV0155AD000AA 4 620000 64 180 64

Note:
The system enables the connection of indoor units with a total capacity within 50% to 130% of that of the corresponding outdoor unit, but
when this capacity ratio exceeds 100% then the actual capacity of each indoor unit will decrease compared to rated capacity when all the
units operate simultaneously.

63
TVR 5G (All Inverter)
Combination of Outdoor Units
Capacity
Capacity Capacity Maximum
Maximum indoor Units
Indoor
Model Number Outdoor Unit Module Combination
Model Number Outdoor Unit Model Number Outdoor Unit Combination
Btu / Hr
Btu/h HP HPkW Units
kW Combination

4TVV0086BD000AA
4TVV0086BK000AA 4TVV0086BD000AA
4TVV0086BK000AA 86000
86,000 8 8 25 25 13 13

4TVV0096BD000AA
4TVV0096BK000AA 4TVV0096BD000AA
4TVV0096BK000AA 95,500 10
95500 10 28 28 16 16
4TVV0115BD000AA 4TVV0115BD000AA 114300 12 34 20
4TVV0115BK000AA 4TVV0115BK000AA 114,300 12 34 20
4TVV0140BD000AA 4TVV0140BD000AA 136500 14 40 23
4TVV0140BK000AA 4TVV0140BK000AA 136,500 14 40 23
4TVV0155BD000AA 4TVV0155BD000AA 153500 16 45 26
4TVV0155BK000AA 4TVV0155BK000AA 153,500 16 45 26
4TVV0182BD000AA 4TVV0182BD000AA 170600 18 50 29
4TVV0182BK000AA 4TVV0182BK000AA 170,600 18 50 29

4TVV0192BK000AA 4TVV0096BK000AA+4TVV0096BK000AA 191,100 20 56 33


4TVV0192BD000AA 4TVV0096BD000AA + 4TVV0096BD000AA 191100 20 56 33
4TVV0211BK000AA
4TVV0211BD000AA 4TVV0096BK000AA+4TVV0115BK000AA
4TVV0096BD000AA + 4TVV0115BD000AA 209,800 22
209800 22 62 62 36 36

4TVV0236BK000AA
4TVV0236BD000AA 4TVV0096BK000AA+4TVV0140BK000AA
4TVV0096BD000AA + 4TVV0140BD000AA 232,000 24
232000 24 68 68 39 39

4TVV0251BD000AA
4TVV0251BK000AA 4TVV0096BD000AA + 4TVV0155BD000AA
4TVV0096BK000AA+4TVV0155BK000AA 249,100 26
249100 26 73 73 43 43

4TVV0278BD000AA
4TVV0278BK000AA 4TVV0096BD000AA + 4TVV0182BD000AA
4TVV0096BK000AA+4TVV0182BK000AA 266100
266,100
28 28
78 78 46 46
4TVV0295BD000AA 4TVV0140BD000AA + 4TVV0155BD000AA 290000 30 85 50
4TVV0295BK000AA 4TVV0140BK000AA+4TVV0155BK000AA 290,000 30 85 50
4TVV0322BD000AA 4TVV0140BD000AA + 4TVV0182BD000AA 307100 32 90 53
4TVV0322BK000AA 4TVV0140BK000AA+4TVV0182BK000AA 307,100 32 90 53
4TVV0337BD000AA 4TVV0155BD000AA + 4TVV0182BD000AA 327100 34 96 56
4TVV0337BK000AA 4TVV0155BK000AA+4TVV0182BK000AA 327,600 34 95 56
4TVV0364BD000AA 4TVV0182BD000AA + 4TVV0182BD000AA 341200 36 100 59
4TVV0364BK000AA 4TVV0182BK000AA+4TVV0182BK000AA 341,200 36 100 59

4TVV0374BK000AA 4TVV0096BK000AA*2+4TVV0182BK000AA 363,400 38 106 63


4TVV0096BD000AA + 4TVV0096BD000AA + 4TVV0182BD000AA 363400 38 106 63
4TVV0374BD000AA
4TVV0391BK000AA 4TVV0096BK000AA+4TVV0140BK000AA+4TVV0155BK000AA 385,600 40 113 64
4TVV0391BD000AA 4TVV0096BD000AA + 4TVV0140BD000AA + 4TVV0155BD000AA 385600 40 113 64
4TVV0406BK000AA 4TVV0096BK000AA+4TVV0155BK000AA*2 402,600 42 118 64
4TVV0406BD000AA 4TVV0096BD000AA + 4TVV0155BD000AA + 4TVV0155BD000AA 402600 42 118 64
4TVV0433BK000AA 4TVV0096BK000AA+4TVV0155BK000AA+4TVV0182BK000AA 419,700 44 123 64
4TVV0433BD000AA 4TVV0096BD000AA + 4TVV0155BD000AA + 4TVV0182BD000AA 419700 44 123 64
4TVV0460BK000AA 4TVV0096BK000AA+4TVV0182BK000AA*2 443,600 46 130 64
4TVV0460BD000AA 4TVV0096BD000AA + 4TVV0182BD000AA + 4TVV0182BD000AA 443600 46 130 64
4TVV0477BK000AA 4TVV0140BK000AA+4TVV0155BK000AA+4TVV0182BK000AA 460,600 48 135 64
4TVV0477BD000AA 4TVV0140BD000AA + 4TVV0155BD000AA + 4TVV0182BD000AA 460600 48 135 64
4TVV0504BK000AA 4TVV0140BK000AA+4TVV0182BK000AA*2 477,700 50 140 64
4TVV0504BD000AA 4TVV0140BD000AA + 4TVV0182BD000AA + 4TVV0182BD000AA 477700 50 140 64
4TVV0519BK000AA 4TVV0155BK000AA+4TVV0182BK000AA*2 494,700 52 145 64
4TVV0519BD000AA 4TVV0155BD000AA + 4TVV0182BD000AA + 4TVV0182BD000AA 494700 52 145 64
4TVV0546BK000AA 4TVV0182BK000AA*3 511,800 54 150 64
4TVV0546BD000AA 4TVV0182BD000AA + 4TVV0182BD000AA + 4TVV0182BD000AA 511800 54 150 64
4TVV0556BK000AA 4TVV0096BK000AA*2+4TVV0182BK000AA*2 532,300 56 156 64

4TVV0573BK000AA 4TVV0096BK000AA+4TVV0140BK000AA+4TVV0155BK000AA+4TVV0182BK000AA
4TVV0096BD000AA + 4TVV0096BD000AA + 556,200 58 163 64
4TVV0566BD000AA 532300 56 156 64
4TVV0182BD000AA + 4TVV0182BD000AA
4TVV0600BK000AA 4TVV0096BK000AA+4TVV0140BK000AA+4TVV
4TVV0096BD000AA + 4TVV0140BD000AA 018+2BK000AA*2 573,200 60 168 64
4TVV0576BD000AA 556200 58 163 64
4TVV0155BD000AA + 4TVV0182BD000AA
4TVV0615BK000AA 4TVV0096BK000AA+4TVV0155BK000AA+4TVV
4TVV0096BK000AA + 4TVV0140BK000AA 018+2BK000AA*2 590,300 62 173 64
4TVV0600BD000AA 573200 62 168 64
4TVV0182BK000AA + 4TVV0182BK000AA
4TVV0642BK000AA 4TVV0096BK000AA+4TVV0182BK000AA+4TVV
4TVV0096BD000AA + 4TVV0155BD000AA +BK000AA*2
018 2 607,300 64 178 64
4TVV0615BD000AA 590300 62 173 64
. 4TVV0182BD000AA + 4TVV0182BD000AA
4TVV0659BK000AA 4TVV0140BK000AA+4TVV0155BK000AA+4TVV
4TVV0096BD000AA + 4TVV0182BD000AA 018+2BK000AA*2 631,200 66 185 64
4TVV0642BD000AA 607300 64 178 64
4TVV0182BD000AA + 4TVV0182BD000AA
4TVV0686BK000AA 4TVV0140BK000AA+4TVV0182BK000AA*3
4TVV0140BD000AA + 4TVV0155BD000AA + 648,300 68 190 64
4TVV0659BD000AA 631200 66 185 64
4TVV0182BD000AA + 4TVV0182BD000AA
4TVV0701BK000AA 4TVV0155BK000AA+4TVV0182BK000AA*3 665,300 70 195 64
4TVV0140BD000AA + 4TVV0182BD000AA + 648300 68 190 64
4TVV0686BD000AA 4TVV0182BD000AA + 4TVV0182BD000AA
4TVV0728BK000AA 4TVV0182BK000AA*4 682,400 72 200 64
4TVV0701BD000AA 4TVV0155BD000AA + 4TVV0182BD000AA + 665300 64
4TVV0182BD000AA + 4TVV0182BD000AA 70 195
4TVV0182BD000AA + 4TVV0182BD000AA + 682400 72 200 64
4TVV0728BD000AA 4TVV0182BD000AA + 4TVV0182BD000AA
Note:
The system enables the connection of indoor units with a total capacity within 50% to 130% of that of the corresponding outdoor unit, but
when this capacity ratio exceeds 100% then the actual capacity of each indoor unit will decrease compared to rated capacity when all the
units operate simultaneously.

64
TVR 5G (Heat Recovery/3 pipes)
Combination of Outdoor Units
Capacity
Model Number Outdoor Unit Module Combination Capacity Capacity Maximum
Maximum
indoorIndoor
Units
Model Number Outdoor Unit Model Number Outdoor Unit Combination
Btu/h Btu / Hr
HP HP kW
HP kW Units Combination

4TVR0086BD000AA
4TV R0086BK000AA 4TVR0086BK004TVR0086BD000AA
0 A A *1 1 86,000 86000
25 8 8 25 13 13
4TVR0096BD000AA
4TV R0096BK000AA
4TVR0096BD000AA 1
4TVR0096BK000AA*1 96,000 96000
28 10 10 28 16 16

4TVR0115BD000AA 4TVR0115BD000AA 1 115000 12 34 20


4TVR0115BK000AA 4TVR0115BK000AA*1 115,000 34 12 20
4TVR0140BD000AA 4TVR0140BD000AA 1 140000 14 40 23
4TVR0140BK000AA 4TVR0140BK000AA*1 140,000 40 14 23
4TVR0155BD000AA 4TVR0155BD000AA 1 155000 16 45 26
4TVR0155BK000AA 4TVR0155BK000AA*1 155,000 45 16 26

4TVR0182BK000AA\ 4TVR0086BK000AA+4TVR0096BK000AA 182,000 53 18 29


4TVR0182BD000AA 4TVR0086BD000AA + 4TVR0096BD000AA 182000 18 53 29
4TVR0192BK000AA 4TVR0096BK000AA+4TVR0096BK000AA 192,000 56 20 33
4TVR0192BD000AA 4TVR0096BD000AA+ 4TVR0096BD000AA 192000 20 56 33
4TVR0211BK000AA 4TVR0096BK000AA+4TVR0115BK000AA 211,000 62 22 36
4TVR0211BD000AA 4TVR0096BD000AA+ 4TVR0115BD000AA 211000 22 62 36
4TVR0236BK000AA 4TVR0096BK000AA+4TVR0140BK000AA 236,000 68 24 39
4TVR0236BD000AA 4TVR0096BK000AA + 4TVR0140BK000AA 236000 24 68 39
4TVR0251BK000AA 4TVR0096BK000AA+4TVR0155BK000AA 251,000 73 26 43
4TVR0251BD000AA 4TVR0096BD000AA + 4TVR0155BD000AA 251000 26 73 43
4TVR0270BK000AA 4TVR0140BK000AA*2 270,000 80
4TVR0270BD000AA 4TVR0140BD000AA 2 270000 28 28 80 46
46
4TV R0295BK000AA
4TVR0295BD000AA 4TVR0140BK004TVR0140BD000AA
0AA+4TVR0155BK000AA+ 4TVR0155BD000AA 295,000 85
295000 30 30 85 50 50
4TVR0310BD000AA
4TV R0310BK000AA 4TVR0155BK004TVR0155BD000AA
0 A A *2 2 310,000 310000
90 32 32 90 53 53

4TVR0332BK000AA 4TVR0096BK000AA*2+4TVR0140BK000AA 332,000 96 34 56

4TVR0332BD000AA
4TV R0347BK000AA 4TVR0096BK004TVR0096BD000AA A2
0AA*2+4TVR0155BK000A + 4TVR0140BD000AA 347,000 332000
101 34 36 96 59 56

4TVR0347BD000AA
4TV R0366BK000AA 4TVR0096BK004TVR0096BD000AA
0AA+4TVR0115BK000AA
+42TV+R4TVR0155BD000AA
0155BK000AA 366,000 347000
107 36 38 101 63 59
4TVR0096BD000AA + 4TVR0115BD000AA +
4TVR0366BD000AA
4TV R0391BK000AA 4TVR0096BK000AA+4TVR0140BK000AA+4TVR0155BK000AA 391,000 366000
113 38 40 107 64 64
4TVR0155BD000AA
4TVR0406BK000AA 4TVR0140BK000AA*3 406,000 120 42 64
4TVR0096BD000AA + 4TVR0140BD000AA +
4TVR0391BD000AA 391000 40 113 64
4TVR0425BK000AA 4TVR0140BK004TVR0155BD000AA
0AA*2+4TVR0155BK000AA 425,000 125 44 64
4TVR0406BD000AA 4TVR0140BD000AA 3 406000 42 120 64
4TVR0450BK000AA 4TVR0140BK000AA+4TVR0155BK000AA*2 450,000 130 46 64
4TVR0425BD000AA 4TVR0140BD000AA 2 + 4TVR0155BD000AA 425000 44 125 64
4TVR0465BK000AA 4TVR0155BK000AA*3 465,000 135 48 64
4TVR0450BD000AA 4TVR0140BD000AA + 4TVR0155BD000AA 2 450000 46 130 64
4TVR0492BK000AA 4TVR0086BK000AA+4TVR0096BK000AA+14TVR0155BK000AA*2 492,000 143 50 64
4TVR0465BD000AA 4TVR0155BD000AA 3 465000 48 135 64
4TVR0502BK000AA 4TVR0096BK000AA*2+4TVR0155BK000AA*2 502,000 146 52 64

4TVR0521BK000AA 4TVR0096BK000AA+4TVR0115BK000AA+4TVR 0155BK000AA*2 521,000 152 54 64


4TVR0086BD000AA + 4TVR0096BD000AA +
4TVR0492BD000AA 492000 50 143 64
4TVR0546BK000AA 4TVR0096BK004TVR0155BD000AA
0AA+4TVR0140BK000AA
+42TVR0155BK000AA*2 546,000 158 56 64

502000 52 146 64
4TVR0502BD000AA
4TV R0561BK000AA 4TVR0140BK004TVR0096BD000AA
0AA*3+4TVR0155BK000AA2 + 4TVR0155BD000AA 2 561,000 165 58 64

4TVR0096BD000AA + 4TVR0115BD000AA +
4TVR0521BD000AA
4TV R0580BK000AA 4TVR0140BK000AA*2+4TVR0155BK000AA*2 580,000 521000
170 54 60 152 64 64
4TVR0155BD000AA 2
4TVR0605BK000AA 4TVR0140BK000AA+4TVR0155BK000AA*3 605,000 175 62 64
4TVR0096BD000AA + 4TVR0140BD000AA +
4TVR0546BD000AA 546000 56 158 64
4TVR0620BK000AA 4TVR0155BK004TVV0155AD000AA
0 A A *4 2 620,000 180 64 64

4TVR0561BD000AA 4TVR0140BD000AA 3 + 4TVV0155AD000AA 561000 58 165 64

4TVR0580BK000AA 4TVR0140BK000AA 2 + 4TVR0155BK000AA 2 580000 60 170 64

4TVR0605BD000AA 4TVR0140BD000AA + 4TVR0155BD000AA 3 605000 62 175 64

4TVR0620BD000AA 4TVR0155BD000AA 4 620000 64 180 64

Note:
The system enables the connection of indoor units with a total capacity within 50% to 130% of that of the corresponding outdoor unit, but
when this capacity ratio exceeds 100% then the actual capacity of each indoor unit will decrease compared to rated capacity when all the
units operate simultaneously.

65
TVR 5G (All Inverter + T3/High Ambient)
Combination of Outdoor Units

Capacity Capacity
Capacity Maximum Indoor
Model Number Outdoor Unit Model Number Outdoor Unit Maximum indoor Units
Model Number Outdoor Unit Module Combination Btu / Hr HP HP kW Units Combination
Combination
Btu/h HP kW
4TVVT086BD000AA 4TVVT086BD000AA 86000 8 25 13
4TVVT086BK000AA 4TVVT086BK000AA 86,000 8 25 13
4TVVT096BD000AA 4TVVT096BD000AA 95500 10 28 16
4TVVT096BK000AA 4TVVT096BK000AA 95,500 10 28 16
4TVVT115BD000AA 4TVVT115BD000AA 114300 12 34 20
4TVVT115BK000AA
4TVVT140BD000AA 4TVVT115BK000AA
4TVVT140BD000AA 114,300 14 1240 34 20
136500 23
4TVVT155BD000AA
4TVVT140BK000AA 4TVVT155BD000AA
4TVVT140BK000AA 136,500 16
153500 1445 40 26 23

4TVVT182BD000AA
4TVVT155BK000AA 4TVVT182BD000AA
4TVVT155BK000AA 170600
153,500 18 1650 45 29 26

4TVVT182BK000AA 4TVVT182BK000AA 170,600 18 50 29

4TVVT192BD000AA 4TVVT096BD000AA + 4TVVT096BD000AA 191100 20 56 33


4TVVT192BK000AA 4TVVT096BK000AA*2 191,100 20 56 33
4TVVT211BD000AA 4TVVT096BD000AA + 4TVVT115BD000AA 209800 22 62 36
4TVVT211BK000AA 4TVVT096BK000AA+4TVVT115BK000AA 209,800 22 62 36
4TVVT236BD000AA 4TVVT096BD000AA + 4TVVT140BD000AA 232000 24 68 39
4TVVT236BK000AA 4TVVT096BK000AA+4TVVT140BK000AA 232,000 24 68 39
4TVVT251BD000AA 4TVVT096BD000AA + 4TVVT155BD000AA 249100 26 73 43
4TVVT251BK000AA 4TVVT096BK000AA+4TVVT155BK000AA 249,100 26 73 43
4TVVT278BD000AA 4TVVT096BD000AA + 4TVVT182BD000AA 266100 28 78 46
4TVVT278BK000AA 4TVVT096BK000AA+4TVVT182BK000AA 266,100 28 78 46
4TVVT295BD000AA 4TVVT140BD000AA + 4TVVT155BD000AA 290000 30 85 50
4TVVT322BD000AA
4TVVT295BK000AA 4TVVT140BD000AA + 4TVVT182BD000AA
4TVVT140BK000AA+4TVVT155BK000AA 307100
290,000 32 3090 85 53 50

4TVVT337BD000AA
4TVVT322BK000AA 4TVVT155BD000AA + 4TVVT182BD000AA
4TVVT140BK000AA+4TVVT182BK000AA 327100
307,100 34 3295 90 56 53

4TVVT364BD000AA
4TVVT337BK000AA 4TVVT182BD000AA + 4TVVT182BD000AA
4TVVT155BK000AA+4TVVT182BK000AA 341200
327,600 36 34100 95 59 56

