Rubber Mounts
Free-Standing Spring
Restrained Spring
Housed Spring
Vibration Mounting Bases
November
2009
Mounting Bases
and Vibration Isolation
This catalog outlines the types of bases and isolators Included in this catalog are easy to use selection
as offered by Greenheck for use with both utility guides and typical specifications. For more complete
and centrifugal fans. The use of isolation equipment selection criteria, refer to the latest ASHRAE
is more important than ever when considering the Handbook, HVAC Applications - Sound and Vibration
trends towards lighter construction of modern Control.
buildings and the increasing use of mechanical
equipment. In addition, the fact that building owners
and occupants are more sensitive to vibration related
problems makes proper selection and installation of Table of Contents
isolation equipment extremely important. Benefits of Greenheck Supplied Bases ................... 3
Mounting Options ..................................................... 4
The advantages of buying fan and isolation Isolator Options ........................................................ 5
equipment directly from Greenheck include proper Mounting Selection Guide ....................................... 6
selection and identification of isolators, assembled Isolator Selection Guide .......................................... 7
fan and base packages, final vibration test and trim Specification Checklist ............................................. 8
balancing of the fan on the isolation base.
Shown below are typical examples of different isolation equipment used with centrifugal fans.
Smaller centrifugal
Utility fans are typically fans can be directly
mounted on mounting mounted on isolators.
rails incorporating either Fan shown is a
neoprene or spring Model 18-BISW Arr. 10
mounts.
Fan shown is
Model SWB-30
2
Benefits of Greenheck
Supplied Bases
Most fans with bases can ship completely assembled and tested
Most Greenheck fans that are ordered with motors,
Typical Vibration Signature
drives, guards and bases can be assembled tested
and shipped as a complete package.
For limitations on sizes that can be shipped
assembled see information below.
Copies of these
Benefits: signatures are
Installation time and costs are reduced. kept on file and
are available
Motors and drives are installed and aligned for
upon request
smooth operation.
Guards and accessories are installed.
Vibration testing of the entire fan package
(excluding utility fans) is performed.
Belt drive fans are tested for maximum allowable
vibration of 0.15 in/sec-peak (filter in). Vibration
readings are taken at each bearing in the
horizontal, vertical and axial direction. These
vibration signatures become part of the fans
permanent records and are available on request.
3
Mounting Options
The mounting options shown on this page (type A, B and C) relate to the Selection Guide for Vibration Isolation
as published in the latest ASHRAE applications handbook, HVAC Applications-Sound and Vibration Control.
See page 6 for mounting selection based on fan arrangements and Greenheck fan types by model number.
Rubber Mount
Structural Bases - Type B2
Structural steel bases consist of structural steel
members welded into a rigid one piece base. Motor
slide rails are included where applicable. Bases are
required for all Arr. 1 and 3 fans with independently
mounted motors. Structural steel bases are
available without isolators, with rubber mounts or
with spring mounts. All structural steel bases with
Without spring mounts incorporate height saving brackets.
Isolators Spring Mount with
Height Saving Bracket
4
Isolator Options
Shown below are the various types of isolators available from Greenheck. The appearance will vary based on
application and isolator manufacturer. Consult factory for seismic application isolation. See page6 for isolator
selection guidelines.
5
Mounting
In addition to structural bases and isolators, your application may require thrust restraints as shown below.
Mounting Selection*
Arr. Fan Type Direct Mount Mounting Rails1 Structural Base2 Inertia Base3
Type A Type B1 Type B2 Type C
AF/BISW
1 NO NO YES YES
IPA
AF/BISW
AF/BIDW NO NO YES YES
3 QEP
QEP-HMOS/HMOT 12-73 CF NO YES YES
QEP-VMOS 12-54 CF NO CF NO
SFD YES YES CF CF
4 QEP YES NO CF CF
IPA CF NO CF CF
8 IPA CF NO CF CF
AF/BISW 7-36
CF NO YES YES
IPA 5-19
9
AF/BISW 40-73
CF NO YES YES
IPA 21-41
SFB/SWB YES YES CF CF
AF/BISW 7-36 YES NO YES YES
10
AF/BISW 40-73 CF NO YES YES
4
IPA 5-19 YES NO YES YES
*Consult factory on any fan isolation if an inlet box is required.
