Professional Documents
Culture Documents
V Contact 7 - 12kV: Data Sheet Contactor: 1.1 General
V Contact 7 - 12kV: Data Sheet Contactor: 1.1 General
DATA SHEET
Item Description
1 Manufacturer ABB PT S.p.A. Unit Operativa Sace T.M.S.
1.1 Standard product Yes
1.2 Quality certification ISO 9001
1.3 Environmental Management System cert. ISO 14001
1.4 Country Italy
1.5 City , Address 24044 Dalmine (BG), via Friuli 4
2 Type of contactor (SF6, Vacuum, etc) Vacuum
3 Type designation
3.1 Fixed V7 - V12
3.2 Withdrawable for CBE11 / CBF11 V7/C - V12/C
3.3 Withdrawable for UniSafe and PowerBox V7/W - V12/W
3.4 Withdrawable for UniMotor V7/UN - V12/UN
3.5 Withdrawable for Unigear type ZS1 V7/P - V12/P
3.6 Withdrawable for ZS1 V7/Z - V12/Z
4 Testing Authority ABB PT S.p.A. Unit Operativa Sace T.M.S.
ABB SACE LV
CESI
5 Standards IEC 60470
Item Description
COMBINED WITH
8 Rated Making and Breaking capacity (AC4) CONTACTOR STARTER
FUSES
8.1 Making current (100 closing op.) A 4 000 4 000 4 000
8.2 Breaking current (25 opening op.) A 4 000 4 000 4 000
9 Short time rating V7 - V12
9.1 Short time current for 1 sec A 6 000 6 000 6 000
9.2 Short time current for 30 sec A 2 500 2 500 2 500
10 Maximum rated withstand overcurrent Ap 55 000
for 1/2 period (peak value)
11 Mechanical endurance (operating cycles)
11.1 Electrical latching n operations 1 000 000 1 000 000 1 000 000
11.2 Mechanical latching n operations 250 000 250 000 250 000
12 Electrical life - Electrical latching
(operating cycles)
12.1 AC3 category n operations 100 000
12.2 at rated current (AC1 category) n operations 1 000 000
13 Apparatus wear classification C C C
14 Breaking capacity under short circuit (O-3min-
CO-3min-CO)
14.1 V7 A 6 000 4 000
14.2 V12 A 4 000 4 000
15 Making capacity under short circuit (O-3min-CO-
3min-CO)
15.1 V7 A 15 000 15 000
15.2 V12 A 8000 8000
16 Limit above which the fuse blows A 5 000
17 Opening time, from trip initiation to contact msec 1525
separation (V7-V12): with or without current
Electrical Latching or Mechanical Latching msec 1525
18 Maximum time interval between opening msec 1
of first and last phase
19 Making time, from supply of closing coil to msec 4080
contact touch (V7-V12) : with or without current
1.3.1 General
Item Description
1 Number of bottles 3 (1 if single pole version is required)
2 Type of power device
2.1 for closing Electromagnetic
2.2 for opening Electrical Latching Spring
Mechanical latching Spring - release operation by an opening coil
(Emergency operation available)
3 Number of opening trip device per phase
3.1 Single pole mechanism 1 spring
3.2 Three pole mechanism 1 spring
4 Weights of contactors (V7 - V12)
4.1 Fixed version with/without fuse holder kg 40/25
4.2 Withdrawable for CBE enclosure kg 55
4.3 Withdrawable for ZS1 switchgear kg 55
4.4 Withdrawable for UniSafe switchgear and kg 55
PowerBox module
4.5 Withdrawable for Unigear type ZS1 kg 55
switchgear
4.6 Withdrawable for UniMotor enclosure kg 45
5 Stroke of moving contacts mm 5 (V7) ; 6 (V12)
6 Type of arcing contacts (and material) Butt-Butt contact (AgWC)
7 Type of arc control device Control of field inside the vacuum interrupter