4TVVT364BK000AA 4TVVT182BK000AA*2 341,200 36 100 59

4TVVT374BD000AA 4TVVT096BD000AA + 4TVVT096BD000AA + 4TVVT182BD000AA 363400 38 106 63


4TVVT374BK000AA 4TVVT096BK000AA*2+4TVVT182BK000AA 363,400 38 106 63

4TVVT391BD000AA
4TVVT391BK000AA 4TVVT096BD000AA + 4TVVT140BD000AA + 4TVVT155BD000AA
4TVVT096BK000AA+4TVVT140BK000AA+4TVVT155BK000AA 385,600 40
385600 40113 113 64 64

4TVVT406BD000AA
4TVVT406BK000AA
4TVVT096BD000AA + 4TVVT155BD000AA + 4TVVT155BD000AA
4TVVT096BK000AA+4TVVT155BK000AA*2 402,600 42
402600 42118 118 64 64

4TVVT433BD000AA 4TVVT096BD000AA + 4TVVT155BD000AA + 4TVVT182BD000AA 419700 44 123 64


4TVVT433BK000AA 4TVVT096BK000AA+4TVVT155BK000AA+4TVVT182BK000AA 419,700 44 123 64

4TVVT460BD000AA 4TVVT096BD000AA + 4TVVT182BD000AA + 4TVVT182BD000AA 443600 46 130 64


4TVVT460BK000AA 4TVVT096BK000AA+4TVVT182BK000AA+*2 443,600 46 130 64

4TVVT477BD000AA 4TVVT140BD000AA + 4TVVT155BD000AA + 4TVVT182BD000AA 460600 64


4TVVT477BK000AA 4TVVT140BK000AA+4TVVT155BK000AA+4TVVT182BK000AA 460,600 48 48135 135 64

4TVVT504BD000AA 4TVVT140BD000AA + 4TVVT182BD000AA + 4TVVT182BD000AA 477700 50 140 64


4TVVT504BK000AA 4TVVT140BK000AA+4TVVT182BK000AA*2 477,700 50 140 64

4TVVT519BD000AA
4TVVT519BK000AA 4TVVT155BD000AA + 4TVVT182BD000AA + 4TVVT182BD000AA
4TVVT155BK000AA+4TVVT182BK000AA*2 494,700 52
494700 52145 145 64 64

4TVVT546BD000AA
4TVVT546BK000AA 4TVVT182BD000AA + 4TVVT182BD000AA + 4TVVT182BD000AA
4TVVT182BK000AA*3
511800
511,800
54 54
150 150
64 64

4TVVT556BK000AA 4TVVT096BK000AA*2+4TVVT182BK000AA*2 532,300 56 156 64


4TVVT096BD000AA + 4TVVT096BD000AA + 532300 56 156 64
4TVVT566BD000AA
4TVVT573BK000AA 4TVVT182BD000AA + 4TVVT182BD000AA
4TVVT096BK000AA+4TVVT140BK000AA+4TVVT155BK000AA+4TVVT182BK000AA 556,200 58 163 64
4TVVT096BD000AA + 4TVVT140BD000AA +
4T4TVVT576BD000AA
VVT600BK000AA 4TV4TVVT155BD000AA
VT096BK000AA+4TVVT+144TVVT182BD000AA
0BK000AA+4TVVT182BK000AA*2 573,200 58
556200 60163 168 64 64
4TVVT096BK000AA + 4TVVT140BK000AA +
4T4TVVT600BK000AA
VVT615BK000AA 4TV4TVVT182BK000AA
VT096BK000AA+4TVVT+154TVVT182BK000AA
5BK000AA+4TVVT182BK000AA*2 573200
590,300
62 62
168 173 64 64

4TVVT615BD000AA 4TVVT096BD000AA + 4TVVT155BD000AA + 590300 64


4TVVT642BK000AA 4TVVT096BK000AA+4TVVT182BK000AA*3
4TVVT182BD000AA + 4TVVT182BD000AA 607,300 62 64173 178 64
4TVVT096BD000AA + 4TVVT182BD000AA + 607300 64 178 64
4TVVT642BD000AA
4TVVT659BK000AA 4TV4TVVT182BD000AA
VT140BK000AA+4TVVT+
154TVVT182BD000AA
5BK000AA+4TVVT182BK000AA*2 631,200 66 185 64
4TVVT140BD000AA + 4TVVT155BD000AA + 631200 64
4TVVT659BD000AA
4TVVT686BK000AA 4TVVT182BD000AA + 4TVVT182BD000AA
4TVVT140BK000AA+4TVVT182BK000AA*3 648,300 66 68185 190 64
4TVVT140BD000AA + 4TVVT182BD000AA + 648300 68 64
4TVVT686BD000AA
4TVVT701BK000AA 4TVVT155BK000AA+4TVVT182BK000AA*3
4TVVT182BD000AA + 4TVVT182BD000AA 665,300 70190 195 64
4TVVT155BD000AA + 4TVVT182BD000AA + 70
4TVVT701BD000AA
4TVVT728BK000AA 4TVVT182BK000AA*4
4TVVT182BD000AA + 4TVVT182BD000AA
665300
682,400 72195 200 64 64
4TVVT182BD000AA + 4TVVT182BD000AA + 682400 70 200 64
4TVVT728BD000AA 4TVVT182BD000AA + 4TVVT182BD000AA
Note:
The system enables the connection of indoor units with a total capacity within 50% to 130% of that of the corresponding outdoor unit, but
when this capacity ratio exceeds 100% then the actual capacity of each indoor unit will decrease compared to rated capacity when all the
units operate simultaneously.

66
Indoor Units Lineup

One-way Cassette
Two-way Cassette
Compact Four-way Cassette
Four-way Cassette
Low Static Pressure Duct
Concealed Duct Unit (A5 Type)
High Static Pressure Duct
Ceiling&Floor
Wall-mounted
Console
Fresh Air Processing Unit

67
Offering Summary
Indoor Units Offering Summary
TVR Indoor Units

Indoor Unit capacity in Kw 1.8 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 10 11.2 12.5 14 16 20 25 28 40 45 56

Indoor unit capacity in Btu/hr 6,000 7,500 9,500 12,300 15,000 19,000 24,000 27,000 31,000 34,1000 38,000 42,000 48,000 55,000 75,000 85,300 95,500 140,000 155,000 190,000

Low Static Pressure Duct x x x x x x

Medium Static Pressure Duct x x x x x x x x x x

High Static Pressure Duct x x x x x x x x x x x x

Full fresh air Duct x x x x x

One-way Cassette x x x x x x

Two-way Cassett x x x x x x

New Compact cassette 360 x x x x

Four-way Cassette standard x x x x x x x x x x

High Wall (A-series) x x x x x

High Wall (B-series) x x x x x


High Wall (R-series) x x x

Convertible x x x x x x x x x

Console x x x x

23

68
Description Summary -
Indoor Units Range
Model number TYPE OF UNITS BTU/H Capacity (kW)

4TVL0006A10WEAA New Ducted -Low Static Pressure (5 Pa) 6 1.8

4TVL0007A10WEAA New Ducted -Low Static Pressure (5 Pa) 8 2.2

4TVL0009A10WEAA New Ducted -Low Static Pressure (5 Pa) 10 2.8


4TVL0012A10WEAA New Ducted -Low Static Pressure (5 Pa) 12 3.6

4TVL0015A10WEAA New Ducted -Low Static Pressure (5 Pa) 15 4.5

4TVL0019A10WEAA New Ducted -Low Static Pressure (5 Pa) 19 5.6

4TVD0007A10WEAA Ducted -Medium Static Pressure (10-100 Pa) 8 1.8


4TVD0009A10WEAA Ducted -Medium Static Pressure (10-100 Pa) 10 2.8
4TVD0012A10WEAA Ducted -Medium Static Pressure (10-100 Pa) 12 3.6
4TVD0015A10WEAA Ducted -Medium Static Pressure (10-100 Pa) 15 4.5
4TVD0019A10WEAA Ducted -Medium Static Pressure (10-100 Pa) 19 5.6
4TVD0024A10WEAA Ducted -Medium Static Pressure (10-100 Pa) 24 7
4TVD0027A10WEAA Ducted -Medium Static Pressure (10-100 Pa) 27 8
4TVD0031A10WEAA Ducted -Medium Static Pressure (10-100 Pa) 31 9
4TVD0038A10WEAA Ducted -Medium Static Pressure (10-100 Pa) 38 11
4TVD0048A10WEAA Ducted -Medium Static Pressure (10-100 Pa) 48 14

4TVH0024A10WEAA Ducted -High Static Pressure (30 - 196 Pa) 24 7

4TVH0027A10WEAA Ducted -High Static Pressure (30 - 196 Pa) 27 8

4TVH0030A10WEAA Ducted -High Static Pressure (30 - 196 Pa) 31 9

4TVH0038A10WEAA Ducted -High Static Pressure (30 - 196 Pa) 38 11

4TVH0048A10WEAA Ducted -High Static Pressure (30 - 196 Pa) 48 14

4TVH0055A10WEAA Ducted -High Static Pressure (30 - 196 Pa) 55 16

4TVH0140A10WEAA Ducted -High Static Pressure (30 - 196 Pa) 136 40

4TVH0155A10WEAA Ducted -High Static Pressure (30 - 196 Pa) 154 45

4TVF0042A10WEAA Ducted -Full Fresh Air 43 12.5

4TVF0048A10WEAA Ducted -Full Fresh Air 48 14

4TVF0075A10WEAA Ducted -Full Fresh Air 68 20

4TVF0085A10WEAA Ducted -Full Fresh Air 85 25

4TVF0096A10WEAA Ducted -Full Fresh Air 96 28

4TVA0006A10REAA 1-Way-Cassette 6 1.8

4TVA0007A10REAA 1-Way-Cassette 8 2.2

4TVA0009A10REAA 1-Way-Cassette 10 2.8

4TVA0012A10REAA 1-Way-Cassette 12 3.6

4TVA0015A10REAA 1-Way-Cassette 15 4.5

4TVA0019A10REAA 1-Way-Cassette 19 5.6

69
09
Description Summary -
Indoor Units Range
Model number TYPE OF UNITS BTU/H Capacity (kW)

4TVE0007A10REAA 2-Way-Cassette 8 2.2

4TVE0009A10REAA 2-Way-Cassette 10 2.2

4TVE0012A10REAA 2-Way-Cassette 12 2.8

4TVE0015A10REAA 2-Way-Cassette 15 3.6

4TVE0018A10REAA 2-Way-Cassette 19 4.5

4TVE0024A10REAA 2-Way-Cassette 24 7.1

4TVB0007A10REAA 4 Way-Cassette Compact 360 8 2.2

4TVB0009A10REAA 4 Way-Cassette Compact 360 10 2.8

4TVB0012A10REAA 4 Way-Cassette Compact 360 12 3.6

4TVB0015A10REAA 4 Way-Cassette Compact 360 15 4.5

4TVC0009A10REAA 4 Way-Cassette Standard 10 2.8

4TVC0012A10REAA 4 Way-Cassette Standard 12 3.6

4TVC0015A10REAA 4 Way-Cassette Standard 15 4.5

4TVC0018A10REAA 4 Way-Cassette Standard 19 5.6

4TVC0024A10REAA 4 Way-Cassette Standard 24 7

4TVC0027A10REAA 4 Way-Cassette Standard 27 8

4TVC0030A10REAA 4 Way-Cassette Standard 31 9

4TVC0034A10REAA 4 Way-Cassette Standard 34 10

4TVC0038A10REAA 4 Way-Cassette Standard 38 11.2

4TVC0048A10REAA 4 Way-Cassette Standard 48 14

4TVW0007A10REBA Hi Wall S series 8 2.2

4TVW0009A10REBA Hi Wall S series 10 2.8

4TVW0012A10REBA Hi Wall S series 12 3.6

4TVW0015A10REBA Hi Wall S series 15 4.5

4TVW0018A10REBA Hi Wall S series 19 5.6

4TVW0007A1HREBA Hi Wall S series with Electric Heat 8 2.2

4TVW0009A1HREBA Hi Wall S series with Electric Heat 10 2.8

4TVW0012A1HREBA Hi Wall S series with Electric Heat 12 3.6

4TVW0015A1HREBA Hi Wall S series with Electric Heat 15 4.5

4TVW0018A1HREBA Hi Wall S series with Electric Heat 19 5.6

4TVW0007A10REAA Hi Wall C series 8 2.2

4TVW0009A10REAA Hi Wall C series 10 2.8

4TVW0012A10REAA Hi Wall C series 12 3.6

4TVW0015A10REAA Hi Wall C series 15 4.5

4TVW0018A10REAA Hi Wall C series 19 5.6

70
Description Summary -
Indoor Units Range
Model number TYPE OF UNITS BTU/H Capacity (kW)

4TVW0007A1HREAA Hi Wall C series with Electric Heat 8 2.2

4TVW0009A1HREAA Hi Wall C series with Electric Heat 10 2.8

4TVW0012A1HREAA Hi Wall C series with Electric Heat 12 3.6

4TVW0015A1HREAA Hi Wall C series with Electric Heat 15 4.5

4TVW0018A1HREAA Hi Wall C series with Electric Heat 19 5.6

4TVW0024A10REAA Hi Wall R series 24 7

4TVW0027A10REAA Hi Wall R series 27 8

4TVW0031A10REAA Hi Wall R series 31 9

4TVX0012A10REAA Convertible (Floor/Ceiling) 12 3.6

4TVX0015A10REAA Convertible (Floor/Ceiling) 15 4.5

4TVX0018A10REAA Convertible (Floor/Ceiling) 19 5.6

4TVX0024A10REAA Convertible (Floor/Ceiling) 24 7.1

4TVX0027A10REAA Convertible (Floor/Ceiling) 27 8

4TVX0030A10REAA Convertible (Floor/Ceiling) 31 9

4TVX0038A10REAA Convertible (Floor/Ceiling) 38 11

4TVX0048A10REAA Convertible (Floor/Ceiling) 48 14

4TVX0055A10REAA Convertible (Floor/Ceiling) 55 16

4TVG0007A10REAA Console 8 2.2

4TVG0007A10REAA Console 10 2.8

4TVG0007A10REAA Console 12 3.6

4TVG0007A10REAA Console 15 4.5

26

71
09
One-way Cassette
Indoor Units Lineup
One-way Cassette Power supply
Model

Auto Restart Fresh Air


Power supply
Cooling capacity
Auto Addressing Cleanable Panel
Auto Restart Fresh Air

Cooling capacity
Follow Me
Auto Addressing Anti-Cold Air Function
Cleanable Panel

FollowLED
LED Me Display Super
Anti-Cold High Air Flow
Air Function
DISPLAY Heating capacity

Built-in Drain Pump


LED LED Display Super High Air Flow
DISPLAY Heating capacity

Built-in Drain Pump

Thickness 6-1/32in.(153mm) only Auto swing


Rated input

Cooling

Thickness 6-1/32in.(153mm) only thickness of Auto swing


Rated input
Compact design,ultra slim body with a minimum Auto swing mechanism guarantees even
Heating
6-1/32in.(153mm) for model 18-36,especially suitable for distribution of airflow and better balance Rated current
Compact design,ultra slim body with a minimum thickness of Auto swing mechanism guarantees even
narrow ceiling , such as in lobbies and small meeting rooms. of room temperature. Cooling
6-1/32in.(153mm) for model 18-36,especially suitable for distribution of airflow and better balance Rated current
Heating
narrow ceiling , such as in lobbies and small meeting rooms. of room temperature.
Airflow rateH/M/L

Airflow rateH/M/L
Thickness 6-1/32in.
Sound pressure lev
(153mm) only UItra Thin
Thickness 6-1/32in.
Sound pressure level(H/M/L)
(153mm) only UItra Thin Single-flow design suits Refrigerant
Standard built-in drain pump with 29-17/32in.(750mm) pump corner installation
Single-flow design suits Refrigerant
head. built-in drain pump with 29-17/32in.(750mm) pump
Standard corner installation

head. Net dim.(W


Indoor Unit

29-17/32in.(750mm) Indoor Unit Gross dim.(

29-17/32in.(750mm) NetGross

Net dim.(W
Panel

Fresh air, improved air quality Panel Gross dim.(

Fresh air, improved air quality


NetGross
Reserved fresh air intake port for high quality air Special enzyme sterilization and filtering technology
supply requirement,
Reserved create
fresh air intake portafor
comfort and healthy
high quality air can enzyme
Special filter thesterilization
bacteria, and
smog, pollen,
filtering etc. Provide
technology L(flare)
supply requirement, create a comfort and healthy
environment. can plenty
filter the bacteria,
clean, healthysmog, pollen,airetc.
and natural Provide
supply. Piping connections
environment. plenty clean, healthy and natural air supply. Piping connections G(flare)

Drain pipin
Standard Controlle
Standard Controller

Notes:
Notes: 1. Nominal cooling cap
(horizontal)
1. Nominal cooling capacities are ba
(horizontal)
2. Nominal heating cap
Acetaldehyde 2. Nominal heating capacities are b
(horizontal)
Acetaldehyde (horizontal)
3. Sound Level is mea
3. Sound Level is measured 4.59ft(1
Acetic acid Formol NH3
Acetic acid Formol NH3

72
Model 4TVA0006A10REAA 4TVA0007A10REAA 4TVA0009A10REAA 4TVA0012A10REAA 4TVA0015A10REAA 4TVA0019A10REAA

Power supply 1-phase,208-230V,60Hz 1-phase,220-240V,60Hz

kW 1.8 2.2 2.8 3.6 4.5 5.6

Cooling capacity kcal/h 1500 1900 2400 3100 3900 4800

Btu/h 6100 7500 9600 12300 15400 19100

kW 2.2 2.6 3.2 4 5 6.3

Heating capacity kcal/h 1900 2200 2800 3400 4300 5400

Btu/h 7500 8900 10900 13600 17100 21500

Cooling 41 41 41 41 80 85
Rated input W
Heating 41 41 41 41 80 85

Cooling 0.24 0.24 0.25 0.25 0.37 0.39


Rated current A
Heating 0.24 0.24 0.25 0.25 0.37 0.39

m3/h 523/404/275 523/404/275 573/456/315 573/456/315 704/630/503 860/810/702


Airflow rateH/M/L
CFM 308/238/162 308/238/162 337/268/185 337/268/185 414/370/296 506/476/413

Sound pressure level(H/M/L) dB(A) 37/34/30 38/34/30 39/37/34 40/38/34 41/39/35 42/40/36

Type R410A
Refrigerant Control
method EXV

45-5/327-7/825-13/64
Net dim.(WHD) 41-1/26-21/3216-47/64(1054169425) (1147200640)
in.(mm)
54-21/6410-7/1630-33/64
Indoor Unit Gross dim.(WHD) 45-15/329-41/6419-19/64(1155245490) (1380265775)

27.8/35.3(12.5/16) 28.8/36.4(13/16.5) (69.5/82.1)31.5/37.2


NetGross lbs.(kg)

46-29/641-7/1618-5/16 46-29/641-7/1618-5/16 56-7/6425/6429-23/32


Net dim.(WHD) (118036.5465) (118036.5465) (142510755)
in.(mm)
48-1/24-7/3220-23/64 48-1/24-7/3220-23/64 59-1/164-21/6434-1/4
Panel Gross dim.(WHD) (1232107517) (1232107517) (1500110870)

NetGross lbs.(kg) 7.7/11.5(3.5/5.2) 7.7/11.5(3.5/5.2) 19.6/26.5(9/12)

L(flare) in.(mm) 1/4 ( 6.35) 1/4( 6.35) 1/4( 6.35) 3/8( 9.53)

Piping connections G(flare) in.(mm) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 5/8( 15.9)

Drain piping in.(mm) OD 63/64( 25) OD 63/64( 25) OD 63/64( 25)

Standard Controller Wireless remote controller (TCONTRM05A)

Notes:
1. Nominal cooling capacities are based on the following conditions: return air temp. : 80.6F(27C)DB,66.2F(19C)WB,and outdoor temp.: 95F(35C)DB,equivalent ref. piping: 26.25ft. (8m)
(horizontal)
2. Nominal heating capacities are based on the following conditions: return air temp.: 68F(20C)DB, outdoor temp.: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref. Piping: 26.25ft. (8m)
(horizontal)
3. Sound Level is measured 4.59ft(1.4m) below the unit

73
Indoor Units Lineup
Two-way Cassette
Power

Coolin
Auto Restart Fresh Air

Auto Addressing Cleanable Panel

Follow Me Anti-Cold Air Function


Heatin

LED LED Display Super High Air Flow


DISPLAY

Built-in Drain Pump Power

Rated

Quiet operation High airflow


Airflow

Optimized airflow duct with low resistance makes High airflow for high ceiling application guaran-
noise level get reduced greatly, min. 24dB(A). tees equal comfort of large space. It makes Sound

every customer of the room get even distribu-


Stylish design and slim body tion of airflow and temperature.
Refrige

Thanks to the stylish appearance and slim body, the


unit can be harmonious with the room decoration and
ambient. Slim body with only 11-13/16in.(300mm) Body
height needs small suspended ceiling space. Installa-
tion is free of story height limitation which makes the
decoration much more flexible.
Panel

12in.(305mm)
11-13/16in.(300mm)

Piping
connec
Standard built-in drain pump with 29-17/32in.(750mm)
pump head (higher pumphead can be customized).
Standa

Notes:
29-17/32in.
1. Nomina
(750mm)
26.25ft(
2. Nomina
26.25ft
3.Sound L

Flat-type suction grille design makes maintenance


work very easy.

