Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

PRESSURE REDUCING AND SUSTAINING VALVE

E2115-02

OPERATING & MAINTENANCE


MANUAL

Via L.Galvani 6 tel. 0039 0461 248311 ISI SRL


38105 Lavis TN fax 0039 0461 247024
Italy
OPERATION CONTROL of the main valve is returned to the
pressure reducing pilot (4).
The pressure reducing/sustaining valve E2115-02
(SCH002) is controlled by a normally open
diaphragm actuated, two way, spring loaded, MOUNTING
adjustable pressure reducing control pilot (4), set
to maintain a constant outlet pressure from the The mounting principle of a regulating valve is
main valve and by normally closed diaphragm shown in the SCH 450 (at the end of this
actuated, two way, spring loaded adjustable procedure); the choice of the proper "by-pass"
pressure discharging control pilot (5), set to alternative must be taking into consideration the
maintain a minimum pressure at valve inlet, which following points:
is open when upstream pressure is above the
setting point. a) Can the main transport/feeding line be put
As long as the inlet pressure is higher than the out of service during some hours (corresponding
value of the prescribed minimum value, the main to the requested time for maintening the MAIN
valve (1) is controlled by the pressure reducing VALVE), without generating problem for the
pilot (4); the set point of the downstream reduced exploitation of the system? In particular, it must be
pressure, which is sensed under the pilot noted that an empty system may required several
diaphragm, is adjustable within the indicated days to be vented properly.
spring range of the pilot.
b) Has the downstream zone of the system to be
As downstream pressure increases, the protected against any risk of pressure surge
diaphragm pushes against the spring, allowing the (quick closing of heavy demands, closing time of
pilot poppet loaded by an auxiliary spring to be pressure reducing valve)?
pulled towards its closed position, restricting the In order to get the best accuracy from the
flow through the pilot (4) and modulating the main pressure reducing/sustaining valve operation, the
valve towards a closed position. preset values for the reduced downstream
pressure and the minimum upstream pressure
The closing speed can be adjusted by the should be included in the indicated range of the
independent flow regulator "CLOSING SPEED" pilot valves. If it is very near of the extreme limits
located in the lockable central control "TUP-93". of the range, it would then be advisable to replace
the spring by the correct one.
As downstream pressure decreases, the control
pilot 4) throttles towards open, modulating the Available 263 APN 263 SS PV20C
main valve towards open. ranges (brassNi) (SS-316) (BZ/biNi)
press.red. press.red. Press.sustain.
The opening speed can be adjusted by the 0,1 - 2,0 X X X
independent flow regulator "OPENING SPEED" 1,4 - 12,0 X X X
located in the lockable central control "TUP-93". 7,0 - 21,0 - X X

Valve inlet pressure can drop as upstream or


Should installation require the main valve stem to
downstream demands increase. When there is a
be horizontal (cover pointed sideways),
decrease of upstream pressure to the sustaining
manufacturer should be consulted concerning
set-point of pilot (5), this one throttles towards
valves of DN 200 mm and larger.
closed, modulating the main valve towards closed
NOTE:
an appropriate amount to maintain the desired All sizes on request are available with a
upstream pressure, regardless the drop of additional venting cover device ( venting cock
pressure at the outlet of the valve (eventually may installed at the top of the cover ) to permit a
become null). simple escaping of air during the first
The set-point of the pressure sustaining pilot (5), commissioning.
which is sensed under the pilot diaphragm through
a sensing line connected to the inlet of the
INSTALLATION-START UP see.sch002
lockable central control "TUP-93" (unfiltered
intake), is adjustable within the indicated spring
range of the pilot. - Before the installation of the regulating valve
As upstream pressure rises above the sustaining (and respective strainer), it is recommended to
set-point, the control pilot (5) throttles open: flush the upstream line, in order to clear it of slags
and other debris.
E2115-02AUG00 PRESSURE REDUCING AND SUSTAINING VALVE 2
FM 0800
Rel 1.2 ISI PROPERTY INFORMATION
Note: An efficient flushing should be made with a gradually increase the pressure, up to the
fluid velocity of at leat 1,5 m/s during several prescribed one.
hours!
STEP 3
- Install the valve so that the FLOW ARROW Adjust the central control "TUP-93" as prescribed
marked on the valve body matches flow through above.
the line.
STEP 4
Open upstream isolation valve SLOWLY of
UPSTREAM DOWNSTREAM
one/two turns, in order to allow a controlled
filling of the regulating
valve, which is going to close (2C closed). Vent air
- Close upstream and downstream isolation of cover through the safety venting cock mounted
valves on the valve position indicator E50 (8).

