OverCurrentandEarthFaultProtectionofTransformer
BackupprotectionofelectricaltransformerissimpleOverCurrentandEarthFaultprotectionappliedagainstexternalshortcircuit
andexcessiveoverloads.TheseovercurrentandearthFaultrelaysmaybeofInverseDefiniteMinimumTime(IDMT)orDefiniteTimetype
relays.GenerallyIDMTrelaysareconnectedtotheinfeedsideofthetransformer.
Theovercurrentrelayscannotdistinguishbetweenexternalshortcircuit,overloadandinternalfaultsofthetransformer.Foranyoftheabove
fault,backupprotectioni.e.overcurrentandearthfaultprotectionconnectedtoinfeedsideofthetransformerwilloperate.
Backupprotectionisalthoughgenerallyinstalledatinfeedsideofthetransformer,butitshouldtripboththeprimaryandsecondarycircuit
breakersofthetransformer.
OverCurrentandEarthFaultprotectionrelaysmaybealsoprovidedinloadsideofthetransformertoo,butitshouldnotintertriptheprimary
sidecircuitbreakerlikethecaseofbackupprotectionatinfeedside.Theoperationisgovernedprimarilybycurrentandtimesettingsandthe
characteristiccurveoftherelay.Topermituseofoverloadcapacityofthetransformerandcoordinationwithothersimilarrelaysatabout
125to150%offullloadcurrentofthetransformerbutbelowtheminimumshortcircuitcurrent.
Backupprotectionoftransformer has four elements, three over current relays connected each in each phase and one earth fault relay
connectedtothecommonpointofthreeovercurrentrelaysasshowninthefigure.ThenormalrangeofcurrentsettingsavailableonIDMT
overcurrentrelaysis50%to200%andonearthfaultrelay20to80%.
Anotherrangeofsettingonearthfaultrelayisalsoavailableandmaybeselectedwheretheearthfaultcurrentisrestrictedduetoinsertionof
impedanceintheneutralgrounding.Inthecaseoftransformerwindingwithneutralearthed,unrestrictedearthfaultprotectionisobtainedby
connectinganordinaryearthfaultrelayacrossaneutralcurrenttransformer.
Theunrestrictedovercurrentandearthfaultrelaysshouldhavepropertimelagtocoordinatewiththeprotectiverelaysofothercircuitto
avoidindiscriminatetripping.
http://www.electrical4u.com/backupprotectionoftransformerovercurrentandearthfault/ 1/3
2/21/2017 BackupProtectionofTransformer|OverCurrentandEarthFault|Electrical4u
Like 2 1
Previous Next
CloselyRelatedArticles
ProtectionSysteminPowerSystem
TripCircuitSupervision
DifferentialProtectionofGeneratororAlternator
AnnunciationSystemAlarmAnnunciator
RotorEarthFaultProtectionofAlternatororGenerator
LossofFieldorExcitationProtectionofAlternatororGenerator
OvervoltageProtection
MotorProtectionCircuitBreakerorMPCB
StatorEarthFaultProtectionofAlternator
InterTurnFaultProtectionofStatorWindingofGenerator
SmallandLargeMotorProtectionScheme
MotorThermalOverloadProtection
ElectricalFaultCalculation|PositiveNegativeZeroSequenceImpedance
ExternalandInternalFaultsinTransformer
TransformerProtectionandTransformerFault
GeneratorProtection
ProtectionofLinesorFeeder
BusbarProtection|BusbarDifferentialProtectionScheme
ProtectionofCapacitorBank
MoreRelatedArticles
TypesofElectricalProtectionRelaysorProtectiveRelays
MotorProtectionRelayforHighVoltageInductionMotor
FeederProtectionRelays
PickUpCurrent|CurrentSetting|PlugSettingMultiplierandTimeSettingMultiplierofRelay
ElectromagneticRelayWorking|TypesofElectromagneticRelays
InductionCupRelayWorkingPrincipleConstructionandTypes
OverCurrentRelayWorkingPrincipleTypes
DifferentialRelay
ThermalRelayWorkingPrincipleConstructionofThermalOverloadRelay
DistanceRelayorImpedanceRelayWorkingPrincipleTypes
http://www.electrical4u.com/backupprotectionoftransformerovercurrentandearthfault/ 2/3
2/21/2017 BackupProtectionofTransformer|OverCurrentandEarthFault|Electrical4u
InstantaneousRelay
InverseTimeRelay|DefiniteTimeLagRelay
BackupRelay
NewArticles
SeriesResistance
StepDownTransformers
StepUpTransformer
SiliconSemiconductor
VoltageDropCalculation
InsulatedGateBipolarTransistor|IGBT
20112017electrical4u.Thecontentiscopyrightedtoelectrical4uandmaynotbereproducedonotherwebsites.
http://www.electrical4u.com/backupprotectionoftransformerovercurrentandearthfault/ 3/3