74
Model 4TVE0007A10REAA 4TVE0009A10REAA 4TVE0012A10REAA 4TVE0015A10REAA 4TVE0018A10REAA 4TVE0024A10REAA

Power supply 1-phase, 208-230V, 60Hz

kW 2.2 2.8 3.6 4.5 5.6 7.1

Cooling capacity kcal/h 1,900 2,400 3,100 3,900 4,800 6,100

Btu/h 7,500 9600 12,300 15,400 19,100 24,200

kW 2.6 3.2 4 5 6.3 8

kcal/h 2200 2,800 3,400 4,300 5,400 6,900


Heating capacity

Btu/h 8,900 10,900 13,600 17,100 21,500 27,300

Cooling 78 78 83 115 133 205


Power input W
Heating 78 78 83 115 133 205

Cooling 0.35 0.45 0.45 0.55 0.55 0.75


Rated current A
Heating 0.35 0.45 0.45 0.55 0.55 0.75

m3/h 674/509/381 674/509/381 740/577/435 878/689/561 941/776/654 1,236/1,110/864


Airflow rate(H/M/L)
CFM 397/300/224 397/300/224 436/340/256 517/406/330 554/457/385 727/653/509

Sound pressure level(H/M/L) dB(A) 33/29/24 36/32/29 36/32/29 39/35/30 39/35/30 44/40/34

Type R410A
Refrigerant Control
method EXV

Net dim.(WHD) 46-9/3211-49/6423-17/64(1172299591)


in.(mm)

Body Gross dim.(WHD) 53-11/3215-3/426-37/64(1355400675)

Net/gross lbs.(kg) 75/94(34/42.5) 75/94(34/42.5) 75/94(34/42.5) 80.5/99(36.5/45) 80.5/99(36.5/45) 80.5/99.3(36.5/45)

Net dim.(WHD) 56-19/642-3/3226-49/64(143053680)


in.(mm)
Panel Gross dim.(WHD) 60-3/645-1/830-1/8(1525130765)

Net/gross lbs.(kg) 23/33(10.5/15) 23/33(10.5/15) 23/33(10.5/15) 23/33(10.5/15) 23/33(10.5/15) 23/33(10.5/15)

L(flare) in.(mm) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 3/8(9.53) 3/8(9.53)

Piping
G(flare) in.(mm) 1/2(12.7) 1/2(12.7) 1/2(12.7) 1/2(12.7) 5/8(15.9) 5/8(15.9)
connections

Drain piping in.(mm) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32)

Standard Controller - Wireless remote controller (TCONTRM05A)

Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature : 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref. piping:
26.25ft(8m) (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB,outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref. piping:
26.25ft (8m) (horizontal)
3.Sound Level is measured 4.59ft.(1.4m) below the unit

75
Indoor
Compact Four-way Units
Cassette Lineup
Compact Four-way Cassette
Model 4TVB0007A10

Power supply

Auto Restart Fresh Air kW 2.2

Cooling capacity kcal/h 1,900


Auto Restart Fresh Air
Auto Addressing Cleanable Panel
Btu/h 7,500
Auto Addressing Cleanable Panel
kW 2.4
Follow Me Anti-Cold Air Function
Follow Me Anti-Cold Air Function kcal/h
Heating capacity 2,100

Built-in Drain Pump


Built-in Drain Pump LED LED Display Btu/h 8,200
LED LED Display
DISPLAY
DISPLAY

Cooling 51
Super High Air Flow
Super High Air Flow Power input W
Heating 43

Cooling 0.175
Rated current A
Heating 0.175

Compact design, easy installation and maintenance m3/h 532/397/292

Compact design, easy installation


m)
Extremely compactand maintenance
casing makes
(22-7
/16init perfectly match with
(570
mm)
Airflow rate(SH/H/M/L)
CFM 313/234/172

(57
0m the ambient decoration. Little space is required for
6in
(22-7
/1 (22-7
Extremely compact casing makes it perfectly
/16in installation into a shallow ceiling.
(570
match with
Sound pressure level(H/M/L) dB(A) 35.8/33.4/2

) mm)
0 mm Due to its compact body and light weight, all models can
the ambient decoration. Little space is required for Type
(57
in be installed without a hoist.
/16 Refrigerant
(22
-7 installation into a shallow ceiling. Control method

Due to its compact body and light weight, all models can
Net dim.(WHD)
in.(mm)
be installed without a hoist. Body
Gross dim.(WHD)

Quiet operation, soft air supply Uniform air flow of four ways Net/gross lbs.(kg) 35.3/44.1/(16
Indoor Units Lineup

Net dim.(WHD)
Diffuser in.(mm)
Panel Gross dim.(WHD)

Quiet operation,
3-D spiral fan bladesoft air supply Uniform air flow of four ways Net/gross lbs.(kg) 6.6/11(3/5

in.(mm) 1/4(6.35
Indoor Units Lineup

L(flare)
Streamline plate ensures quietness The four air discharge port provides strong circulating Piping
Diffuser G(flare) in.(mm) 1/2(12.7
Advanced 3-D spiral fan design reduces the air air flow to cool or heat every corner of the room and connections
resistance and operation noise. realizes even temperature distribution; by choosing high Drain piping OD 63/64( 2
in.(mm)
airflow mode, high ceiling application over 1/8in.(3m)
3-D spiral fan can
blade get equal comfort. Standard Controller

360Airflow outlet Lift pump Notes:


1. Nominal cooling capacities are based on the following conditions: return air t
Streamline plate ensures quietness The four air discharge port provides strong circulating
26.25ft (8m) (horizontal)
2. Nominal heating capacities are based on the following conditions: return air t
Advanced 360air outlet fan
3-D spiral provides strong
design reduces the air air flow to cool or heat every corner of 26.25ft
the(8m)room and
(horizontal)

resistancecirculating air flow to cool or 19-11/16 in. 3.Sound Level is measured 4.59ft. (1.4m) below the unit.
and operation noise. realizes even temperature
(500mm)
distribution; by choosing high
heat every corner of the room
airflow mode, high ceiling application over 1/8in.(3m)
and realizes even temperature
can get equal comfort.
distribution. Drain up pump with 19-11/16 in.(500mm) pump head
fitted as standard, max. up to 600mm pump head.
360Airflow outlet Lift pump N

360air outlet provides strong


circulating air flow to cool or 19-11/16 in.
(500mm)
heat every corner of the room
and realizes even temperature
distribution. Drain up pump with 19-11/16 in.(500mm) pump head
fitted as standard, max. up to 600mm pump head.

76
Model 4TVB0007A10REAA 4TVB009A10REAA 4TVB0012A10REAA 4TVB0015A10REAA

Power supply 1-phase, 208-230V 60Hz

kW 2.2 2.8 3.6 4.5

Cooling capacity kcal/h 1,900 2,400 3,100 3,900

Btu/h 7,500 9,600 12,300 15,400

kW 2.4 3.2 4 5

kcal/h 2,100 2,800 3,400 4,300


Heating capacity

Btu/h 8,200 10,900 13,600 17,100

Cooling 51 52 58 58
Power input W
Heating 43 44 50 51

Cooling 0.175 0.175 0.21 0.21


Rated current A
Heating 0.175 0.175 0.21 0.21

m3/h 532/397/292/215 539/408/310/231 632/496/359/263 632/496/359/263


Airflow rate(SH/H/M/L)
CFM 313/234/172/127 317/240/182/136 372/292/211/155 372/292/211/155

Sound pressure level(H/M/L) dB(A) 35.8/33.4/23.4 35.8/33.4/23.4 41.5/35.6/28.8 41.5/35.6/28.8

Type R410A
Refrigerant
Control method EXV

Net dim.(WHD) 22-7/1610-15/6422-7/16(570260570)


in.(mm)
Gross dim.(WHD) 26-9/1611-7/3226-9/16(675285675)
Body

Net/gross lbs.(kg) 35.3/44.1/(16/20) 35.3/44.1/(16/20) 39.7/48.5(18/22) 39.7/48.5(18/22)

Net dim.(WHD) 25-15/321-31/3225-15/2(64750647)


in.(mm)
Panel Gross dim.(WHD) 28-5/324-27/3228-5/32 (715123715)

Net/gross lbs.(kg) 6.6/11(3/5) 6.6/11(3/5) 6.6/11(3/5) 6.6/11(3/5)

L(flare) in.(mm) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35)

Piping
G(flare) in.(mm) 1/2(12.7) 1/2(12.7) 1/2(12.7) 1/2(12.7)
connections

Drain piping in.(mm) OD 63/64( 25) OD 63/64( 25) OD 63/64( 25) OD 63/64( 25)

Standard Controller Wireless remote controller (TCONTRM05A)

Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature : 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref. piping:
26.25ft (8m) (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB,outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref. piping:
26.25ft (8m) (horizontal)
3.Sound Level is measured 4.59ft. (1.4m) below the unit.

77
Indoor Units Lineup
Four-way Cassette
Four-way Cassette
Model

Power supply Power supply

Cooling capacity Cooling capac


Auto Restart Fresh Air
Auto Restart Fresh Air

Auto AddressingAuto Addressing


Cleanable Panel Cleanable Panel Heating capacity Heating capac

Follow Me Cooling
Follow MeAnti-Cold Air Function
Anti-Cold Air Function Power input Power input
Heating
Cooling
Built-in Drain Pump
Built-in LED
LED Drain Display
Pump LED Display Rated current Rated current
DISPLAY
LED Heating
DISPLAY

Airflow rate(SH/H/M/L)
Airflow rate(SH
Super High Air Flow
Super High Air Flow
Sound pressure level(H/M/L)
Sound pressu

Refrigerant Refrigerant

Quiet operation, soft air supply


Quiet operation, soft air supply Four-way airflow(4-stage fan speed)fan speed)
Four-way airflow(4-stage Net dim.(WHD)
Body GrossBody
dim.(WHD)
Streamline plate ensures
Streamline quietness
plate ensures quietness Net/gross
Advanced 3-DAdvanced 3-D spiralreduces
spiral fan design the reduces
fan design air the air Net dim.(WHD)
Panel dim.(WHD)
GrossPanel
resistance and operation noise.
resistance and operation noise.
Net/gross
L(flare)
Piping Piping
Diffuser Diffuser connections
G(flare)
connections
Drain piping
Standard Controller Standard Con
3-D spiral fan blade
3-D spiral fan blade

Model

Easy troubleshooting
Easy troubleshooting Uniform Uniform
airflow ofairflow
four ways
of four ways Power supply Power supply

By adding digital tube displayer


By adding on displayer
digital tube the display
onboard, The four air discharge
the display board, portdischarge
The four air provides port
strong circulating
provides strong circulating Cooling capacity Cooling capac
the Error Codes can be
the Error displayed
Codes can bedirectly on it directly
displayed which on it which
air flow to cool
airor heat
flow to every
cool orcorner of thecorner
heat every room andof the room and
helps to find helps
and shoot the
to find andtrouble.
shoot the trouble. realizes evenrealizes
temperature distribution; by choosing by choosing
even temperature distribution;
Heating capacity
high airflowhigh
mode, high mode,
airflow ceiling high
application over
ceiling application over Heating capac
Indoor Units Lineup

Indoor Units Lineup

1/8in.(3m) can get equal


1/8in.(3m) comfort.
can get equal comfort. Cooling
Power input Power input
Heating

360Airflow outlet outlet


360Airflow Reserved multi-function
Reserved ports ports
multi-function Rated current
Cooling
Rated current
Heating

360air outlet360air
provides strong
outlet provides strong Airflow rate(SH/H/M/L)
Airflow rate(SH

circulating aircirculating
flow to cool
air or
flow to cool or To another room
Sound pressure level(H/M/L)
Sound pressu
To another room
heat every corner of thecorner
heat every room of the room
Refrigerant Refrigerant
Fresh Air Intake
and realizes and
evenrealizes even Fresh Air Intake
Net dim.(WHD)
temperature temperature
distribution distribution Body GrossBody
dim.(WHD)
Net/gross

High lift pump


High lift pump Panel
Net dim.(WHD)
GrossPanel
dim.(WHD)

Drain pump can take


Drain pumpup the
cancondenser
take up thewater to
condenser water toUltra-thin machine body
Ultra-thin for easy
machine installation
body for easyand
installation and Net/gross

750mm which helps which


750mm to make easier
helps installation
to make maintenance,
easierofinstallation of min. 230mmmin.
maintenance, in height.
230mm in height. Piping
L(flare)
Piping
G(flare)
the drain piping
the system.
drain piping system. connections connections
Drain piping
Standard Controller Standard Con

29-17/32in. 29-17/32in. 9-1/16in.(230mm)


9-1/16in.(230mm) Notes: Notes:
(750mm) (750mm) 1. Nominal cooling capacities arecool
ba
1. Nominal
26.25ft. (8m) (horizontal)
26.25ft. (8m)
2. Nominal heating capacities
2. Nominalare ba
hea
26.25ft. (8m) (horizontal)
26.25ft. (8m)
3. Sound Level is measured
3. Sound4.59ft.
Level(

78
Power supply
Model
Indoor Units Lineup
4TVC0009A10REAA 4TVC0012A10REAA 4TVC0015A10REAA

1-phase, 220-240V, 60Hz


4TVC0018A10REAA 4TVC0024A10REAA

kW 2.8 3.6 4.5 5.6 7.1


Cooling capacity kcal/h 2,400 3,100 3,900 4,800 6,100
Btu/h 9,600 12,300 15,400 19,100 24,200
kW 3.2 4 5 6.3 8
Heating capacity kcal/h 2,800 3,400 4,300 5,400 6,900
Btu/h 10,900 13,600 17,100 21,500 27,300
Cooling 90 90 90 90 115
Power input W
Heating 90 90 90 90 115
Cooling 0.4 0.4 0.4 0.4 0.5
Rated current A
Heating 0.4 0.4 0.4 0.4 0.5

m3/h 1,155/847/766/640 1,155/847/766/640 1,207/864/755/658 1,207/864/755/658 1,327/1,157/955/749


Airflow rate(SH/H/M/L)
CFM 680/499/451/377 680/499/451/377 710/509/444/387 710/509/444/387 781/681/562/441
Sound pressure level(H/M/L) dB(A) 42/38/35 42/38/35 42/38/35 42/38/35 45/42/39
Type R410A
Refrigerant
Control method EXV
Net dim.(WHD) 35-19/329-1/1633-5/64(904230840)
in.(mm)
Body Gross dim.(WHD) 37-19/32x10-15/64x37-19/32(955x260x955)
Net/gross lbs.(kg) 53 /61.7(24/28) 53 /61.7(24/28) 57.3 /66.2(26/30) 57.3 /66.2(26/30) 57.3 /66.2(26/30)
Net dim.(WHD) 37-13/322-9/6437-13/32(95054.5950)
in.(mm)
Panel Gross dim.(WHD) 40-3/43-35/6440-3/4(1,035901,035)
Net/gross lbs.(kg) 11.0/19.9(5/9) 11.0/19.9(5/9) 11.0/19.9(5/9) 11.0/19.9(5/9) 11.0/19.9(5/9)

L(flare) in.(mm) 1/4(6.35) 1/4(6.35) 1/4(6.35) 3/8(9.53) 3/8(9.53)


Piping
G(flare) in.(mm) 1/2(12.7) 1/2(12.7) 1/2(12.7) 5/8(15.9) 5/8(15.9)
connections
Drain piping in.(mm) OD 1-17/64( 32)
Standard Controller - Wireless remote controller (TCONTRM05A)

Model 4TVC0027A10REAA 4TVC0030A10REAA 4TVC0034A10REAA 4TVC0038A10REAA 4TVC0048A10REAA

Power supply 1-phase, 220-240V, 60Hz

kW 8 9 10 11.2 14
Cooling capacity kcal/h 6,900 7,700 8,600 9,600 12,000
Btu/h 27,300 30,700 34,100 38,200 47,800
kW 9 10 11.1 12.5 15
Heating capacity kcal/h 7,700 8,600 9,500 10,800 12,900
Btu/h 30,700 34,100 37,900 42,700 51,200
Cooling 115 160 160 160 180
Power input W
Heating 115 160 160 160 180
Cooling 0.5 0.7 0.7 0.7 0.8
Rated current A
Heating 0.5 0.7 0.7 0.7 0.8

m3/h 1,357/1,236/973/729 1,795/1,590/1,300/1,090 1,795/1,590/1,300/1,090 1,795/1,590/1,300/1,090 1,881/1,678/1,358/1,115