Notes: 1
. Type B1 - Not available on DB, BAD or TAD discharges
2. Type B2 - Consult factory on DB, BAD and TAD discharges
3. Type C - Not available on DB, BAD or TAD discharges
4. Type A Direct Mount is not available if an inlet box is required
6
Isolator Selection Guide
The most important part of selecting the proper isolator is determining the deflection required. The following
examples will help guide you to selecting the proper isolator. Chart 1
Example 1:
If deflection is already specified, use that number Deflection Applications Isolator Type
for isolator selection process. Select isolator type Indoor/Outdoor Single Deflection
up to 1/4 in.
based on required deflection and application as Wheel Sizes 36 in. or Rubber Mount
shown in Chart 1. less where 0.3 in. or less Double Deflection
up to 1/2 in. deflection is required Rubber Mount
NOTE:
1 in., 2 in., Free Standing
Indoor
Deflections of 1-, 2-, 3- and 4-inch will be assumed 3 in.^, or 4 in.^ Spring Mounts
as nominal. Indoor/Outdoor
1 in., 2 in., Restrained Spring
It is critical that deflection or efficiencies specified Fans subject to wind
3 in., or 4 in. Mounts
as minimum be stated as minimum on quotes and loading or torquing forces
orders.
Indoor Housed Spring
W
hen selecting an isolator, nominal deflection must up to 1 in.*
Non-critical applications Mounts
be greater than minimum deflection.
*Consult factory above 1 in.
^Consult factory above 2 in.
Example 2: 6.0
Chart 2
If isolator efficiency is specified, calculate the 90 95 98 99 ISOLATION EFF. %
4.0
deflection required based on the fan RPM or motor 80
RPM whichever is lower. The criteria shown in the 3.0
EX
70
sample below is illustrated in Chart 2 for approximate
TR
EM
deflection. To calculate the deflection accurately use 2.0
STATIC DEFLECTION (INCHES)
EL
CR
the following equation:
YC
1.5
ITI
RIT
NO IMUM
CA
MI
ICA
RM
L
N
2 1.0
L
Deflection = 188 100/(100-E)+1
AL
0.8
RPM
0.6
0.5
e.g. 95% Efficiency, 700 Fan RPM, 1800 motor RPM
0.4
RE
SO
700
E
0.2
In this example select 2 inch deflection isolator
400
500
600
800
1000
1500
2000
3000
4000
Example 3:
If no deflection or isolator efficiency is specified, then use Application Efficiency* Chart 3
the efficiencies shown in Chart 3 and calculate Deflection as Minimum 70-80%
shown in Example 2.
Normal 80-90%
*NOTE: Assumes that the fan is installed on an extremely Critical 90-95%
stiff foundation Extremely Critical 95-99%
For further information on calculating deflection required, see ASHRAE Selection Guide for Vibration Isolation.
This is especially important for critical and above grade applications.
7
Specification Checklist
To ensure proper isolation selection and application, the specifications must include
the following information:
Fan Size Mounting Rails
Model qRails with Rubber Mounts
qUtility: qSFB qSFD qSWB qRails with Spring Mounts (Indoor)
qSeries 21: qAFSW qBISW qRails with Spring Mounts (Outdoor)
qAFDW qBIDW Structural Steel Base
qSeries 41: qAFSW qBISW qStructural Base (no isolators)
qAFDW qBIDW qStructural Base with Rubber Mounts
qIndustrial: qIPA qIPO qIPW Deflection: q1/4 in. q1/2 in.
qPlenum: qHorizontal: Standard qStructural Base with Spring Mounts
qHorizontal: Motor on Top Deflection:
qHorizontal: Motor on Side Nominal: q1 in. q2 in. q3 in. q4 in.
qVertical (upblast) Minimum:
Arrangement Isolator Type:
q1 q3 q4 q8 q9 q10 qFree Standing
qHoused
Rotation
qRestrained
qCW qCCW
Concrete Inertia Base
Discharge
qInertia Base with Spring Mounts
qTH qBH qUB qTAU
Deflection:
qBAU qDB qTAD qBAD
Nominal: q1 in. q2 in. q3 in. q4 in.
Class/Duty qMinimum:
Series 21/41, Plenum: qI qII qIII qIV Isolator Type:
Industrial: qStd. qHvy. qFree Standing
Motor Position qHoused
Arrangement 9: qLeft qRight qRestrained
Arrangements 1 & 3: qW qX qY qZ Base Thickness:
qStandard Depth
Fan RPM: ______________________
qMin. Depth
Motor q6 in. q8 in. q10 in. q12 in.
Horsepower: ____________________
Coating (on Base)
RPM: ___________________________
qStandard Coating
Frame Size: _____________________
qSpecial Coating Required
Space Limits/Comments: _________________ Specify Coating:___________________________
__________________________________________ __________________________________________
__________________________________________ __________________________________________
Our Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period
of one year from the shipment date. Any units or parts which prove defective during the warranty
period will be replaced at our option when returned to our factory, transportation prepaid. Motors are
warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck
prove defective during this period, they should be returned to the nearest authorized motor service
station. Greenheck will not be responsible for any removal or installation costs.
Prepared to Support
As a result of our commitment to continuous improvement, Greenheck reserves the right to change Green Building Efforts
specifications without notice.