HYDRONIC
TERMINALS
This document can be subjected to variations. Descriptions, performance data, images and diagrams are indicative only.
For further information contact Climaveneta Comunications/Marketing Department or visit www.climaveneta.com
Fan Coil Range
HYDRONIC
TERMINALS
i-LIFE2
2021002 / 2041004
VERSION
FEATURES
ACCESSORY
COMMANDS
Hot water coil kit
EK PLUG-IN CONTROL /EKW WALL MOUNTED connected to i-HB Power Board that must be mounted
CONTROL on board of the unit. Kit RS485 - interface for Building Management System
User interface for selection of functioning mode Kit control board to manage 0-10V or 3 points
(OFF/summer/winter/AUTO), fan speed IK CONTROL WITH LCD SCREEN modulating valve unit
(Max/Med/Min/AUTO), temperature set. Control of main Interface with LCD screen with user-friendly icons.
Main coil 2-way/3-way valve unit
and additional coil valve unit (summer/winter - 2 and 4 Control kit for universal installation: wall-mounted as well
as plug-in. Selection of functioning mode Additional coil 2-way/3-way valve unit
pipes installation). Management of traditional ON/OFF valve
unit or modulating valve unit 0-10V or 3 points. Air and (OFF/summer/winter/AUTO), fan speed Kit LIFE2 BOX
water temperature probe. Multifunction digital input (Max/Med/Min/AUTO), temperature set. Control iK could Kit Gateway interface for MyHome Bticino System
configurable by user. Configuration dip switch. Modbus function manually or with weekly timer regulation
configurable by the customer. Control of main coil valve Air intake grille kit with version cover
protocol for installation in BMS (e.g. Idrorelax system by
Climaveneta). Installation and management of Master-Slave unit (summer/winter - 2 pipes) and additional coil (winter Straight and angular (90) plenum kits for air outlet
system up to 8 LIFE fan coil units. Easy control installation - 4 pipes). Management of traditional ON/OFF valve unit Plenum kit with round, straight or 90 air ducts.
thanks to 2 wires connection. or modulating valve unit 0-10V or 3 points (supply 230
Straight and angular (90) plenum kits for air inlet
VAC or 24V). Parameters configurable directly by user.
INFRARED REMOTE CONTROL Modbus protocol for installation in Building Management Heating element kit
Set-point regulation. Easy selection of the functioning mode System (e.g. Idrorelax system by Climaveneta). Horizontal and vertical fan coil auxiliary tray
(cooling, heating, dehumidification, ventilation), and the fan Installation and management of Master-Slave system up
speed (Max, Med, Min, AUTO). User-sfriendly compact to 8 LIFE fan coil units. Easy control installation thanks to
remote control with fine aethetics. The receiver must be 2 wires connection through HB power board.
5
2P 4P
2 PIPES 4 PIPES CONTROLLER
B
6
HYDRONIC TERMINALS
i-LIFE2
2021002
2P 4P
2 PIPES 4 PIPES CONTROLLER
i-LIFE2
2041004
2P 4P
2 PIPES 4 PIPES CONTROLLER
i-LIFE2
2041004
2P 4P
2 PIPES 4 PIPES CONTROLLER
12
HYDRONIC TERMINALS
a-LIFE2
1021002 / 1041004
VERSION
FEATURES
WITH CABINET OR BUILT-IN VERSION Left-hand water connections, easy convertible into
right-hand, by simply turning the coil
1,50-7,50 kW 6-speed autotransformer;
Air filter on all models.
The new a-LIFE2 fancoil has been specifically developed to be adapted to every ambient
thanks to its modern and minimal design which is result of the full experience and Automatically closing flap to cover and protect
electric controls from dripping water (in conformity
Climavenetas know-how on this range of products. Centrifugal fan with 6 speed via with directive 60335-2-40).
auto-transformer. Thanks to the different versions, with cabinet or buit in, low air intake Auxiliary drain pan with thermal insulation for all
or front air intake, vertical or horizontal installation, it results very easy to find the perfect Horizontal versions, made of galvanized steel.
solution any time. Plastic drain pan for all Vertical versions.