- Preset the central control "TUP-93": STEP 5


A) reaction speed (RS) (normally preset in Open completely upstream isolating valve. Check
factory), should be located on: 2,5 downstream pressure gauge. If during the step 4
B) opening speed (OS) = 2 the main chambre with air wasn't able to close
C) closing speed (CS) = 6 very fast, the downstream pressure could be the
same that inlet. Take out the downstream
- Open isolating cocks 2 A-B and maintain pressure ( throught the manometer gauge holder
closed the 2C, of control circuit- ball valve 9 downstream side) until to rich the 0
If not included in the order, install two pressure value .
gauges (one for each side) by utilizing the gauge Open the 2C and wait few second in terms to
holder ball valves (9). check the downstream pressure to 0 value.
The isolating valves ( before the Y strainer
Turn the reducing control adjusting screw
and after the pressure reducer) are in closed
CLOCKWISE (IN) to increase the pressure at the
position.
prescribed value. Slowly 180 degree for time and
wait the pressure stabilized on the new value step
START UP OF AN AUTOMATIC CONTROL by step.
VALVE REQUIRES THAT PROPER
PROCEDURES BE FOLLOWED. TIME MUST STEP 7
BE ALLOWED FOR THE VALVE TO REACT When the desired pressure is reached, gradually
TO ADJUSTMENTS AND THE SYSTEM TO open the downstream isolating valve.
STABILIZE. THE OBJECTIVE OF THE It is recommended to fill the downstream system
FOLLOWING PROCEDURE IS TO BRING THE with a low flow, in order to avoid any surge due to
VALVE INTO SERVICE IN A CONTROLLED the presence of air in the system, which should be
MANNER. vented through the venting device installed at the
outlet of the regulating valve, as well as through
A) SETTING THE PRESSURE REDUCING the one(s) installed in the system itself.
CONTROL
STEP 8
STEP 1 Allow the system to stabilize. OPEN then
On pressure sustaining pilot (5), loose lock nut completely the downstream isolation valve.
and turn the setting screw counterclockwise
(OUT), until the screw is practically unloaded,
which will allow the pilot (5) to stay OPEN during
the pressure reducing set-up procedure. STEP 9
Fine-tune the pressure reducing pilot valve to the
STEP 2 set point:
On pressure reducing pilot (4), loose lock nut and
turn the setting screw counterclockwise (OUT), SCREW CLOCKWISE (IN) ----> increases the
until the screw is practically unloaded. This is outlet pressure
simulating the lowest setting value of the range,
from which the commissioner will have to SCREW COUNTERCLOCKWISE (OUT) ---->
decreases the outlet pressure

E2115-02AUG00 PRESSURE REDUCING AND SUSTAINING VALVE 3


FM 0800
Rel 1.2 ISI PROPERTY INFORMATION
Then lock the setting screw by its locking nut!
SCREW CLOCKWISE(IN) ----> increases the
STEP 10: "(TUP 93)" inlet pressure
The opening speed adjustment restricts the
control flow out of the main valve control chamber. SCREW COUNTERCLOCKWISE (OUT) ---->
If recovery of pressure is too slow pre-setting of decreases the inlet pressure
the
flow regulator at value (2) upon increased Then lock the setting screw by its locking nut!
downstream demand, increase the adjustment of
the regulator progressively up to (3) or even higher STEP 6
setting, if requested, which will increase the rate of Open upstream isolation valve to return to normal
opening. operation.
If recovery of downstream pressure is too quick,
as indicated by a rapid increase in pressure,
possibly higher than the desired set-point, TROUBLE SHOOTING
decrease the adjustment of the regulator
progressively up to (0,5) at the maximum. Do not
close the regulator completely on (0), since the Downstream pressure value equalizes upstream
opening speed would then become too long! value.

