Column Verification
Column Verification
Column Verification
Fy = 355 MPa
H= 1200 mm
tw= 20 mm
B= 500 mm
tf = 40 mm
w= 13 mm
Column:
Fy = 355 MPa
H= 500 mm
tw= 20 mm
B= 500 mm
tf = 25 mm
Load:
Length of concentrated Load: N= 500.0 mm
Web Yielding
For 1200X500X20X40 beam:
The contact reaction is: P = 780.0 kN for a web thickness of 20 mm
Distance from the outer face of the flange to web toe: k= 38 mm
Web Crippling
For 1200X500X20X40 beam:
When the concentrated load is applied at a distance less than H/2 from the end of the member:
R <= 1395.08 kN > P => OK
(AISC ASD Sect. K1)
(K1.3)
(K1.5)