An Introduction
3. Use of water
Viking Page 3
Our objectives for EconAqua
Viking Page 5
Viking Page 6
Our objectives for EconAqua
Viking Page 7
Our objectives for EconAqua
Viking Page 8
Our objectives for EconAqua
Viking Page 9
Our objectives for EconAqua
Viking Page 10
Our objectives for EconAqua
Viking Page 11
Our objectives for EconAqua
Viking Page 12
Our objectives for EconAqua
Viking Page 13
EconAqua is for licensees only
Viking Page 14
Customer Benefits
Is different
Saves space
Saves time
Saves water
Saves money
Viking Page 15
Thank you
any questions?
Viking Page 16
Part 2 Water
Standard Systems
Viking Page 19
1. Wet pipe alarm valve NMX
2. Valve head
3. Gate valve for water supply
4. Alarm test valve
5. Drip check valve
6. Valve seat
7. Vent valves
8. Shut-off valves for pressure gauges
9. Pressure gauge for pipework
10. Pressure gauge for water supply
11. Alarm pressure switch
12. Water motor alarm gong - AG 2
13. Strainer
14. Drain valve
15. Retard chamber
16. Alarm shut-off valve
17. Non-return valve
18. By-pass pipe
Viking Page 20
Dry system
Viking Page 21
Viking Page 22
Pre-action system
Viking Page 23
Preaction valve TAV-VMX & TMX/S
Detectors
Detectors
Type A Type B
Pipe network
Pipe network
Air supply
Air supply
Alarm channel
24V-DC
Alarm channel
Alarm line
Viking Page 24
Type A:
Standard preaction single interlock valve
To avoid false release
Interacts with the FD-System
Release of a sprinkler does not cause release of the valve.
Signal of FD-System is mandatory to open release the valve
Note: In case of malefunction of the FD-System the preaction single interlock operates as a normal
dry valve.
Type B:
Non interlock valve
Dry system with is normally supported/accelerated by the FD-system
Operates lake a normal dry valve with accelerator
FD system opens valve even if no sprinkler is released
Viking Page 25
Attention!
Type A & Type B:
Actuation of the FD-System always causes the release of the valve!.
Type A:
Release of a sprinkler will not cause release of the valve
Type B:
Release of a sprinkler will open the valve!
Viking Page 26
Special finish cover plates
Protective Cap
Removal Tool
Small or Large
Cover plate
Installation tool.
Viking Page 28
Viking Page 29
VdS CEA Guidelines for Sprinkler Systems 4001 en
NFPA 13 FM Global
Viking Page 30
Thank you
any questions?
Viking Page 31
Part 3 Storage
Rolled Paper
Storage
Rack
Storage
Viking Page 33
Types of storage
Palletized
Storage
Idle Pallet
Storage
Viking Page 34
Types of storage
Viking Page 35
Types of storage
Baled Cotton
Storage
Rubber Tire
Storage
Viking Page 36
Viking Product Seminar
Part 2 - Sprinklers
Control Mode
Storage
Sprinklers
Storage Fires are very demanding and require more water to control them than standard
occupancy hazards.
Due to the nature of the fire and the subsequent heat release, NFPA 13 places limitations
on the orifice size that can be used based on density requirements. (mm/min)
Viking Page 38
Control mode sprinklers for storage
Larger K factors develop larger water droplets that are able to penetrate the fire
plume and the thermal updraft.
Larger K factors also can discharge the same water flow rate at much lower
pressures, so they are more efficient at controlling the fire.
Lower starting pressures at the sprinkler may save the sprinkler designer a pipe
size in their calculations, which will lower the cost of the system installation.
Viking Page 39
Control mode sprinklers for storage
Maximimum Minimun PSI for K PSI for K PSI for K PSI for K
Storage Density Coverage Area
Spacing Flow Rate 5.6 8.0 11.2 16.8
0.20 gpm/ft 130 ft 15'-0" 26 gpm 12.7 psi 10.56 psi 3.1 psi 1.5 psi
(8,2 lpm/m) (12,08 m) (4,2 m) (98,4 lpm) (,88 Bar) (,72 Bar) (,22 Bar) (,1 Bar)
0.25 gpm/ft 100 ft 12'-0" 25 gpm 19.2 psi 9.7 psi 4.9 psi 1.48 psi
(10,2 lpm/m) (9,29m) (3,65 m) (94,6 lpm) (1,37 Bar) (,67 Bar) (,34 Bar) (,1 Bar)
0.3 gpm/ft 100 ft 12'-0" 30 gpm 28.6 psi 14 psi 7.1 psi 3.1 psi
(12,3 lpm/m) (9,29m) (3,65 m) (113,5 lpm) (1,98 Bar) (,97 Bar) (,49 Bar) (,22 Bar)
0.45 gpm/ft 196 ft 12'-0" 45 gpm 64.5 psi 31.6 psi 16 psi 7.1 psi
(18,4 lpm/m) (18,2m) (3,65 m) (170,3 lpm) (4,45 Bar) (2,18 Bar) (1,1 Bar) (,49 Bar)
0.6 gpm/ft 100 ft 12'-0" 60 gpm 114 psi 56.25 psi 28.6 psi 12.7 psi
(24.6 lpm/m) (9,29m) (3,65 m) (227 lpm) (7,92 Bar) (3,88 Bar) (1,97 (,88 Bar)
Viking Page 40
Viking Product Seminar
Part 2 - Sprinklers
In-Rack Storage
Sprinklers
In-rack sprinklers
Generally, when storage exceeds 7.6m in racks and control mode sprinklers are
utilized, levels of in-rack sprinklers are within the rack structure.