STEP 11: "(TUP-93)" First of all verify if this problem arises from
leakage inside the main valve (1), seal problem of
The closing speed adjustment restricts the control
quad-ring on inox sealing seat (SCH016 pos. 4
flow into the main valve control chamber,
and 15), or failure of diaphragm (SCH016 pos.
controlling the valve closing speed. 17), or it is caused by a small leakage from the
Its maximum pre-setting (6) is insuring the highest pilot (4) (SCH002).
closing speed possible, in order to avoid any To identify the part subject to intervention, act as
downstream pressure increase, when the demand follows:
is decreasing. If however the too quick closing is 1. Close downstream isolating valve. It is not
generating surge in the upstream system, then possible to verify shortly possible causes
decrease the adjustment of the regulator without this isolation. Flow rate must be at 0 l/s
progressively down to (5) or any lower value. Do value. Follow drawing SCH002 and close ball
not decrease more than value (1), in order to still valve (2C). Upstream and downstream gauges
insure a proper closing of the valve. will show the same value of static pressure.
2. Discharge the part of the line on main valve
SETTING THE SUSTAINING CONTROL upstream up to reach an upstream pressure
value of 0 bars. This operation may be carried
out by the gauge holder ball valve with drain
STEP 1 hole or through the device installed on
This procedure requires the lowering of the valve upstream between main valve (1) and isolating
inlet pressure! valve.
3. After releasing close the ball valve or the other
STEP 2 device. Wait a little time verifying that the
Leave downstream isolation valve full open and gauge does not reach again any pressure
close the upstream isolation valve until the inlet value over 0 bar. Shut off control circuit by the
pressure drops to or below the desired setting. ball valve (2C) forcing main valve (1) to close.
Downstream gauge will show a 0 pressure
STEP 3 value thanks to main valve (1) bubble
Turn the sustaining pilot screw clockwise (IN) until tightness. In the opposite case, if downstream
the inlet pressure begins to increase, or pressure value comes to the upstream one,
counterclockwise (OUT) to decrease, stopping at disassemble main valve (1) and replace or the
the desired pressure. quad-ring or the diaphragm. It is advisable to
have always at your disposal a main valve (1)
STEP 4 spare gaskets set so to put in service the valve
Allow pressure to stabilize. autonomously and with no waste of time.
During reassembling of cover and main body,
fasten softly (without forcing) the nuts of stud
STEP 5
bolts and centering pins between body and
Fine-tune the pressure sustaining pilot valve to the cover. The connections of control circuit on the
set point: cover will indicate the right position.