COMMANDS
PS PLUG-IN/PSW WALL MOUNTED input configurable by user. Configuration dip switch. Modbus
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF protocol for installation in BMS (e.g. Idrorelax system by
valve unit control (summer/winter for 2 pipes installation), Climaveneta). Installation and management of Master-Slave
ON/OFF second valve unit control (winter for 4 pipes system up to 8 LIFE fan coil units. Easy control installation
installation). Remote water temperature probe. thanks to 2 wires connection.
ACCESSORY
MT PLUG-IN/MTW WALL MOUNTED IK CONTROL WITH LCD SCREEN
Fan speed slider, mode slider (OFF/summer/winter). Thermostat Interface with LCD screen with user-friendly icons. Control kit Hot water coil kit
with set point regulation. ON/OFF valve unit control for universal installation: wall-mounted as well as plug-in. Kit Bus Adapter for BMS
(summer/winter for 2 pipes installation), ON/OFF second valve Selection of functioning mode (OFF/summer/winter/AUTO),
unit control (winter for 4 pipes installation). Room temperature fan speed (Max/Med/Min/AUTO), temperature set. Kit RS485 - interface for Building Management System
probe. Remote water temperature probe. Control iK could function manually or with weekly timer Kit Gateway interface for MyHome Bticino System
AT PLUG-IN/ATW WALL MOUNTED regulation configurable by the customer. Control of main coil
Interface SPB Kit
Mode button (OFF/summer/winter/AUTO), fan speed button valve unit (summer/winter - 2 pipes) and additional coil
(Max/Med/Min/AUTO). Thermostat with set point regulation. (winter - 4 pipes). Management of traditional ON/OFF valve Kit control board to manage 0-10V or 3 points
ON/OFF valve unit control (summer/winter for 2 and 4 pipes unit or modulating valve unit 0-10V or 3 points (supply 230 modulating valve unit
installation). Control of traditional or PWM modulating valve VAC or 24V). Parameters configurable directly by user. Main and additional coil valve unit ON/OFF, PWM,
units. Room temperature probe and water temperature probe. Modbus protocol for installation in Building Management 0-10V, 3 points 2-way or 3-way
Digital input configurable as: window contact, economy, heating System (e.g. Idrorelax system by Climaveneta).
or cooling remote changeover, periodic ventilation. Installation and management of Master-Slave system up to 8 Kit LIFE2 BOX
Configuration dip switch. TTL serial port with Modbus protocol LIFE fan coil units. Easy control installation thanks to 2 wires Plenum kit with round, straight or 90 air ducts.
for installation in BMS. connection through HB power board
Air intake grille kit with version cover
EK PLUG-IN CONTROL /EKW WALL MOUNTED CONTROL INFRARED REMOTE CONTROL Horizontal and vertical fan coil auxiliary tray
User interface for selection of functioning mode Set-point regulation. Easy selection of the functioning mode
(OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), (cooling, heating, dehumidification, ventilation), and the fan Electric heaters
temperature set. Control of main and additional coil valve unit speed (Max, Med, Min, AUTO). User-sfriendly compact
(summer/winter - 2 and 4 pipes installation). Management of remote control with fine aethetics. The receiver must be
traditional ON/OFF valve unit or modulating valve unit 0-10V or connected to i-HB Power Board that must be mounted on
3 points . Air and water temperature probe. Multifunction digital board of the unit.
13
2P 4P
2 PIPES 4 PIPES CONTROLLER
B
14
HYDRONIC TERMINALS
a-LIFE2
1021002
2P 4P
2 PIPES 4 PIPES CONTROLLER
a-LIFE2
1041004
2P 4P
2 PIPES 4 PIPES CONTROLLER
a-LIFE2
1041004
2P 4P
2 PIPES 4 PIPES CONTROLLER
LIFE2 BOX
LIFE2 BOX is a wall-mounted accessory that allows users to prepare the fan coil water and LIFE2 BOX 102/104-202/204
electrical connections in advance. The fan coil is fitted inside the structure when the work LIFE2 BOX 302-304/402-404
has been completed, thus simplifying the operations to be performed on site. LIFE2 BOX 502-504/602-604
The kit consists of a galvanised sheet metal structure, front closing panel and frame with
manually adjustable flap. The kit is available in version painted RAL 9003 and also
NEUTRAL version (raw metal sheet).
LIFE2 BOX can house i-LIFE2 fan- coils, DLIV/DLIO version: low air inlet, vertical outlet.
It is available for sizes 100/200, 300/400, 500/600.