In-rack sprinklers require water shields to protect their operating elements from
the ceiling sprinklers. Water shields are required to be a minimum of 76mm in
diameter.
In-rack sprinklers are intermediate level sprinklers, as there is at least one level of
sprinklers above them.
Viking Page 43
Control mode sprinklers for storage
In-rack sprinklers
In-rack sprinklers are typically have k factors of 80 and 115, but in some cases are
as large as 161.
In-rack sprinklers are usually located in the longitudinal flue space of the rack, but
can be located at the face of the rack loading entrance and can be located within
the
storage space within the rack.
Rack structures with solid barriers require levels of in-rack sprinklers above the
storage where the solid barriers exist.
Viking Page 44
Viking Product Seminar
Part 2 - Sprinklers
Control Mode
Special Application
Sprinklers
The K161 CMSA upright sprinkler was the first storage sprinkler developed
with full scale fire tests series.
As an upright sprinkler, it can be installed on dry systems and double interlocked Pre-action
systems. The greatest use of this sprinkler has been in the protection of freezers, rolled
paper storage, and rubber tire storage. Known for many years as a Large Drop sprinkler, it
was the first storage sprinkler to prove that large water droplets penetrated the fire plume
more effectively than water droplets from standard spray sprinklers that have smaller water
droplets.
Viking Page 46
K161 Upright CMSA (VK540)
Viking Page 47
K283 Pendant CMSA (VK592)
Viking Page 48
K283 Pendant CMSA (VK592)
Cartoned
Unexpanded
Plastics
Viking Page 49
K283 Pendant CMSA (VK592)
Viking Page 50
K283 Pendant CMSA (VK592)
Stems spaced less than 2.3m but more than 0.9m on centers, regardless of the
depth of tee, must be located at the horizontal Plane or 25mm above the
horizontal plane of the bottom of the stems.
Not allowed for ESFR
Viking Page 51
Viking Product Seminar
Part 2 - Sprinklers
Suppression Mode
Storage Sprinklers
ESFR Sprinklers were developed by Factory Mutual in the early 1980s. ESFR
sprinklers are suppression sprinklers meaning these type of sprinklers are
designed not to control a fire, but to suppress the fire.
ESFR sprinklers in standard commodity storage, such as Class l, Class ll, Class lll,
Class lV, commodities and plastic commodities, can eliminate in-rack sprinklers.
ESFR sprinklers are limited to wet type sprinkler systems and must be installed in
buildings that have flat ceilings or roofs. (Flat ceilings are defined as roof pitches
no greater than 50mm in 300mm.
Viking Page 53
In-rack protection
Viking Page 55
Pendant ESFR sprinklers
Viking Page 56
Pendant ESFRs
Avoid Obstructions
Do not have any obstruction directly
Below the pendent ESFR sprinkler head.
Avoid obstructions
Obstructions
Of particular concern
Viking Page 59
Cold-soldering which causes sprinkler skipping
Viking Page 60
Pendant ESFRs
Viking Page 61
K202 Design criteria
Viking Page 64
K322 and K363 ESFRs
Viking Page 65
K322 and K363 ESFRs
Viking Page 66
K202 Upright ESFR
Viking Page 68
K202 Upright ESFR
Upright
Commodity
K = 202
Class 1-4 and Cartoned Unexpanded Plastic (35 ft. Roof Max) Yes
Uncartoned Unexpanded Plastic No
Cartoned Expanded Plastic, 30 ft. Roof Yes
Uncartoned Expanded Plastic No
Heavyweight Roll paper Yes
Plastic-Coated Heavyweight Roll Paper Yes
Medium Weight Roll Paper Yes
Light Weight (Tissue) Roll Paper No
Rubber Tires On-Side and On-Tread Yes
Aerosols
Level 1 Aerosols on floor and in open-frame racks only No
YES
Flammable Liquids No
Idle Pallets
Viking
on floor storage of idle wooden pallets only Page 69 No
Yes
K202 Upright ESFR
Viking Page 70
K202 Upright ESFR
Upright ESFR
Viking Page 72
When the ceiling height does not exceed
10.7m, and the commodities being stored are
within the allowable protection schemes of
upright ESFR sprinklers.
Viking Page 74
When room exists above the sprinkler line for an upright ESFR sprinkler, turning
the outlet to the pendent sprinkler 180 and installing an upright ESFR is a cost
effective method of repairing the problem.
Viking Page 75
Viking Product Seminar
Part 2 - Sprinklers
Changes to FM Rules
Viking Page 77
New FM Changes
CMDA
ESFR Storage Sprinkler
CMSA
Viking Page 78
New FM Changes
Viking Page 79
K 11.2 Pendent QR, e.g. Viking VK 377
K 22.4 Pendent QR
Pendent SR K 14
Pendent SR K 25.2
Upright K 11.2 QR, e.g. Viking VK 531
Upright K 16.8 QR
Upright K 25.2 SR
Upright K 11.2 SR, e.g. Viking VK 530
Upright K 19.6 SR
Upright K 25.2 SR
Viking Page 85
Viking Page 86
Viking Page 87
Introduction to Foam Foam Types
- Aircraft hangars
- Logistics / Storage occupancies
- Enclosed spaces
- Hazards subject to 3-dimensional fires
- LNG Storage Tanks
Viking Page 88
Foam Discharge Video
Viking Page 89
Thank you
any questions?
Viking Page 90
Karl Keller
kellerk@viking-emea.com
Ambrogio Pertile
pertilea@viking-emea.com
www.viking-emea.com