Airflow rate(SH/H/M/L)
CFM 799/727/573/429 1,057/936/765/642 1,057/936/765/642 1,057/936/765/642 1,107/988/799/656
Sound pressure level(H/M/L) dB(A) 45/42/39 48/45/43 48/45/43 48/45/43 50/47/44
Type R410A
Refrigerant
Control method EXV
Net dim.(WHD) 35-19/329-1/1633-5/64(
904230840) 35-19/3211-13/1633-5/64(904300840)
in.(mm)
37-19/32x10-15/64x37-19/ 37-19/32x11-13/16x37-19/32(955x330x955)
Body Gross dim.(WHD)
32(955x260x955)
Net/gross lbs.(kg) 57.3/66(26/30) 70.5/81.6(32/37) 70.5/81.6(32/37) 70.5/81.6(32/37) 70.5/81.6(32/37)
Net dim.(WHD) 37-13/322-9/6437-13/32(95054.5950)
in.(mm)
Panel Gross dim.(WHD) 40-3/43-35/6440-3/4(1,035901,035)
Net/gross lbs.(kg) 11.0/17.6(5/8) 11.0/17.6(5/8) 11.0/17.6(5/8) 11.0/17.6(5/8) 11.0/17.6(5/8)
L(flare) in.(mm) 3/8(9.53) 3/8(9.53) 3/8(9.53) 3/8(9.53) 3/8(9.53)
Piping
G(flare) in.(mm) 5/8(15.9) 5/8(15.9) 5/8(15.9) 5/8(15.9) 5/8(15.9)
connections
Drain piping in.(mm) OD 1-17/64( 32)

Standard Controller - Wireless remote controller (TCONTRM05A)

Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature : 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref. piping:
26.25ft. (8m) (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB,outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref. Piping:
26.25ft. (8m) (horizontal)
3. Sound Level is measured 4.59ft. (1.4m) below the unit
79
Indoor Units Lineup
Model 4TV
Mod

Low Static Pressure


Low Static Duct Duct
Pressure Power supply Power supply208-

kW

Cooling capacity kcal/h


Cooling capacity

Btu/h
Auto Restart Anti-Cold Air Function
Auto Restart Anti-Cold Air Function
kW

Heating capacity kcal/h


Heating capacity
Auto AddressingAuto Addressing
Super High Air Flow
Super High Air Flow
Btu/h

Follow Me Follow Me Rated


Cooling Cooling
Rated W
input input
Heating Heating
Wireless remote Wireless
controllerremote controller Cooling
Rated Rated A Cooling
current current
Heating Heating

m/h 606(3
Airflow rate(SH/H/M/L)
Airflow rate(SH/H/
CFM 3

External Static Pressure


ExternalPa
Static Pres
Sound pressure levelSound pressure le
( H/M/L) dB(A)
( H/M/L)

Low sound
Lowlevel
sound level Refrigerant type
Type
Refrigerant
Control type
type
Dimension Dimensi
(WHD) in.(mm)
(WHD
Utilizes the Utilizes
centrifugal
the type
centrifugal type Packing
Indoor Indoor Packing
(WHD) in.(mm)
unit (WHD
blower, provides a minimum
blower, provides a minimum
unit
Net(Gross) Net(Gro
lbs.(kg)
weight weight
noise level noise
of 24dB (A),of an
level 24dB (A), an L(flare) in.(mm)
L(flare)

excellent choice for choice


hotels for hotels
Piping
excellent
Piping
connections G(flare) in.(mm)
connections G(flare)

and other and


sound-sensitive
other sound-sensitive
Drain piping in.(mm)
Drain pip

Standard Controller Standard Controlle


places. places.
Notes: Notes:
1. Nominal cooling1.capacities
Nominal cooare
V shape
More evaporator--
Smooth
V
More airflow
shape
Smooth good
with lessfor
evaporator--
airflow heat
turbulence
good
with lessfor heat Convenient
turbulence for installation
installation
Convenient for installation
installation
(horizontal)
2. Nominal heating
(horizontal)
capacities
2. Nominal heaare
exchanging
exchanging and maintenance
and maintenance (horizontal) (horizontal)
3.Sound level is measured at 1.4is
3.Sound level
* External static pressure is stati
* External base
V shape evaporator
V shapedesign enhances
evaporator heat
design exchanging
enhances heat exchanging The EXV is fixed inside
The EXV is the indoor
fixed insideunit.
the indoor unit.
efficiency about 22%. about 22%.
efficiency

CompactCompact
design design Options Options
Min.5mm Min.5mm

29-17/32in.(750mm)
29-17/32in.(750mm)
8-17/64in.(210mm)
8-17/64in.(210mm)

Ceiling Ceiling
ceiling ceiling
Uniform 8-17/64in.(210mm) in height, compact
Uniform 8-17/64in.(210mm) in height, compact A drain pump with pump
A drain 29-17/32in.(750mm)
with 29-17/32in.(750mm)
design for easy locate where
design for easy locate space ceiling
where is ceiling is
space pumphead ispumphead
an optionalisaccessory.
an optional accessory.
limited, limited,
The whole body
The adopts fireproof
whole body plastic
adopts material
fireproof plastic material
the minimumthe
weight is 30.9lbs(14kg).
minimum weight is 30.9lbs(14kg).

80
Model 4TVL0006A10WEAA 4TVL0007A10WEAA 4TVL0009A10WEAA 4TVL0012A10WEAA 4TVL0015A10WEAA 4TVL0019A10WEAA 4TVL0024A10WEAA

Power supply 208-230V~1Ph~60Hz 208-230V~1Ph~60Hz 208-230V~1Ph~60Hz 208-230V~1Ph~60Hz 208-230V~1Ph~60Hz 208-230V~1Ph~60Hz 208-230V~1Ph~60Hz

kW 1.8 2.2 2.8 3.6 4.5 5.6 7.1

Cooling capacity kcal/h 1500 1900 2400 3100 3900 4800 6100

Btu/h 6100 7500 9600 12300 15400 19100 24200


ction
kW 2.2 2.6 3.2 4 5 6.3 8

Heating capacity kcal/h 1900 2200 2800 3400 3900 5400 6900
low
Btu/h 7500 8900 10900 13600 17100 21500 27300

Cooling 59 59 59 65 105 105 130


Rated
W
input
Heating 59 59 59 65 105 105 130

Rated Cooling 0.26 0.26 0.26 0.3 0.5 0.5 0.6


current A
Heating 0.26 0.26 0.26 0.3 0.5 0.5 0.6

m/h 606(30pa)/578/512/409 606(30pa)/578/512/409 606(30pa)/578/512/409 646(30pa)/617/551/441 803(30pa)/824/690/609 803(30pa)/824/690/6091207(30pa)/1060/970/811


Airflow rate(SH/H/M/L)
CFM 357/340/301/241 357/340/301/241 357/340/301/241 380/363/324/260 473/485/406/358 473/485/406/358 710/624/571/477

External Static Pressure Pa 10(10~30) 10(10~30) 10(10~30) 10(10~30) 10(10~30) 10(10~30) 10(10~30)
Sound pressure level
( H/M/L) dB(A) 35/27/24 35/27/24 35/27/24 38/32/28 39/32/29 39/32/29 41/33/30

Type R410A R410A R410A R410A R410A R410A R410A


Refrigerant type Control
type EXV EXV EXV EXV EXV EXV EXV

Dimension 46-29/648-17/6418-1/2
in.(mm) 29-9/648-17/6418-1/2(740210470) 37-51/648-17/6418-1/2(960210470)
(WHD) (1180210470)

Indoor Packing
in.(mm) 35-53/649-1/1620-5/64(910230510) 44-31/649-1/1620-5/64(1130230510) 53-5/329-1/1620-5/64
unit (WHD) (1350230510)
Net(Gross)
weight lbs.(kg) 32.0/39.7(14.5/18) 39.7/49.6(18/22.5) 39.7/49.6(18/22.5) 49.6/58.5(22.5/26.5)

L(flare) in.(mm) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 3/8( 9.53) 3/8( 9.53)
Piping
connections G(flare) in.(mm) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 12.7 5/8( 15.9) 5/8( 15.9)

Drain piping in.(mm) OD 63/64( 25)

Standard Controller Wired controller TCONTKJR29BKE (6 meters connection wire)

Notes:
1. Nominal cooling capacities are based on the following conditions: return air temp.: 27CDB, 19CWB, and outdoor temp.:35CDB, equivalent ref. piping: 8m
(horizontal)

Indoor Units Lineup


2. Nominal heating capacities are based on the following conditions: return air temp.: 20CDB, outdoor temp.: 7CDB, 6CWB, and equivalent ref. Piping: 8m
(horizontal)
3.Sound level is measured at 1.4m below the air outlet.
* External static pressure is based on high speed indoor air flow.

81
Indoor Units Lineup
Model

Concealed Duct Unit


Concealed Duct(A5
UnitType)
(A5 Type) Power supply Power su

Cooling capacityCooling c
Auto Restart Auto Restart Fresh Air Fresh Air

Follow Me Follow Me Anti-Cold Air Anti-Cold Air Heating capacityHeating c


Function Function

Built-in Drain Pump Wired Controller


Built-in Drain Pump Wired Controller Cooling
Rated Rated
input Heating
input

Auto Addressing Super High Air Super


Flow High Air Flow Rated Cooling
Auto Addressing Rated
current current
Heating

Connectable ToConnectable
Duct To Duct Airflow rate(SH/H/M/L)
Airflow ra

ESP(external staticESP(exter
pressure

Sound pressure level(H/M/L


Sound pre

Refrigerant Refrigera

Net dim.(WHD

Compact size
Compact size ExternalExternal
static pressure
static pressure Indoor
Unit
Indoor
Gross dim.(WHD
Unit

Min.3/16in.(5mm)
Min.3/16in.(5mm) Four speedFour
fan motor
speed(Super high(Super
fan motor speed high
as speed as NetGross
L(flare)
an optional)an optional) Piping Piping
8-9/32in. 8-9/32in.
or 10-5/8in. connections G(flare)
connections
or 11-13/16in.
or 10-5/8in.
or 11-13/16in.
Change theChange
wiring connection from SH tofrom SH to
the wiring connection Drain piping

Ceiling Ceiling
H to change
Hthe ESP. the ESP.
to change Standard Controller
Standard

Only 8-9/32in.(210mm) (22~71 models)


Only 8-9/32in.(210mm) or 10-5/8in.
(22~71 models) or 10-5/8in. Model
(270mm) (80(270mm)
to 112 models) or 11-13/16in.(300mm)
(80 to 112 models) or 11-13/16in.(300mm)
(140 model) in height. Power supply Power su
(140 model) in height.

Convenient installation
Convenient installation Cooling capacityCooling c

The EXV is ThefixedEXV


inside of theinside
is fixed indoorofunit.
the indoor unit. Heating capacityHeating c
Indoor Units Lineup

Indoor Units Lineup

Standard filter placedfilter


Standard in anplaced
aluminumin anframe, which
aluminum is removable
frame, which is downward
removable from bottom.
downward from bottom.
Suction chamber is included as standard equipment.
Suction chamber is included as standard equipment. Rated input
Coolin
Rated inp
Heatin
Fresh air hole,
Freshair air
inlet/outlet
hole, air flange are standard
inlet/outlet forstandard
flange are easy duct
forconnection.
easy duct connection.
Coolin
Air inlet from
Airback
inletisfrom
standard
back isand from bottom
standard as optional
and from withoptional
bottom as the samewithconnectable duct.
the same connectable duct. Rated current Rated cu
Heatin

Airflow rate (SH/H/M/L)


Airflow ra
Air intake from
Airback
intake from back Air intake from
Airbelow
intake from below drain pump as standard
drain pump as standard
ESP(external static press
ESP(exte
Sound pressure Sound
level(H/M
pr

29-17/32 29-17/32 Refrigerant Refrigera


(750mm) (750mm) Net di
Indoor Unit Gross
Indoor Un
NetGr
ceiling ceiling L(flare
Piping connections G(flare
Piping co
Drain
Standard ControS
lletar ndard
FlexibleFlexible
control and convenient
control for maintenance
and convenient for maintenance Notes: Notes:
1. Nominal cooling capac
1. Nomin
95F(35C)DB,equivalent
95F(35
Standard Wired remote
Standard controller
Wired remoteTCONTKJR29BKE.
controller TCONTKJR29BKE. (horizontal) (horizont
The Electrical
Thecontrol box control
Electrical can be box
removed
can be1mremoved
away from
1m the unit,
away fromeasy
thetounit,
access
easywhen needswhen
to access maintenance.
needs maintenance. 2. Nominal heating capac
2. Nomin
and equivalent ref.
andpiping
equi
Standard functional
Standardport such asport
functional Remote On/Off
such as Dry contact
Remote switch
On/Off Dry and Alarm
contact switch signal output
and Alarm (220V).
signal output (220V). (horizontal) (horizont
3. Sound Level is3.measur
Sound
* external static pressure
* externa
* Specifications are subje
* Specific

82
Model 4TVD0007A10WEAA 4TVD0009A10WEAA 4TVD0012A10WEAA 4TVD0015A10WEAA 4TVD0019A10WEAA 4TVD0024A10WEAA

Power supply 1-phase,208-230V,60Hz


kW 2.2 2.8 3.6 4.5 5.6 7.1

Cooling capacity kcal/h 1900 2400 3100 3900 4800 6100

Btu/h 7500 9600 12300 15400 19100 24200

kW 2.6 3.2 4.0 5.0 6.3 8.0

Heating capacity kcal/h 2200 2800 3400 4300 5400 6900

Btu/h 8200 10900 13600 17100 21500 27300

Cooling 66 72 77 100 100 125


Rated W
input Heating 66 72 77 100 100 125

ow Cooling 0.24 0.24 0.28 0.48 0.48 0.6


Rated
A
current Heating 0.24 0.24 0.28 0.48 0.48 0.6
588(30pa) 588(30pa) 614(30pa) 763(30pa) 763(30pa)
m3/h 1127(30pa)/1029/934/781
/538/456/375 /538/456/375 /597/514/429 /811/684/575 /811/684/575
Airflow rate(SH/H/M/L)
CFM 346/317/268/221 346/317/268/221 361/351/303/253 449/477/403/338 449/477/403/338 663/606/550/460
ESP(external static pressure) Pa 10(10-30) 10(10-30) 10(10-30) 10(10-30) 10(10-30) 10(10-30)

Sound pressure level(H/M/L) dB(A) 36/35/32 36/35/32 38.6/37.5/33.8 39/37.9/34 39/37.9/34 41.4/39/35

Type R410A
Refrigerant Control
method EXV
37-51/64x8-17/64x19- 37-51/64x8-17/64x19- 46-29/64x8-17/64x19-
Net dim.(WHD) 29-9/64x8-17/64x19-11/16(740x210x500) 11/16(960x210x500) 11/16(960x210x500) 11/16(1180x210x500)
Indoor in.(mm) 43-57/6411-7/ 43-57/6411-7/ 52-9/1611-7/
Unit Gross dim.(WHD) 34-1/411-7/3220-43/64(870285525) 3220-43/64 3220-43/64 3220-43/64
(1115285525) (1115285525) (1335285525)

NetGross lbs.(kg) 38.6/44.1(17.5/20) 38.6/44.1(17.5/20) 38.6/44.1(17.5/20) 49.6/57.3(22.5/26) 49.6/57.3(22.5/26) 61.8/69.5(28/31.5)


L(flare) in.(mm) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 3/8( 9.53) 3/8( 9.53)
Piping
connections G(flare) in.(mm) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 5/8( 15.9) 5/8( 15.9)
Drain piping in.(mm) OD 63/64( 25) OD 63/64( 25) OD 63/64( 25) OD 63/64( 25) OD 63/64( 25) OD 63/64( 25)
Standard Controller Wired controller TCONTKJR29BKE (6 meters connection wire)

Model 4TVD0027A10WEAA 4TVD0031A10WEAA 4TVD0038A10WEAA 4TVD0048A10WEAA

Power supply 1-phase,208-230V,60Hz


kW 8 9 11.2 14
Cooling capacity kcal/h 6900 7700 9600 12000
Btu/h 27300 30700 38200 47800
kW 9 10 12.5 15.5
Heating capacity kcal/h 7700 8600 10800 13300

Indoor Units Lineup


Btu/h 30700 34100 42700 52900
Cooling 133 134 378 352
Rated input W
Heating 133 134 378 352
Cooling 1 1 1.8 1.55
Rated current A
Heating 1 1 1.8 1.55
m3/h 1,388(50pa)/1,345/1,165/1,013 1,388(50pa)/1,345/1,165/1,0131,851(80pa)/1,800/1,556/1,400 1,745(100pa)/1,905/1,636/1,400
Airflow rate (SH/H/M/L)
CFM 817/792/686/596 817/792/686/596 1,089/1,059/916/824 1,027/1,121/963/824
ESP(external static pressure) Pa 20(10-50) 20(10-50) 40(10-80) 40(10-100)
Sound pressure level(H/M/L) dB(A) 45.4/39.8/37 45.4/39.8/37 48.0/41.9/38 47.7/43.2/39
Type R410A
Refrigerant
Control method EXV
50-25/3211-13/1634-1
Net dim.(WHD) 48-27/6410-5/830-33/64(1230270775) /16(1290300865)
in.(mm) 55-1/814-49/6436-27
Indoor Unit Gross dim.(WHD) 53-11/3213-25/3131-19/64 1355350795 /64(1400375925)
NetGross lbs.(kg) 84/102.5(38/46.5) 88.2/105.8 40/48 88.2/105.8 40/48 108.0/127.9(49/58)
L(flare) in.(mm) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53)
Piping connections G(flare) in.(mm) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9)
Drain piping in.(mm) OD 63/64( 25)
Standard Controller Wired controller TCONTKJR29BKE (6 meters connection wire)
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature:
95F(35C)DB,equivalent ref. piping: 26.25ft. (8m)
(horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB, outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB,
and equivalent ref. piping: 26.25ft. (8m)
(horizontal)
3. Sound Level is measured 4.59ft. (1.4m) below the unit.
* external static pressure are based on high speed indoor airflow.
* Specifications are subject to change without prior notice for product improvement.