20
HYDRONIC TERMINALS
a-LIFE2 HP
3021204
VERSION
FEATURES
B
COMMANDS
2P 4P
2 PIPES 4 PIPES DUCT CONTROLLER
a-LIFE2 HP / DFIO - DLIO 0302 0402 0502 0602 0702 0802 0902 1002 1102 1202
ELECTRICAL DATA
Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Max absorbed power W 127 127 115 115 196 196 225 225 285 285
2 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow m3/h 561 623 705 783 1004 1116 1390 1544 1740 1933
Total capacity in cooling mode (1) kW 2,88 3,28 3,74 4,14 4,62 5,20 6,20 7,20 8,05 8,60
Sensible capacity in cooling mode (1) kW 2,39 2,77 3,15 3,53 3,91 4,44 5,14 5,91 6,99 7,32
Max water flow (1) m3/h 0,496 0,565 0,644 0,713 0,795 0,895 1,067 1,240 1,386 1,481
Mad pressure drop (1) kPa 31,5 31,9 12,2 15,2 19,5 22,4 33,5 43,1 14,2 15,9
Total capacity in heating mode (2) kW 3,83 4,35 4,96 5,49 6,13 6,91 8,22 9,55 10,7 11,4
Water flow in heating (2) m3/h 0,496 0,563 0,642 0,711 0,794 0,895 1,065 1,237 1,383 1,478
Pressure drop in heating (2) kPa 26,7 31,9 10,4 12,9 16,8 19,6 29,4 37,9 14,1 15,8
Noise Pressure (3) dB(A) 52 56 47 51 52 55 54 59 57 59
Noise Power (4) dB(A) 61 65 56 60 61 64 63 68 66 68
MED SPEED
Air flow m3/h 500 555 525 583 767 852 1078 1198 1547 1719
Total capacity in cooling mode (1) kW 2,31 2,70 3,04 3,23 3,57 4,49 5,70 6,25 7,50 8,10
Sensible capacity in cooling mode (1) kW 1,90 2,24 2,48 2,66 2,84 3,74 4,67 5,15 6,46 7,03
Max water flow (1) m3/h 0,398 0,465 0,523 0,556 0,615 0,773 0,981 1,076 1,291 1,394
Mad pressure drop (1) kPa 20,2 21,6 8,0 9,2 11,6 16,7 28,3 32,5 12,3 14,0
Total capacity in heating mode (2) kW 3,07 3,58 4,03 4,28 4,74 5,96 7,57 8,29 9,95 10,8
Water flow in heating (2) m3/h 0,398 0,464 0,522 0,555 0,614 0,772 0,980 1,074 1,289 1,393
Pressure drop in heating (2) kPa 17,5 22,1 7,0 8,0 10,3 14,9 25,2 29,2 12,2 14,0
Noise Pressure (3) dB(A) 45 52 41 44 41 49 51 54 55 57
Noise Power (4) dB(A) 54 61 50 53 50 58 60 63 64 66
MIN SPEED
Air flow m3/h 392 435 464 516 584 649 923 1026 1381 1534
Total capacity in cooling mode (1) kW 2,08 2,21 2,28 2,92 3,22 3,50 4,83 5,40 6,90 7,40
Sensible capacity in cooling mode (1) kW 1,69 1,82 1,84 2,37 2,49 2,78 3,88 4,42 5,83 6,25
Max water flow (1) m3/h 0,358 0,380 0,393 0,503 0,554 0,603 0,832 0,930 1,188 1,274
Mad pressure drop (1) kPa 16,3 14,5 4,5 7,5 9,4 10,1 20,4 24,3 10,4 11,7
Total capacity in heating mode (2) kW 2,76 2,94 3,02 3,88 4,27 4,65 6,41 7,16 9,15 9,82
Water flow in heating (2) m3/h 0,358 0,380 0,391 0,502 0,553 0,602 0,831 0,927 1,186 1,272
Pressure drop in heating (2) kPa 14,3 15,1 4,0 6,6 8,5 9,3 18,6 22,3 10,3 11,7
Noise Pressure (3) dB(A) 42 45 34 41 38 41 47 51 54 54
Noise Power (4) dB(A) 51 54 43 50 47 50 56 60 63 63
SIZE AND WEIGHT
A (5) mm 745 745 945 945 1145 1145 1345 1345 1545 1545
B (5) mm 215 215 215 215 215 215 215 215 215 215
H (5) mm 450 450 450 450 450 450 450 450 450 450
Operating weight (5) kg 14 15 20 21 24 25 28 29 31 34
Notes:
1 Room temperature 27C d.b./19C w.b.; Chilled water (in/out) 7/12C
2 Room temperature 20C d.b.; Hot water (in/out) 50/* C (with identical flow note1)
3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground
4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
22
HYDRONIC TERMINALS
a-LIFE2 HP
3021204
2P 4P
2 PIPES 4 PIPES DUCT CONTROLLER
i-LIFE Slim
102502
VERSION
FEATURES
i-LIFE SLIM is the new fan coil Climaveneta, with inverter technology for heating, cooling and
dehumidifying. Its elegant design with only 13 cm depth makes i-LIFE Slim the perfect solution for
residential applications. The fan coil is also available with i-LIFE R-SLIM inverter version with radiant
panel. The brushless motor allows a perfect adaptation to thermal load, without any temperature
fluctuations. Tangential fans operate through continuous air flow modulation, with no speed steps or
relay switching as traditional fan coil units. High efficiency is guaranteed in any HVAC installation
setup, in combination with any low temperature heat generator.
