Dielectric Withstand: Design Rules
Dielectric Withstand: Design Rules
Partial discharge
The measurement of partial discharges (IEC 62271-200) is a suitable
means of detecting certain weaknesses.
However, it is not possible to establish a reliable relationship between
the results of partial discharge measurement and the life expectancy.
Therefore, it is not possible to give acceptance criteria for partial
discharge tests carried out on a complete product.
AMTED300014EN.indd 41
Design rules Dielectric withstand
42 AMTED300014EN.indd
Design rules Dielectric withstand
The values for distances in air given in the table above are minimum
values determined by considering dielectric properties, they do not
include any increase which could be required to take into account the
design tolerances, short circuit effects, wind effects, operator safety, etc.
*These indications are relative to a distance through a single air gap, without taking into account
the breakdown voltage by tracking across the surfaces, related to pollution problems.
and metallic earthed structures. The choice of an insulator shall take into
account the level of pollution.
These levels of pollution are described in Technical Specification IEC TS
60815-1 clause 8. Selection and dimensionning of high-voltage insulators
intended for use in polluted conditions - Part 1 - definitions, information
Lf : tracking path and general principles.
AMTED300014EN.indd 43