83
Indoor Units Lineup
High Static Pressure Duct Model 4TVH0024A1

High Static Pressure Duct Power Supply

kW 7.1
Power Supply
Cooling kcal/h 6,100
Auto Restart Anti-Cold Air Function
Btu/h 24,200
Capacity
Auto Restart Anti-Cold Air Function kW 8
Auto Addressing Connectable To Duct Heating Capacity
kcal/h 6,900
Btu/h 27,300
Auto Addressing Connectable To Duct
Follow Me Cooling 414
Power input W
Heating 414
Follow Me 1.9
Cooling Power input
Wired Controller Rated current A
Heating 1.9

Wired Controller 1,720/1,532/1


m3/hRated current
Indoor air flow (H/M/L)
CFM 1,012/902/7
ESP(external static pressure) Pa Indoor air flow (H/M/
25(25~ 19
48/46/44.
Flexible duct design
Sound pressure level(H/M/L) dB(A)
ESP(external static p
Type

Flexible duct design


Refrigerant Sound pressure leve
Control method
Four speed fan motor (medium high speed as an option only for 71~160 model) Refrigerant
Net dimension WHD in.(mm)
External static pressure can be
Four speed upmotor
fan to 196Pa (71~160high
(medium models) or 280Pa
speed as an (400~450 models).
option only for 71~160 model)
Net dimension
External static pressure can be up to 196Pa (71~160 models) or 280Pa (400~450 models). Packing dimension WHD in.(mm)

Net/Gross Weight Packing dimension


lbs.(kg) 102.6/114.7(
the longest distance
of air supply is 14m in.(mm) 3/8( 9
L(flare) Net/Gross Weight
the Fresh air in
longest take
distance
of air supply is 14m G(flare) in.(mm) 5/8( 1
Min. Piping Connections
Fresh air in take
420mm 450mm Drain piping in.(mm) OD 1-17/6
Min. Piping Connections
420mm 450mm
INDOOR UNIT Standard Controller -

Air supply The height of air Air returINDOOR


n UNIT Standard Controller
supply is 6.5m
The height of air INDOOR UNIT Model 4TVH0048A10
Air supply Air return
supply is 6.5m
INDOOR
The max distance of air supply is about 45.9ft.(14m) while the height of air supply is about UNIT
21.3ft.(6.5m). Power Supply

With 16-17/32in(420mm)
The maxthickness
distancebody,
of airthe minimum
supply distance
is about above the ceiling
45.9ft.(14m) while isthe
17-23/32in(450mm).
height of air supply is about 21.3ft.(6.5m).
kWPower Supply 14
Cooling kcal/h 12,00
With 16-17/32in(420mm) thickness body, the minimum distance above the ceiling is 17-23/32in(450mm). Btu/h 47,80

Added flexibility with four speed fan


Capacity
kW 16

Added flexibility with four speed fan Heating Capacity


kcal/h 13,80

Four speed fan motor(model 71 to 160) Btu/h 54,60


Indoor Units Lineup

Cooling 527
Four speed fan motor(model 71 to 160) Power input W
Indoor Units Lineup

Heating 527

Convenient installation Rated current


Cooling
A
Power input 2.03

Convenient installation
The EXV is fixed inside the indoor unit (for 71~450 model), no need extra connection.
Heating
m3/hRated current
2.03
2,969/2,694
Indoor air flow (H/M/L)
Standard filter placed
The EXV in anisaluminum frame,the
fixed inside which is removable
indoor downwardmodel),
unit (for 71~450 from bottom.
no need extra connection. CFM 1,746/1,586
Indoor air flow (H/M/1
50(50~
Flange for air in/outlet
Standard duct filter
connection
placed is in
standard.
an aluminum frame, which is removable downward from bottom. ESP(external static pressure) Pa
Sound pressure level(H/M/L) 53/50/4
dB(A)ESP(external static
Flange for air in/outlet duct connection is standard. p

Flexible control and convenient for maintenance Refrigerant


Type Sound pressure leve

Standard WiredFlexible control and convenient


and wireless for maintenance Control method
Refrigerant
remote controller TCONTKJR29BKE, remote controller TCONTRM05A is as an Net dimension WHD in.(mm) 51-3/16
option. Standard Wired remote controller TCONTKJR29BKE, and wireless remote controller TCONTRM05A is as an Net dimension
The display board is connected with the E-box in factory, easier trouble-shooting by LED display.
option. Packing dimension WHD in.(mm) 56-17/321

Easy access filters


Theboth in rearboard
display & bottom
is connected with the E-box in factory, easier trouble-shooting by LED display. Net/Gross Weight
Packing dimension
lbs.(kg) 149.9/154.3
Standard functional
Easy port such as
access remote
filters on/off
both dry contact.
in rear & bottom L(flare) in.(mm) 3/8( 9
Net/Gross Weight
Standard functional port such as remote on/off dry contact.
Option Double-skin drainage panPiping Connections
G(flare) in.(mm) 5/8( 1

Option Double-skin drainage pan Drain piping in.(mm) OD 1-17/64


Piping Connections

Standard Controller -
29-17/32in.(750mm) Standard Controller
Notes:
29-17/32in.(750mm) 1. Nominal cooling capacities are based on the following conditions: return air tem
Notes:
Piping:26.25ft(8m)(horizontal)
1. Nominal cooling ca
2. Nominal heating capacities are based on the following conditions: return air tem
ceiling Piping: 26.25ft(8m)(horizontal)
Piping:26.25ft(8m)
2. Nominal heating ca
Optional drain pumps with 29-17/32in.(750mm) ceiling
Double-skin drainage pan, double production for 3. Sound Level is measured 4.59ft. (1.4m) below the unit. Piping: 26.25ft(8m)

pumphead. your ceiling.(for 71~450 Double-skin


Optional drain pumps with 29-17/32in.(750mm) model) drainage pan, double production* for Specifications are subject to change without prior notice3.forSound
productLevel
improveme
is me

pumphead. your ceiling.(for 71~450 model) * Specifications are

84
Model 4TVH0024A10WEAA 4TVH0027A10WEAA 4TVH0030A10WEAA 4TVH0038A10WEAA

Power Supply 208~230V-1Ph-60Hz


kW 7.1 8 9 11.2
Cooling kcal/h 6,100 6,900 7,700 9,600
Air Function
Btu/h 24,200 27,300 30,700 38,200
Capacity
kW 8 9 10 12.5
ble To Duct Heating kcal/h 6,900 7,700 8,600 10,800
Btu/h 27,300 30,700 34,100 42,700
Cooling 414 402 409 409
Power input W
Heating 414 402 409 409

Cooling 1.9 1.9 2.01 2.01


Rated current A
Heating 1.9 1.9 2.01 2.01
m3/h 1,720/1,532/1,338 1,690/1,560/1,320 2,252/2,030/1,610 21,98/1,978/1,570
Indoor air flow (H/M/L)
CFM 1,012/902/788 994/918/777 1,326/1,195/948 1,294/1,164/924
ESP(external static pressure) Pa 25(25~ 196) 37(37~ 196) 37(37~ 196) 50(50~ 196)
Sound pressure level(H/M/L) dB(A) 48/46/44.5 48/46/44.5 52/49/47 52/49/47
Type R410A
Refrigerant
Control method EXV

Net dimension WHD in.(mm) 37-31/6416-17/3227-11/64(952420690)

Packing dimension WHD in.(mm) 42-29/3217-21/6430-15/64(1090440768)

Net/Gross Weight lbs.(kg) 102.6/114.7(46.5/52) 102.6/114.7(46.5/52) 110.3/124.6(50/56.5) 110.3/124.6(50/56.5)

L(flare) in.(mm) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53)

G(flare) in.(mm) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9)
Piping Connections
Drain piping in.(mm) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32)

Standard Controller - Wired controller TCONTKJR29BKE (6 meters connection wire)

Model 4TVH0048A10WEAA 4TVH0055A10WEAA 4TVH0140A10WEAA 4TVH0155A10WEAA

Power Supply 208~230V-1Ph-60Hz


kW 14 16 40 45
Cooling kcal/h 12,000 13,800 34400 38,700
Btu/h 47,800 54,600 136500 153,500
Capacity
kW 16 16.5 45 50
Heating kcal/h 13,800 14,200 38700 43,000
Btu/h 54,600 56,300 153,500 170600
Indoor Units Lineup
Cooling 527 532 1,600 1,600
Power input W
Heating 527 532 1,600 1,600
Cooling 2.03 2.31 7.5 7.5
Rated current A
Heating 2.03 2.31 7.5 7.5
m3/h 2,969/2,694/2,469 2,969/2,694/2,469 7,180/6,150/4,600 7,180/6,150/4,600
Indoor air flow (H/M/L)
CFM 1,746/1,586/1,453 1,746/1,586/1,453 4,226/3,620/2,708 4,226/3,620/2,708
ESP(external static pressure) Pa 50(50~ 196) 50(50~ 196) 200(50~280) 200(50~280)
Sound pressure level(H/M/L) dB(A) 53/50/48 54/52/50 61/59/56 61/59/56
Type R410A
Refrigerant
Control method EXV

is as an Net dimension WHD in.(mm) 51-3/1615-3/427-13/64(1300420691) 77-9/1615-3/435-17/32(1970668902.5)

Packing dimension WHD in.(mm) 56-17/3217-23/3230-15/64(1436450768) 82-31/6431-1/237-61/64(2,095800964)

Net/Gross Weight lbs.(kg) 149.9/154.3(68/70) 153.3/167.6(69.5/76) 518/551(235/250) 518/551(235/250)

L(flare) in.(mm) 3/8( 9.53) 3/8( 9.53) 1/2( 12.7) 1/2( 12.7)

G(flare) in.(mm) 5/8( 15.9) 5/8( 15.9) 7/8( 22.2) 7/8( 22.2)
Piping Connections
Drain piping in.(mm) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32) OD 1-17/64( 32)

Standard Controller - Wired controller TCONTKJR29BKE (6 meters connection wire)

Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref.
Piping:26.25ft(8m)(horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB, outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref.
Piping: 26.25ft(8m)(horizontal)
r 3. Sound Level is measured 4.59ft. (1.4m) below the unit.

* Specifications are subject to change without prior notice for product improvement.
85
Indoor Units Lineup
Ceiling & Floor
Ceiling & Floor P
Cooli

Cooling capacity

Auto Restart Cleanable Panel Heat

Auto Restart Cleanable Panel Heating capacity


Auto Addressing Anti-Cold Air Function
Powe
Auto Addressing Anti-Cold Air Function Co
Power input
Follow Me LED LED Display He
DISPLAY
Rated
Follow Me LED Display Co
LED Rated current
DISPLAY
He
Airflo

Airflow rate(H/M/L)
Soun

Sound pressure le
Refri

Panel with LED display Refrigerant

Panel with LED display Net d

The front panel and display panel have different colors to choose: white and brown to big panel, blue and Net dimension(W
Pack
brown for small
The front panel and panel,
display and
panel the different
have other colors cantobe
colors customized
choose: whiteaccording
and browntotothe
bigcustomers demands.
panel, blue and
Packing dimension
brown for small panel, and the other colors can be customized according to the customers demands. Net/G
Convenient for installation Net/Gross weight
Convenient for installation Pipin
L(
The ceiling type can be easily installed into a corner of Piping conn
G
The ceiling
thetype can even
ceiling be easily
if theinstalled
ceiling isinto a corner
very narrowof connections
Stand
Dr
the ceilingIteven if the ceiling
is especially usefulis when
very narrow
installation of an air Standard Controller

It is especially useful in
conditioner when installation
the center ofceiling
of the an air is impossible
conditioner in to
due thea center of the
structure ceiling
such as oneis impossible
lighting
The unit can be installed either horizontally on the P
due to a structure such as one lighting ceilingeither
or vertically against Cooli
The unit can be installed horizontally on the
the wall.
ceiling or vertically against the wall. Cooling capacity
Low noise, creates quiet and comfortable environment
Low noise, creates quiet and comfortable environment Heat

Drop ceiling
Indoor Units Lineup

Heating capacity
>20
Drop ceiling
Indoor Units Lineup

>20 Powe
Co
198mm Power input
He
Rated
198mm
Co
Rated current
Air Outlet He
Airflo
Airweight
Slim and sleek design starting at just 66lbs.(30kg) in Outlet means quick,easy & neat installation. Airflow rate(H/M/L)
Soun
Low design
Slim and sleek noise operation,
starting atlowest to 36dB(A) in weight means quick,easy & neat installation.
just 66lbs.(30kg)
Sound pressure le
Refri
Low noise operation, lowest to 36dB(A)
Auto swing and wide angle air flow Refrigerant

Auto swing and wide angle air flow Net d


Auto Swing & Wide-angle Airflow Net dimension(W
Auto Swing & Wide-angle Airflow 1.The unit has auto horizontal swing and auto vertical swing function, Pack

1.The unit has auto


which horizontal
supplies moreswing
even and
and auto vertical airflow.
comfortable swing function, Packing dimension
Net/G
which supplies more even and comfortable airflow.
2.Three airflow speed: high/middle/low, double air guides. Net/Gross weight
Pipin
2.Three airflow speed:ofhigh/middle/low,
3.Adoption the electronic double air guides.
expansion valve, ensure precise flow L(
conn
Piping
G
3.Adoption control,
of the as
electronic expansion valve, ensure
well lower modulation noise when EXV precise flow
operating. connections
Stand
Dr
control, 4.Smoother
as well lowerairflow
modulation noiseturbulence.
with less when EXVOwing operating.
to the multiple-blade Standard Controller
Notes:
1. Nom
4.Smootherfan airflow withairless
and the turbulence.
guide Owing
design, the airflowtoisthe multiple-blade
getting smoother and more Notes: pipin
1. Nominal cooling cap
fan and the air guide design, the airflow is getting smoother and more
comfortable.
2. Nom
piping: 26.25ft. Pipin
(8m
2. Nominal heating cap
comfortable. 3. Floo
Piping: 26.25ft.(8m)
Ceil
3. Floor standing :Soun
* Spe
Ceiling mounted:Sou

* Specifications are su

86
Model 4TVX0012A10REAA 4TVX0015A10REAA 4TVX0018A10REAA 4TVX0024A10REAA

Power supply 220~240V-1Ph-60Hz


kW 3.6 4.5 5.6 7.1
Cooling capacity kcal/h 3,100 3,900 4,800 6,100
Btu/h 12,300 15,400 19,100 24,200
kW 4 5 6.3 8
nel Heating capacity kcal/h 3,400 4300 5,400 6,800
Btu/h 13,600 17,100 21,500 27,300
unction Cooling 50 148 148 148
Power input W
Heating 50 148 148 148
Cooling 0.55 0.55 0.55 0.57
Rated current A
Heating 0.55 0.55 0.55 0.57
m3/h 600/480/400 750/650/550 750/650/550 750/650/550
Airflow rate(H/M/L)
CFM 353/283/235 441/383/324 441/383/324 441/383/324
Sound pressure level(H/M/L) dB(A) 40/38/36 43/41/38 43/41/38 43/41/38
Type R410A
Refrigerant
Control method EXV

Net dimension(WHD) in.(mm) 38-31/327-63/6425-63/64(990203660)

Packing dimension(WHD) in.(mm) 42-7/8x11-21/32x29-9/32(1089x296x744)

Net/Gross weight lbs.(kg) 57.3/70.6(26/32) 61.7/75.0(28/34) 61.7/75.0(28/34) 61.7/75.0(28/34)


L(flare) in.(mm) 1/4( 6.35) 1/4( 6.35) 3/8( 9.53) 3/8( 9.53)
Piping
G(flare) in.(mm) 1/2( 12.7) 1/2( 12.7) 5/8( 15.9) 5/8( 15.9)
connections
Drain piping in.(mm) OD 5/8( 16) OD 5/8( 16) OD 5/8( 16) OD 5/8( 16)
Standard Controller - Wireless remote controller (TCONTRM05A)

Model 4TVX0027A10REAA 4TVX0030A10REAA 4TVX0038A10REAA 4TVX0048A10REAA 4TVX0055A10REAA

Power supply 220~240V-1Ph-60Hz


kW 8 9 11.2 14 16
Cooling capacity kcal/h 6,900 7,700 9,600 12,000 13,800
Btu/h 27,300 30,700 38,200 47,800 54,600
kW 9 10 12.5 15 18
Heating capacity kcal/h 7,700 8,600 10,800 12,900 15,477
Btu/h 30,700 34,100 42,700 51,200 61,400

Indoor Units Lineup


Cooling 183 183 245 245 378
Power input W
Heating 183 183 245 245 378
Cooling 0.6 0.6 0.83 0.83 1.75
Rated current A
Heating 0.6 0.6 0.83 0.83 1.75
m3/h 1,200/900/700 1,200/900/700 1,980/1,860/1,730 1,980/1,860/1,730 2,300/2,100/1,800
Airflow rate(H/M/L)
CFM 706/530/412 706/530/412 1,165/1,095/1,018 1,165/1,095/1,018 1,354/1,236/1,060
Sound pressure level(H/M/L) dB(A) 45/43/40 45/43/40 47/45/42 47/45/42 47/45/42
Type R410A
Refrigerant
Control method EXV
50-25/647-63/6425-63 65-3/4 x9-39/64x26-49/64 65-3/4x11-7/32x26-49/64
Net dimension(WHD) in.(mm)
/64(1280203660) (1670 x244x680) (1670x285x680)
54-19/64x11-21/32x29-19/64 69-29/64 x12-61/64x29-59/64 69-7/8x14-27/32x29-59/64
n, Packing dimension(WHD) in.(mm)
(1379x296x744) (1764x329x760) (1775x377x760)
Net/Gross weight lbs.(kg) 76.1/90.4(34.5/41) 76.1/90.4(34.5/41) 119.0/130.1(54/59) 119.0/130.1(54/59) 126.5/139.7(57.5/63.5)
L(flare) in.(mm) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53)
Piping
G(flare) in.(mm) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9)
w connections
Drain piping in.(mm) OD 5/8( 16) OD 5/8( 16) OD 5/8( 16) OD 5/8( 16) OD 5/8( 16)
Standard Controller - Wireless remote controller (TCONTRM05A)
e Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref.
e piping: 26.25ft. (8m) (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB, outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref.
Piping: 26.25ft.(8m) (horizontal)
3. Floor standing :Sound level is measured 3.28ft(1m) from air-outlet in horizontal distance, 3.28ft(1m) above the floor in vertical distance.
Ceiling mounted:Sound level is measured 3.28ft(1m) from air-outlet in horizontal distance,3.28ft(1m) from air-outlet in vertical distance.

* Specifications are subject to change without prior notice for product improvement.