COMMANDS
A
IKS iHBS controller has a touch button and a LED for the
ON BOARD CONTROLLER visualization of the devices operation. All the parameters B
On-board control for unit with cabinet complete with touch are set up from iKSW.
keypad with 8 touch key, LCD display with white light ACCESSORY
ATS
symbols. Modulating fan speed with PID logic, temperature
CONTROLLER WITH 4 SPEED REGULATION
regulation, winter/summer mode, automatic mode for the
Controller for units with cabinet. Interface with 4 keys for Drain Pan for horizontal installation
speed regulation, night mode for a silent operation.
the temperature selection, winter/summer mode, 4 speed Main coil 2-way/3-way valve unit
Minimum water probe and solenoid management.
regulation, display for room temperature vizualization.
REMOTE CONTROL IKSW Minimum water temperature probe and solenoid valve Fitting for air intake in built-in installation
Remote controller for built-in and with cabinet units management. Telescopic air flow duct and 90 duct for false
complete with touch keypad with 8 touch keys, LCD ceiling and build in installation
HBS CONTROL
display with white light symbols. Alluminium air flow vent for wall mounting
POWERBOARD CARD
Modulating fan speed with PID logic, temperature
Simple on board controler for built-in units or with cabinet Alluminium Air intake grid
regulation, winter/summer mode, automatic mode for the
units, to be coupled with ATW Climaveneta remote control
speed regulation, night mode for a silent operation. UVC air sterilisation device
or other remote controlers which manage the regulation of
Minimum water probe and solenoid valve management.
the fixed fan speeds. HBS has a touch button and a LED Casing for build in version - i-LIFE Slim Box
A maximum of 31 fancoils can be connected to the iKSW
for the visualization of the device's operation. All the Casing cover panel with frame and front panel grid
controller for open space rooms.
parameters are set up from the remote controler.
IHBS Eurokonus adapter
ON BOARD SEMPLIFIED CONTROL Pair of decorative and structural feet
Simple on board controller for buit - in and with cabinet
units, to be coupled with remote controller iKSW.
