Supply air temp. = Room temp. - [(sensible heat gain without ventilation(kcal/h) / supply
28 Supply air temperature Ts ( C ) room temp. - (item21 /(item24 x 0.3)
air volume(m3/h) x 0.3)] or V=Hs'/0.3x(tr-ts) or ts=tr-Hs'/V x 0.3
29 Sensible heat ratio (SHR) % item20 / item22 Total Sensible Cooling Capacity /Total Cooling Capacity
30 No. of people x Air quantity required for ventilation / person (m3/h)
31 Air quantity required for ventilation Space surface in square feet x Air quantity required for ventilation / (m3/h) PER SQ FT OF FLOOR MINIMUM
32 No. of air changes per hour x Air quantity required for ventilation / air changes per hour
33 Total air quantity required for ventilation (m3/h) (Vo) items 30+31+32
34 Total air quantity required for ventilation (CFM) item33 / 1.7
35 Room air quantity (m3/h) (Vr)
Mixed air temperature=[(Air volume required for ventilation/Supply air volume required)
36 Mixed air temperature Tm (C) items (33/24 x 27) + (35/24 x 26) x Outside temperature)]+[(Room air volume/Supply air volume required) x Room
temperature)] or Tm=((Vo/Vs) x To) + ((Vr/Vs) x Tr)
37 COIL T (C) items 36 - 28 COIL T = Tm - Ts (C)
38 COIL T (F) item 37 x 1.8
39 Supply air temperature (F) (item28 x 9/5)+32
40 Mixed air temperature (F) (item36 x 9/5)+32