87
Indoor Units Lineup
Wall-mounted S
Wall-mounted
Auto Restart
S type p
Auto Restart M
Auto Addressing
S type panel C type panel Pow
Co
Auto Addressing
S type panel C type panel Cleanable Panel
Cooling capacity
Cleanable Panel He
Anti-Cold Air Function

Heating capacity
R type panel Anti-Cold Air Function
Follow Me Po

R type panel Follow Me Power input Ra


LED LED Display
DISPLAY

Rated current
LED Display Air
LED
DISPLAY

So
Airflow rate(H/M/L

Rele
Sound pressure

Panel with LED display Refrigerant


Ne
Panel The
withfrontLED display
panel and display panel have different colors to choose: white and brown for big panel, blue and Net dimension(W
Pa

The front brown for small


panel and panel.
display panel have different colors to choose: white and brown for big panel, blue and Ne
Packing dimensio
brown for small panel. Gro

Convenient installation Net weight


Gross weight
Pip
Convenient installation
Multi-refrigerant outlet pipe method: left\right\rear, more con
Piping
flexibleoutlet
Multi-refrigerant for installation.
pipe method: left\right\rear, more connections
Sta

The EXV is built-in the indoor unit, compact size, longer the
flexible for installation. Standard Controll

The EXV connection pipe;


is built-in the Gasunit,
indoor pipe:compact
18-27/64in.(468mm)/Liquid
size, longer the pipe:
Rear
21-21/32in.(550mm), more flexible for
connection pipe; Gas pipe: 18-27/64in.(468mm)/Liquid pipe:the installation. M
Left Right
Adopts new more
21-21/32in.(550mm), type fixing plate,
flexible for which means easy to install and
the installation.
Rear
Pow
Co
stable.
Adopts new type fixing plate, which means easy to install and Left Right

Cooling capacity
stable. Auto swing louver Easy
maintenance He

Auto swing louver Easy maintenance


Indoor Units Lineup

auto swing louver function The front panel can be removed for easy Heating capacity
Indoor Units Lineup

ensures that the air


The front maintenance
panel can beaccess.
Po
auto swing louver function removed for easy
direction
ensures that the aircorresponds to
maintenance access. Power input
the mode selected. Open panel Ra
direction corresponds to 1

the mode selected. Open panel Rated current


Air
1 2
So
Airflow rate(H/M/L
Step 2
3
Rele
Sound pressure
Step Swing 3
4

Refrigerant
Ne
Swing 4

Optimal comfort through better flow control and quiet operations


Net dimension(W
Pa

Optimal comfort through better flow control and quiet operations


The mechanical expansion valve offers 2,000-stage
Ne
Packing dimensio
Gro
Net weight
element positions
The mechanical expansionto ensure
valve precise flow control and less
offers 2,000-stage Gross weight
Pip

element positions to ensure precise flow control and for


modulation noise when the EXV is operating a quiet and
less con
comfortable environment. Three air flow
modulation noise when the EXV is operating for a quiet and speeds: low, Piping
Sta
connections
medium and high; double air guides. Smoother
comfortable environment. Three air flow speeds: low, airflow and Notes
Standard Controll
less turbulence is ensured by the multi-blade
medium and high; double air guides. Smoother airflow and fan and the 1. No
Notes: pip
air guide design.
less turbulence is ensured by the multi-blade fan and the 2. No
1. Nominal cooling ca
Pip
piping: 26.25ft(8m)
air guide design. 3. So
2. Nominal heating ca

* Sp
Piping: 26.25ft(8m
3. Sound level is mea

* Specifications are
88
S type panel
Model 4TVW0007A10REBA 4TVW0009A10REBA 4TVW0012A10REBA 4TVW0015A10REBA 4TVW0018A10REBA

Power supply 4TVW0007A10REBA 220~240V-1Ph-60Hz


kW 2.2 2.8 3.6 4.5 5.6
Cooling capacity kcal/h 1,900 2,400 3,100 3,900 4,800
Btu/h 7,500 9,600 12,300 15,400 19,100
kW 2.4 3.2 4 5 6.3
Heating capacity kcal/h 2,100 2,800 3,400 4,300 5,400
tion
Btu/h 8,200 10,900 13,600 17,100 21,500
Cooling 28 28 28 51 51
Power input W
Heating 28 28 28 51 51
Cooling 0.14 0.14 0.14 0.2 0.2
Rated current A
Heating 0.14 0.14 0.14 0.2 0.2
m3/h 525/480/430 525/480/430 590/520/480 860/755/630 925/860/755
Airflow rate(H/M/L)
CFM 309/283/253 309/283/253 347/306/283 506/444/371 544/506/444
Sound pressure level(H/M/L) dB(A) 35/32/29 35/32/29 35/32/29 40/38/34 40/38/34
Type R410A
Refrigerant
Control method EXV

Net dimension(WHD) in.(mm) 36-1/32x9-1/16x11-13/32(915230290) 42-7/32 x9-1/16x12-13/32(1072230315)

Packing dimension(WHD) in.(mm) 40-5/32x12-13/32x15-11/32(1020315390) 46-15/3212-13/3216-11/32(1180315415)

Net weight lbs.(kg) 28.7(13) 28.7(13) 28.7(13) 33.4(15.1) 33.4(15.1)


Gross weight lbs.(kg) 37.1(16.8) 37.1(16.8) 37.1(16.8) 43/19.5 43/19.5
L(flare) in.(mm) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 3/8( 9.53)
Piping G(flare) in.(mm) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 5/8( 15.9)
connections Drain piping in.(mm) OD 21/32( 16.5) OD 21/32( 16.5) OD 21/32( 16.5) OD 21/32( 16.5) OD 21/32( 16.5)
Standard Controller - Wireless remote controller (TCONTRM05A)

Model 4TVW0007A1HREBA 4TVW0009A1HREBA 4TVW0012A1HREBA 4TVW0015A1HREBA 4TVW0018A1HREBA


ar
Power supply 220~240V-1Ph-60Hz
Right kW 2.2 2.8 3.6 4.5 5.6
Cooling capacity kcal/h 1,900 2,400 3,100 3,900 4,800
Btu/h 7,500 9,500 12,300 15,400 19,100
kW 2.4+0.75 3.2+0.75 4+0.75 5+0.9 6.3+0.9
Heating capacity kcal/h 2,100+600 2,800+600 3,400+600 4,300+800 5,400+800

Indoor Units Lineup


Btu/h 8,200+2,600 10,900+2,600 13,600+2,600 17100+3100 21,500+3,100
Cooling 28 28 28 51 51
Power input W
Heating 28 28 28 51 51
Cooling 0.14 0.14 0.14 0.2 0.2
Rated current A
Heating 0.14+3.38 0.14+3.38 0.14+3.38 0.20+4.05 0.20+4.05
m3/h 525/480/430 525/480/430 590/520/480 860/755/630 925/860/755
Airflow rate(H/M/L)
CFM 309/283/253 309/283/253 347/306/283 506/444/371 544/506/444
Sound pressure level(H/M/L) dB(A) 35/32/29 35/32/29 35/32/29 40/38/34 40/38/34
Type R410A
Refrigerant
Control method EXV

Net dimension(WHD) in.(mm) 36-1/32x9-1/16x11-13/32(915230290) 42-7/32 x9-1/16x12-13/32(1072230315)

Packing dimension(WHD) in.(mm) 40-5/32x12-13/32x15-11/32(1020315390) 46-15/3212-13/3216-11/32(1180315415)

Net weight lbs.(kg) 29.3(13.3) 29.3(13.3) 29.3(13.3) 34.2(15.5) 34.2(15.5)


Gross weight lbs.(kg) 37.7(17.1) 37.7(17.1) 37.7(17.1) 43.9(19.9) 43.9(19.9)
L(flare) in.(mm) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 3/8( 9.53)
Piping G(flare) in.(mm) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 5/8( 15.9)
connections Drain piping in.(mm) OD 21/32( 16.5) OD 21/32( 16.5) OD 21/32( 16.5) OD 21/32( 16.5) OD 21/32( 16.5)
Standard Controller - Wireless remote controller (TCONTRM05A)

Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature : 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref.
piping: 26.25ft(8m)(horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB, outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref.
Piping: 26.25ft(8m)(horizontal)
3. Sound level is measured 3.28ft.(1m) below the air out-let both in horizontal and vertical distance.

* Specifications are subject to change without prior notice for product improvement.

89
C type panel R
Model 4TVW0007A10REAA 4TVW0009A10REAA 4TVW0012A10REAA 4TVW0015A10REAA 4TVW0018A10REAA

Power supply 220-240V~, 1Ph, 60Hz Po


kW 2.2 2.8 3.6 4.5 5.6
Cooling capacity kcal/h 1,900 2,400 3,100 3,900 4,800 Co
Btu/h 7,500 9,600 12,300 15,400 19,100
kW 2.4 3.2 4 5 6.3
Heating capacity kcal/h 2,200 2,800 3,400 4,300 5,400 He
Btu/h 8,900 10,900 13,600 17,100 21,500
Cooling 28 28 28 45 45
Power input W
Heating 28 28 28 45 45 Po
Cooling 0.14 0.14 0.14 0.2 0.2
Rated current A
Heating 0.14 0.14 0.14 0.2 0.2 Ra
m3/h 557/520/467 557/520/467 557/520/467 842/722/597 842/722/597
Airflow rate(H/M/L)
CFM 328/306/275 328/306/275 328/306/275 496/425/351 496/425/351
Ai
Sound pressure level(H/M/L) dB(A) 35/32/29 35/32/29 35/32/29 40/38/34 40/38/34
Type R410A So
Refrigerant
Control method EXV
Re
Net dimension(WHD) in.(mm) 36-1/32x8-9/32x11-13/32(915210290) 42-7/328-9/3212-13/32(1070210315)
Ne
Packing dimension(WHD) in.(mm) 40-5/3211-13/1615-5/32(1020300385) 45-7/8x11-7/32x15-9/16(1165x285395) Pa
Ne
Net weight lbs.(kg) 26.5(12) 26.5(12) 26.5(12) 33.1(15) 33.1(15)
Gr
Gross weight lbs.(kg) 38.6(17.5) 38.6(17.5) 38.6(17.5) 41.9(19) 39.7(18)
L(flare) in.(mm) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 3/8( 9.53) Pi
Piping G(flare) in.(mm) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 5/8( 15.9) co
connections Drain piping in.(mm) OD 21/32( 16.5) OD 21/32( 16.5) OD 21/32( 16.5) OD 21/32( 16.5) OD 21/32( 16.5)
Standard Controller - Wireless remote controller (TCONTRM05A) St
Note
1. No
Model 4TVW0007A1HREAA 4TVW0009A1HREAA 4TVW0012A1HREAA 4TVW0015A1HREAA 4TVW0018A1HREAA pip
2. No
Power supply 220-240V~, 1Ph, 60Hz Pip
kW 2.2 2.8 3.6 4.5 5.6 3. Flo
Ce
Cooling capacity kcal/h 1,900 2,400 3,100 3,900 4,800
Btu/h 7,500 9,600 12,300 15,400 19,100 * Sp

kW 2.4+0.75 3.2+0.75 4+0.75 5+0.9 6.3+0.9


Heating capacity kcal/h 2,200+600 2,800+600 3,400+600 4,300+800 5,400+800
Indoor Units Lineup

Btu/h 8,900+2600 10,900+2,600 13,600+2,600 17,100+3,100 21,500+3,100


Cooling 28 28 28 45 45
Power input W
Heating 28 28 28 45 45
Cooling 0.14 0.14 0.14 0.2 0.2
Rated current A
Heating 0.14+3.38 0.14+3.38 0.14+3.38 0.2+4.05 0.2+4.25
m3/h 557/520/467 557/520/467 557/520/467 842/722/597 842/722/597
Airflow rate(H/M/L)
CFM 328/306/275 328/306/275 328/306/275 496/425/351 496/425/351
Sound pressure level(H/M/L) dB(A) 35/32/29 35/32/29 35/32/29 40/38/34 40/38/34
Type R410A
Refrigerant
Control method EXV

Net dimension(WHD) in.(mm) 36-1/32x8-9/32x11-13/32(915210290) 42-7/328-9/3212-13/32(1070210315)

Packing dimension(WHD) in.(mm) 40-5/3211-13/1615-5/32(1020300385) 45-7/8x11-7/32x15-9/16(1165x285395)

Net weight lbs.(kg) 26.5(12) 26.5(12) 26.5(12) 33.1(15) 33.1(15)


Gross weight lbs.(kg) 38.6(17.5) 38.617.5 38.617.5 41.9(19) 41.9(19)
L(flare) in.(mm) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 3/8( 9.53)
Piping G(flare) in.(mm) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 5/8( 15.9)
connections Drain piping in.(mm) OD 21/32( 16.5) OD 21/32( 16.5) OD 21/32( 16.5) OD 21/32( 16.5) OD 21/32( 16.5)
Standard Controller - Wireless remote controller (TCONTRM05A)
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature : 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref.
piping: 26.25ft(8m)(horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB, outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref.
Piping: 26.25ft(8m)(horizontal)
3. Sound level is measured 3.28ft.(1m) below the air out-let both in horizontal and vertical distance.

* Specifications are subject to change without prior notice for product improvement.

90
R type panel
Model 4TVW0024A10REAA 4TVW0027A10REAA 4TVW0031A10REAA

Power supply 1-phase, 220-240V, 60Hz


kW 7.1 8 9
Cooling capacity kcal/h 6,100 6,900 7,700
Btu/h 24,200 27,300 30,700
kW 8 9 10
Heating capacity kcal/h 6,900 7,700 8,600
Btu/h 27,300 30,700 34,100
Cooling 79 95 95
Power input W
Heating 79 95 95
Cooling 0.33 0.39 0.39
Rated current A
Heating 0.33 0.39 0.39
m3/h 1,190/780/580 1,320/840/640 1,320/840/640
Airflow rate(H/M/L)
CFM 700/459/341 776/494/376 776/494/376
Sound pressure level(H/M/L) dB(A) 45/42/39 48/43/38 49/43/38
Type R410A
Refrigerant
Control method EXV
Net dimension(WHD) in.(mm) 49-7/329-41/6412-51/64(1250245325)
Packing dimension(WHD) in.(mm) 52-61/6413-3/1616-59/64(1345335430)
Net weight lbs.(kg) 43.819.9
Gross weight lbs.(kg) 55.125
L(flare) in.(mm) 3/8( 9.53)
Piping
G(flare) in.(mm) 5/8( 15.9)
connections
Drain piping in.(mm) OD 21/32( 16.5)
Standard Controller - Wireless remote controller (TCONTRM05A)
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref.
A piping: 26.25ft. (8m) (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB, outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref.
Piping: 26.25ft.(8m) (horizontal)
3. Floor standing :Sound level is measured 3.28ft(1m) from air-outlet in horizontal distance, 3.28ft(1m) above the floor in vertical distance.
Ceiling mounted:Sound level is measured 3.28ft(1m) from air-outlet in horizontal distance,3.28ft(1m) from air-outlet in vertical distance.

* Specifications are subject to change without prior notice for product improvement.

Indoor Units Lineup

91
Indoor Units Lineup
Console
High
Auto Restart Cleanable Panel Built
Activ
Auto Addressing Anti-Cold Air Function

Two a
Follow Me LED LED Display
DISPLAY

Four dir
two opt
only.

Air O
Air Ou

Compact size and stylish


The elegant and thin unit body complements the existing decor and saves space.
The EXV is installed inside of the indoor unit for added compactness.
Bottom

Flexible installation
Can be installed on the floor or lower wall
As a floor standing type, it can be semi or fully accessed
without losing capacity.
Cooling capa

High comfort Heating capa


Indoor Units Lineup

Flexible air blow: vertical auto swing and wide angle louvers ensure that warm air reaches every corner Power input
of the room and increases the air flow coverage.
Indoor unit adopts DC motor with five fan speeds to meet different requirements. Rated curren

Applies the Fujikoki mechanical expansion valve which offers 2,000-stage element positions to ensure
Airflow rate(H
precise flow control and lower modulation noise when the EXV is operating.
Sound press

Refrigerant
Powerful mode can be selected for rapid cooling or heating Net dimensio
Packing dime
COOLING MODE HEATING MODE Net weight
Gross weight

Piping
connections

Standard Con

Notes:
1. Nominal cooling
2. Nominal heating
Quick cooling To maintain temperature Anti-cold air Normal operation 3.Sound level is me

* Specifications a

92
High efficiency filter
Built in formaldehyde nemesis filter
Active-carbon and biological anti-virus filter are optional.
on

Two air outlets and four air inlets Low-noise design


Four directions of air inlet; Five-speed indoor unit; low noise; low power
two options of air outlet: Up and Down; or Up consumption.
only.

Air Outlet
Air Outlet

Air Inlet
Air Inlet

Bottom, top, and right/left side, for better ventilation. Low noise operation, lowest to 26dB(A)

Model 4TVG0007A10REAA 4TVG0009A10REAA 4TVG0012A10REAA 4TVG0015A10REAA

Power supply 220-240V~, 1Ph, 60Hz


kW 2.2 2.8 3.6 4.5
Cooling capacity kcal/h 1,900 2,400 3,100 3,900
Btu/h 7,500 9,600 12,300 15,400
kW 2.6 3.2 4.0 5.0
Heating capacity kcal/h 2,200 2,800 3,400 4,300
Indoor Units Lineup

Btu/h 8,900 10,900 13,600 17,100


Cooling 20 25 25 45
Power input W
Heating 20 25 25 45
Cooling 0.09 0.11 0.15 0.2
Rated current A
Heating 0.09 0.11 0.15 0.2
m3/h 468/450/395 468/450/395 467/427/395 540/481/421
Airflow rate(H/M/L)
CFM 275/265/232 275/265/232 275/251/232 318/283/248
Sound pressure level(H/M/L) dB(A) 38/32/26 39/33/27 39/33/27 42/39/36
Type R410A
Refrigerant
Control method EXV
Net dimension(WHD) in.(mm) 27-9/16x8-9/32x23-5/8(700x210x600)
Packing dimension(WHD) in.(mm) 31-7/8 x12-1/64x27-15/16 (810x305x710)
Net weight lbs.(kg) 30.9(14) 33(15) 33(15) 33(15)
Gross weight lbs.(kg) 42.9(19) 44.1(20) 44.1(20) 44.1(20)
L(flare) in.(mm) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35) 1/4( 6.35)
Piping
G(flare) in.(mm) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7) 1/2( 12.7)
connections
Drain piping in.(mm) OD 5/8( 16) OD 5/8( 16) OD 5/8( 16) OD 5/8( 16)
Standard Controller - Wireless remote controller (TCONTRM05A)

Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature : 80.6F(27C)DB,66.2F(19C)WB,and outdoor temperature: 95F(35C)DB,equivalent ref. piping: 26.25ft(8m) (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 68F(20C)DB, outdoor temperature: 44.6F(7C)DB,42.8F(6C)WB, and equivalent ref. Piping: 26.25ft(8m)(horizontal)
3.Sound level is measured 3.28ft.(1m) from the air out-let in horizontal distance and 3.28ft.(1m) above the floor in vertical distance.

* Specifications are subject to change without prior notice for product improvement.

93
Indoor Units Lineup
Fresh
h Air Processing Unit Power Supply

Capacity

Power input

Rated current

Indoor air flow (H/

ESP (external stat

Sound pressure le

Refrigerant

Net dimension

Healthy and comfortable Packing dimensio

Net/Gross Weight
Fresh air is imported, provides a healthy and comfortable living environment.
Piping Connection

100% Fresh air processing unit


Standard Controlle
the longest distance
of air supply is 14m Both fresh air filtration and heating/cooling can be
Fresh air in take Notes:
achieved in a single system. 1. Nominal cooling c

Indoor units and fresh air processing unit can be 2. Nominal heating c
3. Sound level is me
connected to the same refrigerant system, increasing
INDOOR UNIT * External static
design flexibility and greatly reducing total system costs. *Connection
Specifications
The height of air Conditi
Air supply Air return
supply is 6.5m The following restri

* When outdoor-a

* When outdoor-a

* Outdoor-air pro
Indoor Units Lineup

High external static pressure * The fresh air pr

External static pressure can be up to 196Pa(125~140 models) and 280Pa(200~280 models) for more flexible duct
applications. The maximal distance of air supply is about 45.9ft.(14m) and the maximum height of air supply is
about 21.3ft.(6.5m).
Innovative air supply technology for excellent room temperature control
Layout Example:
Outdoor Units

Indoor Unit Indoor Unit

Outdoor Air processing unit

Air-conditioning Fresh air supply

94
Model 4TVF0042A10WEAA 4TVF0048A10WEAA 4TVF0075A10WEAA 4TVF0085A10WEAA 4TVF0096A10WEAA

Power Supply 208230V-1Ph-60Hz

kW 12.5 14 20 25 28

Cooling kcal/h 10,800 12000 17,200 21,500 24,100

Btu/h 42,600 47,800 68,200 85,300 95,500


Capacity
kW 10.5 12 18 20 22
Heating kcal/h 9,000 10,300 15,500 17,200 18,900

Btu/h 36,000 41,000 61,400 68,200 75,000

Cooling 468 468 616 616 616


Power input W
Heating 468 468 616 616 616

Cooling 2.4 2.4 4.2 4.4 4.4


Rated current A
Heating 2.4 2.4 4.2 4.4 4.4

m3/h 2,142/1,870/1,611 2,142/1,870/1,611 3,210/2,700/2,200 3,205/2,750/2,300 3,205/2,750/2,300


Indoor air flow (H/M/L)
CFM 1,261/1,101/948 1,261/1,101/948 1,889/1,589/1,295 1,886/1,619/1,354 1,886/1,619/1,354

ESP (external static pressure) Pa 50(50~196) 50(50~196) 200(50~280) 200(50~280) 200(50~280)

Sound pressure level(H/M/L) dB(A) 54/52/50 53/50/48 54/53/51 55/54/52 55/54/52

Type R410A
Refrigerant
Control method EXV

Net dimension WHD in.(mm) 51-3/1616-17/3227-11/64(1300420690) 56-13/1618-1/231-57/64(1443470810)

Packing dimension WHD in.(mm) 56-17/3217-23/3230-1/4(1,436450768) 59-13/3221-21/3238-31/32(1,509550990)

Net/Gross Weight lbs.(kg) 153.2/167.5(69.5/76) 153.2/167.5(69.5/76) 251/274(114/124) 251/274(114/124) 251/274(114/124)

L(flare) in.(mm) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53) 3/8( 9.53)
Piping Connections G(flare) in.(mm) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9) 5/8( 15.9)

Drain piping in.(mm) OD 1-17/64( 32)

Standard Controller - Wired controller TCONTKJR29BKE(6 meters connection wire)

Notes:
1. Nominal cooling capacities are based on the following conditions: outdoor air temperature:91.4F(33C)DB75.2F(24C)WB, equivalent ref. piping:26.25ft. (8m)(horizontal).
2. Nominal heating capacities are based on the following conditions: outdoor air temperature:32F(0C)DB30.2F(-1C)WB, equivalent ref. piping:26.25ft. (8m)(horizontal).
3. Sound level is measured 4.59ft.(1.4m) from the air out-let.