25
2P 4P
2 PIPES 4 PIPES CONTROLLER
TECHNICAL
NFT / U DATA i-LIFE Slim
26
HYDRONIC TERMINALS
i-LIFE Slim
102502
TECHNICAL
NFT / U DATA i-LIFE Slim
27
2P 4P
2 PIPES 4 PIPES CONTROLLER
TECHNICAL
NFT / U DATA i-LIFE Slim
28
HYDRONIC TERMINALS
MHD2
3060
VERSION
- Base Version
FEATURES
A B
COMMANDS ACCESSORY
2P
2 PIPES WALL CONTROLLER
TECHNICAL
NFT / U DATA MHD
MHD2 30 40 50 60
ELE CTRICAL DATA
Power suppl y V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50
Max absorbed power W 24 28 40 50
2 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow m/h 436 632 780 920
Total capacity in cooling mode (1) kW 2,15 2,67 4,00 4,63
Sensible capacit y in cooling mode (1) kW 1,82 2,13 3,02 3,91
Max water flow (1) m/h 0,37 0,46 0,69 0,80
Mad pressure drop (1) kPa 8,9 15,0 38,5 49,9
Total capacity in heating mode (2) kW 2,48 3,20 4,20 5,07
Water flow in heating (2) m/h 0,37 0,46 0,69 0,79
Pressure drop in heating (2) kPa 9,0 14,9 38,5 49,7
Noise Pressure (3) dB(A) 34 41 44 49
Noise Power (4) dB(A) 45 52 55 60
MED SPEED
Air flow m/h 376 522 691 810
Total capacity in cooling mode (1) kW 1,85 2,00 3,00 3,86
Sensible capacit y in cooling mode (1) kW 1,60 1,62 2,57 3,26
Max water flow (1) m/h 0,32 0,34 0,52 0,66
Mad pressure drop (1) kPa 7,6 10,3 25,7 37,9
Total capacity in heating mode (2) kW 2,18 2,40 3,64 4,25
Water flow in heating (2) m/h 0,32 0,34 0,52 0,67
Pressure drop in heating (2) kPa 7,7 10,2 26,0 38,1
Noise Pressure (3) dB(A) 31 31 41 45
Noise Power (4) dB(A) 42 42 52 56
MIN SPEED
Air flow m/h 334 403 570 697
Total capacity in cooling mode (1) kW 1,65 1,78 2,67 3,36
Sensible capacit y in cooling mode (1) kW 1,42 1,45 2,13 2,83
Max water flow (1) m/h 0,28 0,31 0,46 0,58
Mad pressure drop (1) kPa 6,8 8,8 21,9 30,7
Total capacity in heating mode (2) kW 1,91 2,13 3,21 3,67
Water flow in heating (2) m/h 0,28 0,30 0,46 0,58
Pressure drop in heating (2) kPa 6,8 8,7 21,8 31,1
Noise Pressure (3) dB(A) 27 28 37 42
Noise Power (4) dB(A) 38 39 48 53
SIZE AND WEI GHT
A (5) mm 845 845 920 920
B (5) mm 180 180 200 200
H (5) mm 270 270 298 298
Operating weight (5) kg 10 10 13 13
Notes:
1 Room temperature 27C d.b./19C w.b., Chilled water (in/out) 7/12C
2 Room temperature 20C d.b., hot water (in/out) 50/* C (identical flow rate note 1)
3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground
4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
30
HYDRONIC TERMINALS
HWD
6021104
VERSION
- base version
FEATURES
HWD are Climaveneta ducted hydronic terminal units. The fan units at Remote control to manage main unit functions to
provide a total enviroment comfort. Full Auto
available working pressures, through internal insulation, ensure excellent function;
acoustic comfort levels. The compactness and ease of installation make
Arrangement for electronic control of two on/off
HWD a suitable hydronic terminal unit for any type of setting. valve unit in the water circuit;
COMMANDS
2P 4P
2 PIPES 4 PIPES CONTROLLER
TECHNICAL
HWD DATA HWD
HWD 0602 0703 0803 0904 1003 1104
ELECTRICAL DATA
Power supply V/ph/Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
Max absorbed power W 370 370 440 440 900 900
2 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow 1300 1300 1600 1600 2200 2500
Total capacity in cooling mode (1) kW 4,80 6,20 8,00 9,70 11,5 15,1
Sensible capacity in cooling mode (1) kW 3,00 4,00 5,20 6,50 7,40 10,2
Max water flow (1) 0,826 1,066 1,376 1,668 1,978 2,597
Mad pressure drop (1) kPa 12,0 8,0 14,0 35,0 24,0 23,0
Total capacity in heating mode (2) kW 6,61 8,48 11,8 12,1 16,7 18,7