E2115-02AUG00 PRESSURE REDUCING AND SUSTAINING VALVE 4


FM 0800
Rel 1.2 ISI PROPERTY INFORMATION
In absence of losses and with a downstream Verify perfect closing of position indicator drain
gauge showing a 0 value, act as follows: cock. In the opposite case the valve does not
1. Loosen the protection of pilot (4) adjusting work. In control chamber pressure value is 0.
screw; Make sure also ball valves (2 A-B-C) are in open
2. Loosen completely pilot (4) adjusting screw position.
and turn it counterclockwise up to release
completely the inner spring; Pilot dripping (4) (5)
3. Open again ball valve (2C). Downstream
pressure value can remain at 0 or it can rise up The diaphragm of pressure control pilot is
to the minimum allowed by pilot control range damaged. Lets start replacing it.
(standard pilot: 1,4 bar).
When downstream demand rises, downstream
If the pressure on downstream gauge comes to pressure decreases to unacceptable values
higher values, the breakdown is caused by the Verify that Reaction Speed (RS) value is exactly
pilot. In this case act as follows: 2,5. In case of regulations at lower or different
values repeat adjusting as previously explained
1. Close ball valves (2 A-B-C), see drawing (see INSTALLATION). If after regulations the inlet
SCH014-A; pressure can come to a value near the one of
2. Remove bottom plug (pos. 14) avoiding to lose outlet pressure (for example P1=4, P2=3.5) lead
the spring (pos. 16) between bottom plug and reaction speed at value 3. Then adjust again the
shutter. This spring is essential for pilot pilot (4). Due to this fact the valve regulates up to
working; reach the pressure loss value of the valve.
3. Extract, by using tweezers, the shutter (pos.
18) e check seal zone characterized by a 45 Recommended spare parts:
rubber cone. Eliminate possible foreign matters Full set of gaskets for E2001;
that can create leakage even at 0 value. It is Full set of gaskets for 263 (specify the model:
advisable to have always at your disposal for 263AP in nickel plated brass or 263 SS in
such services a pilot (4) full set of gaskets; stainless steel).
4. Reassemble the pilot (4) by slipping the shutter Full set of gasket for PV20C.
stem into the proper guide, the spring and the
pertinent plug ;
5. Open ball valves (2 A-B-C); MAINTENANCE
6. Release downstream pressure by the proper
device or through the gauge holder ball valves; If the valve has been installed as per enclosed
7. After releasing close the ball valves or the drawing, the quality of constructive materials
other device. Wait a little time verifying that the should produce no wear of the internal
downstream pressure reported by the gauge components. However we are recommending:
remains at 0 or at the most comes to the
minimum pressure adjustable according to the
type of pilot.
AFTER 6 MONTHS OF SERVICE:
If downstream pressure value equalizes the Control and clean the filter on TUP-93 (see
upstream one we suggest to contact our SCH017). The results of this inspection will permit
Customer Service. to fix the frequency of such control.
NOTE: A plugged screen will prevent any flow of
Hunting control fluid into the pilot circuit, which will put the
main valve progressively out of control.
Verify the position of speed regulators on control
unit TUP-93 (pos. 3). Hunting may be reduced by
regulating the two speeds with completely different AFTER 12/18 MONTHS OF SERVICE:
values.
For example: - Control and clean the TUP-93 (3) screen.
In case of standard regulations (OS=2, CS=6) - Take the main valve (1) apart, by removing first
there is no hunting; the complete pilot circuit.
OS=3, CS=3, the possibility of hunting is higher - Then unscrew the stud nuts and remove the
for a valve under particular working conditions cover and internal diaphragm assembly.
with low flow. - Check for any eventual damage of the QUAD-
RING and the diaphragm.

Lack of regulation

E2115-02AUG00 PRESSURE REDUCING AND SUSTAINING VALVE 5


FM 0800
Rel 1.2 ISI PROPERTY INFORMATION
- Clean thoroughly the internal part of the valve,
grease slightly the stem at both guided locations
(water grease, non toxic !!).
- Assemble main valve (1) and pilot circuit.
- Put the valve back into service.

This control should then allow to determine the


cycle of the requested maintenance, since it is
taking into consideration the true service
conditions of the valve.

STORAGE

The valves from ND 40 to ND 200 are packed in


special cardboard boxes. Outside the carton are
clearly pointed out:
- The arrow indicating the position of the valve;
- The name of the customer;
- The code of the valve;
- The number of order confirmation.
The valve is protected by two hardening foam
cushions, carefully coated by a thermal plate. This
kind of packing if properly stored avoids all the
damages originated from transport, unloading,
and handling before installation. Avoid to store it
under the rain for more than 24 hours!
Open the upper side of the carton and remove the
upper cushion. Do not lift the valve by utilizing the
pilot, the pilot circuit, or the position indicator. For
any kind of handling we recommend to utilize
proper eyebolts.

For any further information contact our


Customer Service, indicating all data as per
inox plate on main valve body. Give full
detailed informations about working
conditions, the type of problem, and report the
adjusting values (OS-CS-RS).

E2115-02AUG00 PRESSURE REDUCING AND SUSTAINING VALVE 6


FM 0800
Rel 1.2 ISI PROPERTY INFORMATION

You might also like