* External static pressure are based on high speed indoor airflow.


*Connection
Specifications are subject to change without prior notice for product improvement.
Conditions:
The following restrictions must be observed in order to maintain the indoor units connected to the same system.

* When outdoor-air processing units are connected, the total connection capacity must be within 50% to 100% of that of the outdoor units.

* When outdoor-air processing units and standard indoor units are connected, the total connection capacity of the outdoor-air processing units must not exceed 30% of that of the outdoor units.

* Outdoor-air processing units can be used without indoor units.

Indoor Units Lineup


* The fresh air processing unit is not available for Heat Recovery/3Pipes System.

95
ERV-
ERV - Energy Recovery
Energy Recovery Ventilator
Ventilator

Larger air supply rate Model Names


enhanced heat exchange efficiency TERV0120AB0AA TERV0300AB0AA
enhanced energy saving TERV0175AB0AA TERV0470AB0AA
TERV0235AB0AA TERV0600AB0AA

The heat recovery ventilator (ERV) can reclaim


the energy energy lost through ventilation and
reduce room temperature fluctuations caused by
the ventilation process. By utilizing the latest
technologies and techniques, Trane ERV
guarantees outstanding performance. The heat TERV0900AC0AA TERV1200AC0AA
exchange core is made of chemically treated
paper that optimally controls temperature and
humidity in a given room. Temperature exchange
efficiency exceeds 65%, and enthalpy exchange
efficiency ranges from 50 to 65%.

RA
(Returm air
from room)
SA
Heat 14
C
Cold air
0 0C
u
Moisture
SA
(Supply air
to room)
Moisture
EA
6
C Heat Warm air
C
20C

Heat exchange plate

EA
(EXhust air
to outdoors)

OA
(Fresh air from
outdoors)

96
58
ERV - Energy Recovery
ERV-
Ventilator
Energy Recovery Ventilator

Low noise
Sound proof material is used to guarantee quiet operation.

Compact design, flexible installation and easy maintenance

With a height of just 264mm and a weight of 23kg, the unit


can be easily installed in a limited space. 264mm

Multiple modes for different scenarios

Heat exchange mode


When the airflow generated by fans travels across the heat exchange core, the temperature difference
between the two channels of the core causes natural thermal transmission. On summer days, hot outdoor air is
cooled by the indoor exhaust air; in winter, cold outdoor air is heated by the indoor exhaust air.The energy
contained in the exhaust air can be reclaimed to improve energy efficiency.

Bypass mode
In mild climates where the temperature and humidity difference between indoors and outdoors is small, the
unit works as conventional ventilation fan. Both the supply fan and exhaust fan work at the same speed
(auto/low/medium/high).

Heat exchange mode


Damper Bypass mode Damper

EA RA EA RA

Element Element

OA SA OA SA

59

97
ERV-- Energy Recovery
ERV
Energy Recovery Ventilator
Ventilator

Air supply mode


It is one kind of bypass mode with air supply fan speed higher than exhaust fan speed. It can
be used in mild climate area where large amount fresh air is needed.

Exhaust air mode Auto mode


It is also one kind of bypass mode with exhaust fan speed The controller chooses heat exchange mode or
higher than air supply fan speed. It can be used in mild bypass mode according to the temperature
climate area where large amount exhaust air needs to be difference between outdoor and indoor
expelled. temperature. Both the two fans work at low speed.

Flexible control
th other indoor units via controller is possible
Interlocking control with

EA

SA RA

IDU

Centralized control
SA
TCONTCCM30A

98
60
Specifications
Model TERV0235AB0AA TERV0300AB0AA

Power Supply V/ph/Hz 220-240/1/60


65 65
Temp. Exchange Efficiency (%) [60Hz] % 65 65
70 70
High 50 50
Enthalpy For Cooling Medium 50 50
Exchange Low 55 55
High % 60 60
Efficiency (%)
For Heating Medium 60 60
[50Hz]
Low 65 65
Heat High 32 35
Exchange Medium 31 34
Mode Low 25 28
Sound Level dB(A)
High 33 36
Bypass
Medium 32 35
Mode
Low 27 30
Dimensions(WDH) mm 944927270 10,381,026270
Machine Weight kg 31 41
Casing - Galvanized steel plate
Heat Exchange System - Air to air cross flow total heat (Sensible heat + latent heat) exchange
Heat Exchange Element Material - Specially processed nonflammable paper
Type - Centrifugal fan
Airflow Rate High 400 500
[60Hz] Medium m /h
3
400 500
Low 300 375
Fan High 80 80
ESP (Pa) [60Hz] Medium Pa 65 68
Low 43 45
Motor Output W 80 120
Duct diameter /mm 144 194
Operation ambient condition - '-7C-43C (DB), 80%RH or less

Specifications
Model TERV0470AB0AA TERV0600AB0AA TERV0900AC0AA TERV1200AC0AA

Power Supply V/ph/Hz 220-240/1/60 380/3/60


65 65 65 65
Temp. Exchange Efficiency (%) [60Hz] % 65 65 / /
70 70 / /
High 50 50 50 50
Enthalpy For Cooling Medium 50 50 / /
Exchange Low 55 55 / /
High % 60 60 60 60
Efficiency (%)
For Heating Medium 60 60 / /
[60Hz]
Low 65 65 / /
Heat High 39 40 51 53
Exchange Medium 38 39 / /
Mode Low 32 33 / /
Sound Level dB(A)
High 40 41 52 54
Bypass
Medium 39 40 / /
Mode
Low 34 35 / /
Dimensions(WDH) mm 1,2861,006388 1,2861,256388 1,6001,270540 1,6501,470540
Machine Weight kg 62 79 163 182
Casing - Galvanized steel plate
Heat Exchange System - Air to air cross flow total heat (Sensible heat + latent heat) exchange
Heat Exchange Element Material - Specially processed nonflammable paper
Type - Centrifugal fan
Airflow Rate High 800 1,000 1,500 2,000
[60Hz] Medium m3/h 800 1,000 / /
Low 600 750 / /
Fan High 100 100 160 170
ESP (Pa) [60Hz] Medium Pa 82 85 / /
Low 54 58 / /
Motor Output W 360 360 450 450
Duct diameter /mm 242 242 346326 346326
Operation ambient condition - '-7C-43C (DB), 80%RH or less

Note:
1. Three speeds (low/med/high) are available for ERV models 200 to 1000; one speed is available for HRV models 1500 to 2000.
2. The sound level is measured at 1.4m below the body center in an anechoic chamber.
3. The airflow rate can transmit between low and high modes.
4. The temperature exchange efficiency is the mean value between cooling and heating
5. Efficiency is measured under the following conditions:
* Cooling Condition: Air Exhaust Temp. 27C DB,19.5CWB., Fresh Air Temp. 35C DB,28CWB
* Heating Condition: Air Exhaust Temp. 21C DB,13CWB., Fresh Air Temp. 5C DB,2CWB

99
Control Systems
Control System-sNetwork
-
Control
Network Control
Trane Router
Centralized Control

Indoor Centralized Controller


(Touch-style Key)

X,Y,E

Trane Remote Users Monitoring


TCONTCCM30A
Service Centre System

Connectable to
various sized Gateway
Weekly Schedule
Centralized Controller

X,Y,E

TCONTIF441V4PA58 TIMSWENETMA
TCONTCCM09A

Indoor Centralized
Controller
Lonworks BMS TCONTLWGW64E
X,Y,E

TCONTCCM03A

BACnet BMS

TCONTCCM08A
Outdoor Centralized
Controller

Web monitoring system F1,F2,E K1,K2,E

TCONTCCM02A

Note: The wires in the diagram show the signal flows only,
while not represent the actual connecting ways.
Modbus BMS TCONTMBGW01E

100
Control Systems - Network
Control

Individual control
Wired controller
TCONTKJR10B
TCONT10BDPC
TCONTKJR12B
TCONTKJR120B
TCONTKJR86C
TCONTKJR90AE
TCONTKJR90A1E
TCONTKJR90BME
TCONTKRJ29BKE

Remote controller
TCONTR51CE
TCONTRM05A

Accessories
Card-key Interface TCONTNAM05A

TCONTNAM05A

TCONTKJR10B

Card-key

Infared Sensor TCONTNAM09A

Infrared control box

TCONTKJR10B

Infrared sensor module

Outdoor units

101
Comparison of Controllers
Item Rem ote c ontroller W ired Controller Centralized Controller

TCONT TCONT
TCONT TCONT KJR10B TCONT TCONT CCM03A TCONT TCONT
RM05A R51CE TCONT KJR90AE KRJ29BKE TCONT CCM09A KJR90BME
KJR12B CCM30A
removable 1 1 1 64 64/16 16

On/Off

Operation mode setting

Fan speed setting -

Room temp. setting -

Vertical swing - - - - - -

Horizontal swing -

Air direction - - - - - - -
A/C control
Economic mode - - - - -
function
Group setting - - - - -

Keyboard lock - -

Mode lock - - - - - -

Remote signal receiving - - - - - - -

26 shortcut setting - - - - - - - -

Silent mode - - - - - - -

Backlight /- -

Current time - /- - - -

Display RC prohibition - - - - - -

Address - - - - - -

Error code - - - - - -

Period - - - - - - Week -

On/Off per day - - - - - - 4 -


Timer
On/Off per week - - - - - - 28 -

On/Off timer -

FOLLOW ME - - -/ - - - -

Emergent stop - - - - - - -

Emergent start - - - - - - -

Address setting - - - - - -

Control BMS access - - - - - - -

Control via internet - - - - - - -

Air filter cleaning reminding - - /- - /- - -

10 heat function - - - - - - - -

: Available controller functions


- : Not available controller functions
64

102
Control Systems- -
Control Systems
Wireless RemoteController
Wireless Remote Controller

Functions TCONTRM05A TCONTR51CE

Portable device Simplified user interface


The wireless remote controller is a portable control Users can synchronize the air conditioners param-
device that enables users to control the A/C eters with the display panel on the wireless remote
anywhere within a distance of 11m. controller to precisely control a room's environment.

Temp 1

Transmitting display 2 3 ON/OFF


Running mode 4

5 Time

6 Lock

ON OFF
7 Time ON/OFF

Economic operation 8
9 Fan speed

Background light
The background light allows users to operate the
device in a dark room. The device lights up when a
button is pressed, and turns off when a given AUTO

operation is completed. Auto Mode DRY Mode HEAT Mode COOL Mode

Economic Addressing
FAN Mode Lock operation setting

Built-in timer
The built-in daily timer offers the convenience of
automatically starting and stopping the system at set ON 24C OFF
times. 0 3 6 9 12 15 18 21 Time

Setting addresses The indoor unit is set to work in automode from 8:00 to 20:00

Besides the machines auto addressing function,


users can set the indoor units address on
the wireless remote controller.

Specifications
Model TCONTRM05A TCONTR51CE
Dimensions (HWD)(mm) 1506520 1406015

Power (V) 1.5V(LR03/AAA)2

65

103
Control Systems - Wired
Control Systems -
Controller
Wired Controller

TCONTKJR10B
TCONTKJR12B TCONTKJR29BKE
TCONT10BDPC
TCONTKJR120B
Functions TCONTKJR86C
Follow me
With the FOLLOW ME function, the wired controller
Sensor part can detect the air temperature at the users altitude
instead that of the ceiling or floor. This helps making
the room environment comfortable and the
temperature accurate.
FOLLOW ME Button
*The follow me function is available for
TCONTKJR12B/TCONTKRJ29BKE model.

Remote signal Air filter cleaning


receiving function reminding
TCONTKRJ29BKE provides a The air filter cleaning reminder
Remote signal
receiving signal receiver for wireless function provided by TCONTKJR10B/
remote controller. The signal TCONTKRJ29BKE reminds users via
Air filter cleaning
reminding icon is then sent to the indoor unit. the wired controller when the filter
of an indoor unit needs cleaning.
Silent mode
Under the cooling, heating and
Locking wired controller
Silent Key
TCONTKRJ29BKE
auto mode,when operate the The locking function can be used to
(Touch-style key)
Silent mode, it can reduce the prevent other people from using the
running noise through setting controller.
the fan speed to low. This will
help you bring a quieter envi-
ronment. TCONTKRJ29BKE
Display panel
Wired controller
Easy connection
The wired controller conveniently connects to the
indoor units display panel via a connecting wire. Indoor main board

Specifications
TCONTKJR10B
TCONTKJR12B
TCONT10BDPC
Dimensions (HWD)(mm)
Model 12012015 12012015 TCONTKRJ29BKE
Power (V) DC 5V
12012020

104
Control
Control Systems
Systems - - Wired
Controller
Wired Controller

TCONTKJR90AE
Functions
Features
General function
Small and easy to install
Suitable for all types of indoor units
Can be stored in a mounting cabinet

Built-in timer
TCONTKJR90AE
The built-in daily timer offers the convenience of automatically
starting and stopping the system at set times.

Specifications
Model TCONTKJR90AE

Dimensions (HWD)(mm) 908613

Power (V) DC 5V

105
Control Systems- -
Control Systems
Centralized Controller
Centralized controller

Indoor Centralized Controller

COOL Mode Swing With the PC or


gateway communication

Wireless Remote
HEAT Mode Keyboard lock Controller Lock

TCONTCCM03A TCONTCCM30A
Fan Mode Cooling Lock Heating Lock

Functions
Centralized control Three lock modes
The centralized controller is a multifunctional device that can Centralized controller provides a superior
control up to 64 indoor units within a maximum connection way to manage the indoor units. Users are
length of 1,200m. able to make their own choice from locking
The device connects to the master outdoor units of Trane's the wireless controller, locking the running
newly designed products to simplify and centralize the wiring mode or lock the centralized controller's
configuration. The two connection modes are as follows: keyboard as they wish.

X,Y,E P,Q,E P,Q,E P,Q,E

Locking
king king
Locking Locking
king
ning
Running mote
Remote board
Keyboard
X,Y,E X,Y,E X,Y,E X,Y,E ode
Mode troller
Controller

Indoor unit working status display Air filter cleaning reminding function
The centralized controller displays indoor units' working The air filter cleaning reminder function is only
status and error codes so users can easily identify faults available on the touch-key central controller
via checking the error codes table in the user's manual TCONTCCM30A. The "FL" icon indicates that the
before contacting a service engineer. air filter in a given indoor unit needs cleaning.

Error code or Connecting


protection code status matrix

GROUP QUERY RUN SET


Air filter cleaning
#GROUPALL 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16
reminding icon
(1.6)

ERROR # MODE AUTO


00+
INLINE ON OFF PROTECT
16+

ROOM.TEMP SET.TEMP 32+


T3 OFF
FAN 48+
T2A
Hr ON T2B Hr
OPR.UNSUCCESS

TCONTCCM30A

106
Control Systems -
Centralized Controller
Functions
Stylish design Single/unified control
CCM's stylish design suits high-end environments. The control object can be either a single unit or all
The keyboard lock function is used to prevent units, which vastly simplifies the control process.
r
cation
operational mistakes. Operation signal feedback ensures that all units are
working in the correct mode.

ote
ck

OPR.UNSUCCESS

or
re
ng
ng Easy installation
Centralized controller offers two different appearances to mostly suit the installation. The A structure must
be embedded into the wall and the B structure doesnt need. Both of them are easy to operate.

Upper side outlet

Rear side outlet


B

Under side outlet

*The A,B structure is available for TCONTCCM30A


on and TCONTCCM03A only has B structure B structure leading-out mode sketch

Access to network monitoring


e The centralized controller is able to bridge up to 64 indoor units on the network monitoring and building
management systems.
X,Y,E F1,F2,E

MAX.64

Indoor CCM

Specifications
Model TCONTCCM03A TCONTCCM30A
51
Model
Dimensions (H*W*D)(mm) 17911974 18012278 and 18012268

Power (V) 198-242V(50/60Hz)

107
Control Systems -
Control Systems
Centralized -
Controller
Centralized Controller
Weekly schedule centralized AUTO

Auto Mode COOL Mode HEAT Mode Fan Mode

DRY Mode Sending query order Swing Keyboard lock

TCONTCCM09A
Cooling Lock Heating Lock Wireless Remote With the PC or gateway
Controller Lock communication

Functions
Weekly schedule
8:00 16:00 23:59
TCONTCCM09A can include up to 64 indoor units in
Sun 28C 22C 24C
the weekly schedule. Users can set up to 4 periods Mon 26C 22C 17C 23C

per day, and select the desired running mode and Tue 26C 22C 17C 23C

Wed 26C 22C 17C 23C


room temperature. The operating object can be a
Thu 26C 22C 26C

single indoor unit or all the indoor units. Fri 26C 22C 26C

Sat 28C off 24C

Three lock modes Single/unified control mode


Centralized controller TCONTCCM09A provides The control object can be either a single unit or all
a superior way to manage the indoor units. Users units, which vastly simplifies the control process.
are able to make their own choice from locking the Operation signal feedback ensures that all units are
wireless controller, locking the running mode or working in the correct mode.
lock the TCONTCCM09A

OPR.UNSUCCESS

king
Locking king
Locking Locking
king
ning
Running mote
Remote Keyboard
board
ode
Mode troller
Controller

Indoor unit working status display


Error code or Connecting
TCONTCCM09A displays indoor units' working protection code status matrix
status and error codes so users can easily identify GROUP QUERY RUN SET

faults via checking the error codes table in the user's #GROUPALL 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16
(1.6)

ERROR # MODE AUTO


00+
INLINE ON OFF PROTECT
16+

manual before contacting a service engineer.