Water flow in heating (2) 0,826 1,066 1,376 1,668 1,978 2,597
Pressure drop in heating (2) kPa 9,0 7,0 14,0 22,8 21,0 20,0
Noise Pressure (3) dB(A)
Noise Power (4) dB(A) 68 68 72 72 78 80
MED SPEED
Air flow 1171 1171 1357 1357 1985 2243
Total capacity in cooling mode (1) kW 4,50 5,70 7,20 8,50 10,7 13,9
Sensible capacity in cooling mode (1) kW 2,80 3,70 4,60 5,90 6,90 9,70
Max water flow (1) 0,774 0,980 1,238 1,462 1,840 2,391
Mad pressure drop (1) kPa 11,0 7,0 11,0 27,0 22,0 21,0
Total capacity in heating mode (2) kW 6,19 7,88 9,34 10,6 13,7 16,8
Water flow in heating (2) 0,774 0,980 1,238 1,462 1,840 2,391
Pressure drop in heating (2) kPa 8,0 6,0 12,0 24,9 19,0 13,0
Noise Pressure (3) dB(A)
Noise Power (4) dB(A) 65 65 69 69 76 77
MIN SPEED
Air flow 1021 1021 1057 1057 1585 1771
Total capacity in cooling mode (1) kW 4,10 5,20 6,00 7,00 9,10 11,7
Sensible capacity in cooling mode (1) kW 2,60 3,40 3,90 4,80 6,00 8,00
Max water flow (1) 0,705 0,894 1,032 1,204 1,565 2,012
Mad pressure drop (1) kPa 9,0 6,0 9,0 21,6 17,0 15,0
Total capacity in heating mode (2) kW 5,65 7,80 7,75 9,00 13,5 14,5
Water flow in heating (2) 0,705 0,894 1,032 1,204 1,565 2,012
Pressure drop in heating (2) kPa 8,0 5,0 7,0 18,7 9,0 13,0
Noise Pressure (3) dB(A)
Noise Power (4) dB(A) 62 62 63 63 70 72
SIZE AND WEIGHT
A (5) mm 900 900 1050 1050 1250 1250
B (5) mm 695 695 695 695 750 750
H (5) mm 295 295 295 295 315 315
Operating weight (5) kg 41 43 50 52 63 63
Notes:
1 Room temperature 27C d.b./19C w.b.; Chilled water (in/out) 7/12C
2 Room temperature 20C d.b.; Hot water (in/out) 50/* C (with identical flow note1)
3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground
4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
32
HYDRONIC TERMINALS
HWD
6021104
TECHNICAL
HWD DATA HWD
HWD 602 703 803 904 1003 1104
ELECTRICAL DATA
Power supply V/ph/Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
Max absorbed power W 370 370 440 440 900 900
4 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow 1300 1300 1600 1600 2200 2500
Total capacity in cooling mode (1) kW 4,80 6,20 8,00 9,70 11,5 15,1
Sensible capacity in cooling mode (1) kW 3,00 4,00 5,20 6,50 7,40 10,2
Max water flow (1) 0,826 1,066 1,376 1,668 1,978 2,597
Mad pressure drop (1) kPa 12,0 8,0 14,0 35,5 24,0 23,0
Total capacity in heating mode (2) kW 9,10 9,10 11,8 11,8 16,7 18,0
Water flow in heating (2) 0,783 0,783 1,015 1,015 1,436 1,548
Pressure drop in heating (2) kPa 9,0 9,0 14,0 34,1 13,0 15,0
Noise Pressure (3) dB(A)
Noise Power (4) dB(A) 68 68 72 72 78 80
MED SPEED
Air flow 1171 1171 1357 1357 1985 2243
Total capacity in cooling mode (1) kW 4,50 5,70 7,20 8,50 10,7 13,9
Sensible capacity in cooling mode (1) kW 2,80 3,70 4,60 5,90 6,90 9,70
Max water flow (1) 0,774 0,980 1,238 1,462 1,840 2,391
Mad pressure drop (1) kPa 11,0 7,0 11,0 27,3 22,0 21,0
Total capacity in heating mode (2) kW 8,60 8,60 10,6 10,6 15,6 16,8
Water flow in heating (2) 0,740 0,740 0,912 0,912 1,342 1,445
Pressure drop in heating (2) kPa 8,0 8,0 12,0 29,2 11,0 13,0
Noise Pressure (3) dB(A)
Noise Power (4) dB(A) 65 65 69 69 76 77
MIN SPEED
Air flow 1021 1021 1057 1057 1585 1771
Total capacity in cooling mode (1) kW 4,10 5,20 6,00 7,00 9,10 11,7
Sensible capacity in cooling mode (1) kW 2,60 3,40 3,90 4,80 6,00 8,00
Max water flow (1) 0,705 0,894 1,032 1,204 1,565 2,012
Mad pressure drop (1) kPa 9,0 6,0 9,0 21,8 17,0 15,0
Total capacity in heating mode (2) kW 7,80 7,80 9,00 9,00 13,5 14,5
Water flow in heating (2) 0,671 0,671 0,774 0,774 1,161 1,247
Pressure drop in heating (2) kPa 7,0 7,0 9,0 21,9 9,0 10,0