8 Coupling possibility with fuses
8.1 V7 6A 250A (with fuse 315A)
8.2 V12 6A 160A (with fuse 200A)
9 Overall dimension
9.1 Fixed version without fuse holder mm 398(H)x365(W)x350(D)
9.2 Withdrawable version for CBE/Univer C - mm 636(H)x532(W)x600(D)
ZS1 - Unisafe - PowerBox - Unigear type
ZS1
9.3 Withdrawable version for UniMotor mm 508(H)x383(W)x768(D)
Item Description
Continuous
Supply voltage of closing electromagnet:
service
current
inrush (min-max)/continuous service
Peak start-up
V A ms A ms A
10.1 Feeder type 1 : 24 - 60 Vdc 24 Vdc 100 1 13 170 0,5
Feeder type 1 : 24 - 60 Vdc 30 Vdc 100 1 13 170 0,5
Feeder type 1 : 24 - 60 Vdc 48 Vdc 110 1 13 170 0,5
Feeder type 1 : 24 - 60 Vdc 60 Vdc 190 1 13 170 0,5
10.2 Feeder type 2 : 100 - 250 Vac/dc 110 Vdc 8,5 1 6,5 170 0,4
Feeder type 2 : 100 - 250 Vac/dc 125 Vdc 8,5 1 6,5 170 0,4
Feeder type 2 : 100 - 250 Vac/dc 220 Vdc 21 1 3,5 170 0,4
Feeder type 2 : 100 - 250 Vac/dc 250 Vdc 21 1 3,5 170 0,4
Feeder type 2 : 100 - 250 Vac/dc 110 Vac 21 1 9,5 170 0,5
Feeder type 2 : 100 - 250 Vac/dc 125 Vac 21 1 9,5 170 0,5
Feeder type 2 : 100 - 250 Vac/dc 220 Vac 37 1 5,5 170 0,5
Feeder type 2 : 100 - 250 Vac/dc 250 Vac 37 1 5,5 170 0,5
Voltage
Feeder type 1 : 24 - 60 Vdc
Peak start-up
V A ms A ms
24 Vdc 100 1 13 170
30 Vdc 100 1 13 170
48 Vdc 110 1 13 170
60 Vdc 190 1 13 170
11.1.2 Shunt-trip release A up to 7A up to 70ms
11.1.3 Surge arrester Yes/No Yes (75V 10J)
11.2 100 - 250 V
11.2.1 Closing electromagnet
Inrush
Voltage
Feeder type 2 : 100 - 250 Vac/dc
Peak start-up
V A ms A ms
110 Vdc 8,5 1 6,5 170
125 Vdc 8,5 1 6,5 170
220 Vdc 21 1 3,5 170
250 Vdc 21 1 3,5 170
110 Vac 21 1 9,5 170
125 Vac 21 1 9,5 170
220 Vac 37 1 5,5 170
250 Vac 37 1 5,5 170
11.2.2 Shunt-trip release A up to 7A up to 70ms
11.2.3 Surge arrester Yes/No Yes (300V 10J)
12 Auxiliary contacts characteristics CLASS 1 (IEC 60694 Par.5.4.4.5.4)
12.1 Self-cleaning Yes
12.2 Rated voltage V 600 AC (50-60Hz) / DC
12.3 Insulating level 50Hz/1min V 2 000
13 Breaking capacity of auxiliary contacts
13.1 At 220V (AC 50/60 Hz) ; cos=0.7 A 3
13.2 At 600V (AC 50/60 Hz) ; cos=0.7 A 1,2
13.3 At 220V (DC) ; L/R=20ms A 2 ohmic load
0,6 inductive load
13.4 Rated current A 10
14 Fuse position contacts
14.1 At 110V (AC 50/60 Hz) ; cos= 0.3 A 80
14.2 At 220V (AC 50/60 Hz) ; cos= 0.3 A 80
14.3 At 220V (DC) ; L/R=5ms A 5
14.4 Rated current A 16
15 Supply voltage of the auxiliary circuit for
mechanical latch contactors
15.1 DC V 24-30-48-60-110-130-220-230-250
15.2 AC 50/60 Hz V 110-120-220-240
16 Voltage working limits
16.1 Drop out voltage: the releasing voltage YES, according IEC 60470
must be included between (10%-75%)Vn
16.2 V-Contact has to be closed with an YES, according IEC 60470
auxiliary voltage between (85%-110%)Vn
17 Number of free Auxiliary contact
(standard, for customer utilization)
17.1 Normally open n 6 (fixed and Withdrawable)
17.2 Normally closed n 6 (fixed and Withdrawable)
18 Cross section of wires for connection of
control circuit
18.1 Supply voltage of 24-60V mm2 2.5
This Data-Sheet refers to the basic version: for particular applications, requirements,
performances ask to ABB PT S.p.A. Unit Operativa Sace T.M.S.