This document provides a worksheet to calculate the sizing of an expansion tank for a cooling system with a flow rate of 57 gpm and cooling load of 341,214 BTUh. It outlines the equations and variables needed such as system volume, temperatures, pressures, and coefficients to calculate the required volume for both a diaphragm-type and closed-type expansion tank. Based on the provided values, the calculations show that a diaphragm-type tank should be 12.6 gallons and a closed-type should be 10.3 gallons.
This document provides a worksheet to calculate the sizing of an expansion tank for a cooling system with a flow rate of 57 gpm and cooling load of 341,214 BTUh. It outlines the equations and variables needed such as system volume, temperatures, pressures, and coefficients to calculate the required volume for both a diaphragm-type and closed-type expansion tank. Based on the provided values, the calculations show that a diaphragm-type tank should be 12.6 gallons and a closed-type should be 10.3 gallons.
This document provides a worksheet to calculate the sizing of an expansion tank for a cooling system with a flow rate of 57 gpm and cooling load of 341,214 BTUh. It outlines the equations and variables needed such as system volume, temperatures, pressures, and coefficients to calculate the required volume for both a diaphragm-type and closed-type expansion tank. Based on the provided values, the calculations show that a diaphragm-type tank should be 12.6 gallons and a closed-type should be 10.3 gallons.
Expansion Tank Sizing Worksheet Proj. No.: Engineer: Date:
Cooling (BTUh) Heating (BTUh) 341,214 BTUh 0 BTUh = 57 gpm x 500 x 42.0 F - 54.0 F T1 = Leaving Water Temperature in 28.43 tons 0.00 BHP T1 T2 Chilled Water Systems T1 = Entering Water Temperature in Hot Vs = 341 gal. OR 0 gal. = Volume in the system Water Systems
T1 = Lower System Temperature (F)
Heating Water (Ambient temperature at fill conditions i.e. 45F to 50F): T1 = 42.0 F Chilled Water (Operating CHW supply temperature i.e. 42F): Dual Temperature (Operating CHW supply temperature i.e. 42F): T2 = Higher System Temperature (F) Heating Water (Operating HW supply temperature i.e. 180F): T2 = 95.0 F Chilled Water (Ambient temperature at fill conditions i.e. 95F): Dual Temperature (Operating HW supply temperature i.e. 180F): PATM = Atmospheric Pressure (psia): = 14.696 psia P1 = System Fill Pressure / Minimum System Pressure (psia): = 12.0 psia P2 = System Operating Pressure / Maximum Operating Pressure (psia): = 60.0 psia V1 = SpV of water at T1 (ft3/Lb.water): = 0.01602 (ASHRAE Fundamentals Handbook) V2 = SpV of water at T2 (ft3/Lb.water): = 0.01651 (ASHRAE Fundamentals Handbook)
X = Linear Coefficient of Expansion: X(steel) = 0.0000065 X(copper) = 0.0000095
Diaphragm-Type Expansion Tank: 0.01651
1 3 x 0.0000065 x 53.0 F 0.01602 Vt = Vs x [((V2/V1)-1)-3XT] [1-(P1/P2)] = 341 x = 12.6 gallons 12.0 psia 1 60.0 psia
Closed-Type Expansion Tank: 0.01651
1 3 x 0.0000065 x 53.0 F 0.01602 Vt = Vs x [((V2/V1)-1)-3XT] [(PATM/P1)-(PATM/P2)] = 341 x = 10.3 gallons Vt = Vs x [((V2/V1)-1)-3XT] [(PATM/P1)-(PATM/P2)] = 341 x = 10.3 gallons 14.696 psia 14.696 psia 12.0 psia 60.0 psia