Noise Pressure (3) dB(A)
Noise Power (4) dB(A) 62 62 63 63 70 72
SIZE AND WEIGHT
A (5) mm 900 900 1050 1050 1250 1250
B (5) mm 695 695 695 695 750 750
H (5) mm 295 295 295 295 315 315
Operating weight (5) kg 41 43 50 52 63 63
Notes:
1 Room temperature 27C d.b./19C w.b., Chilled water (in/out) 7/12C
2 Room temperature 20C d.b., hot water (in/out) 70/60C
3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground
4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
33
2P 4P
2 PIPES 4 PIPES CONTROLLER
34
HYDRONIC TERMINALS
HWD HP
00710121
VERSION
- base version
FEATURES
COMMANDS
2P 4P
2 PIPES 4 PIPES CONTROLLER
TECHNICAL
HWD DATA HWD HP
HWD HP 071 091 101 121
ELECTRICAL DATA
Power supply V/ph/Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz
Max absorbed power W 1 1 2 2
2 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow m/h 3200 3200 4400 5000
Total capacity in cooling mode (1) kW 16,8 20,1 23,4 29,8
Sensible capacity in cooling mode (1) kW 12,3 14,4 17,3 21,7
Max water flow (1) m/h 2,890 3,440 4,020 5,100
Mad pressure drop (1) kPa 24,0 22,0 14,0 11,9
Total capacity in heating mode (2) kW 16,3 19,6 23,0 29,8
Water flow in heating (2) m/h 2,890 3,440 4,020 5,100
Pressure drop in heating (2) kPa 21,1 19,3 12,3 10,5
Noise Pressure (3) dB(A) 60 60 66 69
Noise Power (4) dB(A)
SIZE AND WEIGHT
A (5) mm 1300 1300 1500 1500
B (5) mm 1119 1119 1349 1349
H (5) mm 510 510 625 625
Operating weight (5) kg 121 124 145 149
Notes:
1 Room temperature 27C d.b./19.5 C w.b., Chilled water (in/out) 7/12C
2 Room temperature 20C d.b., hot water (in/out) 45/40C
3 Sound pressure at 1 (m.) from fan front
4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
HRD
021151
VERSION
- base version
FEATURES
COMMANDS
PLATE CONTROLLER
TECHNICAL
HWD DATA HRD
HRD 021 031 051 071 091 101 121 151
ELECTRICAL DATA
Power supply V/ph/Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 400V-3N~50Hz
Max absorbed power W 90 130 294 700 700 700 1100 1500
PERFORMANCE
MAX SPEED
Air flow m/h 290 550 1000 1400 1900 2500 3200 4000
Available static pressure Pa 60 65 90 140 120 110 170 170
Noise Pressure (1) dB(A) 53 54 54 60 58 58 61 62
Efficency (2) % 52,3 54,6 53,4 52,1 51,8 57,6 56,0 55,6
Recovery heat exchanger capacity (2) kW 1,34 2,57 4,60 6,20 8,40 12,30 15,30 19,40
Renewal air temperature (2) C 8,10 8,70 8,30 8,00 7,90 9,40 9,00 8,90
SIZE AND WEIGHT
A (3) mm 990 990 1150 1350 1450 1700 1700 1700
B (3) mm 750 750 860 900 900 1230 1230 1230
H (3) mm 270 270 385 410 470 490 530 630
Operating weight (3) kg 39 41 68 91 99 140 155 179
Notes:
1 Sound pressure at 1 (m.) from fan front
2 Size valued in the following Hypothesis: T inlet external air 5 C; T ambient 20 C ; nominal air capacity
3 Unit in standard configuration/execution, without optional accessories.
38
HYDRONIC TERMINALS
a-CHD
0606 - 2209
VERSION
FEATURES
B
A
COMMANDS ACCESSORY
MTW WALL MOUNTED ATW WALL MOUNTED Main coil 2-way/3-way valve unit
Fan speed slider, mode slider (OFF/summer/winter). Mode button (OFF/summer/winter/AUTO), fan speed Additional coil 2-way/3-way valve unit
Thermostat with set point regulation. ON/OFF valve unit button (Max/Med/Min/AUTO). Thermostat with set
control (summer/winter for 2 pipes point regulation. ON/OFF valve unit control Fresh Air renewal connection
installation), ON/OFF second valve unit control (winter (summer/winter for 2 and 4 pipes installation). Duct Connection Flange
for 4 pipes installation). Room temperature probe. Kit Bus Adapter for BMS
Remote water temperature probe. Control of traditional or PWM modulating valve units.