ROOM.TEMP SET.TEMP 32+
T3 OFF
FAN 48+
T2A
Hr ON T2B Hr
OPR.UNSUCCESS

Specifications
TCONTCCM09A

Dimensions (H*W*D)(mm)
Model 17911974

Power (V) 198-242V(50/60Hz)

108
Control
Control Systems
Systems - -
Centralized
Centralized Controller
Controller

Unified On/Off Controller


Unified controller design with graceful appearance and explicit panel.

Functions TCONTKJR90BME

Unified control
TCONTKJR90BME offers on/off and heating/cooling
functionality for indoor units based on preset
20C
0C 28C
temperatures to ensure easy management. cooling heating

Centralized control
KJR-90B can be used to centrally control up to 16 indoor units.
Max.16

Light indicator
The LEDs on TCONTKJR90BME indicate the indoor units' running status for easy fault detection. The lights
switch off automatically to save energy once a given operation is complete. The indicators are as follows:

Light Blue Red Flash

Single On/Off key Cooling/Fan Heating IDU Error

Unified On/Off key EEPROM Error

Easy installation
TCONTKJR90BME can be easily mounted on the built-in cabinet:

Specifications
Model TCONTKJR90BME

Dimensions (H*W*D)(mm) 90868

Power (V) DC 5V

109
Control
ControlSystems
Systems- -
Accessories
Accessories

Hotel card key interface module


Cooperate with the wired controller to automate control.
Eliminates the need for high voltage power, making the device safe and
steady.
Includes a build-in auto-restart function. TCONTNAM05A O
Installation example Electrical wiring

Wired controller
TCONTKJR10B
TCONTKJR10B
220V
KM
TCONTNAM05A
TCONTNAM05A
Card key
AC contactor
Card key

Wired controller is necessary in this card-key system.

Specifications
Model TCONTNAM05A

Dimensions (H*W*D)(mm) 8672.815.5

Power (V) DC 5V

Digital Power Meter


Calculates power consumption.
Does not need adjusting after long-term use.
Corresponds one outdoor unit to one digital power meter.

TCONTDTS636

Low power consumption Indications and installation

The digital power meter consumes mini- 72


15mm long crack
The digital power meter is tested
mal energy. LCD after manufacture so it can be
Voltage circuit: less than 2W/10VA Impulse
immediately deployment and used
Current circuit: less than 2.5VA on-site. The LED indicators and
201

A phase
230

B phase
C phase

installation schematic are shown in


145 131 the figure on the left.

Specifications
Model TCONTDTS636

Dimensions (H*W*D)(mm) 23014572


Power (V) 200V-500V(50/60Hz)

72

110
Control Systems -
Control Systems -
Accessories
Accessories

Outdoor centralized controller

With the outdoor With the PC or


HEAT lock COOL lock units communication gateway communication

Forced
Cooling

TCONTCCM02A Forced Cooling Low Middle High

Functions
ODU parameters display
Forced
TCONTCCM02A enables users to easily check
Cooling

outdoor units' running status, including


frequency, temperature, current, pressure,
protection codes and error codes.

Graph 2 LCD Screen

111
Control
ControlSystems
Systems --
Accessories
Accessories
Access to network monitoring
TCONTCCM02A can connect up to 8 refrigerant systems and 32 outdoor units to the network monitoring and
building management systems.
K1,K2,E Max.4

system 1

Max.32 K1,K2,E Max.4

system 2

K1,K2,E Max.4

Specifications system 8

Model TCONTCCM02A

Dimensions(HWD)(mm) 12012015

Power (V) 198-242V(50/60Hz)

Remote alarm controller


TCONTKJR32BE

Functions
Simple design
TCONTKJR32BE is specially designed for engineering applications. It does not display the ODUs working
parameters, but it can connect to the alarm device when ODU is working abnormally, the RUN light will flash.

Specifications
Model TCONTKJR32BE

Dimensions (H*W*D)(mm) 1508570


Power (V) 198-242V(50/60Hz)
74

112
ControlSystems
Control Systems- -
Accessories
Accessories

Infra-red sensor controller


TCONTNAM09A
Automatically adjust the room environment.
Automatically extend the shutting down time, avoiding frequent ON/OFF.
Graceful appearance accommodates itself to different buildings.

Installation example Electrical wiring


Infra-red inductive controller

Infra-red
sensor
TCONTKJR10B Display panel
TCONTKJR10B TCONTNAM09A works
CN3
together with the wired CN2
TCONTNAM09A CN1

TCONTNAM09A
controller. S1
TCONTNAM09A
Infra-red inductive
control box
Indoor main board
TCONTKJR10B
Wired controller

Specifications
Model TCONTNAM09A

Dimensions(HWD)(mm) Senor part: 463025.6, Control box: 8672.815.5

Power Powered from display panel. Extra power unnecessary.

ERV wired controller


TCONTKJR27B

Functions
ERV controller Built-in timer
TCONTKJR27B is individually designed for ERV Built-in daily timer offers the convenience of
Energy Recovery Ventilator. The ERV can work in the automatically starting and stopping the ERV at
following modes: exhaust, air supply, bypass, heat the set times.
exchange, and auto. Setup screen example
Set to wednesday: 8:00 to 20:00

AUTO->HEAT EXCHANGE-> ON 24C OFF


EXHAUST->BYPASS->AIR SUPPLY 0 3 6 9 12 15 18 21 Time

Specifications
Model TCONTKJR27B

Dimensions(HWD)(mm) 12012015
Power (V) 198-242V(50/60Hz)

75

113
Control
Control Systems
Systems --
Accessories
Accessories

Control Box
TAYKITAHUKZ01
TVR 4G functions inside.
Match the new outdoor units. TAYKITAHUKZ02
TAYKITAHUKZ03
Introduction
TAYKITAHUKZ01/TAYKITAHUKZ02/TAYKITAHUKZ03 is an independent control box that can connect a AHU
to TVR system to realize centralized control with TVR system. Control box wiring is as follows:
Power supply Power supply
Centralized Controller

P/Q/E X/Y/E

Wired Controller

T1/T2/T2B/T2C

G/L pipe
Fan/pump

x EXV

Power supply

DX AHU or other brand indoor units

Specifications
Model TAYKITAHUKZ01/TAYKITAHUKZ02/TAYKITAHUKZ03

Dimensions(HWD)(mm) 335375150
Power (V) 220-240V~ 50Hz 208-230V~ 60Hz

Trane outdoor unit diagnosis


software TCONTWPMCACE
Display the outdoor units real-time running conditions.
Automatically outputs running status charts.

Wiring diagram
The diagnostic software applies to K1, K2, E of the outdoor units. The corresponding wiring diagram is shown
in the figure on the right.

485A-I
K1,K2,E

Recommended config
Operating system WIN XP SP4/WIN 7

CPU Pentium 4 2G or above


HDD 30G free space

Interface port RS-232 terminal

114
Building
Building Management
Management
System(BMS)
System (BMS)

TIMSWENETMA
TCONTIF441V4PA58

Functions
TIMSWENETMA/TCONTIF441V4PA5, designed specifically to control TVR systems, is based on a centralized
format and dedicated to the complete control and monitoring of all the systems functions. It can be used as a
flexible multi-purpose system and applied to a variety of needs, according to the scale, purpose and control
method of each building.

Up to 4 TIMSWENETMA, 64 refrigerant systems, Proportional power distribution


1,024 indoor units, and 256 outdoor units can be Annual schedule control
controlled by one PC.
Web Access Low-load operation indicate
User friendly operation Generate operational history reports
Central building monitoring and control (daily, weekly, monthly)
Fault display & Warning message
Lock control (individual controllers)
Filter replacement reminder
Set temperature limit
Emergency stop and Alarm signal output

Network Control Application

Can run on Windoww 7_32 bit and


Window XP_32 bit.
Can monitor and control
ntrol A/C anytime,
anywhere by PC, phone,
hone, pad and
notebook computer.
ss: IE, Firefox, Safari
Support WEB access:
and Chrome.
Enables remote access
cess through DSL,
VPNs and so on.

IDU:1024
Max.IDU:1024

115
Building Management
System (BMS)
Various Managements
Simple Operation and Management
Click & Operate, a user-friendly interface allows even non-experts to perform
the building management system easily.

Data Management
Operational information of individual indoor units are monitored, allowing for
distribution of power consumption at outdoor units.
Stores operation data on multiple systems and displays it in graphical format for
visual management.
Uses TIM software to generate tenant reports and help building owners bill for
energy use.

Electricity Charge Distribution(Patented)


Provides information on proportional electrical power distribution to optimize
electricity consumption management.
Uses software to calculate electric power proportional distribution, output and save electricity consumption data for each indoor unit (or
group) which is connected to the intelligent manager.
Applies the patented Trane Calculation Method to calculate consumption rates according to capacity demand which is based on various
parameters: setting temperature, room temperature, running mode, rated HP, public areas, unused rooms, and nighttime use; outputs
this information on a charge calculation sheet to evenly divide power consumption charges among tenants.

Hightlights

Web Access function Visual Navigation


With the web access function, a PC, laptop computer Clicking the jump button will display a list of all
or a smart phone can be used as a remote controller. available screens. Clicking the back button will return
to the previous screen.

Energy Saving Management Data Backup


Based on a predetermined schedule, the Intelligent The Trane-interface will automatically back up data on the
Manager executes capacity control and intermittent installed SD card (2GB) in case system failure occurs,
operations on all air conditioning units to maintain a such as: power failure or system dam. TIM software
high comfort index. also stores the previous 3 months' operational data on
the HDD.

Schedule Control Multiple Lauguages


Automatically performs facility start/stop control, Provides eight language settings:
switches the operating mode, sets temperatures and English French Italian
enables/disables the remote control according to the
Russian German Spanish
present time schedule. 4 sections and 20 actions per
Simple Chinese Traditional Chinese
day for each single unit or group.

Warning Message Electricity Charge Distribution


The system can receive error messages from air Electricity charges can be easily divided when billing
conditioning units in more than one buildings or users for air conditioning power charges; for example,
78
structures via public phone lines. for tenants in a commercial building, offices in a rented
*Requires the Trane "SMS Modem" to send building, or rooms in a hotel.
automatic warning messages to designated phone
numbers.

116
Building Management
System (BMS)

BACnet BMS Gateway


Contains 4 groups of RS-485 communication ports and be able to
connect up to 256 indoor units or 128 outdoor units to the BMS.
Be free to connect to the BMS or not.

Network example TCONTCCM08A

One TCONTCCM08A gateway can connect MAX.4 TCONTCCM02A or TCONTCCM03A,and each 485 port only
can connect one TCONTCCM02A or one TCONTCCM03A.

Outdoor units
TCONTCCM08
Indoor units

TCONTCCM02A

TCONTCCM03A

RS485
Outdoor units

HUB
TCP/IP BACnet/IP protocol

TCONTCCM03A Indoor units

Web monitoring BMS


system

Monitoring units online


TCONTCCM08A allows users to track units' operational status and change their running parameters on Internet
Explorer for maximum control convenience

Wide compatibility
TCONTCCM08A has a wonderful adaptability to the BMS
Company BMS software Brand

APOGEE
1 SIMENS APOGEE A N Y W H E R E

TM

2 TRANE Tracer Summit


TRACER SUMMT

3 Honeywell Alerton

4 Schneider Andover

5 Johnson METASYS

117
Building
Building Management
Management
System
System(BMS)
(BMS)

Modbus BMS Gateway


Supports Modbus protocol networks
Bridges the Trane central A/C system and the BMS
Establishes a Modbus network comprising up to 1,024 indoor units and 64
outdoor units
Transfers data in RTU mode
Provides a wide voltage range: 12-48V DC

Network example
Indoor Units
Modbus agreement system
P,Q,E
E Max.64

TCONTCCM03A
F1,F2,E X,Y,E
K1,K2,E
K1,K2,E
Outdoor Units
Modbus
Modbus Master
Gateway
TCONTCCM02A

E
P,Q,E Max.64

TCONTCCM03A
F1,F2 X,Y,E
K1,K2,E

Modbus K1,K2,E
A+,A-,GND
Gateway
TCONTCCM02A

Max.16

E
P,Q,E Max.64

TCONTCCM03A
F1,F2

Modbus
Gateway
TCONTCCM02A

One Modbus gateway can bridge one refrigerant system with a PC or the Modbus master.

Config A/C System via Web Dimensions


When the Modbus network is set, users can The Modbus Gateway is designed with a small size.
conveniently configure their A/C network system Its equipped a installation track for the easy on-site
over the Internet using different TCP/IP browsers. installation.

10.5
Right Side Front Side
110
36
48

35
25.5

10.5 Installation Track

100 46

80

118
56
Building Management
Building Management
System (BMS)
System (BMS)

LonGW64 BMS Gateway


The new Lonworks gateway has been compliance with LonMark protocol.
It can connect up to 64 indoor units to the BMS.
It realize non-polarity communication,and also the application can be
download online.
TCONTLWGW64E
Network example
(1) Connection method 1: Suitable for all of air (2) Connection method 2: Only suitable for TVR
conditioner systems and connect max.64 indoor units. system and connect max.64 indoor units.
System 1
TCONTLWGW64E
P,Q,E X,Y,E X,Y,E X,Y,E X,Y,E

RS485 X,Y,E
TCONTLWGW64E

P,Q,E
X,Y,E X,Y,E X,Y,E X,Y,E
RS485
Lonworks
net work System 2

P,Q,E

BMS system System N


BMS system

Specifications
Model TCONTLWGW64E

Dimensions (H*W*D)(mm) 31.925.16.1

Power (V) 177~265V AC(50Hz/60Hz)

BM

119
Piping Accessories
Piping Accessories
Outdoor / Indoor Branch Specification
Packing Size (mm)/
Model Features Model name Description
Gross Weight (kg)

4TODK02C 45555185 / For two outdoor


1.4 units connection

4TODK03C 46585265 / For three outdoor


2.7 units connection
Branch joint for

410A outdoor unit


4TODK04C 465115255 / For four outdoor
4 units connection

4TRDK01C 2555090 /
A*<16.6kW
0.48

4TRDK02C 2805095 /
16.6A*<33kW
0.6

Branch joint for


4TRDK03C 31070125 / 33kWA*<66kW
0.87
R410A indoor unit

4TRDK04C
35070170 / 66kWA*<92kW
1.3

4TRDK05C
365110205 / 92kWA*
1.6
A*:The total capacity of indoor units following this branch joint

120
Piping Accessories
Piping Accessories
Outdoor branch drawing
Outdoor branch 4TODK02C 4TODK03C Packing Size (mm)/ 4TODK04C
Features Model name Description
Gross Weight (kg)
0D:31.8 0D:31.8 ID:31.8 0D:31.8 ID:31.8

ID:25.4 ID:25.4 ID:25.4 0D:34.9


0D:34.9
Q2 Q2 Q2
Q7 Q7
ID:38.1 Q1 ID:38.1
Q1 Q1 ID:31.8
ID:31.8
ID:31.8 ID:31.8 ID:34.9 ID:31.8 ID:34.9
0D:31.8 0D:31.8 ID:25.4 0D:31.8
ID:25.4 ID:25.4

ID:38.1
ID:31.8
ID:41.3
ID:34.9
Q5
Gas side
Q4 ID:38.1
Q1
ID:31.8
ID:41.3
ID:31.8 ID:31.8
ID:25.4 0D:31.8
Q5
0D:34.9 ID:41.3
Q1 ID:44.5
ID:31.8
Q3 ID:31.8
ID:25.4 0D:31.8 Q6
ID:38.1

ID:34.9 Q1
ID:31.8
ID:31.8
ID:25.4 0D:31.8

0D:15.9 ID:15.9 0D:15.9 ID:15.9 0D:15.9 ID:15.9

ID:12.7 ID:19.1 ID:12.7 ID:12.7 ID:19.1


ID:19.1
Y2 Y2 Y2
Y6 Y6 Y6

Y1 ID:15.9 Y1 ID:15.9 Y1 ID:15.9

ID:15.9 ID:15.9 ID:15.9


0D:15.9 0D:15.9 0D:15.9
ID:12.7 ID:12.7 ID:12.7

ID:19.1 ID:19.1
ID:22.2 ID:22.2

Liquid side 0D:19.1 Y7


Y7

Y3 Y1 ID:15.9 Y1 ID:15.9
ID:22.2 ID:15.9 ID:15.9
0D:15.9 0D:15.9
ID:12.7 ID:12.7
ID:19.1

0D:22.2 0D:25.4 ID:22.2


ID:25.4
Y4 Y5
Y8
ID:19.1 ID:22.2

Y1 ID:15.9
ID:15.9
0D:15.9
ID:12.7

ID:6.4 ID:6.4

Oil balance pipe


P P(2pcs)

121
Name

4TRDK05C
4TRDK04C
4TRDK03C
4TRDK02C
4TRDK01C
ID:22.2
ID:19.1
ID:22.2 ID:28.6
ID:34.9
ID:28.6 ID:12.7 ID:15.9 ID:12.7
ID:34.9 ID:15.9
OD:34.9 ID:19.1
ID:15.9
ID:12.7 Indoor Branch Drawing
ID:41.3 ID:19.1 ID:22.2 (ID:19.1) (ID:15.9)
OD:34.9 (ID:19.1)
ID:41.3 ID:22.2 (ID:15.9)
ID:44.5 OD:22.2
ID:34.9 OD:28.6 OD:19.1
OD:22.2 OD:19.1
OD:28.6
Gas side joints

ID:22.2 ID:19.1
ID:28.6
Piping

OD:41.3 OD:34.9 OD:28.6 OD:22.2 OD:19.1

ID:41.3 ID:22.2 ID:19.1


ID:34.9 ID:28.6

BM
ID:44.5 ID:38.1 ID:31.8 ID:25.4 ID:15.9

ID:12.7 ID:15.9
ID:9.5 ID:12.7 ID:6.4
ID:6.4
ID:15.9
(ID:19.1) ID:12.7
(ID:15.9) ID:9.5
(ID:19.1) ID:9.5 ID:6.4 ID:9.5
Piping Accessories

(ID:15.9)
Accessories

OD:22.2 (ID:12.7)
OD:19.1 (ID:12.7) ID:6.4
OD:22.2 OD:19.1 ID:9.5 ID:6.4
OD:15.9 OD:12.7
ID:22.2 ID:19.1 OD:9.5
OD:15.9 OD:12.7
ID:12.7 ID:9.5
ID:15.9
OD:9.5
ID:9.5
Liquid Side Joints

OD:22.2 OD:19.1 OD:12.7


OD:15.9
ID:22.2 ID:19.1 OD:12.7
ID:12.7
ID:15.9
ID:25.4 ID:22.2 ID:19.1 ID:9.5 ID:9.5

122
Notes

.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
.......................................................................................................................
123
PF/120815

Literature Order Number TVR5G-SLB001-R410A-60HZ-EN


Dat e Aug 2015
Supersedes NEW
PF/120815

Trane has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice. 2014 Trane

124

Literature Order Number TVR5G-SLB001-R410A-60HZ-EN