Room temperature probe and water temperature Kit Gateway interface for MyHome Bticino System
INFRARED REMOTE CONTROL probe. Digital input configurable as: window contact,
Set-point regulation.Easy selection of the functioning economy, heating or cooling remote changeover,
mode (cooling, heating, dehumidification, ventilation), periodic ventilation. Configuration dip switch.
and the fan speed (Max, Med, Min, AUTO). TTL serial port with Modbus protocol for installation
User-sfriendly compact remote control with fine in BMS.
aethetics. The receiver must be connected to i-HB
Power Board that must be mounted on board of the
unit.
39
2P 4P
2 PIPES 4 PIPES CONTROLLER
TECHNICAL
HWD DATA a-CHD
40
HYDRONIC TERMINALS
i-CHD
706-2209
VERSION
FEATURES
COMMANDS
EK PLUG-IN CONTROL INFRARED REMOTE CONTROL Main coil 2-way/3-way valve unit
EKW WALL MOUNTED CONTROL Set-point regulation. Easy selection of the functioning Kit valves 4For2
User interface for selection of functioning mode mode (cooling, heating, dehumidification, ventilation), and
(OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), the fan speed (Max, Med, Min, AUTO). Fresh Air renewal connection
temperature set. Control of main User-sfriendly compact remote control with fine aethetics. Duct Connection Flange
and additional coil valve unit (summer/winter - 2 and 4 pipes The receiver must be connected to i-HB Power Board that
i-HB Power box
installation). Management of traditional ON/OFF valve unit or must be mounted on board of the unit.
modulating valve unit 0-10V or 3 points. Air and water Kit RS485 - interface for Building Management
temperature probe. Multifunction digital input configurable by System
user. Configuration dip switch. Modbus protocol for installation
in BMS (e.g. Idrorelax system by Climaveneta). Installation and
management of Master-Slave system up to 8 LIFE fan coil
units. Easy control installation thanks to 2 wires connection.
41
2P 4P
2 PIPES 4 PIPES CONTROLLER
TECHNICAL
HWD DATA i-CHD
42
HYDRONIC TERMINALS
CONTROLLERS
THE WIDE RANGE OF AVAILABLE Infrared Remote Control
NS plug-in AT plug-in
NSW wall mounted ATW wall mounted
PS plug-in MT plug-in
PSW wall mounted MTW wall mounted
EK plug-in iK universal
EKW wall mounted
Electronic control with LCD
Room thermostat, manualand display, room thermostat,
automatic regulation of fan, manual and automatic
manual- and automatic regulation of fan, manual- and
mode, change-over, roomand automatic mode change-over,
minimum temperature room and minimum
probes, regulation of electric temperature probes, regulation
heater, valves (on/off or of electric heater, valves (on/off
modulating), serial or modulating), 0-10 V output
connection for mini-network for the regulation of the energy-
and integration into BMSor saving brushless fan motor,
Idrorelax systems serial connection for mini-
network and integration into
BMS or Idrorelax systems
Notes
Refer to the dedicated product's pages for more information about compatibility between the controllers and the single fan coil.
The iK, EK, EKW controllers installed with a-LIFE and a-LIFE HP have to be combined with the 'HB LIFE' power board (cod. 7349051500).
43
For further information about connections to the units, please refer to the technical instructions of each controller.
Notes
(1) Maximum number of units of the same model that can be connected to a single controller
(2) Maximum number of units of different models and sizes that can be connected to a single controller (installing a SPB kit in each unit)
(3) Maximum number of units of the same size and model that can be connected to a controller (installing a single SPB kit)
(*) Current consumption of each unit in (A)
HYDRONIC TERMINALS_07-2014_ENG_00